Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Filename: RunTest.

test Manufacturer:
Date/Time: 07/18/23 19:30:08 Model:
Company: S/N:
Station: Operator:
Circuit: Frequency: 60 Hz
Comments: Knee Type: IEEE 30 Deg

Test Tap IEEE30 V/I IEEE45 V/I IEC 10/50 V/I NP-Ratio M-Ratio % Error Phase Angle Winding Resistance
1 X4-X5 15.52 / 0.2388 13.56 / 0.2014 16.04 / 0.2502 500/5.0 99.161 0.8387 -0.30° [In Ø] 123.97 milliohms

500V Insulation Resistance Test Results


Voltage: 493.8 V
Current: 0.08 MICRO-AMPS
Resistance: >1,000 MEG-OHMS

EZCT-2000 Software Version: 3.0


www.vanguard-instruments.com Page 1
Test # 1 : X4-X5
IEEE 30 IEEE 45 IEC 10/50 NP-RATIO: 500/5.0 Ex V[Volts]: 9.800V
Vkp[Volts]: 15.52 Vkp[Volts]: 13.56 Vkp[Volts]: 16.04 M-RATIO: 99.161 Ex I[Amps]: 0.159
Ikp[Amps]: 0.2388 Ikp[Amps]: 0.2014 Ikp[Amps]: 0.2502 % ERROR: 0.8387 Phase Angle: -0.30° [In Ø]
Winding Resistance: 123.97 milliohms
Test Notes:

Graph Point Current (Amps) Voltage Z (Ohm) Graph Point Current (Amps) Voltage Z (Ohm)
1 0.0200 0.7000 35.00 6 0.2000 13.4600 67.30
2 0.0400 1.6300 40.75 7 0.4000 17.8400 44.60
3 0.0500 2.1300 42.60 8 0.5000 18.2000 36.40
4 0.0800 3.8800 48.50 9 0.8000 18.7300 23.41
5 0.1000 5.1800 51.80 10 1.0000 19.0200 19.02

EZCT-2000 Software Version: 3.0


www.vanguard-instruments.com Page 2
Test # 1 : X4-X5
Data Point Current (Amps) Voltage Z (Ohm) Data Point Current (Amps) Voltage Z (Ohm)
1 0.0119 0.35 29.79 13 0.1387 8.21 59.18
2 0.0142 0.45 31.83 14 0.1663 10.63 63.90
3 0.0178 0.60 33.97 15 0.2063 13.99 67.81
4 0.0213 0.76 35.72 16 0.2561 16.38 63.93
5 0.0263 0.99 37.53 17 0.3177 17.35 54.61
6 0.0323 1.26 39.05 18 0.3676 17.69 48.12
7 0.0394 1.60 40.70 19 0.4478 18.06 40.32
8 0.0479 2.03 42.30 20 0.5746 18.39 32.01
9 0.0593 2.61 43.93 21 0.6764 18.56 27.44
10 0.0744 3.53 47.43 22 0.8263 18.76 22.71
11 0.0884 4.41 49.83 23 1.0083 19.03 18.88
12 0.1080 5.72 52.93

EZCT-2000 Software Version: 3.0


www.vanguard-instruments.com Page 3
Filename: RunTest.test Manufacturer:
Date/Time: 07/18/23 19:30:08 Model:
Company: S/N:
Station: Operator:
Circuit: Frequency: 60 Hz
Comments: Knee Type: IEEE 30 Deg

Test Plan

Tap Nameplate Ratio Ratio Excitation Winding Excitation Excitation Note


Test Test Res. Test Voltage Current
X4-X5 500/5.0 X X X 500.0000 1.0000

Burden Test [ ]
Insulation Test [X]

EZCT-2000 Software Version: 3.0


www.vanguard-instruments.com Page 4