Rigid Footing Moment Capacity
Rigid Footing Moment Capacity
Rigid Footing Moment Capacity
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Rigid Footing Moment Capacity Design Based on ASCE 41-17 & ACI 318-19
DESIGN CRITERIA
1. Soil resists compression only, without tension capacity. Soil bearing pressure
distribution is a plane, and a triangular distribution block when un-full area
compression under the footing.
2. The input P, Mx, & My are net loads on the footing bottom face, which the location
(X1 & Y1) is directly from top building analysis and not has to be at the centroid of
footing bottom section.
3. This general methodology cannot apply to Dynamic Analysis (ASCE 7-22 12.9)
and higher level seismic design, because all CQC results are probability results
without P, Mx, & My load directions.
ANALYSIS
CHECK THE CENTER OF GRAVITY WITHIN FOOTING
XCG = X1 + My / P = 14.00 ft YCG = Y1 - Mx / P = 1.00 ft A = 154.50 ft2
> 0 > 0 (full footing area)
> 9.00 [Satisfactory] < 7.00 AC = 3.78 ft2
< 15.00 < 12.50 (compression contact area)