Professional Documents
Culture Documents
3042 Fro G DC 005 - 1 Operación Rtu
3042 Fro G DC 005 - 1 Operación Rtu
2
Contents
CONTENTS
Contents 3
Chapter 1 - About this guide 7
Chapter 2 - Overview 11
Chapter 3 - Hardware Components 13
Non-redundant Controller 15
Onboard Mixed I/O Module 17
Redundant Controller 20
I/O Modules 22
ControlEdge 2020 Expansion IOMs 22
Foundation Fieldbus Interface Module 26
ST103A Data Acquisition Module 28
3
Contents
Chapter 5 - Maintenance 81
CPM, IOM and IOTA Replacement 82
Safety considerations - PLAN AHEAD! 82
Removal and Insertion Under Power (RIUP) 83
Replacing a CPM 85
Replacing an IOM 86
Replacing an IOTA 86
Spare parts and model numbers 88
4
Contents
Notices 105
5
Contents
6
CHAPTER
Revision history
Revision Date Description
A April 2017 Initial release of document
B October Add ST103A Module related information
2017
C November Support up to 30 Expansion IOMs
2018
D January Add a new non-redundant controller SC-UCMX02
2020
E April 2020 Update Program memory (Flash) and Nonvolatile memory for
redundant controller.
F March Add information for connectors: Terminals of I/O and power
2021 supply of ControlEdge 2020 controller and Expansion IOM
are with TIN Plating, and the other connectors are with Gold
Plating.
7
Chapter 1 - About this guide
Item Description
ControlEdge ControlEdge 900 controllers running the Honeywell control execution
UOC environment (CEE) configured with Experion Control Builder.
Special terms
The following table describes some commonly used industry-wide
and Honeywell-specific terminology:
Terminology Description
CPM Control Processor Module
Expansion IOM I/O Module (IOM) external to the CPM that expand the I/O
capacity
IOTA Input Output Termination Assembly
Left End Plate Left end plate is used only in multi-row 2020 I/O systems. It starts
a new row of IOMs and provides connections for 24Vdc supply to
the row along with I/O Network connections.
Mixed IOM Mixed input/output module, which supports DC current or voltage
type signals, such as analog input, analog output, digital input,
digital output and pulse input.
Onboard IOM I/O Module (IOM) 'onboard' with the CPM
Right End Plate A right end plate is required at the end of each row of expansion
I/O modules, including the row connected to a controller. It allows
additional rows to be added or terminates the I/O network.
Related documents
The following list identifies publications that may contain information
relevant to the information in this document:
8
Chapter 1 - About this guide
9
Chapter 1 - About this guide
10
CHAPTER
2 OVERVIEW
Make sure all the hardware modules used in the system are installed
with the right firmware version and the engineering station has the
latest ControlEdge Builder. You can find the firmware and software
updates on http://www.honeywellprocess.com with valid credentials.
If the equipment is not used in a manner not specified by the
manufacturer, the protection provided by the equipment may be
impaired.
ControlEdge 2020 controller is a modular, powerful, and scalable
system capable of all remote automation and control applications.
When combined with Experion® PKS and its simplified SCADA
configuration, it solves the remote automation requirements.
Starting with R160, a new non-redundant controller SC-UCMX02 is
added in ControlEdge 2020 Platform. SC-UCMX01 is only applicable
to firmware versions R151 and lower.
Task Go to
Check the model number of the hardware See Spare parts and model numbers for
components more information.
Understand and plan the hardware See Hardware Components for more
components of the system information.
Plan the wiring of the system See Wiring and Cabling Planning for
more information.
Install controller and I/O modules See Mounting for more information.
Wire I/O modules See I/O Wiring for more information.
Troubleshoot the system See Diagnostics and Troubleshooting
for more information.
Remove or replace system components See Maintenance for more information.
11
Chapter 2 - Overview
Task Go to
Software configuration See ControlEdge Builder User’s Guide for
more information.
12
CHAPTER
3 HARDWARE COMPONENTS
13
Chapter 3 - Hardware Components
14
Chapter 3 - Hardware Components
Non-redundant Controller
The non-redundant controller consists of a CPM and an IOTA.
Item Description
1 18-30 VDC power supply
2 RS485 Ports (two)
3 RS232 Ports (two)
4 Ethernet Ports (two)
15
Chapter 3 - Hardware Components
Item Description
5 Screw hole: used for locking controller IOTA and expansion I/O IOTA.
6 Expansion Connector: used for connecting with expansion I/O module.
7 Terminal strips: used for connecting I/O cable from the field.
16
Chapter 3 - Hardware Components
Analog Inputs
Table 3-2: Analog Input Channel Specification
Item Specification
Number of Channels 8
Standard Input Range 4~20mA or 1~5VDC, software
configurable
Input Type Single end
Short circuit protection Yes
Isolation No
Transient Voltage Suppression 600W peak pulse power capability at
10×1000µs waveform, repetition rate:
0.01%
A/D resolution 16bit
Full scale accuracy ± 0.1% at 25°C
17
Chapter 3 - Hardware Components
Analog Outputs
Table 3-3: Analog Output Channel Specification
Item Specification
Number of Channels 2
Output Range 4~20mA
Output Type Source
D/A resolution 12bit
Full scale accuracy ± 0.2% at 25°C
Digital Inputs
Table 3-4: Digital Input Channel Specification
Item Specification
Number of Channels 10
Input type Sink (dry contact)
Input Isolation No
Transient Voltage Suppression 600W peak pulse power capability at 10×1000µs
waveform, repetition rate: 0.01%
Input Voltage range 24VDC, +/-10%, external power supply
18
Chapter 3 - Hardware Components
Item Specification
Guaranteed ON voltage 12VDC
Guaranteed OFF voltage 4VDC
Short circuit protection Yes
Digital Outputs
Table 3-5: Digital Output Channel Specification
Item Specification
Number of Channels 6
Maximum Output Power 24VDC, 80mA load per channel, external power
supply
Output Type Sink (voltage free)
Isolation No
Output voltage range 24VDC, +/-10%
On-State Voltage Max 1VDC, load current @ 80mA max
Off-State Voltage 24 V, typical
Max. off state leakage 100uA, maximum
Short circuit protection Yes
Transient Voltage Suppression 600W peak pulse power capability at 10×1000µs
waveform, repetition rate: 0.01%
Typical on resistance 0.8 ohm
Pulse Inputs
Input registers are used to accumulate the positive transitions of each
input and record count.
