Compliance Sheet for air outlets

Project name NBK Last Updated -

Consultant DAR Submission Date -


Contratcor ECS

ID Number Specifications Compliance Notes


1.1 RELATED DOCUMENTS
A Drawings and general provisions of the Contract, including
General and Supplementary
Noted
Conditions and Division 01 Specification Sections, apply to this
Section.
1.2 SUMMARY
A This Section includes the following: Noted
1.3 DEFINITIONS
A Diffuser: Circular, square, or rectangular air distribution outlet,
generally located in the ceiling and comprised of deflecting
members discharging supply air in various directions Noted
and planes and arranged to promote mixing of primary air with
secondary room air.
B Grille: A louvered or perforated covering for an opening in an air
passage, which can be located in a sidewall, ceiling, or floor. Noted

C Register: A combination grille and damper assembly over an air


Noted
opening.
1.3 SUBMITTALS
A Product Data: For each type of product indicated, include the
data sheets are attached
following:
1 Data Sheet: For each type of air outlet and inlet, and accessory
furnished; indicate construction, finish, and mounting details. comply data sheets are attached

2 Performance Data: Include throw and drop, static-pressure drop,


and noise ratings for each type of air outlet and inlet. comply

3 Diffuser, Register, and Grille Schedule: Indicate drawing


designation, room location, quantity, model number, size, and contractor scope
accessories furnished.
4 Assembly Drawing: For each type of air outlet and inlet; indicate
materials and methods of assembly of components. contractor scope

1
B Coordination Drawings: Reflected ceiling plans and wall
elevations drawn to scale to show locations and coordination of
diffusers, registers, and grilles with other items installed in contractor sope
ceilings and walls.

C Source quality-control reports comply


1.5 QUALITY ASSURANCE
A Product Options: Drawings and schedules indicate specific
requirements of diffusers,registers, and grilles and are based on
the specific requirements of the systems selected. Other
manufacturers' products with equal performance characteristics comply
may be considered. Refer to
Division 1 Section "Product Requirements.

B NFPA Compliance: Install diffusers, registers, and grilles


according to NFPA 90A, "Standard
comply
for the Installation of Air-Conditioning and Ventilating Systems.

Parts PART 2 PRODUCTS


2.1 SHEET METAL MATERIALS
Galvanized, Sheet Steel: Lock-fonning quality ASTM A
A 653/A 653M ,Z275(G90) coating designation; mill- comply electrostatic bowder coating
phosphatized finish for surfaces of ducts exposed to view.
B Carbon-Steel Sheets: ASTM A 1008/A 1008M, cold-rolled
sheets,commercial quality,with oiled, exposed matte finish. comply

C Aluminum Sheets: ASTM B 209M (ASTM B 209), Alloy


3003, Temper Hl4, sheet form; with standard, one-side bright
finish for ducts exposed to view and mill finish for concealed Out of scope
ducts.
D Extruded Aluminum: ASTM B 221M (ASTM B 22 1), Alloy
6063, Temper T6 comply

E Reinforcement Shapes and Plates: Galvanized steel


reinforcement where installed on galvanized, sheet metal
Out of scope
ducts; compatible materials for aluminum and stainless-steel
ducts.

2
F Tie Rods: Galvanized steel, 6-mm minimum diameter for 900-
mm length or less; 10-mm minimum diameter for lengths longer Out of scope
than 900 mm.
2.2 BAGKD - AND PRESSURE RELIEF DAMPERS
A Description :Gravity balanced, suitable for horizontal or vertical
installations .Dampers shall not produce noise while in operation comply

B Frame: 1.3-mm thick, galvanized, sheet steel, with welded


comply
comers and mounting flange
C Frame: 1.6-mm thick extruded aluminum, with mounting flange.
comply
D Blades: Multiple single-piece blades, 0.6-mm thick, roll-fanned
aluminum, maximum 150-mm width, with sealed edges. comply

E Blades: Multiple single-piece blades, 1.2-mm thick aluminum


sheet, maximum 150-mm width, with sealed edges comply
F Blade Action: Parallel comply
G Blade Seals: Neoprene. comply
H Blade Axles: Nonferrous. comply
I Blade Axles: Galvanized steel. comply
J Tie Bars and Brackets: Aluminum. N/A
K Tie Bars and Brackets: Galvanized steel comply
L Return Spring: Adjustable tension. N/A
M Bearings: Galvanized steel ball Comply as noted push bearings : Bronze
N Accessories:
1 I. Adjustment device to pennit setting for varying differential
static pressure. N/A

2 Counterweights and spring-assist kits for vertical airflow installations. N/A


3 Electric actuators. N/A
4 Chain pulls. N/A
5 Screen Mounting: Front mounted in sleeve. comply
a Sleeve Thickness: 20-gage (1.0-mm) minimum comply
b Sleeve Length: 6 inches (152 mm) minimum. comply
6 Screen Mounting: Rear mounted comply
7 Screen Material: [Galvanized steel] [Aluminum]. comply
8 Screen Type: Bird. comply
9 90-degree stops. comply
2.3 MANUAL-VOLUME DAMPERS

