DISCRIMINATION

BUILDING LOAD (02-MSB-A1)

Project : Terra Data Center

Discrimination Building (A1) Load


Sampling Route Test for Setting Circuit Breaker

From switchboard : TH-BKK1-01-02-MSB-001-A1

1
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Discrimination Building (A1) Load

Project : Terra data center


Discription : Setting and test trip for Building (A1) Load Route
Switchboard : TH-BKK1-01-02-MSB-001-A1

Test Participation
No. Name-Last name Company Signature Date
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

2
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

TABLE OF DISCRIMINATION SETTING PROTECTION TRIP UNIT OF CIRCUIT BREAKER SIMULATION TEST

Panel :01-02-MSB-001-A1 Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
1 ACB MAIN 01-02-MSB-001-A1 5,000 5,000 ACB E6.2H D/O Ekip Hi Touch LSIG L: I1= 0.87 t1= 6 I1 4.350 t1 6.000 - - - 10.000 10% 7.353 13.53 10.261 ✓
S: I2= 5.5 t2= 0.35 I2 27.500 t2 0.350 - - - 50.000 20% 0.252 0.462 0.351 ✓
I: I3= 15 I3 75.000 t3 - - - - 80.000 <30ms - 0.030 0.023 ✓
G Internal (Alarm Only) : I4= 0.16 t4= 0.7 I4 0.800 t4 0.700 - - - 2.500 10% 0.567 0.847 Alarm (G Trip OFF) ✓
G External : = 0.16 t= 0.7 I4 (Ext) 0.800 t4 0.700 - - - 1.600 10% 0.567 0.847 0.717 ✓
2 CB1 01-02-LVSB-003-A 4,000 4,000 ACB E4.2S D/O Ekip Hi Touch LSIG L: I1= 0.9 t1= 5 I1 3.600 t1 5.000 - - - 8.000 10% 6.561 11.990 9.148 ✓
S: I2= 5.2 t2= 0.25 I2 20.800 t2 0.250 - - - 40.000 20% 0.180 0.330 0.252 ✓
I: I3= 14.5 I3 58.000 t3 - - - - 64.000 <30ms - 0.030 0.022 ✓
G: I4= - t4= - I4 - t4 - - - - - 10% - - - -
3 CB2 01-02-IUSB-001-A1 800 800 MCCB T6L800 D/O R800 PR222/DS LSI L: I1= 0.78 t1= 18 I1 0.624 t1 18.000 - 1.600 - - 10% 70.920 129.800 98.560 ✓
S: I2= 5.8 t2= 0.5 I2 4.640 t2 0.500 - 7.200 - - 20% 0.360 0.660 0.500 ✓
I: I3= 10.5 I3 8.400 t3 - - 12.800 - - <50ms - 0.050 0.020 ✓
4 CB3 01-03-IUSB-001-A1 800 800 MCCB T6L800 D/O R800 PR222/DS LSI L: I1= 0.78 t1= 18 I1 0.624 t1 18.000 - 1.600 - - 10% 70.920 129.800 98.560 ✓
S: I2= 5.8 t2= 0.5 I2 4.640 t2 0.500 - 7.200 - - 20% 0.360 0.660 0.500 ✓
I: I3= 10.5 I3 8.400 t3 - - 12.800 - - <50ms - 0.050 0.020 ✓
5 CB4 01-02-MSB-001-A1 (01-08-LVSB-001) 160 160 MCCB XT2L160 R160 PLUG-IN Ekip LSI L: I1= 1 t1= 60 I1 0.160 t1 60.000 0.320 - - - 10% 97.200 178.200 135.672 ✓
S: I2= 5.5 t2= 0.4 I2 0.880 t2 0.400 1.440 - - - 20% 0.256 0.576 0.414 ✓
I: I3= - I3 - t3 - - - - - <50ms - - - -
6 CB5 01-02-MSB-001-A1 (01-08-LVSB-002) 250 250 MCCB XT4L250 R250 PLUG-IN Ekip LSI L: I1= 1 t1= 60 I1 0.250 t1 60.000 0.500 - - - 10% 97.200 178.200 135.172 ✓
S: I2= 5.5 t2= 0.4 I2 1.375 t2 0.400 2.250 - - - 20% 0.256 0.576 0.427 ✓
I: I3= - I3 - t3 - - - - - <50ms - - - -
7 CB6 1-02-BW-001-A1 (BUSWAY 1000A) 1,250 1,250 ACB E2.2S D/O Ekip Hi Touch LSIG L: I1= 0.8 t1= 60 I1 1.000 t1 60.000 - - 2.500 - 10% 97.200 178.200 87.074 ✓
S: I2= 10 t2= 0.25 I2 12.500 t2 0.250 - - 13.750 - 20% 0.180 4.116 0.252 ✓
I: I3= 15 I3 18.750 t3 - - - 20.000 - <30ms - 0.030 0.023 ✓
G: I4= - t4= - I4 - t4 - - - - - 10% - - - -
8 CB8 01-02-LVSB-002-A (DAY-0HVAC/HYD LOAD) 800 800 MCCB T6L800 R800 D/O PR222/DS LSI L: I1= 0.62 t1= 18 I1 0.496 t1 18.000 - 1.600 - - 10% 44.82 82.17 62.272 ✓
S: I2= 8.2 t2= 0.25 I2 6.560 t2 0.250 - 7.200 - - 20% 0.18 4.428 0.250 ✓
I: I3= 10.5 I3 8.400 t3 - - 12.800 - - <50ms - 0.050 0.020 ✓
9 CB9 01-08-LVSB-002-A 400 400 MCCB T5L400 R400 PLUG-IN PR222/DS LSI L: I1= 0.6 t1= 18 I1 0.240 t1 18.000 - 0.800 - - 10% 42.03 77 58.319 ✓
S: I2= 8.2 t2= 0.25 I2 3.280 t2 0.250 - 3.600 - - 20% 0.18 4.152 0.250 ✓
I: I3= - I3 - t3 - - - - - <50ms - - - -

3
DISCRIMINATION
TABLE OF DISCRIMINATION SETTING BUILDING LOAD (02-MSB-A1) PROTECTION TRIP UNIT OF CIRCUIT BREAKER SIMULATION TEST

Panel :01-02-MSB-001-A1 Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
10 CB11 SPARE 250 250 MCCB XT4L250 R250 PLUG-IN Ekip LSI L: I1= 1 t1= 60 I1 0.250 t1 60.000 - 0.500 - - 10% 97.200 178.200 135.523 ✓
S: I2= 5.5 t2= 0.4 I2 1.375 t2 0.400 - 2.250 - - 20% 0.016 0.576 0.411 ✓
I: I3= 10 I3 2.500 t3 - - 4.000 - - <50ms - 0.050 0.010 ✓
11 CB12 SPARE 250 250 MCCB XT4L250 R250 PLUG-IN Ekip LSI L: I1= 1 t1= 60 I1 0.250 t1 60.000 - 0.500 - - 10% 97.200 178.200 135.968 ✓
S: I2= 5.5 t2= 0.4 I2 1.375 t2 0.400 - 2.250 - - 20% 0.016 0.576 0.414 ✓
I: I3= 10 I3 2.500 t3 - - 4.000 - - <50ms - 0.050 0.006 ✓
12 CB13 SPARE 400 400 MCCB T5L400 R400 PLUG-IN PR222/DS LSI L: I1= 1 t1= 18 I1 0.400 t1 18.000 - 0.800 - - 10% 117.000 213.400 162.000 ✓
S: I2= 5.8 t2= 0.1 I2 2.320 t2 0.100 - 3.600 - - 20% 0.072 0.132 0.100 ✓
I: I3= - I3 - t3 - - - - - <50ms - - - -
13 CB14 SPARE 400 400 MCCB T5L400 R400 PLUG-IN PR222/DS LSI L: I1= 1 t1= 18 I1 0.400 t1 18.000 - 0.800 - - 10% 117.000 213.400 162.000 ✓
S: I2= 5.8 t2= 0.1 I2 2.320 t2 0.100 - 3.600 - - 20% 0.072 0.132 0.100 ✓
I: I3= - I3 - t3 - - - - - <50ms - - - -
14 CB10 01-01-FPCP-002 (FIRE PUMP) 800 1,250 ACB E2.2S D/O Ekip Hi Touch LSIG L: I1= 0.525 t1= 144 I1 0.420 t1 144.000 - - 2.500 - 10% 26.370 48.290 N/C
S: I2= 8.5 t2= 0.1 I2 6.800 t2 0.100 - - 12.500 - 20% 0.012 0.132 N/C
I: I3= 15 I3 12.000 t3 - - - 20.000 - <30ms - 0.030 N/C
G: I4= - t4= - I4 - t4 - - - - - 10% - - N/C
15 CB7 01-01-LVSB-002-A (HVAC/HYD LOAD) 400 400 MCCB T5L400 R400 PLUG-IN PR222/DS LSI L: I1= 1 t1= 18 I1 0.400 t1 18.000 - 0.800 - - 10% 117.000 213.400 162.000 ✓
S: I2= 5.8 t2= 0.1 I2 2.320 t2 0.100 - 3.600 - - 20% 0.072 0.132 0.100 ✓
I: I3= - I3 - t3 - - - - - <50ms - - - -