Table 3-6: Pulse Input Channel Specification
Item Specification
Number of Channels 2
Input Isolation No
19
Chapter 3 - Hardware Components
Item Specification
Transient Voltage Suppression 600W peak pulse power capability at 10×1000µs
waveform, repetition rate: 0.01%
Input Type Sink
Input Voltage range 5~10Volt peak to peak
Input Frequency 0 to 10kHZ
Input Impedance 97 kohm
Minimum high level single width 40us
Guaranteed ON voltage 4.5V
Guaranteed OFF voltage 1.5V
PI configuration As pulse input or digital input
Accumulator rate Accumulator and rate functions
Filter Configurable
Short circuit protection Yes
Redundant Controller
The redundant controller consists of two CPMs and an IOTA.
20
Chapter 3 - Hardware Components
Item Description
1 18-30 VDC power supply (two)
2 RS485 Ports (two)
3 RS232 Ports (two)
4 Ethernet Ports (four) Ethernet port1 and port2 for the left CPM (SLOT1).
Ethernet port3 and port4 for the right CPM (SLOT2).
5 Screw hole: used for locking controller IOTA and expansion I/O IOTA.
6 Expansion Connector: used for connecting with expansion I/O module.
Item Specification
Processor Dual Core ARM® Cortex™-A9 Core (32 bit) 667 MHz
Dynamic memory (RAM) 256 Megabytes
Program memory (Flash) 256 Megabytes
Nonvolatile memory 16 Mbits
Nonvolatile memory data life 20+ years (no battery required)
21
Chapter 3 - Hardware Components
Item Specification
Real-time clock resolution 1 ms
Execution cycle time >=20 ms
Time Synchronization Simple Network Time Protocol (SNTP) or DNP3
Programming port Ethernet port
SD card support 32GB Class 6 / Class 10 industry standard, not hot-
swappable, maximum weight 3g (0.0066 lb, 0.1058
oz)
I/O Modules
I/O modules contains ControlEdge 2020 Mixed I/O, the ST103A and
Series C Fieldbus Interface Module (FIM4).
n I/O Module
A device that contains most of the electronics required to perform
a specific I/O function. The IOM plugs onto the IOTA.
22
Chapter 3 - Hardware Components
Item Description
1 Chassis ground
2 Left expansion connector: used for connecting with controller, expansion I/O
23
Chapter 3 - Hardware Components
Item Description
module or left end plate.
3 Rotary switch (two): used for setting the address of IOM. The controller can
configure and communicate with IOM according to this address. Set the
switches to the two digit address . The upper switch (10) is used to set the tens
digit and the lower switch (1) sets the ones digit. For expansion IOMs of
Revision A, you can set the rotary switch from 1 to 9. And for expansion IOMs
of Revision B, you can set the rotary switch from 1 to 99. See Mounting a
Controller with Expansion IOMs for more information.
ATTENTION:
l The address must be unique across all I/O modules connected to
the same ControlEdge 2020 controller.
l Unless the location is known to be non-hazardous, do not adjust
the switches while the equipment is powered.
4 Terminal strips: used for connecting I/O cable from the field.
5 Screw holes: used for locking IOTAs between two expansion I/O Modules.
6 Right expansion connector: used for connecting with expansion I/O module or
right end plate.
24
Chapter 3 - Hardware Components
Item Description
1 Left expansion connector: connects to a controller or an expansion I/O
module.
2 Ethernet port 1: allows additional rows to be added or terminates the I/O link.
3 Ethernet port 2: allows additional rows to be added or terminates the I/O link.
25
Chapter 3 - Hardware Components
Item Description
1 18-30 VDC power supply
2 Right expansion connector: connects to an expansion I/O module.
3 Screw holes: used for locking left end plate and expansion I/O IOTA.
4, 5 Ethernet port 1 and Ethernet port 2: extends the I/O link to another row.
26
Chapter 3 - Hardware Components
The RFIM solution interfaces with ControlEge RTU using FIM4, along
with a Modbus TCP interface. FIM4 shipped from the factory contains
latest released boot image by default. Users have to upgrade to RFIM
firmware using Firmware Manager. For more information, see
"Remote FIM configuration" in the Remote Fieldbus Interface Module
Solution.
27
Chapter 3 - Hardware Components
Item Description
Type of Inputs 0 to 5 Volt or 4-20 mA nominal i/p type
Isolation All channels individually isolated to 50 V RMS
Conversion Method Integrating charge - balance
Effective resolution More than 18 bits, auto zero, auto calibrate
Conversion time Less than 100 mSec per channel
Scan Rate All channels can be acquired in under 1 second
Series mode rejection >100 dB at 50 Hz and 60 Hz
28
Chapter 3 - Hardware Components
Item Description
Voltage Common mode range ±50 V relative to computer ground or other input
Calibration Period 2 Years to 0.005% of Voltage. 5 Years to 0.01 % of
Voltage
Item Description
Type of Inputs Differential voltage inputs
Input Range 0 to +5.5 V
Accuracy +/- 0.005% of FSD at 23 °C
Ambient Temperature +/- 7 ppm/°C from 23°C in the range 0 to 45°C. 0.05% -
effect 40°C to +85°C
Item Description
Type of Inputs Isolated current inputs
Input Range 0 to 22mA.
Accuracy +/- 0.02% of FSD at 23 °C
Ambient Temperature +/-10 ppm/°C from 23°C in range 0°C to 45°C. .0.1% -40°C
effect to +85°C
Item Description
Type of Inputs 4 wire using Pt 100 RTD
Temperature measuring range -100°C to +300°C.
