Professional Documents
Culture Documents
ch3 Part1
ch3 Part1
Chapter Three
Wiring Methods and Regulations
42 Lecturer:
Dr. Habeeb J. Nekad
Chapter Three Wiring Methods and Regulations
Fluorescent lamps
To calculate the load power of fluorescent lamps, the lost power in the ballast
circuit must be added (25% of lamp power in the absence of information
about it from the manufacturers), and the power factor must be choosing as
below:
Fluorescent lamp without capacitance for power factor correction: 0.6
Fluorescent lamp with capacitance for power factor correction: 0.86
Fluorescent lamp with electronic ballast circuit: 0.96
Required Current (at 230V)
Power (W) Magnetic Ballast Electronic
Without Capacitance With Capacitance Ballast
18 0.2 0.14 0.1
36 0.33 0.23 0.18
58 0.5 0.36 0.28
43 Lecturer:
Dr. Habeeb J. Nekad
Chapter Three Wiring Methods and Regulations
44 Lecturer:
Dr. Habeeb J. Nekad
Chapter Three Wiring Methods and Regulations
√
If the motor data (efficiency and power factor) are not available, the
following table can be used to determine the value of the load current at the
indicated working voltage level. In this table, the average values for each of
the efficiency and power factor have been selected, assuming that the motor is
connected in a delta form.
Current Current
Output Current for 3-ph motors (A) for 1-ph for DC
Power motors motors
(A) (A)
kW hp 220V 380V 400V 415V 440V 500V 220V 220V
0.37 0.5 1.8 1.03 1 1 1 1 3.12 2.26
0.55 0.75 2.75 1.6 1.5 1.5 1.4 1.21 4.76 3.31
0.75 1 3.5 2 2 2 1.68 1.5 6.01 4.29
1.1 1.5 4.4 2.6 2.55 2.5 2.37 2 7.6 6.35
1.5 2 6 3.5 3.5 3.5 3.06 2.6 10.4 8.25
2.2 3 8.7 5 5 5 4.42 3.8 15.1 12.3
---- ---- ---- ---- ---- ---- ---- ---- ---- ----
7.5 10 27 15.5 14.8 14 13.7 12 46.8 38.4
---- ---- ---- ---- ---- ---- ---- ---- ---- ----
75 100 239 138 136.8 135 125 105 414 364
---- ---- ---- ---- ---- ---- ---- ---- ---- ----
315 430 1000 584 562 535 504 442 1728 1547
45 Lecturer:
Dr. Habeeb J. Nekad
Chapter Three Wiring Methods and Regulations
Note: It is known that not all loads in a particular location or facility are
connected to the electrical power source at the same time. Therefore, in order
to achieve an acceptable, reliable and economical electrical design, an
diversity coefficient of variation must be selected for the electrical system
loads.
46 Lecturer:
Dr. Habeeb J. Nekad
Chapter Three Wiring Methods and Regulations
The cost of conduit installation is higher than other wiring methods due
to the cost of materials and labor. In residential, construction a high degree of
physical damage protection may not be not required so the expense is not
justified.
Two main categories of conduit body are considered here: metal
conduits and non-metal conduit. Conduit systems can be differentiated by
their wall thickness, mechanical stiffness, and tubing material. Conduit
materials are often chosen for their mechanical protection, corrosion
resistance, and the overall installation cost.
Rigid Metal Conduit (RMC)
RMC is a thick-walled, threaded tubing. It is generally made of coated
steel, stainless steel, or aluminum. The conduit is connected together by
screwing connectors to the main tubes. Rigid metal conduit provides
significant protection from impacts and other damage. It can be used as a
grounding conductor for short runs, but it is best practice to use wiring that
has a grounding wire. The thicker walls of RMC protects the cables inside
from electromagnetic interference (EMI), which can be harmful to sensitive
equipment.
47 Lecturer:
Dr. Habeeb J. Nekad
Chapter Three Wiring Methods and Regulations
48 Lecturer:
Dr. Habeeb J. Nekad
Chapter Three Wiring Methods and Regulations
While EMT provides a good amount of protection for the cables inside,
it should not be used in hazardous areas where it is exposed to sever damage
(like power plants or around vehicular traffic.) EMT is not suitable for wet
areas or where corrosive fumes and vapors exist – special corrosive-resistant
tubing and gasketed clamps are required in these areas.
Like RMC, the cut ends of the tubing must be reamed to remove all
sharp edges.
Some electricians are skeptical of using EMT in critical areas because
the set-screws in the clamps can loosen over time. In order to prevent this, a
torque wrench or driver can be used to be sure the screws are set to the correct
tension as required by the manufacturer.
Intermediate Metal Conduit (IMC)
As its name suggests, Intermediate Metal Conduit (IMC) has walls that
are thinner than RMC, but thicker than EMT. Thus the weight of IMC also
falls between RMC and EMT. Intermediate Metal Conduit is threadable, but it
can also be un-threaded and used with clamp-type fittings. IMC is generally
made from steel and can be coated.
Flexible Metal Conduit (FMC)
Flexible metal conduit (FMC) is typically available in diameters between
3/8 inch and 3 inch, but larger sizes can sometimes be found. It is made by
coiling self-interlocked aluminum or steel strips, which forms a hollow tube
49 Lecturer:
Dr. Habeeb J. Nekad
Chapter Three Wiring Methods and Regulations
that wires can be pulled through. FMC comes in a standard wall (sometimes
called full wall) thickness or a reduced wall thickness. Most manufacturers
also produce an extra-flexible FMC for tighter bend radiuses, but this is
generally not approved.
without cutting and welding the pipe. Special ENT connectors are used –
these are generally snap-in connections and are not watertight.
Liquid-Tight Flexible Nonmetallic Conduit (LFNC) is also available for
use where the conduit will be subjected to moisture.
Notes about wiring in conduit:
The wiring must be carried out using single-conductor cables insulated
with non-sheathing material for a voltage of 600/1000, and the
conductor shall be stranded of highly conductive copper.
All cables used in the wiring of lighting systems and power sockets
must be continuous between specific end points and no joints are
allowed in the cables.
All joints shall be made in ceiling flowerpots, switches, power sockets
or other end boxes
The diameters of the pipes that are used are 20, 25, 32, 38, 50, 75, or
100 mm. Do not use pipes with diameters smaller than 20 mm.
The number of cables installed in the pipe must be in accordance with
the recommendations mentioned in the electrical installation
regulations IEE
There should be separate pipes for cables of different circuit classes or
with different levels of voltage
3-4 Switches:-
3-4-1 Lighting Switches:-
Lighting switches shall be suitable for use in alternating current
circuits, and shall be of the quick-connected and disconnected type. Its
front cover must be made of a plastic insulating material unless
otherwise specified.
52 Lecturer:
Dr. Habeeb J. Nekad
Chapter Three Wiring Methods and Regulations
53 Lecturer:
Dr. Habeeb J. Nekad
Chapter Three Wiring Methods and Regulations
54 Lecturer:
Dr. Habeeb J. Nekad