MODEL
CMB-P-V-J
CMB-P-V-JA
CMB-P-V-KA
CMB-P-V-KB
Il-2
0000004506.BOOK 1 ページ 2017年12月22日 金曜日 午後1時49分
1. SPECIFICATIONS ........................................................................................................................................... 2
2. EXTERNAL DIMENSIONS ............................................................................................................................ 13
3. ELECTRICAL WIRING DIAGRAMS .............................................................................................................. 19
4. SOUND LEVELS ........................................................................................................................................... 28
4-1. Sound levels in cooling mode ............................................................................................................... 28
4-2. Sound levels in heating mode............................................................................................................... 29
4-3. Sound levels in defrost mode................................................................................................................ 30
5. ELECTRICAL CHARACTERISTICS .............................................................................................................. 31
6. OPTIONAL PARTS........................................................................................................................................ 32
6-1. JOINT and REDUCER.......................................................................................................................... 32
6-2. JOINT KIT "CMY-R160-J1" FOR BC CONTROLLER .......................................................................... 37
7. INSTALLATION ............................................................................................................................................. 38
7-1. Installing BC controllers ........................................................................................................................ 38
8. SYSTEM DESIGN ......................................................................................................................................... 39
8-1. Compatibility ......................................................................................................................................... 39
8-2. System examples.................................................................................................................................. 40
MEES17K069 Il-2 1
0000004506.BOOK 2 ページ 2017年12月22日 金曜日 午後1時49分
Model CMB-P104V-J
Number of branch 4
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.067/0.076/0.085 0.054/0.061/0.067
Heating kW 0.030/0.034/0.038 0.024/0.027/0.030
Current input Cooling A 0.31/0.34/0.36 0.25/0.27/0.28
Heating A 0.14/0.15/0.16 0.11/0.12/0.13
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P350
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 596 x 495
in. 9-11/16 x 23-1/2 x 19-1/2
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 23 (51)
Sound power level
Rated operation dB <A> 56(When P200 Outdoor/Heat source unit connected),57(P250),59(P350)
(measured in anechoic room)
Defrost dB <A> 71
Sound pressure level
Rated operation dB <A> 38(When P200 Outdoor/Heat source unit connected),39(P250),40(P350)
(measured in anechoic room)
Defrost dB <A> 53
Accessories Drain Connection pipe, Washer, Tie band
Remarks
Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.
BC controller
MEES17K069 Il-2 2
0000004506.BOOK 3 ページ 2017年12月22日 金曜日 午後1時49分
Model CMB-P106V-J
Number of branch 6
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.097/0.110/0.123 0.078/0.088/0.097
Heating kW 0.045/0.051/0.057 0.036/0.041/0.045
Current input Cooling A 0.45/0.48/0.52 0.36/0.39/0.41
Heating A 0.21/0.23/0.24 0.17/0.18/0.19
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P350
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 596 x 495
in. 9-11/16 x 23-1/2 x 19-1/2
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 27 (60)
Sound power level
Rated operation dB <A> 56(When P200 Outdoor unit connected),57(P250),59(P350)
(measured in anechoic room)
Defrost dB <A> 71
Sound pressure level
Rated operation dB <A> 38(When P200 Outdoor unit connected),39(P250),40(P350)
(measured in anechoic room)
Defrost dB <A> 53
Accessories Drain Connection pipe, Washer, Tie band
Remarks
Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.
BC controller
MEES17K069 Il-2 3
0000004506.BOOK 4 ページ 2017年12月22日 金曜日 午後1時49分
Model CMB-P108V-J
Number of branch 8
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.127/0.144/0.161 0.102/0.115/0.127
Heating kW 0.060/0.068/0.076 0.048/0.054/0.060
Current input Cooling A 0.58/0.63/0.68 0.47/0.50/0.53
Heating A 0.28/0.30/0.32 0.22/0.24/0.25
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P350
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 596 x 495
in. 9-11/16 x 23-1/2 x 19-1/2
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 31 (69)
Sound power level
Rated operation dB <A> 56(When P200 Outdoor unit connected),57(P250),59(P350)
(measured in anechoic room)
Defrost dB <A> 71
Sound pressure level
Rated operation dB <A> 38(When P200 Outdoor unit connected),39(P250),40(P350)
(measured in anechoic room)
Defrost dB <A> 53
Accessories Drain Connection pipe, Washer, Tie band
Remarks
Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.
BC controller
MEES17K069 Il-2 4
0000004506.BOOK 5 ページ 2017年12月22日 金曜日 午後1時49分
Model CMB-P1012V-J
Number of branch 12
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.186/0.211/0.236 0.150/0.168/0.186
Heating kW 0.090/0.102/0.114 0.072/0.081/0.090
Current input Cooling A 0.85/0.92/0.99 0.69/0.74/0.78
Heating A 0.42/0.44/0.48 0.33/0.36/0.38
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P350
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 911 x 639
in. 9-11/16 x 35-7/8 x 25-3/16
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 46 (102)
Sound power level
Rated operation dB <A> 56(When P200 Outdoor unit connected),57(P250),59(P350)
(measured in anechoic room)
Defrost dB <A> 71
Sound pressure level
Rated operation dB <A> 38(When P200 Outdoor unit connected),39(P250),40(P350)
(measured in anechoic room)
Defrost dB <A> 53
Accessories Drain Connection pipe, Washer, Tie band
Remarks
Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.
BC controller
MEES17K069 Il-2 5
0000004506.BOOK 6 ページ 2017年12月22日 金曜日 午後1時49分
Model CMB-P1016V-J
Number of branch 16
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.246/0.279/0.312 0.198/0.222/0.246
Heating kW 0.119/0.135/0.151 0.096/0.108/0.119
Current input Cooling A 1.12/1.22/1.30 0.90/0.97/1.03
Heating A 0.55/0.59/0.63 0.44/0.47/0.50
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P350
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 1,135 x 639
in. 9-11/16 x 44-11/16 x 25-3/16
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 56 (124)
Sound power level
Rated operation dB <A> 56(When P200 Outdoor unit connected),57(P250),59(P350)
(measured in anechoic room)
Defrost dB <A> 71
Sound pressure level
Rated operation dB <A> 38(When P200 Outdoor unit connected),39(P250),40(P350)
(measured in anechoic room)
Defrost dB <A> 53
Accessories Drain Connection pipe, Washer, Tie band
Remarks
Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.
BC controller
MEES17K069 Il-2 6
0000004506.BOOK 7 ページ 2017年12月22日 金曜日 午後1時49分
Model CMB-P108V-JA
Number of branch 8
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.127/0.144/0.161 0.102/0.115/0.127
Heating kW 0.060/0.068/0.076 0.048/0.054/0.060
Current input Cooling A 0.58/0.63/0.68 0.47/0.50/0.53
Heating A 0.28/0.30/0.32 0.22/0.24/0.25
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P900
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 911 x 639
in. 9-11/16 x 35-7/8 x 25-3/16
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P400 to P500 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8)
*13 mm (in.) O.D. P550 28.58 (1-1/8) Brazed
Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8) 28.58 (1-1/8) Brazed or 34.93 (1-3/8)
*13 mm (in.) O.D. P600
Brazed Brazed
mm (in.) O.D. P650 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P700 to P800 28.58 (1-1/8) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P850/P900 28.58 (1-1/8) Brazed 41.28 (1-5/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Total down-stream Indoor
To other BC controller High press. pipe Liquid pipe Low press. pipe
unit capacity
mm (in.) O.D. to P200 15.88 (5/8) Brazed 9.52 (3/8) Brazed 19.05 (3/4) Brazed
mm (in.) O.D. P201 to P300 19.05 (3/4) Brazed 9.52 (3/8) Brazed 22.2 (7/8) Brazed
mm (in.) O.D. P301 to P350 19.05 (3/4) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P351 to P400 22.2 (7/8) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P401 to P600 22.2 (7/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P601 to P650 28.58 (1-1/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P651 to P800 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P801 to P1000 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
mm (in.) O.D. P1001 or above 34.93 (1-3/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 45 (100)
Sound power level Rated operation
dB <A> 62(When P250 Outdoor/Heat source unit connected),65(P450),68(P700),69(P900)
(measured in anechoic room)
Defrost dB <A> 74
Sound pressure level Rated operation
dB <A> 44(When P250 Outdoor/Heat source unit connected),47(P450),50(P700),51(P900)
(measured in anechoic room)
Defrost dB <A> 56
Accessories Drain Connection pipe, Washer, Tie band
Remarks
Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
BC controller
MEES17K069 Il-2 7
0000004506.BOOK 8 ページ 2017年12月22日 金曜日 午後1時49分
Model CMB-P1012V-JA
Number of branch 12
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.186/0.211/0.236 0.150/0.168/0.186
Heating kW 0.090/0.102/0.114 0.072/0.081/0.090
Current input Cooling A 0.85/0.92/0.99 0.69/0.74/0.78
Heating A 0.42/0.44/0.48 0.33/0.36/0.38
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P900
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 1,135 x 639
in. 9-11/16 x 44-11/16 x 25-3/16
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P400 to P500 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8)
*13 mm (in.) O.D. P550 28.58 (1-1/8) Brazed
Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8) 28.58 (1-1/8) Brazed or 34.93 (1-3/8)
*13 mm (in.) O.D. P600
Brazed Brazed
mm (in.) O.D. P650 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P700 to P800 28.58 (1-1/8) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P850/P900 28.58 (1-1/8) Brazed 41.28 (1-5/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Total down-stream Indoor
To other BC controller High press. pipe Liquid pipe Low press. pipe
unit capacity
mm (in.) O.D. to P200 15.88 (5/8) Brazed 9.52 (3/8) Brazed 19.05 (3/4) Brazed
mm (in.) O.D. P201 to P300 19.05 (3/4) Brazed 9.52 (3/8) Brazed 22.2 (7/8) Brazed
mm (in.) O.D. P301 to P350 19.05 (3/4) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P351 to P400 22.2 (7/8) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P401 to P600 22.2 (7/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P601 to P650 28.58 (1-1/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P651 to P800 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P801 to P1000 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
mm (in.) O.D. P1001 or above 34.93 (1-3/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 56 (124)
Sound power level Rated operation
dB <A> 62(When P250 Outdoor/Heat source unit connected),65(P450),68(P700),69(P900)
(measured in anechoic room)
Defrost dB <A> 74
Sound pressure level Rated operation
dB <A> 44(When P250 Outdoor/Heat source unit connected),47(P450),50(P700),51(P900)
(measured in anechoic room)
Defrost dB <A> 56
Accessories Drain Connection pipe, Washer, Tie band
Remarks
Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
BC controller
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.