Resolution 0.01°C
Accuracy 0.05°C
PRT cables Loop resistance up to 600 Ohms
Barriers 9 V, 100 Ohms are satisfactory.
29
Chapter 3 - Hardware Components
Item Description
Security Continuous cable/PRT integrity tests
3 Wire Mode Not recommended, but possible
Item Description
Type Each channel is an individually isolated current
controlled 0 to 21 mA output, that can be used to
sink or source cubicle power
Effective resolution 12 bit minimum.
Accuracy +/- 0.1% at 23°C.
Temperature Coefficient 20ppm / °C
Minimum Load Loop resistance Safe down to zero ohms from +32V external
supply.
Maximum Load Loop resistance 1000 Ohms when powered from +24V external
Maximum External Supply 32 Volts
Output Form Isolated active current controller
Number of field connections 2 terminals per channel
Update time 500mSec to within 1%
Item Description
Configuration Individually Opto-isolated inputs
Max Input Voltage 30V
Min Input on Voltagee 12V
Max Input off voltage 3.0V
Input Impedance 2-2.5K Ohm typical
Protection Surge and reverse voltage protection
Additional Features Filtering and fleeting input detection provided
30
Chapter 3 - Hardware Components
Item Description
Configuration Individually galvanically isolated
Max Output Current 100mA
Min Output Saturation Voltage 2.1V @ 100mA
Max Output Standoff Voltage 32V, limited by input protection
When off|Reset/Power on State All digital outputs OFF
Item Description
Configuration AC Coupled, Galvanically Isolated, with active limiting
Sensitivity 3.0 V peak to peak minimum
Maximum Input Voltage 24V peak to peak
Input current Internally limited to 3mA
Frequency Range 50Hz to 5 kHz.
Accuracy of frequency 10 ppm
measurement
Resolution 25 nanoseconds
Note Info from Solartron – a 220R resistor inline will give approx
3.5V peak to peak signal.
Item Description
Input Type Can use "best in class" differential mode or single
ended.
Configuration Opto-coupled inputs.
Input signal levels +/- 3.5 V to +/- 24 V.
Input current minimum 5 mA
Frequency range DC to 10 kHz.
31
Chapter 3 - Hardware Components
Item Description
Line Integrity Dual back-to-back optos, allowing full quiescent line
and electronic integrity testing, when used with
differential pre-amps and VS300 pulser
Dual Pulse compliance IP 252/76 or API Ch 5.5 level A or B, or E
Item Description
Configuration Digital Ground referenced Differential transceiver
Gating & Direction Software controlled
Use To bus together several streams to a common prover
Signalling RS422 Compatible drive & receive levels
Max output 10 KHz
frequency
Item Description
Configuration Individually Isolated
Max Output Current 100 mA
Max Output Saturation Voltage 2.1 V @ 100 mA
Max Output Standoff Voltage 32V, limited by Transorb
Frequency range DC to 100Hz
Item Description
Contact Form Form B (Normally Closed)
Max current 1A
Max Voltage 32 V, limited by input protection
Maximum Power 30 VA
Control Released on de-power or watchdog restart or software command
32
Chapter 3 - Hardware Components
The ST103A is equipped with two Modbus serial ports to give dual
redundant links to DCS or PLCs.
Item Description
Port Type Dual RS485, two wire half Duplex
Isolation None
Protection Highly ruggedised ports with Full EMC protection, including
transient and surge protection
Biasing/Determination Very light biasing to maintain receivers in an off state when
disconnected
Baud Rate Fixed at 19,200 Baud
Above technical specification may change, the latest data should refer
to the module specification published on the website.
ST103A needs to be procured from Swinton Technology, UK.
Please contact this email id for procurement -
enquires@swintontechnology.com
Swinton Technology's contact details :
Swinton House, Hertford Way
York Road Business Park
Malton - YO17 6YG
United Kingdom
Telephone: +44 (0)1653 698844
Fax: +44 (0)1653 605679
33
Chapter 3 - Hardware Components
34
CHAPTER
In this section:
Environmental Specification 36
Power Considerations 36
Solar Power Supply 38
Installation Declarations 46
Dimensions and Layouts 47
Mounting 57
Wiring and Cabling Planning 64
I/O Wiring 72
Connecting with Wireless I/O 79
35
Chapter 4 - ControlEdge 2020 Platform Installation
Environmental Specification
The operating conditions for ControlEdge RTU Acuity components
are as follows:
Power Considerations
Power Requirements
Power is supplied to the controller and I/O modules through the
power input terminals on the controller IOTA and the left end plate
(when used). The relevant specifications at each power input terminals
are detailed in the following table.
Table 4-1: Power Requirements
36
Chapter 4 - ControlEdge 2020 Platform Installation
Power Consumption
The following three tables are provided for the purpose of sizing
power systems. Three different scenarios are provided with each
having various controller options configured. Select the scenario
most suited and interpolate values when required.
This table only includes power consumption data of the listed
modules and does not include power consumption of any connected
instruments, (transmitters, valves etc.), even if that power is provided
through the I/O module terminals. Allow for instrument power
consumption separately in your power system sizing calculations
along with other components to be powered by the system, (e.g.,
network radio).
Table 4-2: Power Consumption, Non-redundant Controller
Note 2 – Input voltage 24 Vdc; All I/O channels active; no serial ports active; Ethernet
port 2 active; Ethernet ports 1 and 3 not active;
Note 3 – Input voltage 24 Vdc; All I/O channels active; 4 serial ports active; Ethernet
ports 1 and 2 active; Ethernet port 3 not active;
Note 4 – Input voltage 24 Vdc; All I/O channels active; 4 serial ports active; Ethernet
ports 1, 2 and 3 active; Does not include expansion IOMs.
37
Chapter 4 - ControlEdge 2020 Platform Installation
Note 2– Input voltage 24 Vdc; Two controllers; 4 serial ports active; Ethernet ports 1, 2
and 3 active; Does not include expansion IOMs.
