Professional Documents
Culture Documents
MPR500
MPR500
www.itmikro.com
MPR500
Features
• Microprocessor based numerical relay
• Thermal overload
• Overcurrent
• Undercurrent
• Unbalance
• Phase loss
• Phase sequence
• Earth fault
Technical Data
CT RATINGS SETTING RANGES
Rated current, IB : 2-10A Thermal Overload stalled rotor, IS : , 2-12 x lB.
Rated frequency : 50 Hz or 60 Hz 6X : 1 – 40s. Step 0.1 x IB
Burden : <0.3 VA at rated Step 0.1s for 1-10s,
current step 1s for 10-40s.
Thermal withstand : Short circuit, I>> : , 2-12 x lB. Start : 0 – 60s.
Con Step 1 x IB Step 0.1s for 1-10s,
45s : 6x max rated : 0 – 25s. step 1s for 10-60s.
1s : 10x max rated Step 0.1s for 1-10s, Stalled rotor delay : 0 – 60s.
step 1s for 10-25s. Ɵme,tStall Step 0.1s for 1-10s,
Undercurrent, I<< : , 20-90% lB. step 1s for 10-60s.
BINARY INPUT
Rated input voltage : 12V (Supplied Step 1%
internally) : 0 – 60s. INDICATORS
Step 0.1s for 1-10s, Run : Green indicator
step 1s for 10-60s. Trip/Pickup : 7-segment display
AUXILIARY SUPPLY and red indicator
Model MPR 500-240AD : 85 ~ 265 V AC Unbalance, : , 10-50%.
Step 1% Thermal : Yellow indicator
110 ~ 370 V DC
Supply frequency : 50 or 60 Hz : 0 – 25s.
Maximum power Step 0.1s for 1-10s,
: 3 VA typical Step 1s for 10-25s. ENVIRONMENTAL CONDITIONS
Earth fault, IƋ : , 10-60% lB. Temperature : -10°C to 55°C
Step 1% Humidity : 5% to 95%,
OUTPUT CONTACTS non-condensing
Rated voltage : 250V AC Ƌ : 0 – 25s.
:5 A Step 0.1s for 1-10s,
step 1s for 10-25s. ACCURACY
MPR 500
Ordering Information
MODEL DESCRIPTION
DWZϱϬϬͲϮϰϬ &ŽƌϱϬͬϲϬ,njƐLJƐƚĞŵ͕ĂƵdžŝůŝĂƌLJǀŽůƚĂŐĞϴϱΕϮϲϱsŽƌϭϭϬΕϯϳϬs
MPR 500