MEES17K069 Il-2 8
0000004506.BOOK 9 ページ 2017年12月22日 金曜日 午後1時49分
Model CMB-P1016V-JA
Number of branch 16
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.246/0.279/0.312 0.198/0.222/0.246
Heating kW 0.119/0.135/0.151 0.096/0.108/0.119
Current input Cooling A 1.12/1.22/1.30 0.90/0.97/1.03
Heating A 0.55/0.59/0.63 0.44/0.47/0.50
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P900
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 1,135 x 639
in. 9-11/16 x 44-11/16 x 25-3/16
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P400 to P500 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8)
*13 mm (in.) O.D. P550 28.58 (1-1/8) Brazed
Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8) 28.58 (1-1/8) Brazed or 34.93 (1-3/8)
*13 mm (in.) O.D. P600
Brazed Brazed
mm (in.) O.D. P650 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P700 to P800 28.58 (1-1/8) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P850/P900 28.58 (1-1/8) Brazed 41.28 (1-5/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Total down-stream Indoor
To other BC controller High press. pipe Liquid pipe Low press. pipe
unit capacity
mm (in.) O.D. to P200 15.88 (5/8) Brazed 9.52 (3/8) Brazed 19.05 (3/4) Brazed
mm (in.) O.D. P201 to P300 19.05 (3/4) Brazed 9.52 (3/8) Brazed 22.2 (7/8) Brazed
mm (in.) O.D. P301 to P350 19.05 (3/4) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P351 to P400 22.2 (7/8) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P401 to P600 22.2 (7/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P601 to P650 28.58 (1-1/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P651 to P800 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P801 to P1000 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
mm (in.) O.D. P1001 or above 34.93 (1-3/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 63 (139)
Sound power level Rated operation
dB <A> 62(When P250 Outdoor/Heat source unit connected),65(P450),68(P700),69(P900)
(measured in anechoic room)
Defrost dB <A> 74
Sound pressure level Rated operation
dB <A> 44(When P250 Outdoor/Heat source unit connected),47(P450),50(P700),51(P900)
(measured in anechoic room)
Defrost dB <A> 56
Accessories Drain Connection pipe, Washer, Tie band
Remarks
Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
BC controller
MEES17K069 Il-2 9
0000004506.BOOK 10 ページ 2017年12月22日 金曜日 午後1時49分
Model CMB-P1016V-KA
Number of branch 16
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.246/0.279/0.312 0.198/0.222/0.246
Heating kW 0.119/0.135/0.151 0.096/0.108/0.119
Current input Cooling A 1.12/1.22/1.30 0.90/0.97/1.03
Heating A 0.55/0.59/0.63 0.44/0.47/0.50
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P1100
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 1,135 x 639
in. 9-11/16 x 44-11/16 x 25-3/16
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P400 to P500 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8)
*13 mm (in.) O.D. P550 28.58 (1-1/8) Brazed
Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8) 28.58 (1-1/8) Brazed or 34.93 (1-3/8)
*13 mm (in.) O.D. P600
Brazed Brazed
mm (in.) O.D. P650 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P700 to P800 28.58 (1-1/8) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P850 to P1000 28.58 (1-1/8) Brazed 41.28 (1-5/8) Brazed
mm (in.) O.D. P1050/P1100 34.93 (1-3/8) Brazed 41.28 (1-5/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Total down-stream Indoor
To other BC controller High press. pipe Liquid pipe Low press. pipe
unit capacity
mm (in.) O.D. to P200 15.88 (5/8) Brazed 9.52 (3/8) Brazed 19.05 (3/4) Brazed
mm (in.) O.D. P201 to P300 19.05 (3/4) Brazed 9.52 (3/8) Brazed 22.2 (7/8) Brazed
mm (in.) O.D. P301 to P350 19.05 (3/4) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P351 to P400 22.2 (7/8) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P401 to P600 22.2 (7/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P601 to P650 28.58 (1-1/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P651 to P800 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P801 to P1000 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
mm (in.) O.D. P1001 or above 34.93 (1-3/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 65 (144)
Sound power level Rated operation
dB <A> 56(When P300 Outdoor/Heat source unit connected),61(P550),63(P800),66(P1100)
(measured in anechoic room)
Defrost dB <A> 73
Sound pressure level Rated operation
dB <A> 38(When P300 Outdoor/Heat source unit connected),43(P550),45(P800),48(P1100)
(measured in anechoic room)
Defrost dB <A> 55
Accessories Drain Connection pipe, Washer, Tie band
Remarks
Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
BC controller
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.
MEES17K069 Il-2 10
0000004506.BOOK 11 ページ 2017年12月22日 金曜日 午後1時49分
Model CMB-P104V-KB
Number of branch 4
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.060/0.068/0.076 0.048/0.054/0.060
Heating kW 0.030/0.034/0.038 0.024/0.027/0.030
Current input Cooling A 0.28/0.30/0.32 0.22/0.24/0.25
Heating A 0.14/0.15/0.16 0.11/0.12/0.13
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable Main BC controller CMB-P108/1012/1016V-JA, CMB-P1016V-KA
The maximum number of connectable Sub BC controllers 11
The maximum connectable capacity of indoor units P350 for each
External dimension H x W x D mm 246 x 596 x 495
in. 9-11/16 x 23-1/2 x 19-1/2
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. - - -
diameter To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Total down-stream Indoor
To other BC controller High press. pipe Liquid pipe Low press. pipe
unit capacity
mm (in.) O.D. to P200 15.88 (5/8) Brazed 9.52 (3/8) Brazed 19.05 (3/4) Brazed
mm (in.) O.D. P201 to P300 19.05 (3/4) Brazed 9.52 (3/8) Brazed 22.2 (7/8) Brazed
mm (in.) O.D. P301 to P350 19.05 (3/4) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P351 to P400 22.2 (7/8) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P401 to P600 22.2 (7/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P601 to P650 28.58 (1-1/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P651 to P800 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P801 to P1000 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
mm (in.) O.D. P1001 or above 34.93 (1-3/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 21 (47)
Sound power level Rated operation
dB <A> 56(When P200 Outdoor/Heat source unit connected),57(P250),59(P350)
(measured in anechoic room)
Defrost dB <A> 71
Sound pressure level Rated operation
dB <A> 38(When P200 Outdoor/Heat source unit connected),39(P250),40(P350)
(measured in anechoic room)
Defrost dB <A> 53
Accessories Drain Connection pipe, Washer, Tie band
Remarks
Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
BC controller
MEES17K069 Il-2 11
0000004506.BOOK 12 ページ 2017年12月22日 金曜日 午後1時49分
Model CMB-P108V-KB
Number of branch 8
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.119/0.135/0.151 0.096/0.108/0.119
Heating kW 0.060/0.068/0.076 0.048/0.054/0.060
Current input Cooling A 0.55/0.59/0.63 0.44/0.47/0.50
Heating A 0.28/0.30/0.32 0.22/0.24/0.25
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable Main BC controller CMB-P108/1012/1016V-JA, CMB-P1016V-KA
The maximum number of connectable Sub BC controllers 11
The maximum connectable capacity of indoor units P350 for each
External dimension H x W x D mm 246 x 596 x 495
in. 9-11/16 x 23-1/2 x 19-1/2
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. - - -
diameter To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Total down-stream Indoor
To other BC controller High press. pipe Liquid pipe Low press. pipe
unit capacity
mm (in.) O.D. to P200 15.88 (5/8) Brazed 9.52 (3/8) Brazed 19.05 (3/4) Brazed
mm (in.) O.D. P201 to P300 19.05 (3/4) Brazed 9.52 (3/8) Brazed 22.2 (7/8) Brazed
mm (in.) O.D. P301 to P350 19.05 (3/4) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P351 to P400 22.2 (7/8) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P401 to P600 22.2 (7/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P601 to P650 28.58 (1-1/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P651 to P800 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P801 to P1000 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
mm (in.) O.D. P1001 or above 34.93 (1-3/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 28 (62)
Sound power level Rated operation
dB <A> 56(When P200 Outdoor/Heat source unit connected),57(P250),59(P350)
(measured in anechoic room)
Defrost dB <A> 71
Sound pressure level Rated operation
dB <A> 38(When P200 Outdoor/Heat source unit connected),39(P250),40(P350)
(measured in anechoic room)
Defrost dB <A> 53
Accessories Drain Connection pipe, Washer, Tie band
Remarks
Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Can't use singleness. (MAIN BC CONTROLLER is necessary)
BC controller
13.The ambient relative humidity of the BC controller needs to be kept below 80%.
MEES17K069 Il-2 12
0000004506.BOOK
2. EXTERNAL DIMENSIONS
Drain hose I.D.32(1-1/4")
(Accessory) Cutting point Cutting point Note 1. Suspension bolt(ø10) and nut(M10) prepare in the field. <Accessories>
MEES17K069
2. Take notice of service space as follows. • Drain hose I.D.32(1-1/4") ················ 1pc.
Note 4 Note 4
(Please give attention not to occupy service space by letting ducts • Tie band ······································ 3pcs.
• Square washer (with cushion) ·········· 4pcs.
30
and pipes through.)
12
3. Install this product in a location where noise (refrigerant noise) • Square washer ····························· 4pcs.
emitted by the unit will not disturb the neighbors.
20 (For use in quiet environments with low background noise,position
60
14 50 the BC CONTROLLER at least 5m away from any indoor units.)
Drain Piping Detail of X section Detail of Y section 4. Refer to the Installation Manual for refrigerant piping diameter size
when connecting plural indoor units with 1 branch.
5. Refer to the Installation Manual for connection pipe of outdoor unit
diameter size.
6.Refer to the Installation Manual for insulation of connection pipe and
CMB-P104, 106, 108V-J
drain piping.
(High pressure) 7.Refer to the Installation Manual for Installation of drain pan.
Note 5 8.Do not place the BC controller directly on the floor because the
drain pan needs to be installed in a tilted position.
金曜日
2. EXTERNAL DIMENSIONS
119
X 450 200
66
Control box
R1 screw Access
door
午後1時49分
450
304
429
29
(700)
298
(Lifting bolt pitch)
215
132
Service
68
250
space
100
Y
68 23 596
602
219
(Lifting bolt pitch)
Note 5
102 60×A=B
60 Connection pipe of
indoor unit (Liquid)
11
120
Note 4
1 2 3 4 5 6 7 8
Service
space
246
Connection pipe of
indoor unit (Gas)
60 Note 4 (Note 2)
A B
CMB-P104V-J 3 180
(200)
60 72 60×A=B
Il-2
CMB-P106V-J 5 300
CMB-P108V-J 7 420
Unit: mm
Indoor units
13
BC controller
BC controller
MEES17K069
(Accessory) Cutting point Cutting point (Please give attention not to occupy service space by letting ducts • Tie band ······································ 3pcs.