SC-UMIX012 2.0 W
SC-TEPR01 0.0 W
SC-TEPL01 0.0 W
Note 1 – All values exclude power consumption of any connected instruments.
n Solar panels
n Solar battery charger
n Deep cycle batteries
38
Chapter 4 - ControlEdge 2020 Platform Installation
n Battery box
n Solar panel mounting
The first three items in the list requires electrical design calculations.
Load Calculations
Load calculations are based on data sheets of the components that
are expected to be connected. Ensure to state any assumptions in
your calculation. For example all analog loops are assumed to be
100% loaded at 20 mA, radio is expected to operate on 20% transmit
duty (radio consumes considerably more power during transmission
than reception) and so on. For small jobs, a paper calculation along
with a safety margin is sufficient. For larger jobs, an actual
measurement of assembled system may be required. Ensure to
estimate the expected load accurately as possible as this is the most
critical design input for a successful solar system. See the following
table of calculations and assumptions including source of estimated
values for reference.
39
Chapter 4 - ControlEdge 2020 Platform Installation
Duty Power
Curren
Quantit Cycl Suppl Current Power Data
Device t Total
y e y Each (A) (W) Source
(A)
(%) (VDC)
Hardware Solar 1 100 24 0.015 0.015 0.36 datashe
Componen Regulator et
ts
Honeywell 1 100 24 0.064 0.064 1.54 measure
ControlEd d
ge RTU, 28
MIXED IO¹
Honeywell 1 10 24 0.140/0.2 0.151 3.624 datashe
XYR301-E² 50 et
Hardware 0.23 5.52
Total
Instrument None 0 0 24 0 0 0
s Identified³
I/O Analog 6 100 24 0.02 0.12 2.88 Full
Componen Inputs Load
ts⁴
Digital 8 100 24 0.00034 0 0.07 Full
Inputs Load
Analog 1 100 1 0.02 0.02 0.02 50 Ohm
Outputs⁵
Digital 2 100 24 0.0066 0.0132 0.316 Full
Outputs⁶ 8 Load
I/O Total 0.16 3.28
Combined 8.8
Total
40
Chapter 4 - ControlEdge 2020 Platform Installation
41
Chapter 4 - ControlEdge 2020 Platform Installation
Autonomy7
Autonomy determines sizing of your batteries and how long load can
be supplied during no sun days due to heavy cloud and rain.
Autonomy is usually provided as a design input. If this input is not
provided, follow the guidelines in the following table.
Notes 7 – Autonomy: Solar panels are not producing any energy when
at night or for extended periods of time such as heavy cloud or rain
periods, hence all the energy is provided by battery only.
When peak sun hours are reduced, autonomy must be increased.
Table 4-6: Autonomy
Design Calculations
With your design inputs established, you are now in a position to size
the various components. As an example, let’s assume the following
values were determined as design inputs.
42
Chapter 4 - ControlEdge 2020 Platform Installation
Battery Sizing
The batteries must be sized to provide load for the autonomy period.
Sizing not only depends on autonomy but also on batteries selected.
Only deep cycle batteries should be used as these are designed for
deep discharge use. The amount of discharge is known as depth of
discharge or DoD. A DoD of 20% means that 20% of a battery’s
available capacity has been exhausted. The more a battery is
discharged, the shorter its life will be, therefore some compromise
must be made since greater DoD allows smaller batteries but reduces
the service life of the batteries. Generally a figure of 50% is good but
some batteries exhibit good lifetime even down to 80% DoD.
Standard car lead acid batteries are not suitable for solar.
Since batteries are based on an electrochemical reaction, the battery
capacity reduces with lower temperatures. See the following table for
the de-rating factors.
For our example the following battery sizing results are obtained.
43
Chapter 4 - ControlEdge 2020 Platform Installation
ATTENTION:
l The result of the above calculation is the Ah capacity of the
Shunt Charger
Shunt chargers are the simplest kind of solar charger. They are
dependent only on the current which a solar panel can supply. Hence,
a solar panel which provides high voltage and low current is less
effective than a panel which provides low voltage and high current
even though the former panel maybe a higher power rating. The
calculations are given below for our example:
44
Chapter 4 - ControlEdge 2020 Platform Installation
3. Total required panel charge current for load and battery charging:
= Load x (1 + Autonomy / (Recovery / Charge factor))
= 9.6 x (1 + 5 / (5 / 1.1)) = 20.16 A
At this point we now need to select a suitable solar panel. Solar panel
data sheets have many parameters, but the parameters of interest are
Vmp and Imp which are the voltage and current at maximum power
conditions. Vmp can vary from 12 V to 60 V for different panels.
Ideally we are looking for a panel that has a Vmp of greater than or
equal to nominal supply voltage plus 25% which in our example is 24
V + 25% = 30 V. The Canadian Solar CS6P-250M 250W Mono panel is
a good fit with Vmp = 30.4 V and Imp = 8.22 A. Thus we need at least 3
panels connected in parallel to provide a current of 8.22 x 3 = 24.66 A.
We can only have whole panels, not partial panels, so panel selection
can be tedious since no single panel can fit all designs optimally.
MPPT Charger
Unlike the shunt charger, the MPPT charger intelligently adjusts load
on the solar panel so that it operates at its maximum power transfer
point. This energy is then transferred to the batteries with high
efficiency. The MPPT charger fully utilises the power output of the
panel, not just the current. This allows much better utilisation of the
solar panel output and allows far more flexibility in panel selection.
