Professional Documents
Culture Documents
Vip 9615
Vip 9615
com
vip-9615
Digital line distance protection measurement and
control device
Manual V1.01
*This manual may be modified, please check whether the actual product matches
the manual version.
*Hangzhou Jibao Electric Group Co., Ltd. reserves the right to modify and interpret
all information
Table of contents
I. Overview...........................................................................................................................................................3
2. Technical parameters........................................................................................................................................3
3. Protection function description........................................................................................................................7
4. Setting value list and description....................................................................................................................14
5. Device backplane terminal diagram and operating circuit diagram..................................................twenty one
I. Overview
complete set of line protection device with distance, current, voltage protection and three-
phase reclosing as its basic configuration. It is suitable for protection and measurement
systems with voltage levels below 35KV. It can be installed on-site in switch cabinets or
fault location
Reclosing components
overload element
2.1.2Rated AC data:
a) phase voltage
Uh0 V
2.1.3Power consumption:
c) AC current loop The rated current is5AWhen: each phase is not greater than1VA
Current: 0.08In-20In
The inherent action time of the quick action section: 1.2Measured when times the setting
2.2.7Distance measurement error (excluding errors caused by external factors of the device)
In case of metallic failure, it shall not be greater than ±2%.
The distance protection starting component is used to open the power supply of the protection tripping outlet
The criterion for starting the element with a sudden change in phase current is:
△iφ>0.2In+1.25△IT
Iφ(t-2T) are the effective current values at time t, time t-T and time t-2T respectively.
When the sudden change of any phase current is greater than the start-up threshold for three
The static stability damage detection component is used to detect system oscillation caused by static
stability damage under normal operating conditions of the system. The criterion for this element is: any phase-
to-phase impedance lasts for 30ms within the impedance auxiliary element with full impedance characteristics,
and the oscillation center voltage U1Cosφ is less than 0.5 times the rated voltage. When this component
moves, the protection starts and enters the oscillation blocking logic. This element exits when the oscillation
The distance protection has three phase distance protections Zbc, Zca and Zab and three grounding distance
3.2.1Ground
( ) 0 . 02 − 1
Ip
distance
The ground distance is determined by the offset impedance element ZPY , zero sequence reactance element
The impedance element adopts the differential equation algorithm through Fourier integration. The
I N
Ground distance offset impedance elementSection I and IIThe operating characteristics are shown in
80 tp 13 .5 tp
t= t=
I 2 I
( ) −1 ( )−1
Ip Ip
the thick solid line in Figure 3.1. The offset impedanceSection IIIThe operating characteristics are shown by the
thick solid line in Figure 3.2. Among them, the impedance fixed value ZZD is set separately by segment, while the
resistance component fixed value RZD and the sensitive angle φZD share a fixed value for the three segments. The
Ready to take
P st smaller value.
In order to make the resistance components of each section easy to match, the inclination of the
boundary line on the resistor side of this characteristic is equal to the line impedance angle.ФThe same to
facilitate the coordination of sensitivity between the upper and lower line distance protection.
element F1. This component uses positive sequence voltage and loop current for phase comparison. Taking
U̇ 1
−25∘ ≤arg ≤145∘ 其中, K z =K 0 R+ jK 0 X ,
İ A + K z 3 İ 0
The action characteristics are shown by the double-dot chain lines in Figure 3.1 and Figure 3.2.
The characteristic of the positive sequence directional element is that it introduces the voltage of the sound
zero and cannot correctly reflect the direction of the fault. . For this reason, when the three-phase voltages are
all low, the memory voltage is used for phase comparison and the direction is fixed. After the voltage recovers,
4) When a two-phase short circuit is grounded through a transition resistor and a single phase of a double-
ended power line is grounded through a transition resistor, the ground impedance relay will override. Since the
zero-sequence reactance element prevents this override, the ground impedance is also provided with a zero-
sequence reactor X0. The action equation of X0 is (taking phase A zero-sequence reactor X0a as an example):
100 / √ 3
The operating characteristics of X0 are shown as the dotted line X0 in Figure 3.1. As can be seen from
U̇ =Lφφ d İ φφ /dt +R İ φφ ,
1) alternatingOffset impedanceSection I and IIThe operating characteristics are shown in the
thick solid line in Figure 3.1. The offset impedanceSection IIIThe operating characteristics are shown
by the thick solid line in Figure 3.2.distance between phasesOffset characteristics and ground
distance are the same. Among them, the impedance fixed value ZZD is set separately by segment, and
the three segments of the sensitivity angle φZD share a fixed value.alternatingOffset impedanceⅠ,
resistance component of is RZD. The offset threshold is automatically adjusted based on RZD and ZZD.
