Load Schedule Data Rack

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

NAME: POWER PANEL MAIN: 50AT,2P

ENCLOSURE: NEMA 1 NEUTRAL BUSBAR


MOUNTING: SURFACE MOUNTED GROUND BUSBAR

CONNECTED LOAD
CIRCUIT OVERCURRENT PROTECTION
LOAD DESCIRTION VOLTS CONDUCTOR CONDUIT
NO. VA AMP
AT AF KAIC P TYPE
1 RACK 2 230 6400 27.83 30 50 10 1 BOLT ON 3-5.5mm² THHN 15mmØ IMC
2 RACK 4 230 4400 19.13 20 50 10 1 BOLT ON 3-3.5mm² THHN 15mmØ IMC
3 SPARE 230 1000 4.35 20 50 10 1 BOLT ON - -
4 SPARE 230 1000 4.35 20 50 10 1 BOLT ON - -

TOTAL 12800 55.65


@ 80% Demand Factor
ITOTAL = 55.65 *80% USE = 2 - 14sqmm + 1 - 8.0sqmm THHN Wire in 32Ø IMC Pipe
ITOTAL = = 44.52 AMPS