Residence jx
s+
wom 5/8 BID
LPG DETECTOR SENSORS IS NOT FIXED PROPERLY (should
bbe at 30 cm from floor level and sensor propeller should HELIUM
be down direction)
‘THE DOSING SYSTEM IS NOT WORKING HELIUM
‘THE CEILING IS NOT FIXED PROPERLY HELIUM‘SOME ITEM IN THE HOOD NEEDS TO FIX PROPERLY SULITACO
axccrnensswmenesanenorcrounwewen | ELUM
ALALOORORANTRAPISSHAKNEANDNEEDSTOBE | — oy
Surronteo more
r
|
f TerLoonDeantearanea wees ora POR | sy
|? eySLIDING A DOOR IS VERY HARD WHEN MOVING TO
OPEN OR CLOSE veuuee
‘THE SOUNDER ALARM IS NOT HINGED PROPERLY WITH
WALL TILE WHICH IS BROKEN ALREADY AND ANY TIME HEWUM
CAN FALL DOWN
UNDER THE SINK ALL HOSE PIPE LENGTH IS NOT a
‘CORRECT AND TOUCHING THE FLOOR
UNDER THE SINK THER ING FROM THE
INK THERE 1S WATER LEAK ee
ANGLE VALVEINSULATION TERMINATION NOT DONE PROPERLY WIRE erry
IS NOT HUGED WELL
‘SWITHES COVER IS DAMAGE AND NEED TO CHANGE HELIUM
'SWITHES COVER IS DAMAGE AND NEED TO CHANGE HELIUM
‘THE HANDICAP WC IS ou ne FINISHED AND OUT OF J coc uetiunaONE MALE WC IS STILL OUT OF ORDER
SULITACO+HELIUM
‘THE MALE WASHBASIN IS NOT WORKING PROPERLY
HAVE A SENSOR PROBLEM THAT NEEDS TO BE FIXED
AND ADJUSTMENT WELL
SULITACO+HELIUM
‘THE FEMALE WASHBASIN IS NOT WORKING PROPERLY
HAVE A SENSOR PROBLEM THAT NEEDS TO BE FIXED
AND ADJUSTMENT WELL
+
‘SULITACO+HELIUM.
UNDER WASHBASEIN HOSE PIPES MIXING WITH
ELECTRICAL WIRE Hee
BAD PASS
THE SOAP PIPE IS MISSING FROM THE FEMALE | oo oc uctiyig
WASHBASIN‘CHILLED WATER PIPES TEMP SENSOR AND THE DISPLAY
NOT WORKING INSIDE 0.T.S Henne
| WHEN LIVE COOKING IS OPERATING THE SMELL COMING
AND SURROUNDING ALL RESTAURANT HELM
WHEN THE DISHWASHING MACHINE IS OPERATING
MORE STEAM COVERS THE KITCHEN AREA AND WEAK | SULITACO+HELIUM,
SUCTION HAS OCCURRED
DOSING SYSTEM IS NOT WORKING NEED TO CHECK HELIUM
PRESURE PUMP NOT INSTALLED PROPALY AND
ELETRICAL WIRE MOVE ABOVE WATER LINE , SHAKER HELIUM
PLATE HELUIM DAMGE AND CUT SOME PICES INSIDE OTS|F.C.Us CONTROL PANEL THERMOTHATE AND DISPLAY ELON
NOT SHOWING ZONE AREA
INSULATION TERMINATION NOT DONE PROPERLY WIRE] 1.5
IS NOT WELL HUGED
CONDUIT IS NOT FIXED PROPERLY WITH THE CEILING fee
HOLES SHOULD BE COVERED AND SEALED
WATER IS LEAKING UNDER CEILING FROM THE FCUs HELIUM
‘ r SMOKE DETECTORS NEED TO HINGE THE BASE IN THE ee
i CEILING WELLCHILLER #6 DOOR MECHANISM IS NOT CLOSED.
PROPERLY AND NEEDS TO BE SEALING ae
WATER LEAKING FROM THE DEEP FRYERON THE RIGHT |
SIDE
DRAIN ELBOW IS NOT FIXED WITH DRAIN PIPE AND IN cium
DIFFERENT SIZE
LPG SOLENOID PANEL LOCK IS NOT OPENING PROPERLY] HELIUM
LPG CONTROL PANEL MORE GAP BETWEEN THE BOX wieuiune
AND THE WALL‘THE OLD CHILLED WATER PIPES BRANGE SHOULD BE
CLOSED BY ENDCAP FOR MORE SAFTY ae
Partioning of in between deep fryer and the rice boiler | SULITACO
Hot prep area; the steel need grouting at the junction suuraco
areas
Food pick up area needs extra heater suuiTaco
GP-5 undersink wires not properly fixed HeuumHot kitchen : Drainage cover is missing HELIUM
Cold kitchen undersink; wires not well fixed HELIUM
Cold kitchen undersink; wires not well fixed HELIUM
‘SOME SPRINKLES ARE FIXED UPPER THAN THE CEILING feud
LEVEL AND OTHERS WITHOUT COVER
LPG PROP box leak Detector to be installed
HELIUM|43" Restaurant FCU functionality and interface with BMS.
not yet done- Commissioning Failure/ Current status is all HELIUM
[Actuator manual ON mode)
Lift Landing area FCU is not in AUTO working condition. HELIUM
Dishwasher functionality to be confirmed by Sultaco SULTACO
Electrical room to be organized + with Related civil work
land necessary cable dressing electrical /FCU DDC control HELIUM
panel/ Ceiling closure /Cleaning etc
FCU DDC control panel Termination and installation HELIUM
Exhaust duct out-let, Louver to be installed. (Dishwashing euun
lhood and Toilet Extract)
OTS 48" level to be close HELIUM
NOTE: ALL THE CEILING GAPS NEED TO BE FIXED PROPERLY.‘TO BE SHCUEDULE