2) Used for the distance between phasesPositive sequence directional element F1 principle and
groundingdistance usedThe principle of positive sequence directional components is the same.Used
for the distance between phasesThe positive sequence directional element uses positive sequence
Zc)Auxiliarycomponent,
impedanceAuxiliaryThe
characteristics of full
components are not used to determine the scope of faults, but are used in
Within 150ms after the mutation amount is activated, each distance protection is open (short-term open). The
oscillation detection element is put in 150ms after the sudden change is started or after the zero-sequence auxiliary
start or the static stability destruction start. When it is detected that the system has no oscillation, the protection
distances I and II are opened; when it is judged that the system has oscillation and no fault, the protection distance I
and II are blocked; when it is judged that the system has oscillation and there is a fault within the zone, the distance
I, II Stage II protection can operate; when it is judged that the system is oscillating and there is an external fault, the
stage I and II protection will be blocked. Distance III protection is always engaged and is not affected by the
oscillation detection element. The oscillation detection element can be selected out by the control word.
The setting of this component can ensure that the system has quick-acting protection when there is no real
oscillation, and can quickly remove faults in the area when oscillating. Oscillation detection components include
impedance change rate (dZ/dt) detection components and asymmetric fault opening components.
The probability of actual system oscillation is very small, and the system does not oscillate during most
Test whether the system oscillates. When the system does not oscillate, open the distance protection, which
can greatly improve the performance of the protection. The oscillation system is shown in Figure 3.4, where ZM
and ZN are the system impedances on both sides, and ZL is the line impedance.
EM M N
I EN
~ ~
ZM ZL ZN
U
Figure 3.4
Assume the power supply on both sides is EN= EMej , it is not difficult to derive that the measured
ZΣ
Z= −Z M
1−e jδ
Among them Z=ZM+ZN+ZL, is the total impedance of the system. Z The approximate value is automatically
dZ j 2 πZ Σ e jδ
=
dt ( 1−e jδ )2 T
s
Where Ts is the oscillation period. Calculate the oscillation period and dZ/dt in real time to determine whether
When it is determined that the system has no oscillation, the distance protection is opened.
A fault occurs when the system does not oscillate. There will be a sudden change in the measured impedance
when the fault occurs, that is, a change in dZ/dt, but it will not change in the future. The impedance change rate
detection element opens the distance protection after a short delay; asymmetry occurs when the system oscillates.
fault, at least one of the three measured impedances will continue to change, and the impedance change rate
element does not open distance protection; a three-phase fault occurs when the system oscillates, and the three
measured impedances do not change, and the element operates to open distance protection, but at this time the
distance protection The protection can correctly reflect the fault scope. Therefore, this component can open up all
faults when the system does not oscillate and three-phase short circuits when the system oscillates.
Since the impedance change rate detection element cannot be opened when there is an asymmetric fault
under system oscillation, this device is equipped with an opening element for asymmetric faults. Its action
I 0 + I 2 > mI 1
criterion is
This method can effectively prevent the misoperation of the distance protection when an outside fault occurs
under oscillation, and can be open to asymmetric faults within the zone. In order to prevent the malfunction of the
protection caused by the unbalanced output of zero-sequence and negative-sequence currents when the oscillation
system is cut off, the protection is delayed for 50ms.
The oscillation blocking logic is shown in Figure 3.5. When ZDI=1, the impedance section I is opened; when
ZDII=1, the impedance section II is opened. When the oscillation blocking is exited, ZD Ⅰ and ZD Ⅱ are always
open. When the sudden change is started, the time element T2 is opened for a short time for 150ms, and then the
oscillation detection element is put in; after zero sequence start or static stability destruction is started, the latching
is opened for a short time and directly enters the oscillation detection. Since the delay of the distance II section is
greater than the short-term opening time, ZDII also has a section II fixed logic. If the impedance section II acts
during the short-term opening period, ZDII will be fixed through the components 'OR' gate 2 and 'AND' gate 2.