0000004506.BOOK
Note 4 Note 4 and pipes through.) • Square washer (with cushion) ·········· 4pcs.
3. Install this product in a location where noise (refrigerant noise) • Square washer······························ 4pcs.
emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise,position
12
30
20 the BC CONTROLLER at least 5m away from any indoor units.)
60
14 50 4. Refer to the Installation Manual for refrigerant piping diameter size
Drain Piping Detail of X section Detail of Y section when connecting plural indoor units with 1 branch.
5. Refer to the Installation Manual for connection pipe of outdoor unit
CMB-P1012, 1016V-J
diameter size.
6.Refer to the Installation Manual for insulation of connection pipe and
Connection pipe of outdoor unit drain piping.
(High pressure) 7.Refer to the Installation Manual for Installation of drain pan.
8.Do not place the BC controller directly on the floor because the
Note 5 drain pan needs to be installed in a tilted position.
2. EXTERNAL DIMENSIONS
14 ページ 2017年12月22日
66
Control box
450 200
金曜日
89
R1 screw Access
door
450
437
573
Service
39 space
(700)
午後1時49分
374
(Lifting bolt pitch)
303
286
250
73
100
Y
68 23 A
219 B
(Lifting bolt pitch)
11
Note 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
246
Connection pipe of
indoor unit (Gas)
Service
Note 4 space
60
60 150 60×C=D
A B C D (Note 2)
CMB-P1012V-J 911 938 11 660
Il-2
CMB-P1016V-J 1135 1161 15 900
(200)
Unit: mm
Indoor units
14
Note 1. Suspension bolt(ø10) and nut(M10) prepare in the field. <Accessories>
0000004506.BOOK
MEES17K069
space by letting ducts and pipes through.) • Square washer (with cushion) ··········4pcs.
Drain hose I.D.32(1-1/4")
(Accessory) Cutting point Cutting point 3. Please take service space for connection pipe of SUB BC CONTROLLER. • Square washer······························4pcs.
Note 5 Note 5 4. Install this product in a location where noise (refrigerant noise)
emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position
the BC CONTROLLER at least 5m away from any indoor units.)
12
5. Refer to the Installation Manual for refrigerant piping diameter size
30
20
60 when connecting plural indoor units with 1 branch.
14 50
6. Refer to the Installation Manual for connection pipe of outdoor unit
Drain Piping Detail of X section Detail of Y section
or SUB BC CONTROLLER diameter size.
7. Refer to the Installation Manual for insulation of connection pipe and
Connection pipe of outdoor unit drain piping.
15 ページ 2017年12月22日
(High pressure) 8. Refer to the Installation Manual for Installation of drain pan.
9. Do not place the BC controller directly on the floor because the drain
Note 6
CMB-P108, 1012, 1016V-JA
2. EXTERNAL DIMENSIONS
X Note 6
66
Control box
Connection pipe of SUB BC CONTROLLER
(Liquid)
65
89 Note 6
R1 screw
午後1時49分
437
573
Access
39 73 door
357
374
(Lifting bolt pitch)
278
450
303
286
Service
space
(700)
73
250
100
Y
68 23 A
219 B
(Lifting bolt pitch)
Connection pipe of outdoor unit Connection pipe of
(Low pressure) (300)
indoor unit (Liquid)
Note 6
(100)
Note 5
180 60×C=D 120
166 60
11
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Service space
246
Connection pipe of
indoor unit (Gas)
(Note 2,3)
Note 5
60
A B C D
(200)
60 150 60×C=D
CMB-P108V-JA 911 938 7 420
CMB-P1012V-JA 1135 1161 11 660
Il-2
CMB-P1016V-JA 1135 1161 15 900
Unit: mm
Indoor units
15
BC controller
BC controller
MEES17K069
(Accessory) Cutting point Cutting point space by letting ducts and pipes through.) • Square washer (with cushion) ··········4pcs.
0000004506.BOOK
Note 6 Note 6 3. Please take service space for connection pipe of SUB BC CONTROLLER. • Square washer······························4pcs.
4. When using an outdoor unit-38HP(P950) or more, use this product.
5. Install this product in a location where noise (refrigerant noise)
emitted by the unit will not disturb the neighbors.
12
30
20 (For use in quiet environments with low background noise, position
60 the BC CONTROLLER at least 5m away from any indoor units.)
14 50 CMB-P1016V-KA
6. Refer to the Installation Manual for refrigerant piping diameter size
Drain Piping Detail of X section Detail of Y section
when connecting plural indoor units with 1 branch.
7. Refer to the Installation Manual for connection pipe of outdoor unit
or SUB BC CONTROLLER diameter size.
Connection pipe of outdoor unit 8. Refer to the Installation Manual for insulation of connection pipe and
(High pressure) drain piping.
Note 7 9. Refer to the Installation Manual for Installation of drain pan.
10. Do not place the BC controller directly on the floor because the drain Connection pipe of SUB BC CONTROLLER
(High pressure)
2. EXTERNAL DIMENSIONS
X Note 7
66
Control box
金曜日
437
573
39 73
Access
357
午後1時49分
door
374
(Lifting bolt pitch)
278
303
286
450
Service
space
(700)
73
250
100
Y
68 23 1135
219 1161
(Lifting bolt pitch)
Connection pipe of outdoor unit
(Low pressure)
Note 7 (300)
(100)
11
Note 6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
246
Connection pipe of Service space
indoor unit (Gas)
Note 6
60 (Note 2,3)
60 150 60×15=900
(200)
Il-2
Unit: mm
Indoor units
16
0000004506.BOOK
MEES17K069
(Accessory) (Please give attention not to occupy service space by letting ducts and • Tie band ······································ 3pcs.
Cutting point Cutting point
pipes through.) • Square washer (with cushion) ·········· 4pcs.
Note 5 Note 5
3. Can't use singleness. (MAIN BC CONTROLLER is necessary.) • Square washer ····························· 4pcs.
30
4. Install this product in a location where noise (refrigerant noise)
12
emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position
20
CMB-P104V-KB
2. EXTERNAL DIMENSIONS
(High pressure)
Note 6
119
X 450 200
66
Control box
午後1時49分
R1 screw Access
door
35
450
304
429
298
(700)
215
197
132
Service
68
250
space
100
Connection pipe of MAIN BC CONTROLLER
(Liquid) Y
29
Note 6 596
68 23
602
219 (Lifting bolt pitch)
Connection pipe of outdoor unit
(Low pressure) (250)
Note 6
(100)
102 60×3=180
120 60 Connection pipe of
indoor unit (Liquid)
11
Note 5
1 2 3 4
Service
246
space
Il-2
60 72 60×3=180 indoor unit (Gas)
(200)
Note 5
Unit: mm
Indoor units
17
BC controller
BC controller
MEES17K069
Drain hose I.D.32(1-1/4") 2.Take notice of service space as follows. • Drain hose I.D.32(1-1/4") ··········1pc.
0000004506.BOOK
(Accessory) Cutting point Cutting point (Please give attention not to occupy service space by letting ducts and • Tie band ································3pcs.
pipes through.) • Square washer (with cushion) ····4pcs.
Note 5 Note 5
3.Can't use singleness. (MAIN BC CONTROLLER is necessary.) • Square washer ·······················4pcs.
4.Install this product in a location where noise (refrigerant noise)
30
12
emitted by the unit will not disturb the neighbors.
20
(For use in quiet environments with low background noise, position
the BC CONTROLLER at least 5m away from any indoor units.)
CMB-P108V-KB
60
14 50 5.Refer to the Installation Manual for refrigerant piping diameter size
Drain Piping Detail of X section Detail of Y section when connecting plural indoor units with 1 branch.
6.Refer to the Installation Manual for connection pipe of MAIN BC CONTROLLER
or outdoor unit diameter size.
7.Refer to the Installation Manual for insulation of connection pipe and drain piping.
8.Refer to the Installation Manual for Installation of drain pan.
9.Do not place the BC controller directly on the floor because the drain pan needs
Connection pipe of MAIN BC CONTROLLER
2. EXTERNAL DIMENSIONS
18 ページ 2017年12月22日
119
X
66
Control box
35 Access
午後1時49分
door
304
429
450
298
(Lifting bolt pitch)
215
197
(700)
132
68
Service
space
250
100
Connection pipe of MAIN BC CONTROLLER
(Liquid) 29 Y
Note 6 596
68 23
602
219 (Lifting bolt pitch)
Connection pipe of outdoor unit
(Low pressure) (250)
(100)
Note 6
102 60×7=420
120 60 Connection pipe of
indoor unit (Liquid) Service
11
space
Note 5
1 2 3 4 5 6 7 8
(Note 2)
Connection pipe of
(200)
246
Note 5
60
Il-2
60 72 60×7=420
Unit: mm
Indoor units
18
0000004506.BOOK
TR TB02
Indoor/outdoor
MEES17K069
20V~22V 220V~240V Transmission Line
M2
M1
3 1
1
2 CNTR
PS1 2 3
1 3 2 1 2 1 (Red)
CMB-P104V-J
3 T5 T1
1 1
CN03 CN02 CN26 1 1
CNP1 (Yellow) 1 2 2 SV1B
2 2
(Black) X02 3 3 3 SV1A
3 3
X01 5 4 4 SV1C
4 4
X30 7
3 T2
1 1 1
2 CN27(Red)
19 ページ 2017年12月22日
7 7
2 (Red) X31 7 Symbol Name
1 1 T3 TR Transformer
CN28(Blue)
1 1 2 2 SV3B TH11,12,15,16 Thermister sensor
TH11 8 8
2 X06 SV3A
LEV1,3 Expansion valve
t° 3 3 3
10 1 9 9 PS1,3 Pressure sensor
3 X05 SV3C
5 4 4
TH12 10 10 Circuit
3. ELECTRICAL WIRING DIAGRAMS
t° 7 board
5 SW2 SW1 T4 Terminal block
1 1 TB01 (for power source)
CN29(Green)
6 CONT.B 1 2 2 SV4B Terminal block
11 11 TB02 (for Transmission)
7 X08 3 3 3 SV4A
12 12 SV1~4A,B,C Solenoid valve
8 SW4 X07 5 4 4 SV4C
13 13
T1~5 Terminal
X33 7 F01 Fuse AC250V 6.3A F
1 LD1:CPU in
operation Z1 Function setting connector
TH15 CN36(Green)
2
t° CN11 SW5 1
3 14 14
ZNR01 ZNR02 X21 Note 1. TB02 is transmission terminal block.