3
A General: Factory fabricated with required hardware and
accessories. Stiffen damper blades for stability. Include locking
device to hold single-blade dampers in a fixed positionwithout comply
vibration. Close duct penetrations for damper components to
seal duct consistent with pressure class.
1- Pressure Classifications of 500 Pa (2-Inch wg) or Higher: End
bearings or other seals
for ducts with axles full length of damper blades and bearings at comply
both ends of
operating shaft
B Low-Leakage Volume Dampers: Multiple- or single-blade,
parallel- or opposed-blade design as indicated, low-leakage
comply
rating, with linkage outside airstream, and suitable for horizontal
or vertical applications.
1 Steel Frames: Hat-shaped, galvanized, sheet steel channels,
minimum of 1.6 mm thick, with mitered and welded comers;
frames with flanges where indicated for attaching to walls; and comply
flangeless frames where indicated for installing in ducts.
2 Aluminum Frames: Hat-shaped, 1.6-mm thick, extruded-
aluminum channels; frames with flanges where indicated for
comply
attaching to walls; and flangeless frames whereindicated for
installing in ducts.

4
3 Roll-Formed Steel Blades: 1.6-mm thick, galvanized, sheet steel. N/A
4 Roll-Formed Aluminum Blades: 2.5-mm thick aluminum sheet.
N/A
5 Extruded-Aluminum Blades: 1.2-mm thick extruded aluminum.
Comply
6 Blade Axles: Nonferrous. Comply
7 Blade Axles: Galvanized steel Comply
8 Tie Bars and Brackets: Aluminum. N/A
9 Tie Bars and Brackets: Galvanized steel. Comply
C Jackshaft: 25-mm diameter, galvanized steel pipe rotating within
a pipe-bearing assembly mounted on supports at each mullion
Comply as noted Square = 12.5x12.5
and at each end of multiple-damper assemblies..

1 Length and Number of Mountings: Appropriate to connect


linkage of each damper of Comly
a multiple-damper assembly.
D Damper Hardware: Zinc-plated, die-cast core with dial and
handle made of 2.4-mm thick zinc-plated steel, and a 19-mm
hexagon locking nut. Include center hole to suit damper
operating-rod size. Include elevated platform for insulated duct comply
mounting.

4 FIRE DAMPERS
a General: Labeled to UL 555. comply
b Fire Rating: One and one-half hours. comply
c Fire Rating: One and one-half and three hours comply
d Frame: SMACNA Type A with blades in airstream; fabricated with roll-
formed, 0.85-mm thick galvanized steel; with mitered and interlocking comply
comers.
e Frame: SMACNA Type B with blades out of airstream; fabricated with
roll-fonned, 0.85-mm thick galvanized steel; with mitered and comply
interlocking comers.
f Mounting Sleeve: Factory- or field-installed galvanized, sheet steel.
comply
1 Minimum Thickness: 1.3 mm or 3.5 mm thick as indicated, and length
to suit comply
application
2 Exceptions: Omit sleeve where damper frame width pennits
direct attachment of perimeter mounting angles on each side of
comply
wall or floor, and thickness of damper frame complies with
sleeve requirements.

5
G Mounting Orientation: Vertical or horizontal as indicated. comply
H Blades: Roll-formed, interlocking, 0.85-mm thick, galvanized,
sheet steel. In place of interlocking blades, use full-length, 0.85-
comply
mm thick, galvanized steel blade connectors..

I Horizontal Dampers: Include a blade lock and stainless-steel


comply
negator closure spring.
J Fusible Link: Replaceable, 74 or 100 deg C (165 or 212 deg F)
comply
rated.
2.5 SMOKE DAMPERS comply
A General: Labeled to UL 555S. Smoke dampers shall be labeled
for one-and-one-half-hour or three hours rating to UL 555 as per comply
design requirements.
B Smoke Detector: Integral, factory wired for single-point
comply
connection
C Frame and Blades: 1.6-mm thick, galvanized, sheet steel. comply
D Mounting Sleeve: Factory-installed, 1.3-mm thick, galvanized,
sheet steel; length to suit wall or floor application. comply

E Rated pressure and velocity to exceed design airflow conditions.