Essentially we can take the result for the shunt charger and multiply
by the system voltage to determine the power required to meet our
load and charging requirements. For example: 20.16 A x 24 V = 484
Watts
The MPPT charger is not 100% efficient, so allowance must be made
for this. A figure 0.9 (90%) is a reasonable value, thus the solar panel
power requirement is: 484 / 0.9 = 537.6 Watts
In this case, you can choose 2 x Sunmodule plus SW 270 Mono
panels (Vmp = 30.9 V, Imp = 8.81 A) to give a total of 540 Watts. Note
that in the shunt case we used 3 x 250 W panels or 750 W in total. This
illustrates the advantage of MPPT over Shunt chargers. You can also
choose to connect these two panels in series or parallel since MPPT
chargers have a much wider solar voltage range. However you still
need to maintain a minimum panel voltage of nominal supply voltage
plus 25%. Also you need to ensure that combined open circuit voltage
(Voc) of the connected panels does not exceed 90% of maximum
input voltage of the solar regulator.
45
Chapter 4 - ControlEdge 2020 Platform Installation
Installation Declarations
CAUTION: This equipment shall be installed in accordance with
the requirements of the National Electrical Code (NEC),
ANSI/NFPA 70, the Canadian Electrical Code (CEC) or
EN/IEC60079-14 and applicable National regulations in Europe.
See Special Condition of Use for Division 2/Zone 2 Hazardous
Location Installation for more information. The suitability of the
enclosure and installed system shall be acceptable to the local
"authority having jurisdiction," as defined in the NEC, or
"authorized person" as defined in the CEC. Where installed in
outdoor or potentially wet locations, the enclosure shall, at a
minimum, meet the requirements of IP54 in accordance with
CAN/CSA 60529.
46
Chapter 4 - ControlEdge 2020 Platform Installation
In this section:
47
Chapter 4 - ControlEdge 2020 Platform Installation
48
Chapter 4 - ControlEdge 2020 Platform Installation
49
Chapter 4 - ControlEdge 2020 Platform Installation
Number Dimensions
1 36.85
2 183.97
3 98.51
4 132.08
5 140.51
6 77.53
50
Chapter 4 - ControlEdge 2020 Platform Installation
Number Dimension
1 30.12
2 183.97
3 41.91
51
Chapter 4 - ControlEdge 2020 Platform Installation
52
Chapter 4 - ControlEdge 2020 Platform Installation
Item Description
Length on Rail 168mm
Height 56mm
Width across Rail 128mm
Weight 650 grams
Structure: PVC extrusion with passivated steel lid
53
Chapter 4 - ControlEdge 2020 Platform Installation
54
Chapter 4 - ControlEdge 2020 Platform Installation
Table 4-14: Dimensions for a Non-redundant Controller with nine Expansion IOMs
55
Chapter 4 - ControlEdge 2020 Platform Installation
56
Chapter 4 - ControlEdge 2020 Platform Installation
Mounting
ATTENTION:
l The recommended spacing between the ControlEdge 2020
57
Chapter 4 - ControlEdge 2020 Platform Installation
3. Mount the expansion I/O IOTA onto the DIN rail and insert the
expansion I/O IOTA into controller IOTA via the corresponding
connectors.
4. With a ɸ3.0 mm screwdriver, set the rotary switch to the address of
the IOM. For expansion IOMs of Revision A, you can set the rotary
switch from 1 to 9. And for expansion IOMs of Revision B, you can
set the rotary switch from 1 to 99.
5. Mount two screws (M2.5*12) into the screw holes located on IOTA
to lock one IOTA to another.
6. Insert the DIN rail hook to attach every IOTA to the DIN rail.
7. Add Expansion IOMs in either a single row or multi-row.
l To add Expansion IOMs in a single row:
58
Chapter 4 - ControlEdge 2020 Platform Installation
59
Chapter 4 - ControlEdge 2020 Platform Installation
8. Secure the IOTA to the DIN rail with DIN rail stops.
9. Insert the CPM onto IOTA making sure that the CPM matches
properly with the controller IOTA connector.
10. Secure the CPM to the IOTA with two screws located at each side
of the metal cover.
11. Insert IOM onto Expansion I/O IOTA to make sure that the IOM
matches properly with the IOTA connector.
60
Chapter 4 - ControlEdge 2020 Platform Installation
12. Secure the IOM to the IOTA with two screws located at each side
of the metal cover.
Mounting a ST103A
ST103A acting as a slave communicates with the controller which acts
as a master through any one of two RS485 ports over Modbus.
ST103A can be remotely mounted (>1km) to the controller.
To mount ST103A
61
Chapter 4 - ControlEdge 2020 Platform Installation
62
Chapter 4 - ControlEdge 2020 Platform Installation
Analog Input P1 P2 P3 P4 P5 P6 P7 P8
1 (1-5V)-factory OFF
setting
1 (4-20mA) ON
2 (1-5V)-factory OFF
setting
2 (4-20mA) ON
3 (1-5V)-factory OFF
setting
3 (4-20mA) ON
4 (1-5V)-factory OFF
setting
4 (4-20mA) ON
5 (1-5V)-factory OFF ON
setting
5 (4-20mA) ON ON
5 (RTD2) OFF OFF
6 (1-5V)-factory OFF ON
setting
6 (4-20mA) ON ON
6 (RTD1) OFF OFF
63
Chapter 4 - ControlEdge 2020 Platform Installation
NOTE: Access to bit links cover from the unit should only be
attempted by an engineer with suitable training.
If the bit links on the analog board need to be changed you need to
first remove the unit's cover .
To remove the cover of the unit:
1. Remove the Earth stand-off which secures the cover earth tag
using a 9/32" or 7mm socket driver.
2. Remove the M3x6mm pozidrive pan head screw which is next to
the Status LED and above the ETH2 connector.
3. Remove the remaining four M3x20mm pozidrive pan head screws.
4. Remove the cover by lifting it vertically away from the base.
To re-fit the cover:
1. Slid the cover back into position, taking care that the earth tag
slips over the earth stud.
2. Refit the screws to secure the cover.
3. Screw the stand-off back into the Earth Stud.
In this section:
Power Cabling 65
Communication Cabling 68
Grounding and Other Considerations 70
64
Chapter 4 - ControlEdge 2020 Platform Installation
Power Cabling
A ControlEdge 2020 Controller installation requires a 24VDC to
power the controller and IOM. ControlEdge 2020 controller is
equipped with an on-board protection system to protect against
voltage fluctuations beyond the rated range of 18 to 30 VDC.