Figure 3.5
k=segment I, II, III, φ=a, b, c, ab, bc, ca. Zkpyφ represents the φ phase offset impedance of segment k; Choose
phase. ZD1 and ZDⅡ are the distance I and II open outputs of the oscillation locking element respectively. For the
distance II section, after the impedance action, XXφ and For the distance III section, F1φ is also fixed to prevent
the periodic return of the directional element from causing protection failure when system oscillation and fault
occur simultaneously. In addition, the distance III segment can also select offset characteristics according to the
control word.
3.2.6Double loops move rapidly one after another
As shown in Figure 3.9 of the double-circuit line, when the K1 point on the load side fails, the impedance
section III of protection 3 starts. After protection 2 trips, the impedance section III of protection 3 returns. The
impedance section II of protection 1 can use this characteristic to perform successive speed operations. When the
K2 point on the power side fails, for protection 4, because it is a reverse direction fault, the impedance section III
will not start, but the impedance with full impedance characteristicsAuxiliary componentsIt can be started, and
the impedance stage II of protection 2 can use this feature to accelerate the action.
The device is equipped with an output relay that allows the adjacent line to accelerate the impedance section
II and an adjacent line that allows the own line to accelerate the impedance section II, which is used for double-
When the distance element in section III of this line moves and then returns, or section III does not move but
has impedance in the opposite direction.Auxiliary componentsAfter 20ms of action, the protection starts to open
the relay and outputs an acceleration signal to the adjacent line, allowing the adjacent line to accelerate its distance
II segment components.
2. The fault of this line protection measurement is within the range of distance II (including direction
3. There is no acceleration signal when the device is started, and an acceleration signal from another
4. If it still does not return after a short delay (20ms) after meeting all the above three conditions, the
1 K2 K1 2
~
3 4
Figure 3.9 Schematic diagram of
double-circuit wiring
phase on this side disappears. This device uses this feature to accelerate the distance II on its own side. The action
criterion is:
1) The control word "asymmetrical fault continual rapid action" in the setting value is turned on;
2) The fault measured by the line protection on this side is within the range of distance II
3) The line protection measurement on this side fails and no conversion occurs;
4) The current of any phase changes from the load current to the no-load current during the fault;
b) The minimum phase current is less than 0.2In, greater than 0.04In and is not a capacitive current.
b) The minimum phase current is less than 0.2In, greater than 0.04In and is a capacitive current
5) If it still does not return after a short delay (100ms) after meeting the above four conditions, the
according to phase, the current components of each phase are only affected by Table 3-
Interphase I U
directional
elements
A IA UBC
B IB UCA
C IC UAB
3.3.2 The zero sequence direction element action area of this device isArg(3U0/3I0)=-
180~-120and 120~180,3U0 is self-produced, and the external 3I0 terminal wiring does not need to be
The low-voltage component operates when any of the three line voltages is lower than
the low-voltage setting and opens the blocked protection component. This component can be
used to ensure that the device does not malfunction under non-fault conditions such as
The device calculates and performs three-stage overcurrent judgment in real time. In
order to avoid the discharge time of the line arrester, the deviceIEach segment also has
When the device performs three-stage overcurrent judgment, the judgment logic of each
3) The direction conditions corresponding to the overcurrent phase and the low voltage
The implementation method of zero sequence overcurrent element is basically the same
as that of overcurrent element. The outlet will trip when the following conditions are
met:
The inverse time protection element is a protection element whose action time limit naturally matches the
current size in the protected line. By moving the action curve, the full line coordination can be easily achieved.
Common analytical expressions of inverse time characteristics are roughly divided into three categories, namely
standard inverse time, extraordinary inverse time, and extreme inverse time. The inverse time characteristics of this
device are set by the inverse time index in the setting value. The formulas for each inverse time characteristic are as
follows:
a.General inverse time limit(The setting range is 0.007~0.14)
0 .14 tp
t=
I
( )0 .02−1
Ip
13 .5 tp
t=
I
( )−1
Ip
80 tp
t=
I
( )2 −1
Ip
Note: The inverse time limit of the setting value part is the product value of the numerator in the above expression,
This device has inverse time protection function for phase-to-phase current and zero-sequence current.