comply
F Damper Motors: Provide for modulating or two-position action
comply
1 Motor Sizes: large enough so driven load will not require motor
N/A
to operate in service factor range above 1.0.
2 Pennanent-Split-Capacitor or Shaded-Pole Motors: With oil-immersed
N/A not allowed by UL
and sealed gear trains.
3
Spring-Return Motors: Equip with an integral spiral-spring mechanism
where indicated. Enclose entire spring mechanism in a removable N/A
housing designed for service or adjustments. Size for running torque
rating of 17 N x m and breakaway torque rating of 17 N x m
4 Outdoor Motors and Motors in Outside-Air Intakes: Equip with O-ring
gaskets designed to make motors weatherproof. Equip motors with
comply
internal heaters to pennit normal operation at minus 40 deg C (minus
40 deg F).
5 Nonspring-Retum Motors: For dampers larger than 2.3 sq. m,
size motor for running torque rating of 17 N x m and breakaway comply
torque rating of 34 N x m.
6 Two-Position Motor: 230 V, single phase, 50 Hz. comply
7 Two-Position Motor: 380 V, 3 phase, 50 Hz. N/A

6
8 Modulating, Spring-Return Motor: 230 V, single phase, 50 Hz.
N/A
9 Modulating, Spring-Return Motor: 380 V, 3 phase, 50 Hz. N/A
G Accessories:
1 Auxiliary switches for signaling or position indication. comply
2 Test and reset switches, damper or remote mounted as
N/A
practical.
2.6 COMBINATION FIRE AND SMOKE DAMPERS
A Type: Dynamic; rated and labeled according to UL 555 and UL
comply
555S.
B Fire Rating: 1-1/2 and 3 hours. comply
C Frame: Hat-shaped, 0.094-inch- (2.4-mm-) thick, galvanized
sheet steel, with welded comers and mounting flange.

D Heat-Responsive Device: Replaceable, [165 deg F (74 deg C)]


comply
[212 deg F (100 deg C)] rated, fusible links.
E Smoke Detector: Integral, factory wired for single-point
comply
connection.
F Blades: Roll-fonned, horizontal, interlocking 1.6-mm-thick,
comply
galvanized sheet steel
G Leakage: Class I. comply
H Rated pressure and velocity to exceed design airflow conditions
comply
I Mounting Sleeve: Factory-installed, 1.3-mm- thick, galvanized
sheet steel; length to suit wall or floor application. comply

J Master control panel for use in dynamic smoke-management


Out of scope
systems
K Damper Motors: Modulating or two-position action comply
L Comply with NEMA designation, temperature rating, service
factor, enclosure type, and efficiency requirements for motors
comply
specified in Section 230513 "Common Motor Requirements for
HVAC Equipment.
1 Motor Sizes: large enough so driven load will not require motor
comply
to operate in service factor range above 1.0.
2 Permanent-Split-Capacitor or Shaded-Pole Motors: With oil-
N/A
immersed and sealed gear trains.

7
3 Spring-Return Motors: Equip with an integral spiral-spring
mechanism where indicated. Enclose entire spring mechanism in
a removable housing designed for service or adjustments. Size
for running torque rating of 150 in. x !bf (17 N x m) and comply
breakaway torque rating of 150 in. x !bf (I 7 N x m).

4 Outdoor Motors and Motors in Outdoor-Air Intakes: Equip with O-


ring gaskets designed to make motors weatherproof. comply

5 Nonspring-Retum Motors: For dampers larger than 25 sq. ft. (2.3


sq. m), size motor for running torque rating of 150 in. x !bf (17 N
comply
x m) and breakaway torque rating of 300 in. x !bf (34 N x m).

6 Electrical Connection: 230 V, single phase, 50 Hz comply


Accessories:
1 Auxiliary switches for signaling or position indication. comply
2
Test and reset switches, damper or remote mounted as practicle. N/A
2.9 DUCT-MOUNTED ACCESS DOORS AND PANEL

8
A Door shall be rigid and airtight with neoprene gaskets and two or
more chrome-plated enamel painted steel hinges and quick
fastening locking devices. Provide doors as large as practical.
Include vision panel where indicated. Include 25-by-25 mm butt comply
or piano hinge and cam latches. Access doors up to 300 X 300
mm shall have two cam locks, larger sizes shall have four cam
locks.
B Mount doors, if possible, so that air pressure holds them closed. As an
alternative, removable access doors may be used. N/A
C Access doors shall be constructed from stamped sheet metal and
consist of an inner and outer door panel. Where insulated doors are
needed, the inner door shall consist of two panels spot-welded
together which totally encapsulate insulation identical to comply
corresponded ductwork insulation. The inner and outer doors shall be
joined by bolts and threaded handles in such a configuration that the
panels can be drawn together to secure the door to the duct in a
D The handles shall be high impact plastic with threaded metal inserts.
Conical springs shall be used between the door panels to facilitate
installation and removal of the door. Fireproof neoprene gasket shall N/A
be used around the outside edge of the inner or outer panel, but not
both, to seal the door.
E This type of door is approved for use on rectangular, round and flat-
comply
oval ductwork.
F Insulation: 25-mm thick, fibrous-glass or polystyrene-foam board comply