L : Overload protection
S : Time-delayed overcurrent protection
I : Instantaneous overcurrent protection
G : Earth fault protection

I1 : Threshold Overload protection t1 : Trip time Overload protection


I2 : Threshold Time-delayed overcurrent protection t2 : Trip time Time-delayed overcurrent protection
I3 : Threshold Instantaneous overcurrent protection
I4 : Threshold Earth fault protection t4 : Trip time Earth fault protection

4
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Description In AF Breaker Type Setting

Time-Current curve LLL-LL @415V


5 4 3

2 1

1000s No. Description In AF Breaker Type


1 MAIN 01-02-MSB-001-A1 5,000 5,000 ACB E6.2H D/O Ekip Hi Touch LSIG
2 01-02-LVSB-003-A 4,000 4,000 ACB E4.2S D/O Ekip Hi Touch LSIG
100s
3 1-02-BW-001-A1 (BUSWAY 1000A) 1,250 1,250 ACB E2.2S D/O Ekip Hi Touch LSIG
4 01-02-IUSB-001-A1 800 800 MCCB T6L800 D/O R800 PR222/DS LSI
5 01-02-LVSB-002-A (DAY-0HVAC/HYD LOAD) 800 800 MCCB T6L800 D/O R800 PR222/DS LSI

10s

1s

100ms

1A 10A 100A 1kA 10kA 100kA

Time-Current curve LLL-LL @415V

4 3 2

1 No. Description In AF Breaker Type


1000s
1 MAIN 01-02-MSB-001-A1 5,000 5,000 ACB E6.2H D/O Ekip Hi Touch LSIG
2 01-08-LVSB-002-A 400 400 MCCB T5L400 R400 PLUG-IN PR222/DS LSI
3 01-02-MSB-001-A1 (01-08-LVSB-002) 250 250 MCCB XT4L250 R250 PLUG-IN Ekip LSI
100s
4 01-02-MSB-001-A1 (01-08-LVSB-001) 160 160 MCCB XT2L160 R160 PLUG-IN Ekip LSI

10s

1s

100ms

10ms

100mA 1A 10A 100A 1kA 10kA 100kA

5
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

TABLE OF DISCRIMINATION SETTING PROTECTION TRIP UNIT OF CIRCUIT BREAKER SIMULATION TEST

Panel : 01-02-LVSB-003-A Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
1 ACB MAIN 01-02-LVSB-003-A 4,000 4,000 ACB E4.2S D/O Ekip Hi Touch LSIG L : I1= 0.9 t1= 5 I1 3.600 t1 5.00 - - - 8.000 10% 6.561 11.990 9.155 ✓
S : I2= 5.2 t2= 0.25 I2 20.800 t2 0.25 - - - 40.000 20% 0.180 0.330 0.253 ✓
I : I3= 14.5 I3 58.000 t3 - - - - 64.000 <30ms - 0.030 0.023 ✓
G: I4= - t4= - I4 - t4 - - - - - - - - - -
2 CB1 01-02-CH-001 (CHILLER 1 No.1) 1,600 1,600 ACB E2.2S D/O Ekip Hi Touch LSIG L: I1= 1 t1= 7 I1 1.600 t1 7.00 - - 3.200 - 10% 11.340 20.790 15.793 ✓
S: I2= 7 t2= 0.12 I2 11.200 t2 0.12 - - 16.000 - 20% 0.086 0.158 0.121 ✓
I : I3= 15 I3 24.000 t3 - - - 25.600 - <30ms - 0.030 0.023 ✓
G: I4= - t4= - I4 - t4 - - - - - - - - -
3 CB2 01-02-CH-001 (CHILLER 1 No.2) 1,250 1,250 ACB E2.2S D/O Ekip Hi Touch LSIG L: I1= 0.96 t1= 7 I1 1.200 t1 7.00 - - 2.500 - 10% 10.440 19.140 14.562 ✓
S: I2= 7 t2= 0.12 I2 8.750 t2 0.12 - - 12.500 - 20% 0.086 0.158 0.122 ✓
I : I3= 15 I3 18.750 t3 - - - 20.000 - <30ms - 0.030 0.020 ✓
G: I4= - t4= - I4 - t4 - - - - - - - - -
4 CB3 01-02-MCC-004 800 800 MCCB T6L800 D/O R800 PR222/DS LSI L: I1= 0.78 t1= 18 I1 0.624 t1 18.00 - 1.600 - - 10% 70.920 129.800 98.560 ✓
S: I2= 8.8 t2= 0.5 I2 7.040 t2 0.50 - 7.200 - - 20% 0.360 5.840 0.500 ✓
I : I3= 10.5 I3 8.400 t3 - - 12.800 - - <50ms - 0.050 0.020 ✓
5 CB4 01-08-MCC-001 400 400 MCCB T5L400 R400 PLUG-IN PR222/DS LSI L: I1= 0.74 t1= 18 I1 0.296 t1 18.00 - 0.800 - - 10% 63.900 116.600 88.711 ✓
S: I2= 5.8 t2= 0.5 I2 2.320 t2 0.50 - 3.600 - - 20% 0.360 0.660 0.500 ✓
I : I3= 12 I3 4.800 t3 - - 6.400 - - <50ms - 0.050 0.020 ✓
6 CB5 TH-BKK1-RE-CIRCULATION PUMP 01 25 160 MCCB XT2L160 R25 PLUG-IN Ekip LSI L: I1= 1 t1= 60 I1 0.025 t1 60.00 0.050 - - - 10% 97.20 178.20 55.078 ✓
S: I2= 6.5 t2= 0.4 I2 0.163 t2 0.40 0.225 - - - 20% 0.016 0.576 0.418 ✓
I : I3= 10 I3 0.250 t3 - 0.375 - - - <50ms 0.050 0.007 ✓
7 CB6 TH-BKK1-PRESSURISATION TANK 01 63 160 MCCB XT2L160 R63 PLUG-IN Ekip LSI I : I1= 0.62 t1= 60 I1 0.039 t1 60.00 0.126 - - - 10% 37.350 68.530 51.922 ✓
S: I2= 6.5 t2= 0.4 I2 0.410 t2 0.40 0.567 - - - 20% 0.016 0.576 0.416 ✓
I : I3= 10 I3 0.630 t3 - 1.008 - - - <50ms - 0.050 0.005 ✓
8 CB11 SPARE 400 400 MCCB T5L400 R400 PLUG-IN PR222/DS LSI L: I1= 1 t1= 18 I1 0.400 t1 18.00 - 0.800 - - 10% 117.000 213.400 162.000 ✓
S: I2= 5.8 t2= 0.5 I2 2.320 t2 0.50 - 3.600 - - 20% 0.360 0.660 0.500 ✓
I : I3= 12 I3 4.800 t3 - - 6.400 - - <50ms - 0.050 0.020 ✓

L : Overload protection
S : Time-delayed overcurrent protection
I : Instantaneous overcurrent protection
G : Earth fault protection

I1 : Threshold Overload protection t1 : Trip time Overload protection


I2 : Threshold Time-delayed overcurrent protection t2 : Trip time Time-delayed overcurrent protection
I3 : Threshold Instantaneous overcurrent protection
I4 : Threshold Earth fault protection t4 : Trip time Earth fault protection

6
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Time-Current curve LLL-LL @415V


4 3 2 1

No. Description In AF Breaker Type


100s
1 MAIN 01-02-MSB-001-A1 5,000 5,000 ACB E6.2H D/O Ekip Hi Touch LSIG
2 MAIN 01-02-LVSB-003-A 4,000 4,000 ACB E4.2S D/O Ekip Hi Touch LSIG
3 01-02-CH-001 (CHILLER 1 No.1) 1,600 1,600 ACB E2.2S D/O Ekip Hi Touch LSIG
4 01-02-CH-001 (CHILLER 1 No.2) 1,250 1,250 ACB E2.2S D/O Ekip Hi Touch LSIG
10s