65
Chapter 4 - ControlEdge 2020 Platform Installation
66
Chapter 4 - ControlEdge 2020 Platform Installation
Item Description
Input Voltage & Current 20-32V D.C 2W nominal, 4 W Max
No of DC Inputs 2 off, allowing direct connection to redundant
supplies
Galvanic isolation 50V RMS to Instrument Earth
Maximum Input Ripple 2V pp
DC Input Power fail flag 19V +/- 0.5v
Hold up period after powerfail 4ms
flag
Input protection Non-replaceable 1A Input Fuse
Item Description
Output Nominal 12V supply for turbine pre-amplifiers
Isolation Isolated from incoming power and computer 0 V
Regulation Fully regulated
Voltage level 12V, 500mV p-p ripple
Output Current 75 mA
Output protection Electronic current limit and thermal shutdown
67
Chapter 4 - ControlEdge 2020 Platform Installation
Communication Cabling
Ethernet Ports
For redundant controller, Ethernet port1, port2 ,port3 and port4 of
the CPM should be connected to a switch in the Ethernet to make the
redundancy effect. For non-redundant controller, there is no special
requirement for connecting the switch.
The ControlEdge 2020 controller has 2 Ethernet ports and use RJ45
type connectors. See the following figure for the pin assignment:
68
Chapter 4 - ControlEdge 2020 Platform Installation
RS485 Ports
The ControlEdge 2020 controller has two RS485 ports to some
specific equipment. Each port has five terminals: GND, 485 A+, 485 B-,
chassis ground and termination. See the following picture for the
RS485 pin assignment.
RS232 Ports
The ControlEdge 2020 controller has two RS232 ports and use RJ45
type connectors. See the following figure for the pin assignment:
69
Chapter 4 - ControlEdge 2020 Platform Installation
70
Chapter 4 - ControlEdge 2020 Platform Installation
n Use individually shielded twisted pair of cables with full foil shield
coverage, to minimize crosstalk and false counting of pulses from
one channel to another, within the cable bundle.
n Select appropriate wires for pulse counting performance. The foil
along with the overall braid provides effective shielding.
n Low capacitance enables fast counting, ensuring that the pulse
fidelity (pulse distortion) for longer cable lengths is not
compromised.
n Use cables that have a braided shield (55% or greater coverage)
for best EMI/RFI performance. Double shielded cable with a braid
over foil performs best, if the environment is EMI harsh. Proper
grounding of the shields is necessary to obtain the optimum
performance.
n The shields (screen) of the cable carrying the pulse signals can be
grounded at any one or both ends (double termination). If the site
has problem with low frequency ground loops, ground the shield
at one end to minimize common mode noise and interference.
71
Chapter 4 - ControlEdge 2020 Platform Installation
I/O Wiring
All I/O channels share the power source with the system components
while the two analog output devices are powered internally. In most
cases, the other 26 channels require external cabling to introduce the
voltage to field loops from the system power source.
72
Chapter 4 - ControlEdge 2020 Platform Installation
Analog Inputs
See the following diagram for analog input wiring examples.
73
Chapter 4 - ControlEdge 2020 Platform Installation
Analog Outputs
See the following diagram for analog output wiring examples:
74
Chapter 4 - ControlEdge 2020 Platform Installation
Digital Inputs
See the following diagram for digital input wiring examples:
75
Chapter 4 - ControlEdge 2020 Platform Installation
Digital Outputs
See the following diagram for digital output wiring examples:
76
Chapter 4 - ControlEdge 2020 Platform Installation
Pulse Inputs
See the following diagram for pulse inputs wiring examples:
77
Chapter 4 - ControlEdge 2020 Platform Installation
78
Chapter 4 - ControlEdge 2020 Platform Installation
79
Chapter 4 - ControlEdge 2020 Platform Installation
80
CHAPTER
5 MAINTENANCE
In this section:
81
Chapter 5 - Maintenance
82
Chapter 5 - Maintenance
83
Chapter 5 - Maintenance
Or:
84
Chapter 5 - Maintenance
Replacing a CPM
In a system with redundant ControlEdge 2020 controllers, when the
primary CPM fails, the second CPM takes over as the primary. And the
original one becomes the secondary CPM. The secondary CPM
should be replaced.
For other cases, it is recommended to manually switch over before
you remove the primary CPM.
85
Chapter 5 - Maintenance
Replacing an IOM
1. Loosen screws at each side of the module that secures the IOM to
the IOTA.
2. Carefully remove the IOM from the IOTA.
3. Insert the new IOM onto IOTA making sure that the IOM matches
properly with the IOTA connector. Note that all modules are keyed
to ensure that only IOM can be inserted onto Expansion I/O IOTA.
4. Secure the IOM to the IOTA with two screws located at each side
of the plastic cover.
Replacing an IOTA
To replace an IOTA:
86
Chapter 5 - Maintenance
4. Loosen the DIN rail hook that secures the defective IOTA to the
DIN rail.
5. Pull out the terminal strips from the IOTA.
6. Loosen the screws which lock the IOTA from the screw holes and
pull out the connectors from the left and right IOTAs.
7. Remove the IOTA from DIN rail.
8. Mount new IOTA on the DIN rail at the same position as the old
IOTA.
9. Mount the screws at the screw holes of the new IOTA and its left
one to fix it to adjacent IOTAs.
10. Insert the terminal strips onto the IOTA.
11. Completely insert the DIN rail hook to attach the IOTA to the DIN
rail.
12. Insert the CPM or IOM onto IOTA making sure that the CPM or
IOM matches properly with the IOTA connector.
13. Secure the CPM or IOM to the IOTA with two screws located at
each side of the plastic cover.
