Professional Documents
Culture Documents
2.D.C Track Circuit
2.D.C Track Circuit
TRACK CIRCUIT
INTRODUCTION:- In a track circuit, a portion of rail track is electrically
isolated from adjoining rails and included in a circuit to energise a relay. The
occupation or vacancy of the track portion is detected by the condition of track
relay. The length of the track confined within one circuit depends on its working
feasibility and required separation between two running or stalled vehicles on the
track.
Two types of track circuit were devised. One is continuously live and is called a
„CLOSED TRACK CIRCUIT‟. The other one is made live only when occupied by
vehicles and is called an „OPEN TRACK CIRCUIT‟.
According to the nature of supply, the track circuits are categorised as. (1) D.C.
Track Circuits (2) A.C. Track Circuits and (3) Electronic Track Circuit.
OPEN TRACK CIRCUIT:-
The circuit gets completed when the track is occupied through the net resistance of
the vehicle axles occupying the track circuit.
In this type track circuit, if any connection breaks, its occupation goes undetected.
Hence it is used only for limited purpose where its failure does not lead to unsafe
conditions. See Fig.-1.
2) Relay voltage not more than 85 % of its D.A. value when TSR of 0.5 Ohms
is applied. Because,
(a) To have adequate contact pressure and low contact resistance .
(b) To keep the relay energised even when the battery voltage reduces further
( within certain limits ).
3) Relay voltage not less than 125 % 0f P.U. Value when R B is normal and
battery voltage is normal. Because,
a) The percentage release of the track relay reduces by 10 % of the original
value after 10 Lakh operations.
RB
TR
Minim V.R 125 % of
rated P.U
value
:: 5 ::
STAGGERING OF ADJOINING TRACK CIRCUIT RAIL POLARITIES AND
THEIR IMPORTANCE :-
The arrangement shown above in Fig-6, similar feed polarities are connected to
the adjoining track circuit rails. Here, failure of one of the two block joints No.1 or
No.2 can go undetected as it does not drop the track relay on either side. But
later, if the second block joint also fails, both the track circuit feeds come in
parallel.
When 1T is shunted by a vehicle at the feed end, its own feed is effectively
shunted. But 1TR may not drop due to its proximity to the feed of 2T, while the
shunt is remotely connected making it less effective. This is an unsafe condition
which should be avoided.
And in Fig-7, the polarities of track feed across the block joints in between are not
similar. So, when both the block joints No.1 & No.2 fail, both the track feeds get
connected, +ve to -ve and -ve to +ve with high circulating current in between. The
track relays 1TR and 2TR also come across this circuit separately in parallel. With
this, the voltage across the relays gets reduced. As a result, either 1TR or 2TR or
both may drop, according to the fall of track voltage, even without a shunt across .
However, the track relay across which there is a shunt, can not pick up in any
case.
Hence, to make the track circuit working safe at the time of block joint failures, it is
necessary that the track feed polarities are staggered in continuously track
circuited sections.
BLOCK JOINTS (INSULATED RAIL JOINTS)
Two types of these joints are presently in use, (i) Nylon Insulated Rail joints
and (ii) Glued Rail joints.
NYLON INSULATED RAIL JOINTS : In this type ,insulated components are
supplied by the S&T department, which have to be inserted in the rail joint when
track circuit is being installed.
The insulation components of the rail joint are :
(i) End post. 1 No.
(ii) Left hand Side channels 2 No.
(iii) Right hand Side channels 2 No.
(iv) Ferrules or Bushes 8 No.
(v) Nylon backing plates. 4 No.
(vi) Iron backing plates. 4 No.
These insulated components are available in different sizes to suit different
sizes of Rails, Viz. 60 Kg , 52 Kg , 90 R etc.
Certain precautions have to be taken while installing and maintaining these
block joints as detailed below :-
i) The rail ends at these joints shall be cut straight as otherwise, the nylon end
post may break very quickly.
ii) All the holes on the rails shall be drilled at the same height.
:: 6 ::
iii) The holes in the rails and in fish plates shall be in correct alignment. Bolts
shall not be forced into the rails, nor shall they be bent and pushed in as the
bushes can crushed.
iv) Rail chairs are replaced by steel bearing plates on one sleeper each holding
rails on either side of the joint. These plates shall be fixed sufficiently clear
of rail ends to avoid their short circuiting.
v) Dog spikes that hold the bearing plates on to sleepers shall not touch the
fish plates and they shall be tightly driven in the sleepers.
vi) Packing of a couple of sleepers on either side of these joints shall always be
good and no water logging shall be allowed near them.
vii) The fish bolts of these joints should not roll due to swing under the traffic.
For this, the steel backing plates shall be properly bent on the sides to hold
the nuts and bolt heads.
MAINTENANCE OF GLUED JOINTS:
1. The ballast used on track in the vicinity of these joints shall be cleaned to
ensure efficient packing and drainage. Care must be taken to see that the
ballast is clear of rails and rail fastenings.