1s

100ms

10ms
10A 100A 1kA 10kA 100kA

Time-Current curve LLL-LL @415V

5 4 3 2 1
No. Description In AF Breaker Type
1 MAIN 01-02-MSB-001-A1 5,000 5,000 ACB E6.2H D/O Ekip Hi Touch LSIG
2 01-02-MCC-004 800 800 MCCB T6L800 D/O R800 PR222/DS LSI
100s
3 01-08-MCC-001 400 400 MCCB T5L400 R400 PLUG-IN PR222/DS LSI
4 TH-BKK1-PRESSURISATION TANK 01 63 160 MCCB XT2L160 R63 PLUG-IN Ekip LSI
5 TH-BKK1-RE-CIRCULATION PUMP 01 25 160 MCCB XT2L160 R25 PLUG-IN Ekip LSI
10s

1s

100ms

10ms
10A 100A 1kA 10kA 100kA

7
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

TABLE OF DISCRIMINATION SETTING PROTECTION TRIP UNIT OF CIRCUIT BREAKER SIMULATION TEST

Panel : 01-08-LVSB-001 Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
1 MCB MAIN 01-08-LVSB-001 160 160 MCCB XT2N160 R160 PLUG-IN Ekip LSI L: I1= 1 t1= 60 I1 0.160 t1 60.000 0.320 - - - 10% 97.2 178.2
S: I2= 5.5 t2= 0.4 I2 0.880 t2 0.400 1.440 - - - 20% 0.256 0.576
I : I3= - I3 - t3 - 2.560 - - - <50ms - -
2 CB1 PASSENGER L3 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 1 t1= 60 I1 0.063 t1 60.000 0.126 - - - 10% 97.2 178.2
S: I2= 5.5 t2= 0.2 I2 0.347 t2 0.200 0.567 - - - 20% 0.128 0.288
I : I3= - I3 - t3 - 1.008 - - - <50ms - -
3 CB3 LIGHTING & CONTROL LIFT ( R ) 25 160 MCCB XT2N160 R25 PLUG-IN Ekip LSI L: I1= 0.8 t1= 60 I1 0.020 t1 60.000 0.050 - - - 10% 62.19 114.4
S: I2= 4.5 t2= 0.2 I2 0.113 t2 0.200 0.225 - - - 20% 0.488 0.288
I : I3= - I3 - t3 - - - - - <50ms - -

I : Instantaneous overcurrent protection


G : Earth fault protection

I1 : Threshold Overload protection t1 : Trip time Overload protection


I2 : Threshold Time-delayed overcurrent protection t2 : Trip time Time-delayed overcurrent protection
I3 : Threshold Instantaneous overcurrent protection
I4 : Threshold Earth fault protection t4 : Trip time Earth fault protection

8
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Time-Current curve LLL-LL @415V

4 3 2 1

1000s

No. Description In AF Breaker Type


1 MAIN 01-02-MSB-001-A1 5,000 5,000 ACB E6.2H D/O Ekip Hi Touch LSIG
100s
2 MAIN 01-08-LVSB-001 160 160 MCCB XT2N160 R160 PLUG-IN Ekip LSI
3 PASSENGER L3 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI
10s 4 LIGHTING & CONTROL LIFT ( R ) 25 160 MCCB XT2N160 R25 PLUG-IN Ekip LSI

1s

100ms

10ms

100mA 1A 10A 100A 1kA 10kA 100kA 1MA

9
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

10
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)
TABLE OF DISCRIMINATION SETTING PROTECTION TRIP UNIT OF CIRCUIT BREAKER SIMULATION TEST

Panel : 01-08-LVSB-002 Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
1 MCB MAIN 01-08-LVSB-002 200 250 MCCB XT4N250 R200 PLUG-IN Ekip LSI L: I1= 1 t1= 60 I1 0.200 t1 60.000 0.400 - - - 10% 97.2 178.2
S: I2= 5.5 t2= 0.4 I2 1.375 t2 0.400 1.800 - - - 20% 0.256 0.576
I : I3= - I3 - t3 - - - - - <50ms -
2 CB1 GOOD LIFT L1 100 160 MCCB XT2N160 R100 PLUG-IN Ekip LSI L: I1= 1 t1= 60 I1 0.100 t1 60.000 0.200 - - - 10% 97.2 178.2
S: I2= 5.5 t2= 0.2 I2 0.550 t2 0.200 0.900 - - - 20% 0.128 0.288
I : I3= - I3 - t3 - - - - - <50ms -
3 CB3 LIGHTING & CONTROL LIFT ( R ) 25 160 MCCB XT2N160 R25 PLUG-IN Ekip LSI L: I1= 0.8 t1= 60 I1 0.020 t1 60.000 0.050 - - - 10% 62.19 114.4
S: I2= 4.5 t2= 0.2 I2 0.113 t2 0.200 0.225 - - - 20% 0.128 0.288
I : I3= - I3 - t3 - - - - - <50ms -
4 CB6 SPARE 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 1 t1= 60 I1 0.063 t1 60.000 0.126 - - - 10% 97.2 178.2
S: I2= 5.5 t2= 0.2 I2 0.347 t2 0.200 0.567 - - - 20% 0.128 0.288
I : I3= - I3 - t3 - - - - - <50ms -

L : Overload protection
S : Time-delayed overcurrent protection
I : Instantaneous overcurrent protection
G : Earth fault protection

I1 : Threshold Overload protection t1 : Trip time Overload protection


I2 : Threshold Time-delayed overcurrent protection t2 : Trip time Time-delayed overcurrent protection
I3 : Threshold Instantaneous overcurrent protection
I4 : Threshold Earth fault protection t4 : Trip time Earth fault protection

Time-Current curve LLL-LL @415V


5 4 3 2 1

1000s
No. Description In AF Breaker Type
1 MAIN 01-02-MSB-001-A1 5,000 5,000 ACB E6.2H D/O Ekip Hi Touch LSIG
2 MAIN 01-08-LVSB-002 200 250 MCCB XT4N250 R200 PLUG-IN Ekip LSI
100s
3 GOOD LIFT L1 100 160 MCCB XT2N160 R160 PLUG-IN Ekip LSI
4 LIGHTING & CONTROL LIFT ( R ) 25 160 MCCB XT2N160 R25 PLUG-IN Ekip LSI
5 SPARE 63 160 MCCB XT2N160 R263 PLUG-IN Ekip LSI
10s

1s

100ms

10ms

1A 10A 100A 1kA 10kA 100kA

11
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

TABLE OF DISCRIMINATION SETTING PROTECTION TRIP UNIT OF CIRCUIT BREAKER SIMULATION TEST

Panel : 01-01-LVSB-002-A (HVAC/HYD LOAD) Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
1 MCB MAIN 01-01-LVSB-002-B 400 400 MCCB T5N400 R400 PLUG-IN PR222/DS LSI L: I1= 1 t1= 18 I1 0.400 t1 18.000 - 0.800 - - 10% 117 213.4 162.000 ✓
S: I2= 5.8 t2= 0.1 I2 2.320 t2 0.100 - 3.600 - - 20% 0.072 0.132 0.100 ✓
I : I3= - I3 - t3 - - - - <50ms - - - -
2 CB1 TH-BKK1-01-01-DB-004-A 100 160 MCCB XT2N160 R100 PLUG-IN Ekip LSI L: I1= 1 t1= 12 I1 0.100 t1 12.000 0.200 - - - 10% 19.44 35.64 27.107 ✓
S: I2= 7.5 t2= 0.2 I2 0.750 t2 0.200 0.800 - - - 20% 0.016 0.288 0.223 ✓
I : I3= 9 I3 0.900 t3 - 1.600 - - - <50ms - 0.050 0.002 ✓
3 CB2 TH-BKK1-01-01-DB-005-A (Hydraulic Level 1) 160 160 MCCB XT2N160 R160 PLUG-IN Ekip LSI L: I1= 0.92 t1= 12 I1 0.147 t1 12.000 0.320 - - - 10% 16.47 30.14 22.943 ✓
S: I2= 5.5 t2= 0.2 I2 0.880 t2 0.200 1.280 - - - 20% 0.016 0.288 0.217 ✓
I : I3= 9 I3 1.440 t3 - 2.560 - - - <50ms - 0.050 0.003 ✓
4 CB3 TH-BKK1-01-01-MCC-701-A (MUTP-001,002) 100 160 MCCB XT2N160 R100 PLUG-IN Ekip LSI L: I1= 0.8 t1= 12 I1 0.080 t1 12.000 0.200 - - - 10% 12.42 22.77 17.312 ✓
S: I2= 5.5 t2= 0.2 I2 0.550 t2 0.200 0.800 - - - 20% 0.016 0.288 0.208 ✓
I : I3= 9 I3 0.900 t3 - 1.600 - - - <50ms - 0.050 0.005 ✓
5 CB4 TH-BKK1-01-01-MCC-702-A (MUTP-003,004) 160 160 MCCB XT2N160 R160 PLUG-IN Ekip LSI L: I1= 0.78 t1= 12 I1 0.125 t1 12.000 0.320 - - - 10% 11.79 21.67 16.476 ✓
S: I2= 5.5 t2= 0.2 I2 0.880 t2 0.200 1.280 - - - 20% 0.016 0.288 0.211 ✓
I : I3= 9 I3 1.440 t3 - 2.560 - - - <50ms - 0.050 0.002 ✓
6 CB5 TH-BKK1-01-01-MCP-001 (Jet Fans) 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.78 t1= 12 I1 0.049 t1 12.000 0.126 - - - 10% 12.42 22.77 16.480 ✓
S: I2= 5.5 t2= 0.2 I2 0.347 t2 0.200 0.504 - - - 20% 0.016 0.288 0.219 ✓
I : I3= 9 I3 0.567 t3 - 0.945 - - - <50ms - 0.050 0.003 ✓