14. Secure the IOTA to the DIN rail with DIN rail stops.
87
Chapter 5 - Maintenance
88
CHAPTER
89
Chapter 6 - Diagnostics and Troubleshooting
LED
LED Condition Color Note
Status
RS485#1 TX Blink Orange Bi-color LED
RX Blink Green
No communication OFF N/A
RS485#2 TX Blink Orange Bi-color LED
RX Blink Green
No communication OFF N/A
RS232#1 TX Blink Orange Tri-color LED
RX Blink Green
TX and RX Blink Orange/Green
No communication OFF N/A
90
Chapter 6 - Diagnostics and Troubleshooting
LED
LED Condition Color Note
Status
RS232#2 TX Blink Orange Tri-color LED
RX Blink Green
TX and RX Blink Orange/Green
No communication OFF N/A
Power Power good, when power ON Green Single color
(18VDC – 30VDC) is supplied. LED
No power, when no power is OFF N/A
supplied or the power supply
does not meet system
requirements.
Status Boot All LED N/A Tri-color LED
ON
System good in running state ON Green
without error.
System stops with control Flash Green
strategy at 1Hz
System good without control Flash Green
strategy at
0.5Hz
System error ON Yellow
Firmware upgrade Flash Green/Yellow
at
0.5Hz
ETH#1 Communication Blink Green Single color
LED
Connected and no ON Green
communication
Not connected and no OFF N/A
communication
91
Chapter 6 - Diagnostics and Troubleshooting
LED
LED Condition Color Note
Status
ETH#2 Communication Blink Green Single color
LED
Connected and no ON Green
communication
Not connected and no OFF N/A
communication
ETH#3 Communication Blink Green Single color
LED, Used for
Connected, no communication ON Green
Expansion
Not connected, no OFF N/A I/O Modules
communication
92
Chapter 6 - Diagnostics and Troubleshooting
LED
LED Condition Color Note
Status
RS485#1 TX Blink Orange Bi-color
LED
RX Blink Green
No communication OFF N/A
RS485#2 TX Blink Orange Bi-color
LED
RX Blink Green
No communication OFF N/A
93
Chapter 6 - Diagnostics and Troubleshooting
LED
LED Condition Color Note
Status
RS232#1 TX Blink Orange Tri-color
LED
RX Blink Green
TX and RX Blink Orange/Green
No communication OFF N/A
RS232#2 TX Blink Orange Tri-color
LED
RX Blink Green
TX and RX Blink Orange/Green
No communication OFF N/A
Power Power good, when power (18VDC ON Green Single
– 30VDC) is supplied. color
LED
No power, when no power is OFF N/A
supplied or the power supply does
not meet system requirements.
Status Boot All LED N/A Tri-color
ON LED
Primary, system is running with ON Green
control strategy and good
Primary, system is stopped with Blink Green
control strategy and good 1Hz
Primary, system Good without Blink Green
Control strategy 0.5Hz
Secondary synchronized ON Orange
Secondary synchronizing Blink Orange
1Hz
Secondary not synchronized Blink Orange
0.5Hz
System Error ON Yellow
Primary, Firmware Upgrade Blink Green/Yellow
0.5Hz
Secondary, Firmware Upgrade Blink Orange/Yellow
0.5Hz
94
Chapter 6 - Diagnostics and Troubleshooting
LED
LED Condition Color Note
Status
Primary, Format SD Blink Green/Yellow
0.5Hz
Secondary, Format SD Blink Orange/Yellow
0.5Hz
ETH#1 Communication Blink Green Single
color
Connected and no ON Green
LED
communication
Not connected and no OFF N/A
communication
ETH#2 Communication Blink Green Single
color
Connected and no ON Green
LED
communication
Not connected and no OFF N/A
communication
ETH#3 Communication Blink Green Single
color
Port 1 Connected, no communication ON Green
LED,
Not connected, no OFF N/A Down
communication Link
95
Chapter 6 - Diagnostics and Troubleshooting
LED
LED Condition Color Note
Status
ATTENTION: Both ETH3 and ETH4 have two ports for ring solution. Each port
has a LED for status indication.
LED
LED Condition Color Note
Status
Power Power good, when power ON Green Single
(18VDC – 30VDC) is supplied. color
LED
No power, when no power is OFF N/A
supplied or the power supply
doesn’t meet system
requirements.
96
Chapter 6 - Diagnostics and Troubleshooting
LED
LED Condition Color Note
Status
IOM Status Boot All LED N/A Tri-
ON color
LED
System good in running state ON Green
without error.
System error ON Yellow
Firmware upgrade Flash Green/Yellow
at
0.5Hz
No IP address Flash Yellow
at 5Hz
I/O communication error Flash Yellow
at 1Hz
Communication Both ports connected ON Green Bi-
color
One port connected ON Yellow
LED
No port connected OFF N/A
Additional Information
n You may contact the Honeywell Technical Assistance Center (TAC)
or support center listed in the “Support and other contacts”
section of this document, for any issues related to ControlEdge
RTU. Please ensure that you provide all the relevant information,
while requesting support. When requesting support, supply as
many relevant details about the problem.
97
Chapter 6 - Diagnostics and Troubleshooting
98
CHAPTER
AEx ec IIC T4 Gc
AEx nA IIC T4 Gc
ATEX II 3 G Ex ec IIC T4 Gc
IECEx Ex ec IIC T4 Gc
99
Chapter 7 - Special Condition of Use and Approved Standards
For Canada
n The installer shall provide transient over-voltage protection
external to the apparatus such that the voltage at the supply
terminal of the apparatus does not exceed 140% of the voltage
rating of the equipment.
n The installation shall provide a controlled environment that limits
the pollution degree to the pollution degree 2 or better ad defined
in IEC 60664-1.
n The equipment shall be mounted within a tool-secured enclosure
which meets the requirements of CSA 60079-0 and CSA 60079-7
and is capable of accepting the application wiring methods
specified in CEC Part I.
n The enclosure for the equipment shall provide a degree of
protection not less than IP54 in accordance with the test of
enclosure section of CSA 60079-0 and CSA 60079-7 unless the
equipment is afforded an equivalent degree of protection by
location.