TH16 3
4 15 15
t° U U Never connect power line to it.
DSA 16 16
1 SW6 F01 2. The initial set values of switch on CONT. B are as follows.
Z1 2
TYP1
250VAC SW1:0
6.3A F
SW2:0
CN07 CN05
(Yellow) (Red)
1 2 3 4 5 6 1 2 3 4 5 6 1 3 5
CN12
TB01 TO NEXT INDOOR UNIT
L
M M N PULL BOX
LEV3 LEV1
FUSE(16A)
BREAKER(16A)
POWER SUPPLY
~220V-240V
Il-2
50Hz/60Hz
Indoor units
19
BC controller
BC controller
TR TB02 Indoor/outdoor
20V~22V 220V~240V S(SHIELD)
M2 Transmission line
M1
MEES17K069
3 1 1
0000004506.BOOK
2 2 CNTR
PS1 3
1 3 2 1 2 1
3 (Red)
T7 1 1 T1
CN03 CN02 CN26 1 1
CNP1 (Yellow) 1 2 2 SV1B
2 2
(Black)
CMB-P106V-J
X02 3 3 3 SV1A
3 3
X01 5 4 4 SV1C
4 4
X30 7
3 1 1 1 T2
2 2 CN27(Red)
PS3 CNP3 1 2 2 SV2B
1 5 5
3
X04 3 3 3 SV2A
6 6
X03 5 4 4 SV2C
1 CN13 7 7
2 (Red) X31 7
1 1 T3
CN28(Blue)
1
20 ページ 2017年12月22日
CONT.B 1 2 2 SV3B
TH11 8 8
2 X06 3 SV3A
t° 3 3
9 9
3 X05 4
5 4 SV3C
TH12 10 10
金曜日
4 X32 7
t° CN10
5 1 1 T4 (Symbol explanation)
CN29(Green)
6 10 1 1 2 2 SV4B Symbol Name
3. ELECTRICAL WIRING DIAGRAMS
11 11
7 X08 3 3 SV4A Transformer
3 TR
12 12
8 X07 4 4 SV4C
SW2 SW1 LD1:CPU in 5 TH11,12,15,16 Thermister sensor
13 13
operation X33 7 LEV1,3 Expansion valve
1
午後1時49分
CN36(Green) 6 6
7 7
CN07 CN05 8 8
(Yellow) (Red)
1 2 3 4 5 6 1 2 3 4 5 6 1 3 5
Note 1. TB02 is transmission terminal block.
CN12 Never connect power line to it.
TB01 2. The initial set values of switch on CONT. B are as follows.
TO NEXT INDOOR UNIT
L SW1:0
M M
N PULL BOX
LEV3 LEV1
SW2:0
FUSE(16A)
BREAKER(16A)
Il-2
POWER SUPPLY
~220V-240V
50Hz/60Hz
Indoor units
20
0000004506.BOOK
MEES17K069
Note 1. TB02 is transmission terminal block. (Symbol explanation)
Never connect power line to it. Symbol Name
2. The initial set values of switch on CONT. B are as follows. TR Transformer
TH11,12,15,16 Thermister sensor
SW1:0
CMB-P108V-J
LEV1,3 Expansion valve
SW2:0
PS1,3 Pressure sensor
TR TB02 Indoor/outdoor
20V~22V 220V~240V S(SHIELD) REL.B Circuit Relay
M2 Transmission line
M1 CONT.B board BC controller
Terminal block
TB01 (for power source)
7 6 5 4 3 2 1
3 1 1
CN50
21 ページ 2017年12月22日
X01 4 SV1C
T1~10 Terminal
5 4
4 4
X30 7 F01 Fuse AC250V 6.3A F
3 1 1 1 T2
2 2 CNP3
CN27(Red) Z1 Function setting connector
PS3 1 2 2 SV2B
1 3 5 5
X04 3 3 3 SV2A
SV8C
SV8A
SV8B
SV7C
SV7A
SV7B
6 6
X03 5 4 4 SV2C
1 CN13 7 7
2 (Red) X31 7 T8 T7
1 1 T3 4 3 2 1 4 3 2 1
3. ELECTRICAL WIRING DIAGRAMS
CN28(Blue)
午後1時49分
1 CONT.B 1 2 2 SV3B
TH11 8 8
2 X06 3 3 3 SV3A
t° 9 9
3 X05 5 4 4 SV3C T10 4 3 2 1 4 3 2 1
TH12 LD1:CPU in 1010
4 operation X32 7
t° CN10
5 1 1 T4
CN29(Green) 16 15 14 13 12 11 10 9 8 7 6 5 4
6 10 1 1 2 2 SV4B 16 15 14 13 12 11 10 9 8 7 6 5 4
1111
7 X08 3 3 3 SV4A
1212
8 SW2 SW1 X07 5 4 4 SV4C
1313
X33 7
1
TH15 1 1 T5
2 CN30(Black) 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
t° CN11 1 2 2 SV5B
3 SW4 1414
TH16 X10 3 3 3 SV5A
4 1515
X09
CN32
CN33(Red)
t° 4 4
CN35(Blue)
5 SV5C
X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36
CN34(Black)
ZNR01 ZNR02 1616
X34 7
1 SW5
Z1 TYP1 U U
2 1 1 T6
CN31(Yellow)
1 2 2 SV6B CN39
DSA F01 1 1
X12 3 3 3
SW6 3 SV6A REL.B
250VAC 2 2
X11 1
5 4 4 SV6C
6.3A F 3 3
X35 7 7 6 5 4 3 2 1
CN36(Green) CN52
1
X21 3
CN07 CN05
(Yellow) (Red)
1 2 3 4 5 6 1 2 3 4 5 6 1 3 5 TB01 TO NEXT INDOOR UNIT
CN12 L
N PULL BOX
POWER SUPPLY
~220V-240V
M M 50Hz/60Hz
FUSE(16A) BREAKER(16A)
LEV3 LEV1
Il-2
Indoor units
21
BC controller
BC controller
MEES17K069
Never connect power line to it.
0000004506.BOOK
33
X01 5 4 4 SV1C
44 Terminal block
X30 7 TB01
3
(for power source)
1 1 1 T2
PS3 2 2 CN27(Red)
CNP3 CNOUT1 1 2 2 SV2B Terminal block
1 3 55
金曜日
1 X04 3 3 3 SV2A
TB02 (for Transmission)
66
2 X03 5 4 4 SV2C
SV9A
SV9B
SV8A
SV8B
SV7A
SV7B
SV9C
SV8C
SV7C
SV10A
SV10B
SV10C
1 CN13 CONT. B 77 SV1~16A,B,C Solenoid valve
2 (Red) 3 X31 7
4 1 1 T3 T10 T9 T8 T7 T1~20 Terminal
CN28(Blue)
3. ELECTRICAL WIRING DIAGRAMS
1 5 1 2 2 SV3B
TH11 LD1:CPU in 88 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
2 operation 6 X06 3 3 3 SV3A F01 Fuse AC250V 6.3A F
t° 99
3 7 X05 5 4 4 SV3C
TH12 1010 Z1 Function setting connector
4 8 X32 7
t° CN10 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
5 1 1 T4
午後1時49分
10 1 1 CN29(Green)
6 1 2 2 SV4B
2 11 11
7 X08 3 3 3 SV4A 16 15 14 13 12 11 10 9 8 7 6 5 4
3 1212 16 15 14 13 12 11 10 9 8 7 6 5 4
8 SW2 SW1 X07 5 4 4 SV4C
4 1313
X33 7
1
TH15 CNOUT3 1 1 T5
2 CN30(Black)
t° CN11 1 2 2 SV5B
3 SW4 1414
X10 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
TH16 3 3 3 SV5A 1 1 T11
4 1515 CN40
t° X09 5 4 4 SV5C (Yellow) 1 2 2 SV11B
1616 1 3 3 2 1 11
X34 7 CNVCC2 X41 SV11A
X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36
1 ZNR01 ZNR02 3 3 3
CN39
22
CN32
SW5
CN33(Red)
CN35(Blue)
Z1 2 TYP1 (Blue)
CN34(Black)
1 1 T6 X40 5 4 4 SV11C
U U CN31(Yellow) 33
1 2 2 SV6B X42 7
11 1 1 T12
X12 3 3 3 SV6A CN41(Green)
22 1 2 2 SV12B
SW6 DSA F01 44
X11 5 4 4 SV6C X44
250VAC 33 3 3 3 SV12A
6.3A F X35 55
X43 5 4 4 SV12C
CN36(Green) 66
1 X45 7
X21 1 1 T13 T20
3 CN42
1 2 2 SV13B
77
X47 3 3 3 SV13A
88
X46 5 4 4 SV13C
CN07 CN05 99
(Yellow) X48 7
(Red) TO NEXT 1 1 T14
1 234 5 6 1 234 5 6 1 3 5 TB01 CN43(Red)