L : Overload protection
S : Time-delayed overcurrent protection
I : Instantaneous overcurrent protection
G : Earth fault protection

I1 : Threshold Overload protection t1 : Trip time Overload protection


I2 : Threshold Time-delayed overcurrent protection t2 : Trip time Time-delayed overcurrent protection
I3 : Threshold Instantaneous overcurrent protection
I4 : Threshold Earth fault protection t4 : Trip time Earth fault protection

12
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Time-Current curve LLL-LL @400V


5 4 3 2 1
6
No. Description In AF Breaker Type
1 MAIN 01-02-MSB-001-A1 5,000 5,000 ACB E6.2H D/O Ekip Hi Touch LSIG
1000s 2 MAIN 01-01-LVSB-002-B 400 400 MCCB T5N400 R400 PLUG-IN PR222/DS LSI
3 TH-BKK1-01-01-DB-005-A (Hydraulic Level 1) 160 160 MCCB XT2N160 R160 PLUG-IN Ekip LSI
4 TH-BKK1-01-01-DB-004-A 100 160 MCCB XT2N160 R100 PLUG-IN Ekip LSI
5 TH-BKK1-01-01-MCC-701-A (MUTP-001,002) 100 160 MCCB XT2N160 R100 PLUG-IN Ekip LSI
100s 6 TH-BKK1-01-01-MCP-001 (Jet Fans) 63 100 MCCB XT2N160 R63 PLUG-IN Ekip LSI

10s

1s

100ms

10ms

100mA 1A 10A 100A 1kA 10kA 100kA

13
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

14
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

TABLE OF DISCRIMINATION SETTING PROTECTION TRIP UNIT OF CIRCUIT BREAKER SIMULATION TEST

Panel : 01-02-IUSB-001-A1 Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
1 MCB MAIN 01-02-IUSB-001-A1 800 800 MCCB T6S800 D/O R800 PR222/DS LSI L: I1= 1 t1= 18 I1 0.800 t1 18.000 - 1.600 - - 10% 117 213.4 162.000 ✓
S: I2= 5.8 t2= 0.5 I2 4.640 t2 0.500 - 7.200 - - 20% 0.36 0.66 0.500 ✓
I : I3= 10.5 I3 8.400 t3 - - 12.800 - - <50ms - 0.050 0.020 ✓
2 CB1 01-02-SUPS-001-A1 (UPS) 800 800 MCCB T6S800 D/O R800 PR222/DS LSI L: I1= 0.78 t1= 9 I1 0.624 t1 9.000 - 1.600 - - 10% 35.46 65.01 49.280 ✓
S: I2= 4.2 t2= 0.25 I2 3.360 t2 0.250 - 7.200 - - 20% 0.18 0.33 0.250 ✓
I : I3= 10.5 I3 8.400 t3 - - 12.800 - - <50ms - 0.050 0.020 ✓
3 CB2 01-02-SUPS-001-A1 (UPS BYPASS) 800 800 MCCB T6S800 D/O R800 PR222/DS LSI L: I1= 0.78 t1= 9 I1 0.624 t1 9.000 - 1.600 - - 10% 35.46 65.01 49.280 ✓
S: I2= 4.2 t2= 0.25 I2 3.360 t2 0.250 - 7.200 - - 20% 0.18 0.33 0.250 ✓
I : I3= 10.5 I3 8.400 t3 - - 12.800 - - <50ms - 0.050 0.020 ✓
4 CB3 BYPASS TO 01-02-OUSB-001-A1 800 800 MCCB T6S800 D/O R800 PR222/DS LSI L: I1= 0.78 t1= 9 I1 0.624 t1 9.000 - 1.600 - - 10% 35.46 65.01 49.280 ✓
S: I2= 4.2 t2= 0.25 I2 3.360 t2 0.250 - 7.200 - - 20% 0.18 0.33 0.250 ✓
I : I3= 10.5 I3 8.400 t3 - - 12.800 - - <50ms - 0.050 0.020 ✓
5 CB4 SPARE 100 160 MCCB XT2S160 R100 PLUG-IN Ekip LSI L: I1= 1 t1= 60 I1 0.100 t1 60.000 0.200 - - - 10% 97.2 178.2 135.954 ✓
S: I2= 6.5 t2= 0.4 I2 0.650 t2 0.400 0.900 - - - 20% 0.016 0.576 0.420 ✓
I : I3= 10 I3 1.000 t3 - 1.600 - - - <50ms - 0.050 0.009 ✓

Panel : 01-02-OUSB-001-A1 Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
6 ACB1 MAIN 01-02-OUSB-001-A1 800 1,250 ACB E2.2N D/O Ekip Hi Touch LSIG L: I1= 0.79 t1= 20.00 I1 0.632 t1 20.000 - - 1.000 - 10% 51.75 94.93 72.528 ✓
S: I2= 1.40 t2= 0.18 I2 1.120 t2 0.180 - - 2.400 - 20% 0.1296 0.2376 0.183 ✓
I : I3= 7.00 I3 5.600 t3 - - - 8.000 - <30ms - 0.03 0.023 ✓
G : I4= - t4= - I4 t4 - - - - - 10% - - - -
7 ACB2 MAIN 01-02-IUSB-001-A1 800 1,250 ACB E2.2N D/O Ekip Hi Touch LSIG L: I1= 0.79 t1= 20.00 I1 0.632 t1 20.000 - - 1.000 - 10% 51.75 94.93 72.604 ✓
S: I2= 1.40 t2= 0.18 I2 1.120 t2 0.180 - - 2.400 - 20% 0.1296 0.2376 0.182 ✓
I : I3= 7.00 I3 5.600 t3 - - - 8.000 - <30ms - 0.03 0.028 ✓
G : I4= - t4= - I4 t4 - - - - - 10% - - - -
8 ACB3 TIE 800 1,250 ACB E2.2N D/O Ekip Hi Touch LSIG L: I1= 0.79 t1= 20.00 I1 0.632 t1 20.000 - - 1.000 - 10% 51.75 94.93 72.261 ✓
S: I2= 1.40 t2= 0.18 I2 1.120 t2 0.180 - - 2.400 - 20% 0.1296 0.2376 0.180 ✓
I : I3= 7.00 I3 5.600 t3 - - - 8.000 - <30ms - 0.03 0.021 ✓
G : I4= - t4= - I4 t4 - - - - - 10% - - - -
9 CB13 LOAD BANK (3000kW) 800 1,250 ACB E2.2N D/O Ekip Hi Touch LSIG L: I1= 0.63 t1= 12.00 I1 0.504 t1 12.000 - - 1.000 - 10% 51.75 94.93 27.483 ✓
S: I2= 1.40 t2= 0.18 I2 1.120 t2 0.180 - - 2.400 - 20% 0.1296 0.2376 0.181 ✓
I : I3= 7.00 I3 5.600 t3 - - - 8.000 - <30ms - 0.03 0.021 ✓
G : I4= - t4= - I4 t4 - - - - - 10% - - - -
10 CB1 01-02-OUSB-002-A1 250 250 MCCB XT4N250 R250 PLUG-IN Ekip LSI L: I1= 0.80 t1= 36.00 I1 0.200 t1 36.000 0.500 - - - 10% 37.35 68.42 51.766 ✓
S: I2= 2.50 t2= 0.10 I2 0.625 t2 0.100 2.250 - - - 20% 0.064 0.144 0.120 ✓
I : I3= - I3 t3 - - - - - <50ms - 0.050 - -
11 CB3 01-02-OUSB-004-A1 250 250 MCCB XT4N250 R250 PLUG-IN Ekip LSI L: I1= 0.60 t1= 36.00 I1 0.150 t1 36.000 0.500 - - - 10% 20.97 38.5 29.230 ✓
S: I2= 2.50 t2= 0.10 I2 0.625 t2 0.100 2.250 - - - 20% 0.064 0.144 0.008 ✓
I : I3= - I3 t3 - - - - - <50ms - 0.050 - -
12 CB7 01-02-MCC-001 (Chilled Water Pump & Controller) 800 800 MCCB T6N800 PR222/P-LSI R800 L: I1= 0.50 t1= 3.00 I1 0.400 t1 3.000 - - 0.800 - 10% 19.44 35.64 27.000 ✓
S: I2= 1.20 t2= 0.10 I2 0.960 t2 0.100 - - 2.400 - 20% 0.072 0.132 0.100 ✓
I : I3= 4.00 I3 3.200 t3 - - - 8.000 - <50ms - 0.050 0.020 ✓
13 CB8 SPARE 100 160 MCCB XT2N160 R100 PLUG-IN Ekip LSI L: I1= 1.00 t1= 60.00 I1 0.100 t1 60.000 0.200 - - - 10% 97.2 178.2 135.297 ✓
S: I2= 7.00 t2= 0.10 I2 0.700 t2 0.100 0.900 - - - 20% 0.064 0.144 0.110 ✓
I : I3= - I3 t3 - - - - - <50ms - 0.050 - -