100
Chapter 7 - Special Condition of Use and Approved Standards
US Approval Standards
Item Number
Nonincendive electrical equipment for use in Class I and II, UL121201
Division2 and Class III, Division 1 and 2 hazardous (classified) (Ninth Edition)
locations
Explosive atmospheres - Part 0: Equipment – General Requirements UL 60079-0
(Sixth Edition)
Explosive atmospheres - Part 7: Equipment protection by increased UL 60079-7-
safety "e" 2017
Safety Requirements for Electrical Equipment for Measurement, UL Std. No.
Control, and Laboratory Use - Part 1: General Requirements 61010-1 (3rd
Edition)
101
Chapter 7 - Special Condition of Use and Approved Standards
Canadian Standards
Title Number
Nonincendive electrical equipment for use in Class I and II, CAN/CSA-C22.2
Division2 and Class III, Division 1 and 2 hazardous (classified) No. 213 - 17
locations
Safety Requirements for Electrical Equipment for CAN/CSA-C22.2
Measurement,Control, and Laboratory Use, Part 1: General No. 61010-1-12
Requirements
Explosive atmospheres - Part 0: Equipment - General requirements CAN/CSA-C22.2
No. 60079-0:15
Explosive atmospheres - Part 7: Equipment protection by increased CAN/CSA-C22.2
safety "e" No. 60079-7:16
General Requirements - Canadian Electrical Code Part II CAN/CSA C22.2
No. 0-10
(R2015)
ATEX Standards
Title Number
Electrical apparatus for explosive gas atmospheres. Part 0: EN 60079-0: 2018
General Requirements
Explosive atmospheres - Part 7: Equipment protection by EN 60079-
increased safety "e". 7:2015+A1:2018
102
Chapter 7 - Special Condition of Use and Approved Standards
EMC directive
Title Number
Electrical equipment for measurement, control and laboratory EN 61326-1
use - EMC requirements -- Part 1: General requirements
Industrial, scientific and medical (ISM) radio-frequency CISPR 11: 2009+A1
equipment – Electromagnetic disturbance characteristics –
Limits and methods of measurement.
Electromagnetic compatibility (EMC) – Part 3-2: Limits – Limits IEC 61000-3-2
for harmonic current emissions (equipment input current ≤ 16A
per phase)
Electromagnetic compatibility (EMC) – Part 3-3: Limits – IEC 61000-3-3
Limitation of voltage changes, voltage fluctuations and flicker in
public low-voltage supply systems, for equipment with rated
current ≤ 16 A per phase and not subject to conditional
connection
Electromagnetic compatibility (EMC) – Part 4-2: Testing and IEC 61000-4-2
measurement techniques – Electrostatic discharge immunity test
Electromagnetic compatibility (EMC) – Part 4-3: Testing and IEC 61000-4-3:
measurement techniques – Radiated, radio-frequency, 2006+A1:2007+A2
electromagnetic field immunity test
Electromagnetic compatibility (EMC) – Part 4-4: Testing and IEC 61000-4-4:
measurement techniques – Electrical fast transient/burst 2004+A1
immunity test
Electromagnetic compatibility (EMC) – Part 4-5: Testing and IEC 61000-4-5
measurement techniques – Surge immunity test
Electromagnetic compatibility (EMC) – Part 4-6: Testing and IEC 61000-4-6
measurement techniques – Immunity to conducted disturbances,
103
Chapter 7 - Special Condition of Use and Approved Standards
Title Number
induced by radio-frequency fields
Electromagnetic compatibility (EMC) – Part 4-8: Testing and IEC 61000-4-8
measurement techniques – Power frequency magnetic field
immunity test
Electromagnetic compatibility (EMC) – Part 4-11: Testing and IEC 61000-4-11
measurement techniques – Voltage dips, short interruptions and
voltage variations immunity tests
IEC Standards
Title Number
Electrical apparatus for explosive gas atmospheres. Part 0: IEC 60079-0 (2017)
General Requirements
Explosive atmospheres - Part 7: Equipment protection by IEC 60079-7:2017
increased safety "e". Ed 5.1
Marine Approvals
Bureau Veritas (BV)
Item Detail
Certificate Number 52627/AO BV
Requirements Bureau Veritas Rules for the Classification of Steel Ships
EC Code 31
104
Notices
NOTICES
Trademarks
Experion® is a registered trademark of Honeywell International, Inc.
ControlEdge™ is a trademark of Honeywell International, Inc.
OneWireless™ is a trademark of Honeywell International, Inc.
Other trademarks
Microsoft and SQL Server are either registered trademarks or
trademarks of Microsoft Corporation in the United States and/or
other countries.
Trademarks that appear in this document are used only to the benefit
of the trademark owner, with no intention of trademark infringement.
Third-party licenses
This product may contain or be derived from materials, including
software, of third parties. The third party materials may be subject to
licenses, notices, restrictions and obligations imposed by the licensor.
The licenses, notices, restrictions and obligations, if any, may be found
in the materials accompanying the product, in the documents or files
accompanying such third party materials, in a file named third_party_
licenses on the media containing the product, or at
http://www.honeywell.com/en-us/privacy-statement.
Documentation feedback
You can find the most up-to-date documents on the Honeywell
Process Solutions Support website at:
http://www.honeywellprocess.com/support
If you have comments about Honeywell Process Solutions
documentation, send your feedback to: hpsdocs@honeywell.com
Use this email address to provide feedback, or to report errors and
omissions in the documentation. For immediate help with a technical
problem, contact HPS Technical Support through your local
Customer Contact Center, or by raising a support request on the
Honeywell Process Solutions Support website.
105
Notices
Support
For support, contact your local Honeywell Process Solutions
Customer Contact Center (CCC). To find your local CCC visit the
website, https://www.honeywellprocess.com/en-US/contact-
us/customer-support-contacts/Pages/default.aspx.
Training classes
Honeywell holds technical training classes that are taught by process
control systems experts. For more information about these classes,
contact your Honeywell representative, or see
http://www.automationcollege.com.
106