INDOOR UNIT POWER SUPPLY 1 2 2 SV14B
CN12 L 1010
N
~220V-240V REL. B X50 3 3 3 SV14A
PULL BOX 50Hz/60Hz 11 11
X49 5 4 4 SV14C
1212
X51 7 1 1 T15
M M FUSE(16A) BREAKER(16A) CN44(Yellow)
1 2 2 SV15B
1 1313
2 X53 3 3 3 SV15A
LEV3 LEV1 3 1414
4 X52 5 4 4 SV15C
CNOUT2 1515
5 X54
6 7 1 1
1616 T16
7 CN45(Green)
1 2 2 SV16B
8 11
X56 3 3 3 SV16A
1 22
2 X55 5 4 4 SV16C
CNOUT4 33
3 X57 7
4 44
55
66
77
Il-2
88 CMB-P1016V-J ONLY
Indoor units
22
TR TB02 Indoor/outdoor (Symbol explanation)
0000004506.BOOK
MEES17K069
TR Transformer
7 6 5 4 3 2 1 TH11,12,15,16 Thermister sensor
3 1 1
2 CN50 CNTR
PS1 2 3 T9 LEV1,3,4 Expansion valve
3 2 1 2 1 1 3 (Red)
1 3
1 1 T1
CN03 CN02 CN38 CN26 1 1 PS1,3 Pressure sensor
CNP1 (Yellow) 1 2 2 SV1B
2 2
(Black) X02 3 3 3 SV1A REL.B Circuit Relay
3 3
CMB-P108V-JA
X01 5 4 4 SV1C
4 4 CONT.B board BC controller
X30 7
3 1 1 1 T2 Terminal block
2 2
CN27(Red) TB01 (for power source)
PS3 CNP3 1 2 2 SV2B
1 3 5 5
X04 3 3 3 SV2A Terminal block
6 6
X03 5 4 4 SV2C
TB02
1 CN13 7 7
(for Transmission)
2 (Red) X31 7
23 ページ 2017年12月22日
TH12 10 10
4 X32 7 F01
t° CN10 Fuse AC250V 6.3A F
5 1 1 T4
CN29(Green) Z1 Function setting connector
6 1 2 2 SV4B
11 11
7 X08 3 3 3 SV4A
12 12
8 CONT.B X07 5 4 4 SV4C
13 13
X33 7 T11
1
SV8C
SV8A
SV8B
SV7C
SV7A
SV7B
TH15 LD1:CPU in 1 1
3. ELECTRICAL WIRING DIAGRAMS
T5 T10
SVM1
SVM1b
CN30(Black)
午後1時49分
2 operation
t° CN11 1 2 2 SV5B T8 T7
3 14 14
TH16 X10 3 3 3 SV5A
4 10 1 15 15 4 3 2 1 4 3 2 1 4 3 2 1
t° X09 5 4 4 SV5C
16 16
X34 7
1
Z1 TYP1 SW2 SW1
2 1 1 T6
CN31(Yellow) 4 3 2 1 4 3 2 1 4 3 2 1
1 2 2 SV6B
1 1
X12 3 3 3 SV6A
2 2
SW4 X11 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9 8 7 6 5 4
5 4 4 SV6C
3 3 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9 8 7 6 5 4
ZNR01 ZNR02 X35 7
U U
SW5
CN36(Green)
1
DSA
1 X21
F01 3
2 250VAC
3 CN08 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
M 6.3A F
4 (Green) SW6
CN46(Yellow)
5 1
LEV4 6 CN39
X60 3
X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36
3
CN32
CN33(Red)
CN35(Blue)
CN34(Black)
1 1
X62 3
CN07 CN05 7 6 5 4 3 2 1
(Yellow) X61 5
(Red)
1 2 3 4 5 6 1 2 3 4 5 6 1 3 5 CN52 REL. B
6 TO NEXT INDOOR UNIT
CN12 TB01
CN47
L
N PULL BOX
POWER SUPPLY
M M ~220V-240V
50Hz/60Hz
LEV3 LEV1 FUSE(16A) BREAKER(16A)
Il-2
SW1:0
SW2:0
Indoor units
23
BC controller
BC controller
(Symbol explanation)
TR TB02 Indoor/outdoor Symbol Name
MEES17K069
20V~22V 220V~240V S(SHIELD)
M2 Transmission line
TR Transformer
0000004506.BOOK
M1
TH11,12,15,16 Thermister sensor
T19 LEV1,3,4 Expansion valve
3 1 1
2 CNTR T17 T18 PS1,3 Pressure sensor
PS1 2 (Red) 3
1 3 2 1 3 2 1 2 1 1 3
3 1 1 T1
CNVCC1 CN03 CN02 CN38 CN26 1 1 REL.B
CNP1 (Blue) (Yellow) 1 2 2 SV1B
Circuit Relay
2 2
(Black) CONT. B X02 3 3 3 SV1A board BC controller
10 1
3 3 CONT.B
X01 5 4 4 SV1C
LD1:CPU in 4 4
operation X30 7
Terminal block
3 1 SW2 SW1 1 1 T2 TB01 (for power source)
CMB-P1012,1016V-JA
2 2
CN27(Red)
PS3 CNP3 CNOUT1 1 2 2 SV2B
1 3 5 5 Terminal block
SV9C
SV9A
SV9B
SV8C
SV8A
SV8B
SV7C
SV7A
SV7B
SV10C
SV10A
SV10B
1 X04 3 3 3 SV2A TB02
6 6 (for Transmission)
1 SW4 2 X03 5 4 4 SV2C
CN13 7 7 T10 T9 T8 T7
2 (Red) 3 X31 7 SV1~16A,B,C
4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 Solenoid valve
4 1 1 T3
CN28(Blue)
1 5 1 2 2 SV3B SVM1,SVM1b
TH11 SW5 8 8 Solenoid valve
2 6 X06 3 3 3 SV3A
24 ページ 2017年12月22日
t° 9 9 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
3 7 X05 5 4 4 SV3C T1~21 Terminal
TH12 10 10
4 8 X32 7
t° CN10 SW6 F01
5 1 1 T4 16 15 14 13 12 11 10 9 8 7 6 5 4 Fuse AC250V 6.3A F
1 CN29(Green) 16 15 14 13 12 11 10 9 8 7 6 5 4
6 1 2 2 SV4B
11 11
金曜日
7 2
Z1 Function setting connector
X08 3 3 3 SV4A
3 12 12
8 X07 5 4 4 SV4C
4 13 13
X33 7
1
TH15 CNOUT3 1 1 T5 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
3. ELECTRICAL WIRING DIAGRAMS
2 CN30(Black)
t° CN11 1 2 2 SV5B
3 14 14 1 3 3 2 1
TH16 X10 3 3 3 SV5A CNVCC2
X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36
15 15
CN32
CN39
4
CN33(Red)
CN35(Blue)
CN34(Black)
t° X09 5 4 4 SV5C (Blue)
16 16 CN40 1 1 T11
1 X34 7 (Yellow) SV11B
Z1 TYP1 1 2 2
1 1
午後1時49分
2 1 1 T6
CN31(Yellow) X41 3 3 3 SV11A
1 2 2 SV6B 2 2
1 1 X40 5 4 4 SV11C
X12 3 3 3 SV6A 3 3
1 2 2 X42 7
X11 5 4 4 SV6C 1 1 T12
2 3 3 CN41(Green)
3 ZNR01 ZNR02 1 2 2 SV12B
M CN08 X35 7 4 4
4 (Green) X44 3 SV12A
5 U U 5 5 3 3
LEV4 6 CN36(Green) X43 5 4 4 SV12C
1 6 6 CMB-P1016V-JA ONLY
DSA X45 7
1 F01 X21 3 1 1 T13
250VAC CN42 T20
2 1 2 2 SV13B
3 CN07 6.3A F CN46(Yellow) 7 7
M 4 1 X47 3 3 3 SV13A
(Yellow) 8 8
5 X60 X46 5 4 SV13C
LEV3 6 3 REL. B 9 9 4
X48 7
1 1 1 T14
TO NEXT CN43(Red)
1 2 2 SV14B
X62 3 INDOOR UNIT POWER SUPPLY 10 10
CN05 X50 3 3 3 SV14A
(Red) X61 5 TB01 ~220V-240V 11 11
1 2 3 4 5 6
PULL BOX 50Hz/60Hz X49 5 4 4 SV14C
1 3 5 6 L 12 12
CN12 N X51 7
1 1 T15
CN47 CN44(Yellow)
1 2 2 SV15B
FUSE(16A) BREAKER(16A) 13 13
1 X53 3 3 3 SV15A
2 14 14
M 3 X52 5 4 4 SV15C
15 15
4
LEV1 X54 7
5 CNOUT2 16 16 1 1 T16
6 CN45(Green)
1 2 2 SV16B
7 1 1
8 X56 3 3 3 SV16A
2 2
1 X55 5 4 4 SV16C
3 3
2 X57 7
3 CNOUT4 4 4
4 1 1 T21
5 5
2 2 SVM1
6 6
3 3
7 7
4 4 SVM1b
8 8
Note 1. TB02 is transmission terminal block.
Never connect power line to it.
