TESTING & COMMISSIONING

FEEDER PROTECTION RELAY


TEST REPORT

F-PMS-CTC-48, Rev 0,08-Aug-2022

Company National Grid Corporation of the Philippines


Plant/Substation Zamboanga S/S
Location Sangali, Zamboanga City, Zamboanga del Sur
Test Date December 07,2023

INSTRUMENT DATA
Make/Brand Omicron
Model No. CMC 356
Serial No. AN148E/102005943
Calibration Date September 21, 2023-2024

RELAY DATA
Relay Function 67P, 67G, 50/51G
Make Sifang
Model No. CSC - 211
Serial No. SFJB400006807022000003
Settings & Calculation NGCP

RELAY SETTING
Line CT Pri 1000 Line PT Pri 69kV L-L
Line CT Sec 5 Line PT Sec 115V L-L

NOTE: See complete final Relay Setting on a separate sheet.

TEST DATA
1.1 CT MEASUREMENTS (Metering Secondary Injection)
Phase Current Injected (A) Expected Value (A) Measured Value (A) REMARKS

PHASE A 0.1 0.1 0.099 OK


PHASE B 0.2 0.2 0.196 OK
PHASE C 0.3 0.3 0.297 OK
Acceptance Criteria: ≤ ±2.5% setting

1.2 VT MEASUREMENTS (Metering Secondary Injection)


Phase Voltage Injected Expected Value Measured Value REMARKS

PHASE A 10 V 10 V 10 V OK
PHASE B 20 V 20 V 19.987 V OK
PHASE C 30 V 30 V 29.983 V OK
Acceptance Criteria: ≤ ±2.5% setting

2.1 DIRECTIONAL OVERCURRENT (67P_Stage1) I_Set = 8 A, t = 0.01 s


Measured Time (ms) Measured Time (ms) Measured Time (ms) Measured Time (ms)
PHASE Pickup (A) Drop Off (A) @ 106.3% TAP @ 112.5% TAP @ 118.8% TAP @ 125% TAP REMARKS
10ms 10ms 10ms 10ms
PHASE A 8 7.56 37.7 37.8 38.1 35.8 OK
PHASE B 8 7.56 37.4 36.1 37.1 34.3 OK
PHASE C 8 7.56 38.6 38.4 35.8 37.1 OK
Trip Region: Counterclockwise Rotation: from 4° to 175°
Current: ≤ ±2.5% setting or ±0.02In
Acceptance Criteria:
Time Delay: ≤ ± 1% times of setting or +40ms, at 2 times of operating current

2.2 DIRECTIONAL OVERCURRENT (67P_Stage2) I_Set = 1.30 A, TMSp = 0.08


Measured Time (ms) Measured Time (ms) Measured Time (ms) Measured Time (ms)
PHASE Pickup (A) Drop Off (A) @ 150% TAP @ 200% TAP @ 300% TAP @ 400% TAP REMARKS
1376ms 802.3ms 504.2ms 398.4ms
PHASE A 1.3 1.3 1395 820.2 517.5 411.2 OK
PHASE B 1.3 1.275 1393 818.9 517.5 411.6 OK
PHASE C 1.325 1.3 1395 819.9 519.5 411.6 OK
Trip Region: Counterclockwise Rotation: from 4° to 175°
Current: ≤ ±2.5% setting or ±0.02In
Acceptance Criteria:
Time Delay: ≤ ± 1% times of setting or +40ms, at 2 times of operating current

3.1 DIRECTIONAL EARTH FAULT (67G_Stage1) I_Set = 13 A, t = 0.01 s


Measured Time (ms) Measured Time (ms) Measured Time (ms) Measured Time (ms)
PHASE Pickup (A) Drop Off (A) @ 103.9% TAP @ 107.7% TAP @ 111.5% TAP @ 115.4% TAP REMARKS
10ms 10ms 10ms 10ms
3I0 13 12.29 37 37.1 38.1 38.4 OK
Trip Region: Clockwise Rotation: from 20° to -141°
Current: ≤ ±2.5% setting or ±0.02In
Acceptance Criteria:
Time Delay: ≤ ± 1% times of setting or +40ms, at 2 times of operating current

3.2 NON DIRECTIONAL EARTH FAULT (67G_Stage2) I_Set = 0.31 A, TMSg = 0.05
Measured Time (ms) Measured Time (ms) Measured Time (ms) Measured Time (ms)
PHASE Pickup (A) Drop Off (A) @ 322.6% TAP @ 645.2% TAP @ 967.7% TAP @ 1290% TAP REMARKS
295.4ms 184.3ms 150.7ms 133.4ms
3I0 0.325 0.3 310.1 194.4 162 142.5 OK
Trip Region: Clockwise Rotation: from 20° to -141°
Current: ≤ ±2.5% setting or ±0.02In
Acceptance Criteria:
Time Delay: ≤ ± 1% times of setting or +40ms, at 2 times of operating current

Remarks:
TESTING & COMMISSIONING
FEEDER PROTECTION RELAY
TEST REPORT

F-PMS-CTC-48, Rev 0,08-Aug-2022


Signatories:
MIESCOR Client
Tested by: RAFAEL M. CUNANAN Reviewed by: JARETTE S. FERNANDO Witnessed by:

Tested by: JOHN CARLO B. IGNACIO Approved by: PORTIA O. IBIAS Approved by: