Beam Force Detail Summary: C1 Column Size 300x300 (Factored Load)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Job No Sheet No Rev

1
Software licensed to Shinryo Corporation Part
CONNECTED User: Khun Rashaton
Job Title Ref

By Date02-Apr-22 Chd

Client File 24kv_Switchgear_roof_ste Date/Time 17-Aug-2023 11:23

C1 column size 300x300


Beam Force Detail Summary [ factored load ]
Sign convention as diagrams:- positive above line, negative below line except Fx where positive is compression. Distance d is given from
beam end A.
Axial Shear Torsion Bending
Beam L/C d Fx Fy Fz Mx My Mz
(m) (kg) (kg) (kg) (kg-m) (kg-m) (kg-m)
Max Fx 1096 200:1.4DL 0 7311 1056 318 0.022 -1.18E+3 3.45E+3
Min Fx 1096 210:0.9DL+1.6W 4.400 -772 91 209 0.241 144.976 1.77E+3
Max Fy 1096 204:1.2DL+1.0L 0 4311 3098 132 0.006 -591.268 5.28E+3
Min Fy 1095 202:1.2DL+1.0L 0 4553 -4111 694 2.523 -2.58E+3 -9.36E+3
Max Fz 1095 209:1.2DL+1.0E 0 4988 -878 2211 2.822 -7.03E+3 -3.38E+3
Min Fz 1097 208:1.2DL+1.0E 0 4188 -607 -2592 -0.758 8.93E+3 -2.45E+3
Max Mx 1095 201:1.2DL+1.6L 0 6243 -1588 867 3.058 -3.22E+3 -5.49E+3
Min Mx 1099 213:0.9DL+1.6W 0 2211 1055 -440 -1.509 -872.238 2.22E+3
Max My 1097 208:1.2DL+1.0E 0 4188 -607 -2592 -0.758 8.93E+3 -2.45E+3
Min My 1095 209:1.2DL+1.0E 0 4988 -878 2211 2.822 -7.03E+3 -3.38E+3
Max Mz 1096 206:1.2DL+1.0E 0 7085 2948 -45 -0.064 -130.497 8.61E+3
Min Mz 1095 202:1.2DL+1.0L 0 4553 -4111 694 2.523 -2.58E+3 -9.36E+3