Professional Documents
Culture Documents
LAB01
LAB01
OBJECTIVES
1. Understand the basic concepts of BMS and the operation of Direct Digital Controller
(DDC).
2. Configure and program the DDC for the given applications or control strategies.
EQUIPMENT
1. TAC XENTA Master Controller, TAC XENTA I/O Modules (ending with A meaning
providing Analogue/Universal input channels), Mimic panel and I/O Console.
2. PC preloaded with TAC Vista Server/Workstation and Menta DDC Programming tool.
________________________________________________________________________________________
Page 1 - 1 LAB-01
TAC Vista Workstation
Loytec L-IP
LON
Master DDC
Xenta 302
MIMIC
PANEL
M1
AND AI Xenta 421A
AO
DI I/O Expansion
I/O DO
Modules
CONSOLE M2
Xenta 451A
2.1 To Configure the Xenta 403 Controller with Xenta 421A and Xenta 451A(I/O
expansion) modules.
Notes: 1 no XENTA 302 Master Controller is connected to 1 no Xenta 421A and Xenta
451A via LON, expanded by 2 I/O modules: Xenta 421A (4 Universal Inputs and
5 Digital Outputs); Xenta 451A (4 Universal Inputs and 2 Analog Outputs).
1. Launch the MENTA Programming Tool on the desktop. (Alternatively, click Start>All
Programs>Schneider Electric>TAC Tools 5.1.7>Menta)
2. From the Menu select OPTIONS>DEVICE SPECIFICATIONS.
3. In the TYPE field, select the Master DDC to be programmed (Xenta 302).
4. Set the System and Hardware Versions (3.7 and 2) and click OK button to continue.
5. In the I/O EXPANSION Table add desired IO modules (421A, 451A).
6. Workspace is now ready for programming.
________________________________________________________________________________________
Page 1 - 2 LAB-01
3.0. DDC CONTROL APPLICATION
When the alarm is received (DI1), turn on the Buzzer (DO1). {When DI-1 is true, DO-1 will be
activated.}
When the alarm is received (DI1), turn on the Buzzer (DO1) and Alert flashing light (DO2)
simultaneously. {When DI-1 is true, both DO-1 and DO-2 will be activated simultaneously.}
Flashing Light
DI1 DO3 DO4
Trip Alarm
1 1 1
A On/Off B
On= trip alarm
0 0 0
Alarm Buzzer
Exercise 1.3: Control Logic for multi inputs and single output.
________________________________________________________________________________________
Page 1 - 3 LAB-01
When the pump is at "BMS" or "Auto" mode (DI-2) and it is also a duty pump (DI-3), then turn
on the pump (DO-5) when required. {When both DI-2 and DI-3 are true, DO-5 will be
activated.}
Exercise 1.4: Control Logic for multi inputs and single output.
When either pump 1 trip alarm (DI-4) or pump 2 trip alarm (DI-5) comes in, Standby Pump will
take over the duty (DO-6). {When either DI-4 or DI-5 is true, DO-6 will be activated.}
Pump 1 Trip Alarm => DI4 M1(411), MOD 8 X4, ( “Trip alm “= 1)
Pump 2 Trip Alarm => DI5 M1(411), MOD 8 X5, ( “Trip alm “= 1)
Standby Pump Command => DO6 M2(421A), MOD 1 K4 (CH-2 TRIP)
Exercise 1.5: Control Logic for multi inputs and single output.
When the condition [(DI-2 AND DI-3) AND (DI-4 OR DI-5)] is true, and DO-7 will turn on.
DI2
DI3 DI4
On/Off DO 7
On= [(DI2 & DI3)&(DI4 or DI5)]
DI5
________________________________________________________________________________________
Page 1 - 4 LAB-01
DI2 DI3 DI4 DI5 DO7
1 1 1 1 1
1 1 1 0 1
1 1 0 1 1
0 1 1 1 0
0 1 1 0 0
0 1 0 1 0
1 0 1 1 0
1 0 1 0 0
1 0 0 1
0 1
Exercise 1.6:
In a pharmaceutical factory, system starts command a signal to start up pump 1 first. After
running pump 1 for 5 sec, then start pump 2. After running pump 2 for 5 sec, then start pump 3.
Exercise 1.7:
In a pharmaceutical factory, system starts command a signal to start up pump 1 first. After
running pump 1 for 5 sec, then start pump 2. After running pump 2 for 5 sec, then start pump 3.
Any of the running pumps trips out, start stand-by pump 4 with 3 sec delay.
________________________________________________________________________________________
Page 1 - 5 LAB-01