Professional Documents
Culture Documents
Relay Settings in Real Power System
Relay Settings in Real Power System
Consideration
Types of Relay
Based on Application:
Primary
Backup
Overcurrent Relay
Overcurrent is the most used relay protective scheme as compared to
others.
Definition:
An overcurrent relay works on sensing current. It operates whenever
the current exceeds a permissible value or pickup value.
Layout:
An overcurrent relay works such that the system current is sensed by a
current transformer (C.T). The primary side of C.T is connected to the
system and the secondary side with a relay. In case of:
Types:
Instantaneous OCR Definite time OCR Inverse time OCR
Trips after the current exceed the Tripping time is inversely
Trips after the current exceed the
allowable range with a certain time proportional to the magnitude of
allowable range with negligible delay
delay current
Definition:
Minimum amount of current required for the operation of the relay.
Objective:
Power system components work properly at a certain allowed current
and when the magnitude of current exceeds a certain value (as in case
of a fault), it can cause damage to the component and the entire
system reliability is compromised. The relays are designed to operate
above these rated currents. The pickup current is thus set at the
maximum allowed current.
Formula:
Ipu = Rated CT output * %current setting
where,
Current Setting:
Definition:
To adjust the pickup current (Ipu) to the desired value.
Objective:
C.T output comes in standard for example: 5A according to IEC
and 1A according to IEEE.
The current setting sets the pickup value according to it so that the
relay can operate at pickup current instead of working at rated C.T
output
Plug Setting Multiplier (PSM):
Definition:
The ratio of fault current in the relay coil and the pickup current.
Objective:
It defines the severity of a fault. According to the severity of the fault,
the relay may decide the time of operation.
For example:
Formula:
Definition:
A relay time of operation can be adjusted using a time setting
multiplier. Gives the real time of operation (TOP) with respect to
time/PSM curve
Objective:
Sometimes it is desired to trip the relay much earlier than the provided
time from its time/PSM curve.
A dial is provided whose value ranges from 0 to 1, with step of 0.05, the
dial is adjusted at the required value and multiplied with the relay
operating time from time/PSM curve to obtain required time of
operation
Formula:
top = TSM * time PSM curve time
Time/PSM Curve:
Definition:
Time/PSM curve represents graph between time (y-axis) and PSM (x-
axis). It represents the time of operation of a relay according to PSM,
when TSM is 1.
Objective:
The time/PSM curve helps in achieving the time of tripping according to
the severity of overcurrent or fault. The manufacturer provides the
relay time/PSM curve of a relay and it can be created/varied in
microprocessor based relay.
Procedure:
Step1: Calculating pickup-current.
Step2: Converting fault current into relay coil current by dividing
fault current with C.T ratio.
Step3: Calculating PSM
Step4: From the time/PSM curve of a provided relay, determine
the value of time of operation (at TSM=1) from the calculated
PSM.
Step5: Multiplying the time from time/PSM curve with the
required TSM to get the time of operation.
Solved Example:
Considering the following data:
C.T = 100 / 1
TSM = 50%
Solution:
Ipu = 0.8 A
PSM = 10
top = 1s
Principle of Time/Current Grading
A time/PSM curve for relays can be set in any of the three ways, which
are described as:
1. Discrimination by Time:
A constant time setting is given to each relay irrespective of
the magnitude of the current.
The issue with this method is that the relay closest to the
source has the largest delay while it has the maximum fault
current that could flow within the system, which can
damage the system due to a large time delay.
2. Discrimination by Current:
This method is based on the phenomenon that fault current
amplitude varies with a change in impedance between
source and fault.
Primary Protection:
They are concerned with internal fault and are efficient enough to
detect a fault in the least possible time within a zone and gives a trip
signal. Primary protection schemes are usually implemented using
differential, distance, and directional overcurrent protection.
Differential Protection:
Differential protection works on the current matching principle that is
two CTs are connected in a region in such a way that whenever there is
a difference in current within that region, the relay gives a trip signal,
else no tripping.
Distance Protection:
In transmission lines, it is not possible to implement differential
protection. For transmission line protection, distance protection is used
which is based on ohm’s law that measures voltage and current, if the
measured impedance is less than the transmission line impedance then
the relay gives a trip signal.
Backup Protection:
For better reliability purposes, backup protection schemes are used.
They are less efficient than primary protection but are used for the
purpose, if primary protection does not give a trip signal due to some
reason in case of fault, the backup protection trips after some delay.
They are also used in detecting external faults. Backup protection is
achieved using overcurrent relay.
Coordination Methodology
The following methodology is adopted for the overcurrent protection of the power system:
Data Required:
1. Single line diagram, indicating rating, manufacturer, and types of
each element including C.T, motors, generators, transformer,
cables and protective devices (for accurate short circuit
calculation and relay coordination)
2. Impedance of rotating machines and transformers (as they also
take part in fault current)
3. Minimum and maximum fault current. (for time-setting purposes)
4. Maximum loading ( to get an overload of the system)
5. Voltage level (for selection of the type of circuit breaker and relay)
6. Starting and inrush current, damage curves of cables and
transformer, induction motor stalling time and acceleration time
(these variables are considered in order to prevent nuisance
tripping)
Rules:
1. If possible, relays having similarities in operation should be
placed in series.
2. Relay farthest from the source must have a current setting less
than or equal to the relay behind it, as the relay in front requires
less current to operate as compared to the relay behind it.
Ring System:
In the given system, 1 & 8 are non-directional relays while 3, 5 & 7 are
relays that will sense fault in a clockwise direction, and 2, 4 & 6 in
counter-clockwise direction that is 2, 3, 4, 5, 6, 7 are directional relays.
support@allumiax.com