3.8 Acceleration
The acceleration circuit of this device includes two types: manual acceleration and
The manual closing acceleration circuit of this device does not need to be started
by the contacts of the external manual closing handle. This is mainly due to the fact
that after many substations adopt integrated automation systems, the control panel has
been cancelled, and manual operating handles are no longer installed on site. Or just
install a simple operating handle. The same considerations have been made for the non-
corresponding starting reclosing circuit of this device, which will be discussed later.
1)The circuit breaker is in the open position for more than 30 seconds
2)When the circuit breaker changes from open to closed, the acceleration allowed
acceleration. One of the acceleration methods can be selected by the control word.
current settings and corresponding time settings. Compared with traditional protection,
this approach makes the protection configuration more flexible. The overcurrent
acceleration section of this device can also be optionally equipped with low voltage
3.7.1start loop
3.7.2blocking condition
When the circuit breaker is closed, the reclosed charging time is 15 seconds; the
reclosed green light flashes during the charging process, and when fully charged, it
emits a steady green light and no longer flashes. The reclosing "discharge" conditions
a)After the control circuit is disconnected, the reclosing delay is 10 seconds and
automatically "discharges"
b)When the spring has not stored energy, the terminal has a high potential and the
c)The high potential of the reclosing terminal is blocked, and the reclosing terminal
"discharges" immediately
Using this component, decentralized frequency control can be achieved. When the
system frequency is lower than the set frequency, this component can automatically
A slip blocking element is included in the logic of the low-frequency load shedding
function to differentiate between fault conditions, motor backcharging and a real active
power deficit.
Considering that the low-frequency load shedding function only works in steady state,
still needs to be added during the test. When this voltage (UAB) is lower than the
blocking frequency calculation voltage, the low-cycle load shedding component will
automatically exit.
To sum up, the criteria for low-frequency load shedding components are:
b) df/dt<F/T
c) f<F
d) T>TF
Using this component, low-voltage control can be achieved. When the system voltage is
lower than the set voltage, this component can automatically determine whether to remove
the load.
The criteria for low-voltage decommissioning components are: (This function realizes
☆ 2)dV/dt<V/T
3)T>Tudy
The overload element monitors the current of the three phases, and its operating
conditions are:
MAX(I)>Ifh
Time is delayed
where IfhSet value for overload current. The selection of overload alarm and trip
When one of the following three conditions is met, the device reports
2. The sum of the three-phase voltages is greater than8V, the minimum line voltage is
3. The sum of the three-phase voltages is greater than8V, the difference between the
maximum line voltage and the minimum line voltage is greater than16V, judged as
two-phase or single-phasePTDisconnected.
The device is detectingPTAfter the line is disconnected, you can choose according to the
control word to either exit the protection of each section with the direction element or
function can be disabled through the "analog summation self-test" control word.