15
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Panel : 01-02-OUSB-002-A1 Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
14 MCB MAIN 01-02-OUSB-002-A1 250 250 MCCB XT4N250 R250 PLUG-IN Ekip LSI L: I1= 0.8 t1= 36 I1 0.200 t1 36.000 0.500 - - - 10% 37.35 68.42
S: I2= 2.5 t2= 0.2 I2 0.625 t2 0.200 2.250 - - - 20% 0.128 0.288
I : I3= - I3 - t3 - - - - - <50ms - -
15 CB1 01-01-UDB-001-A 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.78 t1= 60 I1 0.049 t1 60.000 0.126 - - - 10% 59.13 108.46
S: I2= 5.5 t2= 0.1 I2 0.347 t2 0.100 0.567 - - - 20% 0.064 0.144
I : I3= - I3 - t3 - - - - - <50ms - -

Panel : 01-02-OUSB-004-A1 Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
16 MCB MAIN 01-02-OUSB-004-A1 250 250 MCCB XT4N250 R250 PLUG-IN Ekip LSI L: I1= 0.6 t1= 36 I1 0.150 t1 36.000 0.500 - - - 10% 20.97 38.5
S: I2= 2.5 t2= 0.2 I2 0.625 t2 0.200 2.250 - - - 20% 0.064 0.144
I : I3= - I3 - t3 - - - - - <50ms - -
17 CB1 CMS-A SERVER RACK 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.62 t1= 60 I1 0.039 t1 60.000 0.126 - - - 10% 37.35 68.53
S: I2= 5.5 t2= 0.05 I2 0.347 t2 0.050 0.567 - - - 20% 0.032 0.072
I : I3= - I3 - t3 - - - - - <50ms - -
18 CB2 BMS-A SERVER RACK 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.62 t1= 60 I1 0.039 t1 60.000 0.126 - - - 10% 37.35 68.53
S: I2= 5.5 t2= 0.05 I2 0.347 t2 0.050 0.567 - - - 20% 0.032 0.072
I : I3= - I3 - t3 - - - - - <50ms - -
19 CB10 SPARE 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.78 t1= 36 I1 0.049 t1 36.000 0.126 - - - 10% 35.46 65.01
S: I2= 5.5 t2= 0.05 I2 0.347 t2 0.050 0.567 - - - 20% 0.032 0.072
I : I3= - I3 - t3 - - - - - <50ms - -

L : Overload protection
S : Time-delayed overcurrent protection
I : Instantaneous overcurrent protection
G : Earth fault protection

I1 : Threshold Overload protection t1 : Trip time Overload protection


I2 : Threshold Time-delayed overcurrent protection t2 : Trip time Time-delayed overcurrent protection
I3 : Threshold Instantaneous overcurrent protection
I4 : Threshold Earth fault protection t4 : Trip time Earth fault protection

Time-Current curve LLL-LL @415V

3 2 1

1000s

No. Description In AF Breaker Type


1 MAIN 01-02-IUSB-001-A1 800 800 MCCB T6S800 D/O R800 PR222/DS LSI
100s
2 01-02-SUPS-001-A1 (UPS) 800 800 MCCB T6S800 D/O R800 PR222/DS LSI
3 SPARE 100 160 MCCB XT2S160 R100 PLUG-IN Ekip LSI

10s

1s

100ms

10ms

100mA 1A 10A 100A 1kA 10kA 100kA

16
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Time-Current curve LLL-LL @415V


2

4 3 1
No. Description In AF Breaker Type
1 MAIN 01-02-OUSB-001-A1 800 1,250 ACB E2.2N D/O Ekip Hi Touch LSIG
100s 2 LOAD BANK (3000kW) 800 1,250 ACB E2.2N D/O Ekip Hi Touch LSIG
3 01-02-MCC-001 (Chilled Water Pump & Controller) 800 800 MCCB T6N800 PR222/P-LSI R800
4 01-02-OUSB-004-A1 250 250 MCCB XT4N250 R250 PLUG-IN Ekip LSI

10s

1s

100ms

10ms

1A 10A 100A 1kA 10kA 100kA

Time-Current curve LLL-LL @415V

3 2 1

No. Description In AF Breaker Type


1000s
1 01-02-OUSB-002-A1 250 250 MCCB XT4N250 R250 PLUG-IN Ekip LSI
2 MAIN 01-02-OUSB-002-A1 250 250 MCCB XT4N250 R250 PLUG-IN Ekip LSI
100s 3 01-01-UDB-001-A 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI

10s

1s

100ms

10ms

100mA 1A 10A 100A 1kA 10kA 100kA

17
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Time-Current curve LLL-LL @415V

3 2 1

No. Description In AF Breaker Type


1000s
1 01-02-OUSB-004-A1 250 250 MCCB XT4N250 R250 PLUG-IN Ekip LSI
2 MAIN 01-02-OUSB-004-A1 250 250 MCCB XT4N250 R250 PLUG-IN Ekip LSI
3 SPARE 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI
100s

10s

1s

100ms

10ms

100mA 1A 10A 100A 1kA 10kA 100kA

18
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

TABLE OF DISCRIMINATION SETTING PROTECTION TRIP UNIT OF CIRCUIT BREAKER SIMULATION TEST

Panel : 01-02-LVSB-002-A (HVAC/HYD LOAD) Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
1 MCB MAIN 01-02-LVSB-002-A 800 800 MCCB T6N800 R800 D/O PR222/DS LSI L: I1= 0.62 t1= 18 I1 0.496 t1 18.000 - 1.600 - - 10% 44.82 82.17 62.272 ✓
S: I2= 8.2 t2= 0.25 I2 6.560 t2 0.250 - 7.200 - - 20% 0.18 4.428 0.219 ✓
I : I3= 10.5 I3 9.600 t3 - - 12.800 - - <50ms - 0.050 0.020 ✓
2 CB1 TH-BKK1-01-02-DB-007-A 160 160 MCCB XT2N160 R160 PLUG-IN Ekip LSI L: I1= 0.94 t1= 60 I1 0.150 t1 60.000 0.320 - - - 10% 85.86 157.3 119.766 ✓
S: I2= 6.5 t2= 0.4 I2 1.040 t2 0.400 1.280 - - - 20% 0.016 0.576 0.426 ✓
I : I3= 9 I3 1.440 t3 - 2.560 - - - <50ms - 0.050 0.005 ✓
3 CB3 TH-BKK1-01-02-DB-009-A 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.78 t1= 60 I1 0.049 t1 60.000 0.126 - - - 10% 59.13 108.46 82.187 ✓
S: I2= 6.5 t2= 0.4 I2 0.410 t2 0.400 0.504 - - - 20% 0.016 0.576 0.418 ✓
I : I3= 9 I3 0.567 t3 - 1.008 - - - <50ms - 0.050 0.003 ✓
4 CB4 TH-BKK1-01-02-WCU-001 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.5 t1= 60 I1 0.032 t1 60.000 0.126 - - - 10% 24.3 44.55 33.906 ✓
S: I2= 6.5 t2= 0.4 I2 0.410 t2 0.400 0.504 - - - 20% 0.016 0.576 0.426 ✓
I : I3= 9 I3 0.567 t3 - 1.008 - - - <50ms - 0.050 0.004 ✓
5 CB6 TH-BKK1-01-02-WCU-005 25 160 MCCB XT2N160 R25 PLUG-IN Ekip LSI L: I1= 0.8 t1= 60 I1 0.020 t1 60.000 0.050 - - - 10% 62.19 114.4 86.438 ✓
S: I2= 6.5 t2= 0.4 I2 0.163 t2 0.400 0.162 - - - 20% 0.016 0.576 0.42 ✓
I : I3= 9 I3 0.225 t3 - 0.250 - - - <50ms - 0.050 0.001 ✓
6 CB12 TH-BKK1-01-02-GBATT-002 100 160 MCCB XT2N160 R100 PLUG-IN Ekip LSI L: I1= 0.8 t1= 60 I1 0.080 t1 60.000 0.200 - - - 10% 62.19 114.4 86.437 ✓
S: I2= 6.5 t2= 0.4 I2 0.650 t2 0.400 0.800 - - - 20% 0.016 0.576 0.417 ✓
I : I3= 9 I3 0.900 t3 - 1.600 - - - <50ms - 0.050 0.004 ✓

L : Overload protection
S : Time-delayed overcurrent protection
I : Instantaneous overcurrent protection
G : Earth fault protection

I1 : Threshold Overload protection t1 : Trip time Overload protection


I2 : Threshold Time-delayed overcurrent protection t2 : Trip time Time-delayed overcurrent protection
I3 : Threshold Instantaneous overcurrent protection
I4 : Threshold Earth fault protection t4 : Trip time Earth fault protection

19
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Time-Current curve LLL-LL @415V


6 5 4 3 2 1

1000s No. Description In AF Breaker Type


1 MAIN 01-02-MSB-001-A1 5,000 5,000 ACB E6.2H D/O Ekip Hi Touch LSIG
2 01-03-IUSB-001-A1 800 800 MCCB T6L800 D/O R800 PR222/DS LSI
3 TH-BKK1-01-02-DB-007-A 160 160 MCCB XT2N160 R160 PLUG-IN Ekip LSI
100s 4 TH-BKK1-01-02-GBATT-002 100 160 MCCB XT2N160 R100 PLUG-IN Ekip LSI
5 TH-BKK1-01-02-DB-009-A 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI
6 TH-BKK1-01-02-WCU-005 25 160 MCCB XT2N160 R25 PLUG-IN Ekip LSI

10s

1s

100ms

10A 100A 1kA 10kA 100kA

20
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

TABLE OF DISCRIMINATION SETTING PROTECTION TRIP UNIT OF CIRCUIT BREAKER SIMULATION TEST

Panel : 01-08-LVSB-002-A Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
1 MCB MAIN 01-08-LVSB-002-A 400 400 MCCB T5N400 PLUG-IN R400 PR222/DS LSI L: I1= 0.6 t1= 18 I1 0.240 t1 18.000 - 0.800 - - 10% 42.03 77 58.319 ✓
S: I2= 8.2 t2= 0.25 I2 3.280 t2 0.250 - 3.600 - - 20% 0.18 4.152 0.25 ✓
I : I3= - I3 - t3 - - - - - <50ms - - - -
2 CB1 01-08-DB-003-A 100 160 MCCB XT2N160 R100 PLUG-IN Ekip LSI L: I1= 1 t1= 60 I1 0.100 t1 60.000 0.200 - - 10% 97.2 178.2 135.36 ✓
S: I2= 8 t2= 0.1 I2 0.800 t2 0.100 0.900 - - - 20% 0.064 0.144 0.108 ✓
I : I3= - I3 - t3 - - - - - <50ms - - - -

L : Overload protection
S : Time-delayed overcurrent protection
I : Instantaneous overcurrent protection
G : Earth fault protection

I1 : Threshold Overload protection t1 : Trip time Overload protection


I2 : Threshold Time-delayed overcurrent protection t2 : Trip time Time-delayed overcurrent protection
I3 : Threshold Instantaneous overcurrent protection
I4 : Threshold Earth fault protection t4 : Trip time Earth fault protection

21
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Time-Current curve LLL-LL @415V

3 2 1
No. Description In AF Breaker Type
1 MAIN 01-02-MSB-001-A1 5,000 5,000 ACB E6.2H D/O Ekip Hi Touch LSIG
1000s
2 MAIN 01-08-LVSB-002-A 400 400 MCCB T5N400 PLUG-IN R400 PR222/DS LSI
3 01-08-DB-003-A 160 160 MCCB XT2N160 R100 PLUG-IN Ekip LSI

100s

10s

1s

100ms

10ms

100mA 1A 10A 100A 1kA 10kA 100kA

22
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

TABLE OF DISCRIMINATION SETTING PROTECTION TRIP UNIT OF CIRCUIT BREAKER SIMULATION TEST

Panel : 01-01-LVSB-001-A Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
1 MCB MAIN 01-01-LVSB-001-A 250 250 MCCB XT4N250 R250 PLUG-IN Ekip LSI L: I1= 0.8 t1= 60 I1 0.200 t1 60.000 0.500 - - - 10% 62.19 114.4 86.375 ✓
S: I2= 5.5 t2= 0.4 I2 1.375 t2 0.400 2.250 - - - 20% 0.256 0.576 0.411 ✓
I : I3= - I3 - t3 - - - - - <50ms - - - -
2 CB1 01-01-DB-001-A 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.8 t1= 60 I1 0.050 t1 60.000 0.126 - - - 10% 62.19 114.4 86.375 ✓
S: I2= 8 t2= 0.2 I2 0.504 t2 0.200 0.567 - - - 20% 0.128 0.288 0.208 ✓
I : I3= - I3 - t3 - - - - - <50ms - - - -
3 CB2 01-01-DB-002-A 100 160 MCCB XT2N160 R100 PLUG-IN Ekip LSI L: I1= 1 t1= 60 I1 0.100 t1 60.000 0.200 - - - 10% 97.2 178.2 135.687 ✓
S: I2= 8 t2= 0.2 I2 0.800 t2 0.200 0.900 - - - 20% 0.128 0.288 0.215 ✓
I : I3= - I3 - t3 - - - - - <50ms - - - -

Panel : 01-02-LVSB-001-A Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
4 MCB MAIN 01-02-LVSB-001-A 400 400 MCCB T5N400 PLUG-IN R400 PR222/DS LSI L: I1= 1 t1= 18 I1 0.400 t1 18.000 - 0.800 - - 10% 117 213.4 162.000 ✓
S: I2= 7 t2= 0.5 I2 2.800 t2 0.500 - 3.600 - - 20% 0.36 0.66 0.500 ✓
I : I3= 12 I3 4.80 t3 - - 6.400 - - <50ms - 0.050 0.020 ✓
5 CB1 01-02-DB-001-A 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.8 t1= 60 I1 0.050 t1 60.000 0.126 - - - 10% 62.19 114.4 86.438 ✓
S: I2= 8 t2= 0.2 I2 0.504 t2 0.200 0.567 - - - 20% 0.128 0.288 0.211 ✓
I : I3= - I3 - t3 - - - - - <50ms - - - -
6 CB2 01-02-DB-002-A 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.8 t1= 60 I1 0.050 t1 60.000 0.126 - - - 10% 62.19 114.4 86.734 ✓
S: I2= 8 t2= 0.2 I2 0.504 t2 0.200 0.567 - - - 20% 0.128 0.288 0.217 ✓
I : I3= - I3 - t3 - - - - - <50ms - - - -

L : Overload protection
S : Time-delayed overcurrent protection
I : Instantaneous overcurrent protection
G : Earth fault protection

I1 : Threshold Overload protection t1 : Trip time Overload protection


I2 : Threshold Time-delayed overcurrent protection t2 : Trip time Time-delayed overcurrent protection
I3 : Threshold Instantaneous overcurrent protection
I4 : Threshold Earth fault protection t4 : Trip time Earth fault protection

23
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Time-Current curve LLL-LL @415V


5 4 3 2 1

No. Description In AF Breaker Type


1000s
1 MAIN 01-02-MSB-001-A1 5,000 5,000 ACB E6.2H D/O Ekip Hi Touch LSIG
2 1-02-BW-001-A1 (BUSWAY 1000A) 1,000 1,250 ACB E2.2S D/O Ekip Hi Touch LSIG
3 MAIN 01-01-LVSB-001-A 250 250 MCCB XT4N250 R250 PLUG-IN Ekip LSI
100s
4 01-01-DB-002-A 100 160 MCCB XT2N160 R100 PLUG-IN Ekip LSI
5 01-01-DB-001-A 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI

10s

1s

100ms

10ms

100mA 1A 10A 100A 1kA 10kA 100kA

Time-Current curve LLL-LL @415V


4 3 2 1

No. Description In AF Breaker Type

1000s 1 MAIN 01-02-MSB-001-A1 5,000 5,000 ACB E6.2H D/O Ekip Hi Touch LSIG
2 1-02-BW-001-A1 (BUSWAY 1000A) 1,000 1,250 ACB E2.2S D/O Ekip Hi Touch LSIG
3 MAIN 01-02-LVSB-001-A 400 400 MCCB T5N400 PLUG-IN R400 PR222/DS LSI

100s 4 01-02-DB-002-A 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI

10s

1s

100ms

10ms

100mA 1A 10A 100A 1kA 10kA 100kA

24
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

25
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

TABLE OF DISCRIMINATION SETTING PROTECTION TRIP UNIT OF CIRCUIT BREAKER SIMULATION TEST

Panel : 01-03-IUSB-001-A1 Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
1 MCB Main Incoming From 01-02-MSB-001-A1 800 800 MCCB T6L800 D/O R800 PR222/DS LSI L: I1= 1 t1= 18 I1 0.800 t1 18.000 - 1.600 - - 10% 117 213.4 162.000 ✓
S: I2= 5.8 t2= 0.5 I2 4.640 t2 0.500 - 7.200 - - 20% 0.36 0.66 0.500 ✓
I : I3= 10.5 I3 8.400 t3 - - 12.800 - - <50ms - 0.050 0.020 ✓
2 CB1 TH-BKK1-01-03-SUPS-001-A1 (Q1) 800 800 MCCB T6L800 D/O R800 PR222/DS LSI L: I1= 0.78 t1= 9 I1 0.624 t1 9.000 - 1.600 - - 10% 35.46 65.01 49.280 ✓
S: I2= 2.4 t2= 0.25 I2 1.920 t2 0.250 - 4.000 - - 20% 0.180 0.330 0.250 ✓
I : I3= 9 I3 7.200 t3 - - 12.800 - - <50ms - 0.050 0.020 ✓
3 CB2 TH-BKK1-01-03-SUPS-001-A1 (Q2) 800 800 MCCB T6L800 D/O R800 PR222/DS LSI L: I1= 0.78 t1= 9 I1 0.624 t1 9.000 - 1.600 - - 10% 35.46 65.01 49.280 ✓
S: I2= 2.4 t2= 0.25 I2 1.920 t2 0.250 - 4.000 - - 20% 0.180 0.330 0.250 ✓
I : I3= 9 I3 7.200 t3 - - 12.800 - - <50ms - 0.050 0.020 ✓
4 CB3 TH-BKK1-01-03-SUPS-001-A1 (By pass) 800 800 MCCB T6L800 D/O R800 PR222/DS LSI L: I1= 0.78 t1= 9 I1 0.624 t1 9.000 - 1.600 - - 10% 35.46 65.01 49.280 ✓
S: I2= 2.4 t2= 0.25 I2 1.920 t2 0.250 - 4.000 - - 20% 0.180 0.330 0.250 ✓
I : I3= 9 I3 7.200 t3 - - 12.800 - - <50ms - 0.050 0.020 ✓
5 CB4 TH-BKK1-01-03-LVSB-002-A 400 400 MCCB T5L400 R400 PLUG-IN PR222/DS LSI L: I1= 0.74 t1= 18 I1 0.296 t1 18.000 - 0.800 - - 10% 63.9 116.6 88.711 ✓
S: I2= 4.2 t2= 0.1 I2 1.680 t2 0.100 - 3.600 - - 20% 0.072 0.132 0.100 ✓
I : I3= 12 I3 4.800 t3 - - 6.400 - - <50ms - 0.050 0.020 ✓
6 CB6 TH-BKK1-01-03-BM-005-A1 63 160 MCCB XT2L160 R63 PLUG-IN Ekip LSI L: I1= 0.62 t1= 60 I1 0.039 t1 60.000 0.126 - - - 10% 37.35 68.53 52.000 ✓
S: I2= 6.5 t2= 0.2 I2 0.410 t2 0.200 0.567 - - - 20% 0.016 0.288 0.215 ✓
I : I3= 10 I3 0.63 t3 - 0.945 - - - <50ms - 0.050 0.001 ✓

26
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Panel : 01-03-OUSB-002-A1 Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
7 ACB1 Main Form 01-03-SUPS-002-A1 800 1,250 ACB E2.2N D/O Ekip Hi Touch LSIG L: I1= 0.79 t1= 20 I1 0.632 t1 20.000 - 1.000 - - 10% 51.75 94.93 72.491 ✓
S: I2= 1.4 t2= 0.18 I2 1.120 t2 0.180 - 4.000 - - 20% 0.130 0.238 0.182 ✓
I : I3= 7 I3 5.600 t3 - - 12.800 - - <30ms - 0.030 0.029 ✓
8 ACB2 Main From 01-03-IUSB-001-A1 800 1,250 ACB E2.2N D/O Ekip Hi Touch LSIG L: I1= 0.79 t1= 20 I1 0.632 t1 20.000 - 1.000 - - 10% 51.75 94.93 72.621 ✓
S: I2= 1.4 t2= 0.18 I2 1.120 t2 0.180 - 4.000 - - 20% 0.130 0.238 0.183 ✓
I : I3= 7 I3 5.600 t3 - - 12.800 - - <30ms - 0.030 0.026 ✓
9 CB1 TH-BKK1-01-03-OUSB-003-A1 400 400 MCCB T5N400 R400 PLUG-IN PR222/DS LSI L: I1= 0.74 t1= 6 I1 0.296 t1 6.000 - 0.800 - - 10% 21.33 39.05 29.570 ✓
S: I2= 3 t2= 0.1 I2 1.200 t2 0.100 - 3.600 - - 20% 0.01 0.132 1.000 ✓
I : I3= 9.5 I3 3.800 t3 - - 6.400 - - <50ms - 0.050 0.020 ✓
10 CB2 TH-BKK1-01-03-OUSB-004-A1 400 400 MCCB T5N400 R400 PLUG-IN PR222/DS LSI L: I1= 0.74 t1= 6 I1 0.296 t1 6.000 - 0.800 - - 10% 21.33 39.05 29.570 ✓
S: I2= 3 t2= 0.1 I2 1.200 t2 0.100 - 3.600 - - 20% 0.01 0.132 0.100 ✓
I : I3= 9.5 I3 3.800 t3 - - 6.400 - - <50ms - 0.050 0.020 ✓
11 CB4 TH-BKK1-01-03-BM-006-A1 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.62 t1= 60 I1 0.039 t1 60.000 0.126 - - - 10% 37.35 68.53 51.797 ✓
S: I2= 5.5 t2= 0.4 I2 0.347 t2 0.400 0.567 - - - 20% 0.016 0.576 0.424 ✓
I : I3= 10 I3 0.630 t3 - 0.945 - - - <50ms - 0.050 0.010 ✓

Panel : 01-03-OUSB-003-A1 Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
12 MCB Main Form 01-03-OUSB-002-A1 400 400 MCCB T5N400 R400 PLUG-IN PR222/DS LSI L: I1= 0.74 t1= 6 I1 0.296 t1 6.000 - 0.800 - - 10% 21.33 39.05 29.570 ✓
S: I2= 3 t2= 0.1 I2 1.200 t2 0.100 - 3.600 - - 20% 0.010 0.132 0.100 ✓
I : I3= 9.5 I3 3.800 t3 - - 6.400 - - <50ms - 0.050 0.020 ✓
13 CB13 TH-BKK1- 01-03-CCU-013 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.5 t1= 60 I1 0.032 t1 60.000 0.126 - - - 10% 24.3 44.55 33.890 ✓
S: I2= 5.5 t2= 0.05 I2 0.347 t2 0.050 0.567 - - - 20% 0.032 0.072 0.072 ✓
I : I3= - I3 - t3 - - - - - <50ms - 0.050 - -
14 CB22 TH-BKK1-01-03-CCU-044 25 160 MCCB XT2N160 R25 PLUG-IN Ekip LSI L: I1= 0.8 t1= 60 I1 0.020 t1 60.000 0.050 - - - 10% 0.778 1.43 86.547 ✓
S: I2= 5.5 t2= 0.05 I2 0.138 t2 0.050 0.225 - - - 20% 0.016 0.048 0.006 ✓
I : I3= - I3 - t3 - - - - - <50ms - 0.050 - -
15 CB26 TH-BKK1-01-03-CCU-050 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.5 t1= 60 I1 0.032 t1 60.000 0.126 - - - 10% 24.3 44.55 33.968 ✓
S: I2= 5.5 t2= 0.05 I2 0.347 t2 0.050 0.567 - - - 20% 0.032 0.072 0.062 ✓
I : I3= - I3 - t3 - - - - - <50ms - 0.050 - -

