Study Summary

CYMCAP Version 8.1 Revision 2


Study: Ampacity Calculation
Execution: HDD-qiddya Dorma road 6 Mr. depth - 5 Mr. Spacing between ckts ,1 Mr. Spacing between cables
Date: 12/13/2023 8:56:55 AM

General Simulation Data


Steady State Option Equally Loaded
Consider Electrical interaction between circuits No

Induced currents in metallic layers as a fraction of conductor current (applied to all single phase circuits) : 0.0

Conductor Resistances Computation Option: IEC-228

Standard Settings Options


General guidance CYMCAPGuidance
Factor on RAC due to magnetic armour CIGREGuidance
Factor on RAC due to magnetic duct CIGREGuidance
Factor on ƛ₁ due to magnetic armour CYMCAPGuidance
Factor on ƛ₁ due to magnetic duct CIGREGuidance
Factor on ƛ₂ due to ƛ'₁ CYMCAPGuidance
ƛ''₁ computation CIGREGuidance
ƛ₂pipe computation CYMCAPGuidance
Wd computation CIGREGuidance
T₂ computation CIGREGuidance
T₄ computation CYMCAPGuidance

Installation Type:Buried Ducts


Ambient Soil Temperature at Installation Depth [°C] 40.0
Native Soil Thermal Resistivity [K.m/W] 1.2
Consider Non-Isothermal Earth Surface No

Results Summary
X coordinate Y coordinate Conductor
Cable No. Cable ID Circuit No. Feeder ID Cable Phase Cable Frequency Daily Load Factor Ampacity [A]
[m] [m] temperature [°C]
1 1200-132KV-SEC-OPTIMIZED 1 A 60.0 1.0 -4.5 6.0 86.6 870.0
2 1200-132KV-SEC-OPTIMIZED 1 B 60.0 1.0 -3.5 6.0 90.0 870.0
3 1200-132KV-SEC-OPTIMIZED 1 C 60.0 1.0 -2.5 6.0 88.9 870.0
4 1200-132KV-SEC-OPTIMIZED 2 A 60.0 1.0 2.5 6.0 88.9 870.0
5 1200-132KV-SEC-OPTIMIZED 2 B 60.0 1.0 3.5 6.0 90.0 870.0
6 1200-132KV-SEC-OPTIMIZED 2 C 60.0 1.0 4.5 6.0 86.6 870.0