3 Control word
0000~FFFF none See control word description
three
4 positive
impedance angle
5 Distance
resistor
6 Zero sequence
auxiliary 0.1~200 A
threshold
7 Zero sequence
resistance 0~4
compensation
8 Zero sequence
reactance 0~4
compensation
9 Phase-to-phase
impedance
10 Phase-to-phase
impedance
11 Phase-to-phase
impedance
serial Constant value
scope unit Remark
number name
12 Interphase
0~20 S
distanceⅠtime
13 Interphase
distance Ⅱ 0.1~20 S
period of time
14 Interphase
period of time
15 Grounding
I impedance
16 Grounding
II impedance
17 Grounding
III impedance
18 Grounding
distance Ⅰ 0~20 S
period of time
19 Grounding
distance Ⅱ 0.1~20 S
period of time
20 Grounding
period of time
one acceleration
serial Constant value
scope unit Remark
number name
distance time
twenty Ranging
0.1~100
two coefficient
25 Current section
0.2~100.0 A
III
26 Current I period
0.0~5.00 S
of time
27 Current Ⅱ
0.1~20.00 S
period of time
28 Current III
0.1~20.00 S
period of time
29 Zero sequence
section I 0.1~20.0 A
current
30 Zero sequence Ⅱ
0.1~20.0 A
section current
31 Zero sequence
current
32 Zero sequence I
0.0~5.00 S
period of time
33 Zero sequence II
0.1~20.00 S
period of time
III period of
time
35 Current
acceleration 0.2~100.0 A
section
36 Current
acceleration 0.0~5.00 S
period
37 Zero sequence
acceleration 0.1~20.0 A
section
38 Zero sequence
acceleration 0.1~5.00 S
time
39 Current
blocking voltage
40 Current inverse
0.2~100.0 A
time reference
41 Current inverse
0.005~127 S
time
42 zero sequence
benchmark
43 zero sequence
0.005~127 S
inverse time
index
46 Overload alarm
6~9000 S
time
47 Overload trip
6~9000 S
time
48 Reclosing check
value
shedding 45.0~49.5 Hz
frequency
blocking voltage
slip
54 Low voltage
voltage
55 Low voltage
decommissioning 0.1~20.0 S
time
serial Constant value
scope unit Remark
number name
56 Latching voltage
10.0~60.0 V/S
change rate
14 The switch accidentally jumps and The switch accidentally jumps and
13 PTDX related section exits (the PTDX related components exit (the
disconnected)
11 Zero sequence inverse time band Zero sequence inverse time without
direction direction
10 Current inverse time band direction Current inverse time limit without
direction
9 Zero sequence III section band Zero sequence section III has no
direction direction
direction direction
direction direction
voltage by voltage
Bit set1meaning of time timed0meaning
voltage by voltage
voltage voltage
direction
voltage
method
1
Reclosing synchronization mode selection
0
0 0 asynchronous mode
0 0 0 null
5 Offset input from section III Exit with offset from segment III
by voltage
circuits
enabled
1 Accelerate Stage III Throw after Accelerate stage III and retreat
after distance
number
number
19 Reclosing Exit/Input
communicatio
event name Remark
n code
Device power on 01H
AD error 04H
Invalid fixed
05H
value
Invalid argument 06H
Throw an
07H
exception
Network 1
08H
abnormality
Network 2
09H
abnormality
communicatio
event name Remark
n code
protection start 01H
Overcurrent
02H
section I
Overcurrent
03H
section II
Overcurrent
04H
section III
Zero sequence
05H
section I
Zero sequence
06H
section II
Zero sequence
07H
section III
Reclosing 08H
overload 0AH
Current
acceleration 0BH
section
Zero sequence
acceleration 0CH
section
Current inverse
0DH
time
zero sequence
0EH
inverse time
low pressure 0FH
Interphase
distance Ⅰ 10H
section
Interphase
distance Ⅱ 11H
section
Interphase
distance Ⅲ 12H
section
Grounding
distance section 13H
I
Ground distance
14H
section II
Ground distance
15H
section III
Asymmetric
sequential rapid 16H
action
Double loops move
rapidly one after 17H
another
Interphase
distance
18H
acceleration
stage II
Interphase
distance
19H
acceleration
stage III
Ground contact
distance
1AH
acceleration
stage II
Ground contact
distance
1BH
acceleration
stage III
CT disconnection 1CH
PT disconnected 1DH
Control circuit
1EH
disconnection
Trip failure 1FH
communicatio
Telemetry name Remark
n code
Ua 01H
Ub 02H
Uc 03H
Ia 04H
ib 05H
Ic 06H
P 07H
Q 08H
COSΦ 09H
F 0AH
communicatio
Remote signal name Remark
n code
The spring is not
01H
charged
Knife gate 1 position 02H
Knife gate 2 position 03H
Knife gate 3 positions 04H
blocking reclosing 05H
remote location 06H
adjacent line
07H
acceleration
Open 8 08H
Open 9 09H
Open 10 0AH
Open 11 0BH
Return 0CH
htK 0DH
TWJ 0EH
total accident 0FH
Alarm total 10H
GPS 11H
Send feedback 12H
5. Device backplane terminal diagram and operating circuit
diagram