2. The joint does not need any special maintenance than that required for
normal track.
3. At least 10 sleeper on the either side of the joint must be well packed before
the joint is instead to avoid damage of the rail.
4. While welding the joint with adjoining rails, the heat shall not spread to the
joint. Heating appliances shall not be applied at a distance of less than 1
mtr. From the joint.
TESTING OF GLUED JOINTS:
Insulation Resistance of glued joint is tested,
In Dry condition : Resistance shall not be less than 25 Mega ohms when
100 V D.C is applied across the joint by a 100 V D.C megger.
In wet condition : Resistance shall not be less than 3 Kilo ohms when 100
V DC. is applied across the joint by a 100 V D.C megger.
ADDITIONAL INSULATIONS ON POINT TURNOUTS IN A TRACK CIRCUIT:
(1) Two or three William's stretcher bars provided on point turnouts have to be
insulated in the middle to avoid a direct short across the track. Two half pieces of
each stretcher are joined with two small support plates and three bolts. The
insulation components of each stretcher bar are:-
(i) Nylon Backing plates 2 Nos.
(ii) Nylon bushes for bolts 3 Nos.
(iii) Nylon washers for bolts & nuts 6 Nos.
:: 7 ::
REGULAR CHECKS AND PREVENTIVE MAINTAINANCE OF
TRACK CIRCUIT:
1. T.S.R. : - It shall be ensure that under no circumstances, the failure of a track
circuit results in a train passage under prohibitive conditions. Any change of
their components or adjustments shall be immediately followed by a test of
TSR. For this, a fixed resistance of minimum TSR value is always available
with the maintenance staff.
2. Track Circuit History Card :- Exact entries shall be made in them and no detail
shall be neglected.
3. The condition of rail bonds shall be checked by tacking track voltage reading
on Feed End and Relay End.
4. The point rodding, stratcher and gauge tie plate insulation must be checked
regularly.
5. Just before monsoon, track relay voltage shall be checked and Ballast from
bottom of the rail must be clean by P.Way staff.
6. The due date of overhauling shall be noted in paint on every Track Relay
prominently in the front so that it is not retained in circuit even for one day
after the overhaul falls due. This period should not exceeding 10 Yrs.
7. Track circuit battery condition shall always be good and its voltage shall be
measured after its charger „OFF‟.
8. In no case, the regulating resistance shall be bypassed to avoid track circuit
failure, particularly in monsoon.
9. Anti-tilting devices shall be provided with shelf type track relay and they shall
not be tampered with.
10. Chargers used with track circuit batteries shall be rated for not less than 3
Ampers.
11. Replace the block joint bushes and end posts once in six months or as
instructed with the help of Engineering staff.
12. Replace the damaged or corroded bonding wires.Arrange for packing of
sleepers at block joints if required.
13. In case of failures, receive failure message and then start the restoration work.
DO’S :-
1) Do not test the track circuit by shunting with a wire only.
2) Do not use relays which does not have test labels.
3) Do not keep the relays in the circuits which are due for overhauling.
4) Do not use short brittle brushes for cleaning the relay contacts.
5) Do not tilt the relays.
:: 8 ::
TYPES OF FAILURES :-
1) NO VOLTAGE : This may happen either due to open circuit (at feed end) or
due to dead short circuit.
METHOD OF TESTING : Disconnect one limb in track lead junction box and
measure the voltage at track side if it is relay end and measure the voltage at cable
side if it is feed end. If the meter shows full cell voltage it means there is a short
circuit.
2) FULL VOLTAGE :
Full voltage at track side – Fault is in the relay end cable or in the relay.
Full voltage at cable side – Fault is in track side.
In case of point zone track circuits failed due to short circuit it may be due
to polarity block joints or insulation joints in gauge tie plates or in ground
connection rods.
It is generally assume that no direct short circuit occurs through sleepers.
If short circuit occurs in PSC sleepers circuit to be disconnected at both ends and
sleepers should be checked with the assistance of Engineering department.
If full voltage (Battery voltage) at track, open circuit to words relay end and
no need to disconnect at track lead junction box. This may be due to rail crack,
continuity bond wire missing. Relay end cable / relay open circuited.
Proceed to words the other end and while doing so check up for rail crack,
missing bond wires etc. by measuring the voltage at various points.
3) LOW VOLTAGE : It may be due to partial short circuit, or high resistance
in rail bonding, or due to poor ballast resistance especially in rainy season.
Condition of ballast and leakage current through it can be ascertained by
measuring and comparing the circuitry current at feed end and relay end. In case
of poor ballast resistance which may be due to poor drainage, damage sleepers
and poor ballast conditions steps can be taken accordingly to improve the same.
RESTRICTIONS:
1. No receiver shall be positioned less than 200 m from any Transmitter on
normal mode and 50 m from low power mode of the same frequency.