Panel : 01-03-OUSB-004-A1 Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
16 MCB Main Form 01-03-OUSB-002-A1 400 400 MCCB T5N400 R400 PLUG-IN PR222/DS LSI L: I1= 0.74 t1= 6 I1 0.296 t1 6.000 - 0.800 - - 10% 21.33 39.05 29.570 ✓
S: I2= 3 t2= 0.1 I2 1.200 t2 0.100 - 3.600 - - 20% 0.010 0.132 0.100 ✓
I : I3= 9.5 I3 3.800 t3 - - 6.400 - - <50ms - 0.050 0.020 ✓
17 CB17 TH-BKK1- 01-03-CCU-037 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.5 t1= 60 I1 0.032 t1 60.000 0.126 - - - 10% 24.3 44.55 33.969 ✓
S: I2= 5.5 t2= 0.05 I2 0.347 t2 0.050 0.567 - - - 20% 0.032 0.072 0.072 ✓
I : I3= - I3 - t3 - - - - - <50ms - 0.050 - -
18 CB24 TH-BKK1- 01-03-CCU-054 25 160 MCCB XT2N160 R25 PLUG-IN Ekip LSI L: I1= 0.8 t1= 60 I1 0.020 t1 60.000 0.050 - - - 10% 0.778 1.43 86.188 ✓
S: I2= 5.5 t2= 0.05 I2 0.138 t2 0.050 0.225 - - - 20% 0.016 0.048 0.007 ✓
I : I3= - I3 - t3 - - - - - <50ms - 0.050 - -
19 CB28 TH-BKK1- 01-03-CCU-052 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI L: I1= 0.5 t1= 60 I1 0.032 t1 60.000 0.126 - - - 10% 24.3 44.55 34.150 ✓
S: I2= 5.5 t2= 0.05 I2 0.347 t2 0.050 0.567 - - - 20% 0.032 0.072 0.068 ✓
I : I3= - I3 - t3 - - - - - <50ms - 0.050 - -

L : Overload protection
S : Time-delayed overcurrent protection
I : Instantaneous overcurrent protection
G : Earth fault protection

I1 : Threshold Overload protection t1 : Trip time Overload protection


I2 : Threshold Time-delayed overcurrent protection t2 : Trip time Time-delayed overcurrent protection
I3 : Threshold Instantaneous overcurrent protection
I4 : Threshold Earth fault protection t4 : Trip time Earth fault protection

27
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Time-Current curve LLL-LL @415V

5 4 3 2 1

No. Description In AF Breaker Type


1000s
1 MAIN 01-02-MSB-001-A1 5,000 5,000 ACB E6.2H D/O Ekip Hi Touch LSIG
2 Main Incoming From 01-02-MSB-001-A1 800 800 MCCB T6L800 D/O R800 PR222/DS LSI
3 TH-BKK1-01-03-SUPS-001-A1 (Q1) 800 800 MCCB T6L800 D/O R800 PR222/DS LSI
100s
4 TH-BKK1-01-03-LVSB-002-A 400 400 MCCB T5L400 R400 PLUG-IN PR222/DS LSI
5 TH-BKK1-01-03-BM-005-A1 63 160 MCCB XT2L160 R63 PLUG-IN Ekip LSI

10s

1s

100ms

10ms

100mA 1A 10A 100A 1kA 10kA 100kA

Time-Current curve LLL-LL @415V


4 3 2 1

No. Description In AF Breaker Type


1000s
1 TH-BKK1-01-03-SUPS-001-A1 (Q1) 800 800 MCCB T6L800 D/O R800 PR222/DS LSI
2 Main Form 01-03-SUPS-002-A1 800 1,250 ACB E2.2N D/O Ekip Hi Touch LSIG
3 TH-BKK1-01-03-OUSB-003-A1 400 400 MCCB T5N400 PLUG-IN R400 PR222/DS LSI
100s
4 TH-BKK1- 01-03-CCU-052 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI

10s

1s

100ms

10ms

100mA 1A 10A 100A 1kA 10kA 100kA

28
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Time-Current curve LLL-LL @415V

3 2 1

No. Description In AF Breaker Type


1000s
1 Main Form 01-03-OUSB-002-A1 400 400 MCCB T5N400 R400 PLUG-IN PR222/DS LSI
2 TH-BKK1- 01-03-CCU-013 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI
3 TH-BKK1-01-03-CCU-044 25 160 MCCB XT2N160 R25 PLUG-IN Ekip LSI
100s

10s

1s

100ms

10ms

100mA 1A 10A 100A 1kA 10kA 100kA

Time-Current curve LLL-LL @415V

3 2 1

No. Description In AF Breaker Type


1000s
1 Main Form 01-03-OUSB-002-A1 400 400 MCCB T5N400 R400 PLUG-IN PR222/DS LSI
2 TH-BKK1- 01-03-CCU-013 63 160 MCCB XT2N160 R63 PLUG-IN Ekip LSI
3 TH-BKK1-01-03-CCU-044 25 160 MCCB XT2N160 R25 PLUG-IN Ekip LSI
100s

10s

1s

100ms

10ms

100mA 1A 10A 100A 1kA 10kA 100kA

29
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

TABLE OF DISCRIMINATION SETTING PROTECTION TRIP UNIT OF CIRCUIT BREAKER SIMULATION TEST

Panel : 01-03-LVSB-002-A Setting Current Injected Simulation (kA) Duration (Sec) Tripped time (sec) Result CTA
Item Breaker No. Description In AF Breaker Type Setting Current (kA) time (Sec) In < 250 In <= 800 <=2500 > 2500 Tolerance Min Max PASS FAIL VERIFY
1 MCB Main Incoming From 01-03-IUSB-001-A1 400 400 MCCB T5N400 R400 PLUG-IN PR222/DS LSI L: I1= 0.74 t1= 18 I1 0.296 t1 18.000 - 0.800 - - 10% 82.26 150.7 88.711 ✓
S: I2= 4.2 t2= 0.10 I2 1.680 t2 0.100 - 3.600 - - 20% 0.072 0.132 0.1 ✓
I: I3= 12 I3 4.800 t3 - - 6.400 - - <50ms - 0.050 0.020 ✓
2 CB1 TH-BKK1-01-03-DB-007-A 100 160 MCCB XT2N160 R100 PLUG-IN Ekip LSI L: I1= 1 t1= 60 I1 0.100 t1 60.000 0.200 - - - 10% 97.2 178.2 135.297 ✓
S: I2= 8 t2= 0.05 I2 0.800 t2 0.050 0.900 - - - 20% 0.016 0.072 0.069 ✓
I: I3= - I3 - t3 - - - - - <50ms - - - -
3 CB2 TH-BKK1-01-03-MCP-004-A 160 160 MCCB XT2N160 R160 PLUG-IN Ekip LSI L: I1= 0.92 t1= 60 I1 0.147 t1 60.000 0.320 - - - 10% 82.26 150.7 114.75 ✓
S: I2= 5.5 t2= 0.05 I2 0.880 t2 0.050 1.440 - - - 20% 0.032 0.072 0.077 ✓
I: I3= - I3 - t3 - - - - - <50ms - - - -

L : Overload protection
S : Time-delayed overcurrent protection
I : Instantaneous overcurrent protection
G : Earth fault protection

I1 : Threshold Overload protection t1 : Trip time Overload protection


I2 : Threshold Time-delayed overcurrent protection t2 : Trip time Time-delayed overcurrent protection
I3 : Threshold Instantaneous overcurrent protection
I4 : Threshold Earth fault protection t4 : Trip time Earth fault protection

30
DISCRIMINATION
BUILDING LOAD (02-MSB-A1)

Time-Current curve LLL-LL @415V


5 4 3 2 1

1000s No. Description In AF Breaker Type


1 MAIN 01-02-MSB-001-A1 5,000 5,000 ACB E6.2H D/O Ekip Hi Touch LSIG
2 01-03-IUSB-001-A1 800 800 MCCB T6L800 D/O R800 PR222/DS LSI
3 Main Incoming From 01-03-IUSB-001-A1 400 400 MCCB T5N400 R400 PLUG-IN PR222/DS LSI
100s
4 TH-BKK1-01-03-MCP-004-A 160 160 MCCB XT2N160 R160 PLUG-IN Ekip LSI
5 TH-BKK1-01-03-DB-007-A 100 160 MCCB XT2N160 R100 PLUG-IN Ekip LSI

10s

1s

100ms

10ms

1A 10A 100A 1kA 10kA 100kA

31