2. The initial set values of switch on CONT. B are as follows.
SW1:0
Il-2
SW2:0
Indoor units
24
(Symbol explanation)
0000004506.BOOK
MEES17K069
M2 Transformer
M1
TR
TH11,12,15,16 Thermister sensor
3 CNTR(Red) 1 T19 LEV1,3,4 Expansion valve
1
2 CN38 T17 T18
PS1 2 3
1 3 2 1 3 2 1 2 1 3 1
3 1 1 T1 PS1,3 Pressure sensor
CNVCC1 CN03 CN02 CN26 1 1
CNP1 (Blue) (Yellow) 1 2 2 SV1B
2 2 REL.B Circuit Relay
(Black) X02 3 3 3 SV1A
10 1 3 3
X01 4 SV1C
CMB-P1016V-KA
SV9C
SV9A
SV9B
SV8C
SV8A
SV8B
SV7C
SV7A
SV7B
SV10C
SV10A
SV10B
6 6 Terminal block
SW4 X03 5 4 4 SV2C
1 CN13 7 7 TB02
2 (Red) X31 7
T10 T9 T8 T7 (for Transmission)
LD1:CPU in
25 ページ 2017年12月22日
1 1 T3 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
operation CN28(Blue) SV1~16A,B,C Solenoid valve
1 1 2 2 SV3B
TH11 SW5 8 8
2 X06 3 3 3 SV3A SVM1,1b Solenoid valve
t° 9 9
3 CNOUT1 X05 5 4 4 SV3C 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
TH12 1010
4 T1~21 Terminal
金曜日
1 X32 7
t° CN10 SW6
5 2 1 1 T4
CN29(Green) 16 15 14 13 12 11 10 9 8 7 6 5 4 F01 Fuse AC250V 6.3A F
6 3 1 2 2 SV4B 16 15 14 13 12 11 10 9 8 7 6 5 4
11 11
7 4 X08 3 3 3 SV4A
8
1212 Z1 Function setting connector
5 X07 5 4 4 SV4C
1313
6 X33 7
1
TH15 7 1 1 T5 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
2 CN30(Black)
t° CN11 8 1 2 2 SV5B
3 1414
1 3 3 2 1
3. ELECTRICAL WIRING DIAGRAMS
X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36
4 1 1515 CNVCC2
X09
CN32
CN39
t° 5 4 4 SV5C (Blue)
1616
CN33(Red)
CN35(Blue)
CN34(Black)
2 X34 1 1 T11
1 7 CN40
Z1 TYP1 3 (Yellow) 1 2 2 SV11B
2 1 1 T6 1 1
4 CN31(Yellow) X41
1 2 2 SV6B 3 3 3 SV11A
1 1 2 2
X12 X40 5 4 4 SV11C
1 CNOUT3 3 3 3 SV6A 3 3
2 2 X42
2 X11 5 4 4 SV6C 7
3 3 1 1 T12
3 CN08 CN41(Green)
M 4 X35 7 1 2 2 SV12B
(Green) 4 4
5 X44 3 SV12A
LEV4 6 CN36(Green) 5 5 3 3
1 X43 5 4 4 SV12C
6 6
1 X21 3 X45 7
1 1 T13 T20
2 ZNR01 CN42
3 CN07 ZNR02 CN46(Yellow) 1 2 2 SV13B
M 7 7
4 (Yellow) 1 X47
U U 3 3 3 SV13A
5 X60 8 8
LEV3 6 3 X46 5 4 4 SV13C
9 9
DSA X48 7
F01 CN47 1 1 T14
1 CN43(Red)
250VAC 1 SV14B
CN05 6.3A F X62 REL. B 10 10 2 2
3
(Red) X50 3 3 3 SV14A
X61 5 11 11
1 2 3 4 5 6 1 3 5 X49 5 4 SV14C
12 12 4
6 TO NEXT
CN12 TB01 INDOOR UNIT X51 7
POWER SUPPLY 1 1 T15
L ~220V-240V CN44(Yellow) SV15B
1 2 2
N PULL BOX 50Hz/60Hz 13 13
X53 3 3 3 SV15A
M 14 14
X52 5 4 4 SV15C
15 15
LEV1 X54 7
16 16 1 1 T16
FUSE(16A) BREAKER(16A) CN45(Green)
1 2 2 SV16B
1 1 1
2 X56 3 3 3 SV16A
3 2 2
X55 5 4 4 SV16C
4 3 3
5 CNOUT2 X57 7
6 4 4 T21
1 1
7 5 5
8 2 2 SVM1
6 6
1 3 3
2 7 7
CNOUT4 4 4 SVM1b
3 8 8
4
Il-2
SW1:0
SW2:0
Indoor units
25
BC controller
BC controller
TR TB02 Indoor/outdoor
20V~22V 220V~240V S(SHIELD)
Transmission line
MEES17K069
M2
0000004506.BOOK
M1
CNTR
3 2 1 2 1 (Red)
CN03 CN02 T5 1 1 T1 CMB-P104V-KB
CN26 1 1
(Yellow) 1 2 2 SV1B
2 2
X02 3 3 3 SV1A
3 3
X01 5 4 4 SV1C
4 4
X30 7
3 1 1 1 T2
2 2 CN27(Red)
PS3 CNP3
1 1 2 2 SV2B
3 5 5
X04 (Symbol explanation)
26 ページ 2017年12月22日
3 3 3 SV2A
6 6
X03 SV2C
Symbol Name
1 5 4 4
CN13 7 7 TR Transformer
2 (Red) X31 7
10 1 TH12,15,16 Thermister sensor
金曜日
1 1 T3
CN28(Blue) LEV3 Expansion valve
1 1 2 2 SV3B
8 8 Circuit
2 X06 CONT.B BC controller
3. ELECTRICAL WIRING DIAGRAMS
5 1 1 T4 (for Transmission)
SW4 operation CN29(Green)
6 1 2 2 SV4B SV1~4A,B,C Solenoid valve
11 11
7 X08 3 3 SV4A
T1~5 Terminal
3
12 12 F01
8 X07 4 4 SV4C
Fuse AC250V 6.3A F
5
SW5 13 13 Z1 Function setting connector
X33 7
1 PS3 Pressure sensor
TH15
2
t° CN11
3 SW6 ZNR01 ZNR02 14 14
TH16 Note 1. TB02 is transmission terminal block.
4 U U 15 15
t° Never connect power line to it.
16 16
1 2. The initial set values of switch on CONT. B are as follows.
TYP1 DSA
Z1 2 F01 SW1:0
250VAC
CN07
6.3A F SW2:0
(Yellow)
1 2 3 4 5 6 1 3 5
TO NEXT
CN12 TB01 INDOOR UNIT
L
N PULL BOX
M
FUSE(16A)
LEV3
BREAKER(16A)
POWER SUPPLY
~220V-240V
Il-2
50Hz/60Hz
Indoor units
26
0000004506.BOOK
MEES17K069
2. The initial set values of switch on CONT. B are as follows. TR Transformer
SW1:0 TH12,15,16 Thermister sensor
SW2:0 LEV3 Expansion valve
PS3 Pressure sensor
REL.B
CMB-P108V-KB
TR TB02 Circuit Relay
Indoor/outdoor
20V~22V 220V~240V S(SHIELD)
M2 Transmission line CONT.B board BC controller
M1 Terminal block
TB01 (for power source)
7654321 Terminal block
1 TB02
CN50 CNTR T9 (for Transmission)
3
27 ページ 2017年12月22日
3 2 1 2 1 1 3(Red)
1 1 T1 SV1~8A,B,C Solenoid valve
CN03 CN02 CN38 CN26 1 1
(Yellow) 1 2 2 SV1B
2 2 T1~10 Terminal
X02 3 3 3 SV1A
3 3
金曜日
6 6
1 X03 5 4 4 SV2C
CN13 7 7
2 (Red) X31 7 T8 T7
3. ELECTRICAL WIRING DIAGRAMS
午後1時49分
1 1 T3 4 3 2 1 4 3 2 1
1
CN28(Blue)
CONT.B 1 2 2 SV3B
8 8
2 X06 3 3 3 SV3A
9 9
3 X05 5 4 4 SV3C T10 4 3 2 1 4 3 2 1
TH12 LD1:CPU in 10 10
4 operation X32 7
t˚ CN10
5 1 1 T4
6 10 1
CN29(Green) 16 15 14 13 12 11 10 9 8 7 6 5 4
1 2 2 SV4B 16 15 14 13 12 11 10 9 8 7 6 5 4
11 11
7 X08 3 3 3 SV4A
12 12
8 SW2 SW1 X07 5 4 4 SV4C
13 13
X33 7
1
TH15 1 1 T5
2 CN30(Black) 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
t˚ CN11 1 2 2 SV5B
3 SW4 14 14
TH16 X10 3 3 3 SV5A
4 15 15
X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36
t˚ X09 5 4 4 SV5C
CN32
ZNR01 ZNR02 16 16
CN35(Blue)
CN33(Red)
CN34(Black)
1 SW5 X34 7
Z1 TYP1 U U
2 1 1 T6
CN31(Yellow)
1 2 2 SV6B CN39
DSA F01 1 1
250VAC X12 3 3 3 SV6A 3
SW6 2 2 REL.B
6.3A F X11 4 4 SV6C
1
5
3 3
X35 7 7 6 5 4 3 2 1
CN36(Green) CN52
1
X21 3
CN07
(Yellow)
1 2345 6 1 3 5 TB01 TO NEXT INDOOR UNIT
CN12 L
N PULL BOX
POWER SUPPLY
~220V-240V
M 50Hz/60Hz
FUSE(16A) BREAKER(16A)
LEV3
Il-2
Indoor units
27
BC controller
0000004506.BOOK 28 ページ 2017年12月22日 金曜日 午後1時49分
80
60
NC -60
50
NC -50
1.5m
40
NC -40
30
NC -30
20 Approximate minimum
audible limit on NC -20
Measurement location continuous noise
10
63 125 250 500 1k 2k 4k 8k
■Cooling operation Octave band central frequency (Hz)
Total down-stream Indoor capacity 63 125 250 500 1k 2k 4k 8k dB(A)
25% 34.0 31.0 34.5 33.5 29.5 32.5 30.5 22.5 38.0
50% 35.0 36.5 41.0 38.0 36.0 37.5 34.0 26.0 43.0
75% 35.0 38.5 43.5 40.0 38.0 39.5 36.0 27.0 45.0
100% 36.0 42.0 47.0 43.0 41.5 42.5 38.0 29.0 48.0
80 80
Octave band sound level (dB)
70 70
NC -70 NC -70
60 60
NC -60 NC -60
50 50
NC -50 NC -50
40 40
NC -40 NC -40
30 30
NC -30 NC -30
80
Octave band sound level (dB)
70
NC -70
60
BC controller
NC -60
50
NC -50
40
NC -40
30
NC -30
20 Approximate minimum
audible limit on NC -20
continuous noise
10
63 125 250 500 1k 2k 4k 8k
■Cooling operation Octave band central frequency (Hz)
Total down-stream Indoor capacity 63 125 250 500 1k 2k 4k 8k dB(A)
25% 37.0 37.5 40.5 37.5 35.5 39.5 35.5 29.5 44.0
50% 38.0 40.0 43.5 40.5 39.5 42.5 38.0 32.0 47.0
75% 39.0 43.0 46.0 43.0 43.0 45.5 41.0 34.5 50.0
100% 39.0 44.0 47.0 44.0 44.5 46.0 42.5 35.5 51.0
Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.
MEES17K069 Il-2 28
0000004506.BOOK 29 ページ 2017年12月22日 金曜日 午後1時49分
80
60
NC -60
50
NC -50
1.5m
40
NC -40
30
NC -30
20 Approximate minimum
audible limit on NC -20
Measurement location continuous noise
10
63 125 250 500 1k 2k 4k 8k
■Heating operation Octave band central frequency (Hz)
Total down-stream Indoor capacity 63 125 250 500 1k 2k 4k 8k dB(A)
25% 39.0 41.0 42.5 40.5 40.5 41.0 40.5 42.0 48.0
50% 41.0 45.0 46.5 44.5 44.0 45.0 43.0 42.0 51.0
75% 41.5 46.5 48.0 45.5 45.5 46.0 43.5 42.5 52.0
100% 43.0 49.0 51.0 48.0 47.5 48.5 44.5 42.5 54.0
80 80
Octave band sound level (dB)
70 70
NC -70 NC -70
60 60
NC -60 NC -60
50 50
NC -50 NC -50
40 40
NC -40 NC -40
30 30
NC -30 NC -30
80
Octave band sound level (dB)
70
NC -70
60
BC controller
NC -60
50
NC -50
40
NC -40
30
NC -30
20 Approximate minimum
audible limit on NC -20
continuous noise
10
63 125 250 500 1k 2k 4k 8k
■Heating operation Octave band central frequency (Hz)
Total down-stream Indoor capacity 63 125 250 500 1k 2k 4k 8k dB(A)
25% 38.5 43.0 47.0 41.5 41.5 42.0 40.5 43.0 49.0
50% 40.5 48.0 51.5 46.0 45.0 45.0 42.0 45.0 52.0
75% 42.0 51.5 54.5 49.0 47.5 47.0 42.5 45.5 54.0
100% 42.5 53.0 56.0 50.5 48.5 47.5 43.0 46.0 55.0
Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.
MEES17K069 Il-2 29
0000004506.BOOK 30 ページ 2017年12月22日 金曜日 午後1時49分
60
NC -60
50
NC -50
1.5m
40
NC -40
30
NC -30
20 Approximate minimum
audible limit on NC -20
Measurement location continuous noise
10
63 125 250 500 1k 2k 4k 8k
■Defrost operation Octave band central frequency (Hz)
Capacity of connected outdoor unit 63 125 250 500 1k 2k 4k 8k dB(A)
(E)P200-(E)P300 31.5 44.5 46.5 39.5 40.5 46.5 49.5 52.0 55.0
(E)P350 34.0 46.5 48.5 41.5 42.0 46.5 50.0 51.0 55.0
(E)P400-(E)P600 36.5 49.0 51.5 44.0 43.5 47.5 50.0 49.0 55.0
(E)P650 37.5 50.0 52.5 44.5 44.0 47.5 50.0 48.0 55.0
(E)P700-(E)P800 38.5 51.0 53.5 45.5 44.5 47.5 50.0 47.0 55.0
(E)P850 39.0 51.5 53.5 46.0 45.0 47.0 50.0 47.0 55.0
(E)P900 39.5 51.5 54.0 46.0 45.0 47.0 50.0 46.5 55.0
(E)P950-(E)P1100 40.0 52.0 54.5 46.5 45.0 47.5 49.5 46.0 55.0
80 80
Octave band sound level (dB)
70 70
NC -70 NC -70
60 60
NC -60 NC -60
50 50
NC -50 NC -50
40 40
NC -40 NC -40
30 30
NC -30 NC -30
70
NC -70
60
BC controller
NC -60
50
NC -50
40
NC -40
30
NC -30
20 Approximate minimum
audible limit on NC -20
continuous noise
10
63 125 250 500 1k 2k 4k 8k
■Defrost operation Octave band central frequency (Hz)
Capacity of connected outdoor unit 63 125 250 500 1k 2k 4k 8k dB(A)
(E)P200-(E)P300 37.5 49.0 51.0 45.0 43.0 45.0 48.0 45.0 53.0
(E)P350 40.0 50.5 53.5 47.0 45.0 46.5 50.0 47.0 55.0
(E)P400-(E)P600 41.5 51.0 54.5 48.0 46.5 47.0 51.5 47.0 56.0
(E)P650 42.0 51.0 54.5 48.0 47.0 46.5 51.5 47.5 56.0
(E)P700-(E)P800 42.0 50.5 55.0 48.0 47.0 46.5 51.5 47.0 56.0
(E)P850 42.0 50.5 55.0 48.0 47.0 46.5 51.5 47.0 56.0
(E)P900 42.0 50.5 55.0 48.0 47.0 46.0 51.5 47.0 56.0
Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.
MEES17K069 Il-2 30
0000004506.BOOK 31 ページ 2017年12月22日 金曜日 午後1時49分
Symbols: MCA (Max. Circuit Amps), MFA (Max. Fuse Amps), RLA (Rated Load Amps)
Power supply
BC controller RLA(A)
Hz Volts Range+-10% MCA(A) MFA(A)
220 0.31
CMB-P104V-J 230 0.45 0.34
240 0.36
220 0.45
CMB-P106V-J 230 0.65 0.48
240 0.52
220 0.58
CMB-P108V-J 230 0.85 0.63
240 0.68
220 0.85
CMB-P1012V-J 230 1.24 0.92
240 0.99
220 1.12
CMB-P1016V-J 230 1.63 1.22
240 1.30
220 0.58
Max.: 264V
CMB-P108V-JA 50/60 230 0.85 15 0.63
Min.: 198V
240 0.68
220 0.85
CMB-P1012V-JA 230 1.24 0.92
240 0.99
220 1.12
CMB-P1016V-JA 230 1.63 1.22
240 1.30
220 1.12
CMB-P1016V-KA 230 1.63 1.22
240 1.30
220 0.28
CMB-P104V-KB 230 0.40 0.30
240 0.32
220 0.55
CMB-P108V-KB 230 0.79 0.59
240 0.63
BC controller
MEES17K069 Il-2 31
0000004506.BOOK 32 ページ 2017年12月22日 金曜日 午後1時49分
CITY MULTI units can be easily connected by using Joint sets and Reducer sets provided by Mitsubishi Electric. Refer to section
"Piping Design" or the Installation Manual that comes with the Joint set or Reducer set for how to install the Joint set or Reducer set.
CMY-Y102SS-G2 mm
For Gas pipe: <Deformed pipe(Accessory)> For Liquid pipe:
ø15.88 ø12.7
(Outside diameter) <Deformed pipe(Accessory)>
28
ø15.88
ø19.05 ø15.88 ø9.52
ø19.05 (Outside diameter) ø9.52 ø6.35
ø19.05 ø9.52
30
18
30
20
(2 Pcs.) 36
58 (2 Pcs.)
ø19.05 ø12.7
(Outside diameter)
<Deformed pipe(Accessory)>
37 54
ø19.05 ø15.88 (2 Pcs.)
ø25.4 ø19.05
(Outside diameter) (Outside diameter) ø9.52
ø6.35
(Outside diameter)
ø19.05
30 ø9.52 20
ø25.4 41
ø25.4 ø19.05 ø22.2 (2 Pcs.) ø12.7
ø12.7
39
20
42
*Pipe diameter is indicated by inside diameter. (2 Pcs.)
CMY-R101S-G mm
ø28.6
43
ø28.6
ø28.6
86
ø28.6 ø28.6
(Outside diameter) (Outside diameter)
ø22.2 ø19.05
80 80
(2 Pcs.) (2 Pcs.) <Accessory>
• Cover ··········1 Pcs.
• Band ··········3 Pcs.
Note. Pipe diameter is indicated by inside diameter.
CMY-R102S-G mm
ø41.28
BC controller
58
ø41.28
ø41.28
116
ø41.28 ø34.93
(Outside diameter) (Outside diameter)
ø34.93 ø28.6
92 50
(2 Pcs.)
ø28.6 ø28.6
(Outside diameter) <Accessory>
(Outside diameter) • Cover ··········1 Pcs.
ø19.05 • Band ··········3 Pcs.
ø22.2
80 80 Note. Pipe diameter is indicated by inside diameter.
MEES17K069 Il-2 32
0000004506.BOOK 33 ページ 2017年12月22日 金曜日 午後1時49分
CMY-R201S-G mm
For High pressure For Low pressure For Liquid line
ø15.88 ø19.05
ø9.52
ø25.4
ø12.7
26
20
16
ø19.05 ø19.05 ø12.7
58 ø25.4 42
66
ø25.4
ø19.05 ø12.7
(Outside diameter)
(Outside diameter) (Outside diameter)
ø15.88 ø19.05 ø9.52
30 41 23
(2 Pcs.) (2 Pcs.) (2 Pcs.)
ø25.4
(Outside diameter)
ø22.2
42
(2 Pcs.)
ø25.4
(Outside diameter)
<Accessory>
ø28.6 • Cover ·················3 Pcs.
54 Note. Pipe diameter is indicated by inside diameter.
(2 Pcs.)
CMY-R202S-G mm
For High pressure For Low pressure For Liquid line
ø19.05 ø19.05
ø12.7
ø25.4 ø25.4
26
26
18
ø15.88 ø15.88
ø25.4 66 ø25.4 66 49
ø25.4 ø25.4 ø15.88
(Outside diameter) (Outside diameter) (Outside diameter)
ø22.2 ø12.7
ø28.6
42 28
54
(2 Pcs.) (2 Pcs.) (2 Pcs.)
ø25.4 ø25.4 ø15.88
(Outside diameter) (Outside diameter) (Outside diameter)
ø19.05 ø9.52
ø19.05
41 41 28
ø25.4 ø25.4 ø12.7
(Outside diameter) (Outside diameter) (Outside diameter)
ø15.88 ø22.2 ø9.52
23
45 42
ø19.05 ø19.05
(Outside diameter) (Outside diameter)
ø15.88 ø22.2 <Accessory>
30 54 • Cover ·················3 Pcs.
Note. Pipe diameter is indicated by inside diameter.
CMY-R203S-G mm
For High pressure For Low pressure For Liquid line
ø19.05 ø25.4
ø12.7
ø25.4 ø31.75
30
26
18
ø15.88
ø25.4 ø31.75 ø15.88
66 49
90
ø25.4 ø31.75 ø15.88
(Outside diameter) (Outside diameter) (Outside diameter)
ø28.6 ø28.6 ø12.7
54 28
(2 Pcs.) 46
ø25.4 (2 Pcs.) ø12.7
ø25.4
(Outside diameter) (Outside diameter) (Outside diameter)
ø9.52
ø19.05 ø19.05 23
41 41
ø25.4 ø25.4
(Outside diameter) (Outside diameter)
ø22.2 ø22.2
42 42
ø19.05 ø25.4
BC controller
MEES17K069 Il-2 33
0000004506.BOOK 34 ページ 2017年12月22日 金曜日 午後1時49分
CMY-R204S-G For High pressure For Low pressure For Liquid line mm
ø19.05 ø25.4 ø15.88
ø25.4 ø31.75 ø19.05
30
26
20
ø19.05
ø25.4 66 ø31.75 58
90
ø25.4 ø19.05 ø31.75 ø19.05 ø15.88
(Outside diameter) (Outside diameter) ø25.4
(Outside diameter) (Outside diameter) (Outside diameter) (Outside diameter)
ø28.6 ø15.88 ø28.6 ø15.88 ø12.7
ø19.05 28
54 30 30
46 41
(2 Pcs.)
ø25.4 ø19.05 ø31.75 ø25.4 ø19.05 ø15.88
(Outside diameter) (Outside diameter) (Outside diameter) (Outside diameter) (Outside diameter) (Outside diameter)
ø19.05 ø22.2 ø22.2 ø12.7 ø9.52
ø34.93
54 37 28
41 69 42
(2 Pcs.)
