Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 3

Check list ACB, VCB, OCB, LT PANEL

Air Circuit Breaker (ACB):

Panel 11 KV VCB type

1 Cleaning of breaker with CRC-226


Removal of old Grease and re-greasing the same with
2 recommended grease
Check condition of arcing contact and gap between fixed and
3 moving arcing contracts shall be checked.
Check condition of arcing contact and gap between fixed and
4 moving arcing contracts shall be checked.
Checking the reset mechanism, tripping of breaker through push
5 button.
Checking the reset mechanism, tripping of breaker through push
6 button.
7 Checking tripping of ACB through protection release.
8 Checking presence and proper tightening of hardware.
9 Checking presence of all cir clips.
Checking condition and alignment of jaw contract with cradle
10 terminals
11 Checking condition of ACB wiring and replace if required.
12 Checking and adjusting gap between hylam sheet and side plate.
13 Checking proper closing of all poles together.
14 Checking working of anti pumping device in case of EDO ACB.
15 Checking alignment of SIC and its operation.
16 Checking scrapping earth alignment.
17 Checking condition of arc chutes.
18 Checking U/V release pickup and drop off.
19 Checking ACB tripping through Shunt release.
20 Checking motor operation in case of EDO ACB.
21 Checking closing coil operation in case of EDO ACB.
22 Checking continuity and proper changeover of aux contract block.
23 Checking IR between phases – phase (ACB Closed condition).
24 Checking IR between phases – earth (ACB closed Condition).
25 Checking IR between phases – earth (ACB in open condition).
26 Setting of release as per the load.
After the inspection, the ACB shall be checked for proper
27 termination by mv drop Test
Vacuum Circuit Breaker (VCB):
1 Cleaning of Vacuum Circuit Breaker with CRC-226
Removal of old grease and re-greasing the same with
2 recommended grease
3 Check condition of SIC Contacts
4 Checking condition and alignment of jaw Contact
5 Checking and proper tightening of hardware
6 Checking proper closing of all poles together
7 Checking of breaker tripping through push button
8 Checking and adjusting gap between hylam sheet and side plate
9 Checking motor operation in case of EDO.
10 Checking of auxiliary contacts continuity proper change over
11 Checking presence of all circlips
12 Checking IR between phase – phase (VCB closed condition)
13 Checking IR between phase – earth (VCB closed condition)
14 Checking IR between phase – earth (VCB in Open condition)
15 Any faculty spare replace by new one, which will be charged extra.
Oil Circuit Breaker (OCB):
1 Cleaning of Oil Circuit Breaker with CRC-226
Removal of old grease and re-greasing the same with
2 recommended grease
3 Check condition of SIC Contacts
4 Checking condition and alignment of jaw Contact
5 Checking and proper tightening of hardware
6 Checking proper closing of all poles together
7 Checking of breaker tripping through push button
8 Checking and adjusting gap between hylam sheet and side plate
9 Checking motor operation in case of EDO.
10 Checking of auxiliary contacts continuity proper change over
11 Checking presence of all circlips
12 Checking IR between phase – phase (OCB closed condition)
13 Checking IR between phase – earth (OCB closed condition)
14 Checking IR between phase – earth (OCB in Open condition)
15 Any faculty spare replace by new one, which will be charged extra

LT Panel: We do following during regular maintenance of LT


Panel
1 Cleaning of Panel Breaker with CRC-226
2 Check condition of Bus bars
3 Checking condition and alignment of jaw Contact
4 Checking and proper tightening of hardwares
5 Checking of breaker tripping through push button
6 Checking motor operation in case of EDO.
7 Checking of auxiliary contacts continuity proper change overs
8 Checking presence of all circlips
9 Checking IR between phase – phase (ACB closed condition)
10 Checking IR between phase – earth (ACB closed condition)
11 Checking IR between phase – earth (ACB in Open condition)
12 Checking of Contactor NO NC Point
13 Checking of ad on block NO NC Point
14 Checking of Control Wiring
15 Checking of Thimble Tightness
16 Checking of MCCB
17 Checking o MCB
18 Any faculty spare replace by new one, which will be charged extra.
Control Wiring: We do following during regular maintenance of
Control Wiring
1 Checking of All Control Wiring
2 Checking of Contactor in NO/NC Point
3 Checking of Glass Relay in NO/NC Point
4 Checking of MCB Terminals
5 Checking of RCCB Terminals
6 Checking of Contactor Coil Resistance
7 Checking of auxiliary Contact
8 Checking of thimble of Terminals
9 Checking of indicator of Panel
10 Checking selectors switch in NO/NC Point
11 Checking of TNC Switch in NO/NC Point
12 Checking of Fuse Link Terminals
13 Checking of Timer Relay Terminals
14 Checking of Amp Meter Tightening at Terminals
15 Checking of voltage meter Tightening at Terminals

You might also like