Professional Documents
Culture Documents
Air Line Chart Making Sheet
Air Line Chart Making Sheet
○CAPACITY CALCULATION
SUPPLY AIR 56,310 CMH SA THRU COIL 30,320 CMH BYPASS AIRFLOW 25,990 CMH
OUTDOOR AIR 20,000 CMH OA RATIO 0.660 (WITH RESPECT TO AIR PASSING TO THE COIL)
SENSIBLE HEAT LOAD 81,647 kcal/H SENSIBLE HEAT LOAD 41,608 kcal/H
LATENT HEAT LOAD 32,522 kcal/H LATENT HEAT LOAD 10,000 kcal/H
TOTAL HEAT LOAD 114,169 kcal/H TOTAL HEAT LOAD 51,608 kcal/H
S H F 0.72 S H F 0.81
REMAINDER LOAD 0 kcal/H REMAINDER LOAD 0 kcal/H
SUPPLY AIR △t 5.0 ℃DB SUPPLY AIR △t 2.5 ℃DB
ENTHALPY DIFF △i 7.4 kcal/kg HEATER △t 17.9 ℃DB
COOLING COIL CAPACITY 296,170 kcal/H HEATING COIL CAPACITY 173,130 kcal/H
CHILLED WATER △t 5.0 ℃ HOT WATER △t 4.2 ℃
CHILLED WATER FLOW 987.2 l/min HOT WATER FLOW 687.0 l/min
HEATER △t 0.3 ℃DB ABSOLUTE HUMIDITY △x 2.4 g/kg
HEATING COIL CAPACITY 2,900 kcal/H HUMIDIFICATION 96.1 kg/H
HOT WATER △t 4.2 ℃
HOT WATER FLOW 11.5 l/min
COOLING MODE
DRY BULB RH HUMIDITY ENTHALPY WET BULB DEW POINT
℃DB %RH g/kg kcal/kg ℃WB ℃DP
① ROOM DESIGN CONDITION 25.0 50 9.9 12.0 16.2 12.0
② OUTDOOR CONDITION 36.0 62 23.5 23.0 29.4 27.6
③ HEAT EXCHANGER OUTLET 30.6 60 16.7 17.5 23.7 21.5
④ MIXED AIR 28.7 58 14.4 15.6 19.2 13.1
⑤ COOLING COIL OUTLET 13.0 90 8.4 8.2 11.6 10.6
⑥ HEATING(REHEAT) COIL OUTLET 13.3 88 8.4 8.3 13.1 10.6
⑦ HUMIDIFIER OUTLET 13.3 88 8.4 8.3 13.1 10.6
⑧ FAN INLET 18.7 68 9.1 10.0 13.1 10.6
⑨ AIR CONDITIONING UNIT OUTLET 20.0 62 9.1 10.3 13.6 10.6
⑩ RETURN AIR 25.0 50 9.9 12.0 16.2 12.0
HEATING MODE
DRY BULB RH HUMIDITY ENTHALPY WET BULB DEW POINT
℃DB %RH g/kg kcal/kg ℃WB ℃DP
① ROOM DESIGN CONDITION 22.0 45 7.4 9.8 14.7 9.5
② OUTDOOR CONDITION -3.1 55 1.6 0.2 -5.4 -10.0
③ HEAT EXCHANGER OUTLET 9.5 61 4.5 5.0 6.2 2.4
④ MIXED AIR 13.8 56 5.5 6.6 11.9 9.1
⑤ COOLING COIL OUTLET 13.8 56 5.5 6.6 11.9 9.1
⑥ HEATING(REHEAT) COIL OUTLET 31.7 19 5.5 11.0 14.6 9.1
⑦ HUMIDIFIER OUTLET 26.7 36 7.9 11.2 15.8 10.1
⑨ AIR CONDITIONING UNIT OUTLET 24.5 40 7.6 10.5 15.8 10.0
⑩ RETURN AIR 22.0 45 7.4 9.8 14.7 9.5
30 31 0.036 夏期冷
29
PSYCHROMETRIC CHART
20 60%
19 0.024
18
0.000
-6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
DAT
dry bulb temperature (℃)
AC UNIT AC3-4 SYSTEM 0 SYSTEM W/ HEAT EXCHANGER WATER HUMIDIFICATION RETURN BYPASS
SUPPLY AIR : 56,310 CMH OUTDOOR AIR : 20,000 CMH OA RATIO: 0.660 (COIL AIRFLOW) HEAT EXCHANGER EFF: 0.50
COIL AIRFLOW: 56,310 × ( 25.0 - 18.7 )/( 25.0 - 13.3 )= 30,320 CMH
COOLING SH : 81,647 kcal/h LH: 32,522 kcal/h SHF: 0.72 HEATING SH : 41,608 kcal/h LH: 10,000 kcal/h SHF: 0.81
COOLING COIL : 1.2×( 15.6 - 8.2 )× 30,320 × 1.10 = 296,170 kcal/h HEATING COIL:0.29×(31.7 - 13.8 )× 30,320 × 1.10 = 173,130 kcal/h
HEATING COIL :0.29×( 13.3 - 13.0 )× 30,320 × 1.10 = 2,900 kcal/h HUMIDIFICATION:1.2×( 7.9 - 5.5 )× 30,320 × 1.10 = 96.1 kg/h