HDD-09 (Ampacity & Indcued Volatge Calculation)
HDD-09 (Ampacity & Indcued Volatge Calculation)
Induced currents in metallic layers as a fraction of conductor current (applied to all single phase circuits) : 0.0
Results Summary
X coordinate Y coordinate Conductor
Cable No. Cable ID Circuit No. Feeder ID Cable Phase Cable Frequency Daily Load Factor Ampacity [A]
[m] [m] temperature [°C]
1 1200-132KV-SEC-OPTIMIZED 1 A 60.0 1.0 -4.5 6.0 86.6 870.0
2 1200-132KV-SEC-OPTIMIZED 1 B 60.0 1.0 -3.5 6.0 90.0 870.0
3 1200-132KV-SEC-OPTIMIZED 1 C 60.0 1.0 -2.5 6.0 88.9 870.0
4 1200-132KV-SEC-OPTIMIZED 2 A 60.0 1.0 2.5 6.0 88.9 870.0
5 1200-132KV-SEC-OPTIMIZED 2 B 60.0 1.0 3.5 6.0 90.0 870.0
6 1200-132KV-SEC-OPTIMIZED 2 C 60.0 1.0 4.5 6.0 86.6 870.0