2. Centre fed track circuit is to be used only where track needs to be longer
than permitted for an end-fed arrangement.
3. Tuned zones should not be located at level crossings.
4. If a level crossing lies in the track circuit, receiver should be located nearer to
the LC and the length should be restricted to 75% of its normal length. Transmitter
shall be connected only in normal power mode.
5. Track magnet of AWS and impedance bond shall not be located in the tuned
zone.
:: 13 ::
6. Track devices of axle counter should not be located within 5 m of tuned zone or
15 m of ETU.
7. Inside the track circuit having frequency A - 1699 Hz. (nom.), track device of
the axle' counter shall be located beyond 200 m from the TX of the track circuit.
For track circuits of frequencies E - 1549 Hz. (nom) & G - 1848 Hz. (nom.), the
distance between Tx of the track circuit and track device of the axle counter shall
not be less than 100 m.
8. An earthing rod is to be provided at every location box and all earth
connections from PSU, lightening arrestors of TX & RX are to be made to this
earth. It may also be necessary to provide such earthing arrangements near TTUs
in lightening - prone areas.
9. Tx and Rx locations must be positioned as close as possible to the units.
10. Two units of the same frequency may be housed in the same location provided
they are fed from separate PSUs.
Transmitter Tuning
Transmitter output voltage
Type Unit Input Voltage
Min. V (AC) Max. V (AC) Min. V (AC) Max. V (AC)
A.C.E. & G 10 11 8 11
B.D.F. & H 15 16 13 16
;; 14 ::
DONT's:
1. Same PSU shall not. be used for feeding more than one transmitter or Receiver
of the same frequency.
2. In electrified sections, measurements should not be made when a train is in the
vicinity.
3. There shall be no impedance bond, level crossing or switch expansion joint
inside the tuned area.
4. Axle counter transmitter and receiver should not be located in the tuned area.
No track device of axle counter of 5 KHz. system shall be located within 200 rnts.
of AFTC transmitter of frequency A and within 100 mts. of frequency E & G.
:: 15 ::
FAULT DIAGNOSIS AND RECTIFICATION:
a) If both adjoining track circuits have failed together, first of all check items
common like power supplies, tuning unit or interconnection.
b) Transmitter End
1. Check for "Singing Noise" produced by Transmitter and tuning unit.
2. Check rail to rail voltage at the Transmitter end. If this is OK, application of a 0.5
ohm TSR across the feed end tuning unit rail connections will lower Rail to Rail
voltage by approximately 50%, if the transmitter end is working OK. As such no
further tests needed to be done at Transmitter end.
3. Test 24 V DC Power Supply Voltage and current to Transmitter and the
Transmitter output voltage.
If readings from these tests show a deviation from the normal limits, the power
supply unit, Transmitter or tuning unit may be faulty.
4. For the integrity of interconnections, check tuning unit input and output voltages.
c) Receiver End:
1. Check companion tuning unit voltage. If it is not within limits, the companion
tuning unit is faulty if the rail to rail voltage at the tuning unit of the failed track
becomes OK when T1 and T2 terminals of companion tuning units are shorted.
2. Check the Receiver input current. If this is very less for the Receiver to operate
(less than 15 mA), the Receiver tuning unit is faulty. If it is adequate but the
Receiver output at R + R - is very less with a satisfactory power supply, change
the, Receiver.
ABB – AUDIO FREQUENCY JOINTLESS TRACK CIRCUIT – STYLE TI –21
The basic block diagram of AF track circuit is shown below. The transmitter
feeds in the AF voltage to the track through tuning unit which is received at the
other end by the receiver. A standard miniature line relay is directly operated by
the Receiver.
The track circuit operates on a frequency shift principle where the basic
frequency is shifted between two frequencies close to each other (+ 17 Hz. & - 17
Hz.). - Both the frequencies are detected independently by the receiver for
energising the track relay. This modulation is made to enable transmission of AF
without getting distorted. There are eight nominal frequencies (A to H) in the range
of 1.5 KHz. to 2.6 KHz. that are employed to have eight. types of track circuits.
This enables two types to be used per track and with the available eight types,
track circuit requirement of quadruple lines can be met.
ELEMENTS OF AFTC:
AFTC consists of
Sl.No Description Quantity Sl.No Description Quantity
1 Transmitter 1 4 Receiver 1
2 Tuning Unit 2 5 Power Supply Unit 2
3 End Termination unit 1 6 Output Relay 1
:: 16 ::
1T 2T
PARALLEL CONNECTION
OF SIMPLE TURNOUT
SERIES CONNECTION
IN SIMPLE TURNOUT
SERIES-PARALLEL
CONNECTION OF TURNOUT
F.M.
SERIES-PARALLEL
CONNECTION OF TURNOUT
F.M.
FOULING MARKS
AND PROTECTION
PARALLEL CONNECTION
FIG-12
F.M.
F.M.
-VE IN PARALLEL
FIG-13
F.M.