Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Vigilon Plus Control Panels

Vigilon Plus Control Panels are available in 3 sizes managing 2, 4 or 6 loops


each accommodating up to 200 devices including advanced fire sensors,
interfaces, call points, alarm sounders and visual alarms.

The Compact Plus 2 loop panels and Vigilon Plus 4 loop panels are
available with integrated 24 hour standby and the 6 loop panel has full 72
hr standby capacity. Advanced networking options allow networking of up
to 200 panels in a multi-domain structure with options of copper or optic
fibre connections.

Vigilon’s back-lit LCD display presents clear indication of Fire or Fault


location and the control panel’s innovative 8-line x 40 character display
with push-button keypad is simple to use. Fire Plans can be tailored to
precisely meet site requirements.

Vigilon’s software allows network areas to be sectored to evacuate or alert


status, or configured with pre-set delays. Description

Fully compatible with Honeywell Gent’s innovative S-Quad range – a The Vigilon Plus Range of Advanced Fire
combined Multi-Sensor range with speech, sounder and EN54-23 Visual Detection Control Panels is applicable for
Alarm devices in one intelligent unit. buildings of any size.

The Vigilon Plus Repeat control panel provides full display and control of
the system. Connecting to the detection loop, the repeat panel provides
a cost effective solution with minimum requirements for cabling and
installation.

Repeat panels are supplied complete with their own 72 hour power supply
and standby batteries.

K E Y F E AT U R E S

• Integral EN54-4 PSU • PC based • The control panel has • Flexible programming • In the event of a fire or
and battery standby commissioning tools a simple user interface options are available fault, Vigilon’s
for 24 hours (4 loop) allow complex fire with LCD screen at the panel analogue addressable
plans to be configured providing accurate technology will
• Integral EN54-4 PSU • All Vigilon devices
information in an provide a detailed log
for 72 hours with • Advanced loop card connect onto the same
emergency of events
external batteries (6 technology allows for two core loop,
loop) system status • Multiple panel separate sounder or • PC based Graphics
monitoring and networks can be repeater panel wiring user interface (GUI)
• Vigilon’s advanced
diagnostics programmed circuits are not available
sensing technology
seamlessly as one required
and powerful software • Vigilon Plus can also • Extended event log
system, allowing for
processing in the be supplied in a range using fl ash memory
fl exible design and
panel quickly of custom colour outer card
system management
identifies real fires doors
Vigilon Plus Control Panels Technical Specifications
ORDER CODES SPECIFICATION
1 TO 2 LOOP CONTROL PANEL COMPACT-PLUS PANEL TYPE Compact Plus 2 Vigilon Plus 4 Loop Vigilon Plus 6 loop Vigilon Plus
1 TO 4 LOOP CONTROL PANEL VIGPLUS-24 Loop Panel panel Repeat Panel
MAX. NO. OF LOOPS 2 4 6 -
1 TO 4 LOOP CONTROL PANEL – NO PRINTER VIGPLUS-24-NP
1 TO 6 LOOP CONTROL PANEL VIGPLUS-72
LOOP CAPACITY 200 with Alarm 200 with an alarm 200 with an alarm Max 4 per loop
Current 800mA current of up to current of up to
VIGILON LOOP CARD VIG-LPC-EN (Max Alarm current 800mA (Equivalent to 800mA (Equivalent
VIGILON NETWORK CARD (COPPER) VIG-NC across both loops 100 sensor sounders to 100 sensor
(1.2 A) VADs) sounders VADs)
VIGILON NETWORK CARD (MULTIMODE VIG-NC-FO
FIBRE) BATTERIES 2 x 12Ah 2 x 21Ah 4 or 8 x 21Ah 1 x 7Ah
VIGILON UPGRADE KIT VIG72-UPGR BATTERY STANDBY 24hrs +30 mins in 24 hours + 30 minutes 72 hours + 30 72 hours
alarm alarm upgradeable to minutes alarm
FLUSH SURROUND VIG-FLUSH 72 hours
VIGILON PLUS REPEAT PANEL VIGPLUS-RPT APPROX. WEIGHT 12 Kg (inc 22 Kg (inc batteries) 10.2 Kg (panel 9Kg (inc
VIGILON PLUS TERMINAL NODE (EN54 VIGPLUS-NODE batteries) only) batteries)
VERSION) FOR MULTIPLE IO CARDS AND 31 Kg (battery
FIBRE NETWORKS (SUPPLIED IN BLACK) enclosure inc four
COMPACT PLUS TERMINAL NODE FOR VIGILON COMPACT-NODE batteries)
PANEL NETWORKS (SUPPLIED IN BLACK) OPERATING TEMP. 0 - 45ºC 0 - 45ºC 0 - 45ºC 0 - 45ºC
STAINLESS STEEL OPTIONS CABLE ENTRY Top and rear knockins
STAINLESS STEEL DOOR FOR VIGILON MAIN VIG-DOOR-SS APPROVALS EN54 Parts 2 & 4 -
CONTROL PANEL
EN54-2 requires that Vigilon 4 & 6 loop panels are restricted to max. 512 sensors and call points
STAINLESS STEEL FLUSH MOUNTING KIT FOR VIG-FLUSH-SS
VIGILON MAIN CONTROL PANEL
System Architecture MCP
CUSTOM COLOUR DOOR Contact Business
Manager Repeat S-Quad Sensor
Panel Sounder

Dimensions (mm) MCP


T-breaker

S-Quad Sensor
Sounder Sprinkler
Interface
Loop Length up Units Door Release or
S-Cubed to 2.5 km Plant Shutdown
2.5km with 2.5mm cable CSA S-Quad Sensor
Alarm 2km with 1.5mm cable CSA
Sounder Sounder
B
Beam Beam
Transmitter S-Quad Sensor sounder Receiver
EN54-23 VAD
Loop 1

WINMAG Manned Loop 2


Loop 3
Centre Link to Loop 4

Fire Station

A C Secure Secure
Node
Vigilon Fibre Copper Loop 1
A B C Plus Network
Loop 6
Network
Vigilon Plus 406 543 172
Battery Box 421 437 174 Node Node
(only required with VIG1-72 Secure
6 loop panel) Honeywell Fibre Optic Loop 2
4 or 6 loop,
Voice Alarm Serial link Domain Loop 3

Compact Plus / Vigilon Plus 338 403 101


Loop 4
24 or 72 hour
(Max 200 panels/
S-Quad standby
Repeat Panel Sensor
nodes per system)
Loop 1

For more information MCP


Up to 200 Devices
www.gent.co.uk per Loop
FAAST
Interface
FAAST
S-Quad Sensor
Honeywell Gent A3 Mimic Panel Speech,
EN54-23 VAD
140 Waterside Road MCP

Hamilton Industrial Park, Content subject to change


Leicester, LE5 1TN without notice.

Telephone: 0203 409 1779 GEN147 | 05/2018


E-mail: gentenquiry@honeywell.com © 2018 Honeywell International Inc.