ø31.75 ø25.4
ø25.4
(Outside diameter) (Outside diameter) (Outside diameter)
CMY-R205S-G For High pressure For Low pressure For Liquid line mm
ø25.4 ø25.4 ø19.05
ø31.75 ø31.75 ø25.4
30
30
26
ø31.75 ø31.75 ø25.4
90 90 66
ø31.75 ø25.4 ø31.75 ø25.4 ø25.4
(Outside diameter) (Outside diameter) ø19.05
(Outside diameter) (Outside diameter) (Outside diameter) (Outside diameter)
ø19.05 ø41.28 ø22.2 ø19.05 ø12.7
ø34.93
41 42 41 37
69 69
(2 Pcs.) (2 Pcs.)
(3 Pcs.) ø25.4
ø31.75 ø25.4 ø31.75
(Outside diameter) (Outside diameter) (Outside diameter) ø25.4 ø12.7
(Outside diameter)
(Outside diameter) (Outside diameter)
ø22.2
ø28.6 ø28.6 ø28.6 ø15.88 ø9.52
42 46 54 23
46 45
(2 Pcs.)
ø31.75 ø25.4
ø31.75 ø25.4 (Outside diameter)
(Outside diameter) (Outside diameter) ø19.05
(Outside diameter) (Outside diameter)
ø25.4 ø34.93 ø31.75 ø15.88
ø28.6
69 54 30
55 54
(2 Pcs.) (2 Pcs.)
ø25.4 ø25.4
(Outside diameter) (Outside diameter) <Accessory>
ø15.88
ø19.05
• Cover ·················3 Pcs.
45 41
Note. Pipe diameter is indicated by inside diameter.
CMY-R301S-G mm
ø19.05
(Outside diameter)
ø15.88
80
ø28.6 ø22.2
(Outside diameter) (Outside diameter)
ø22.2 ø19.05
80 80
BC controller
CMY-R302S-G mm
ø41.28
(Outside diameter) ø34.93
(Outside diameter)
ø34.93 ø28.6
92 50
(2 Pcs.)
MEES17K069 Il-2 34
0000004506.BOOK 35 ページ 2017年12月22日 金曜日 午後1時49分
CMY-R303S-G mm
ø28.6 ø22.2
(Outside diameter) (Outside diameter)
ø22.2 ø19.05
80 80
CMY-R304S-G mm
ø41.28
(Outside diameter) ø34.93
(Outside diameter)
ø34.93 ø28.6
92 50
(2 Pcs.)
CMY-R305S-G mm
CMY-R306S-G mm
ø19.05 ø28.6
(Outside diameter) (Outside diameter)
ø15.88 ø22.2
BC controller
80 80
MEES17K069 Il-2 35
0000004506.BOOK 36 ページ 2017年12月22日 金曜日 午後1時49分
C C
BC controller
(Main)
D D
IU IU IU
IU: Indoor unit
CMY-Y102SS-G2
Between BC and Total down-stream indoor unit capacity: -P200
A Branch joint
indoor units
CMY-Y102LS-G2 Total down-stream indoor unit capacity: P201-P250
Low pressure Between outdoor CMY-R101S-G Outdoor unit capacity: P200-P650
B
pipe joint units and Sub BC CMY-R102S-G Outdoor unit capacity: P700-P1100
CMY-R201S-G Total down-stream indoor unit capacity: -P350
CMY-R202S-G Total down-stream indoor unit capacity: P351-P600
Between Main BC
C Branch joint CMY-R203S-G Total down-stream indoor unit capacity: P601-P650
and Sub BC
CMY-R204S-G Total down-stream indoor unit capacity: P651-P1000
CMY-R205S-G Total down-stream indoor unit capacity: P1001-
CMY-R301S-G For J type (Outdoor unit capacity: P200-P300)
Between outdoor
CMY-R302S-G For JA type (Outdoor unit capacity: P200-P900)
units and BC
CMY-R304S-G For KA type (Outdoor unit capacity: P200-P1000)
D Reducer
CMY-R303S-G For JA type (When using the Sub BC controller)
Between Main BC
CMY-R305S-G For KA type (When using the Sub BC controller)
and Sub BC
CMY-R306S-G For KB type
Main BC controller has two ports for Sub BC controller. Low pressure pipe has to be branched from the outdoor unit.
(“B” in the figure)
Items “B” and “C” are not necessary when J-type BC controller is used.
BC controller
MEES17K069 Il-2 36
0000004506.BOOK 37 ページ 2017年12月22日 金曜日 午後1時49分
This sheet 1pc 1pc 1pc 2pcs 1pc for gas side 1pc for Iiquid side 8pcs 1pc 1pc
Please prepare the following items in the field. 1 Tape for insulation material sealing 2 Extension pipe for refrigerant circuit
2 Joint pipe (for liquid side) 3 Joint pipe (for gas side) mm (in.)
ø19.05(3/4")
ø9.52(3/8") ø15.88(5/8")
ø9.52(3/8")
60(2-3/8")
60(2-3/8")
ø9.52(3/8")
ø15.88(5/8")
226(8-29/32") 226(8-29/32")
Caution: Mixed cooling and heating mode at the same time for IU IU IU IU
Indoor units connecting to 1 port or 2 combined ports is not
Group2 Group3
available. Total Indoor Capacity Indoor Capacity
P81 to P250 P100 to P250
MEES17K069 Il-2 37
0000004506.BOOK 38 ページ 2017年12月22日 金曜日 午後1時49分
Nut (not supplied) Washer (with cushion)(supplied) CMB-P104, 106, 108V-J, CMB-P1012, 1016V-J
* Attach the cushion facing down. CMB-P104, 108V-KB CMB-P108, 1012, 1016V-JA
CMB-P1016V-KA
14mm
Double nut
(not supplied)
14mm
30mm
Minimum
30 mm
Hanging bolt ø10 (Top view)
(M10 screw) Washer (without cushion) (supplied) 30mm
(not supplied)
►Be sure to install the BC controller horizontally, using a level. If the controller is installed at an angle, drain water may leak
out. If the controller is slanted, loosen the fixing nuts on the hanging brackets to adjust its position.
►Provide a downward pitch of 1.5º or below to the BC controller.
►Do not place the BC controller directly on the floor because the drain pan needs to be installed in a tilted position.
BC controller
MEES17K069 Il-2 38
0000004506.BOOK 39 ページ 2017年12月22日 金曜日 午後1時49分
8-1. Compatibility
8. SYSTEM DESIGN
BC controller
Outdoor/Heat source unit Compatibility
Main Sub
PURY-(E)P-Y(S)NW JA/KA type GB1/HB1 type GB1/HB1 type Compatible
PURY-(E)P-Y(S)LM S/W Ver. 7.08 or later JA/KA type KB type GB1/HB1 type Not compatible
PQRY-P-Y(S)LM S/W Ver. 6.42 or later JA/KA type GB1/HB1 type Compatible
PURY-RP-Y(S)JM S/W Ver. 5.58 or later GA1/HA1 type KB type KB type Compatible
PURY-(E)P-Y(S)JM S/W Ver. 1.42 or later GA1/HA1 type KB type GB1/HB1 type Not compatible
GA1/HA1 type KB type Compatible
BC controller
Outdoor/Heat source unit Compatibility
Main Sub
PURY-(E)P-Y(S)NW
PURY-(E)P-Y(S)LM S/W Ver. 7.08 or later
PQRY-P-Y(S)LM S/W Ver. 6.42 or later
JA/KA type KB type Compatible(*)
PURY-RP-Y(S)JM S/W Ver. 5.58 or later
PURY-(E)P-Y(S)JM S/W Ver. 1.42 or later
BC controller
MEES17K069 Il-2 39
0000004506.BOOK 40 ページ 2017年12月22日 金曜日 午後1時49分
Pipe (Liquid)
Pipe (Gas)
IU IU IU IU IU IU IU
(P15-P80) (P100-P250) Max. 3 sets for 1 port. Max. 3 sets for 2 port.
Total capacity < = P80 Total capacity > P80
CMY-R160-J1 (joint)
Possible to remove P140 and under P140, but the IU (each) max < = P80
IU: Indoor unit
capacity should be multiplied by a correction factor 0.97
Pipe (Liquid)
Pipe (Gas)
IU IU IU IU IU IU IU
(P15-P80) (P100-P250) Max. 3 sets for 1 port. Max. 3 sets for 2 port.
CMY-R160-J1 (joint) Total capacity < = P80 Total capacity > P80
Possible to remove P140 and under P140, but the IU (each) max < = P80
capacity should be multiplied by a correction factor 0.97 IU: Indoor unit
MEES17K069 Il-2 40
0000004506.BOOK 41 ページ 2017年12月22日 金曜日 午後1時49分
Pipe
(Liquid)
IU IU IU IU IU IU IU IU IU Pipe (Gas) IU
(P15-P80) (P100-P250) Max. 3 sets for 1 port. Max. 3 sets for 2 port. (P15-P80) (P15-P80)
Total capacity < = P80 Total capacity > P80
CMY-R160-J1 (joint) IU (each) max < = P80
Possible to remove P140 and under P140, but the
capacity should be multiplied by a correction factor 0.97 IU: Indoor unit
PURY-(E)P-Y(S)NW
PURY-(E)P-Y(S)LM S/W Ver. 7.08 or later
PQRY-P-Y(S)LM S/W Ver. 6.42 or later
IU
PURY-RP-Y(S)JM S/W Ver. 5.58 or later
IU
IU IU IU IU IU IU IU IU
(P15-P80) (P100-P250) Max. 3 sets for 1 port. Max. 3 sets for 2 port.
Total capacity < = P80 Total capacity > P80
CMY-R160-J1 (joint) IU (each) max < = P80
Possible to remove P140 and under P140, but the
capacity should be multiplied by a correction factor 0.97 IU: Indoor unit
MEES17K069 Il-2 41
0000004506.BOOK 42 ページ 2017年12月22日 金曜日 午後1時49分
Pipe
(Liquid)
IU IU IU IU IU IU IU IU IU Pipe (Gas) IU IU
(P15-P80) (P100-P250) Max. 3 sets for 1 port. Max. 3 sets for 2 port. (P15-P80) (P15-P80) (P15-P80)
Total capacity < = P80 Total capacity > P80
CMY-R160-J1 (joint) IU (each) max < = P80
Possible to remove P140 and under P140, but the
capacity should be multiplied by a correction factor 0.97 IU: Indoor unit
BC controller
MEES17K069 Il-2 42
Warning
■ Do not use refrigerant other than the type indicated in the manuals provided with the unit and on the nameplate.
- Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, repair, or at the time of disposal of the unit.
- It may also be in violation of applicable laws.
- MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong
type of refrigerant.
■ Our airconditioning equipment and heat pumps contain a fluorinated greenhouse gas, R410A.