Xeku
Xeku
User Manual
Table 1
Model & Spec. XJ3-2 XJ3-G, XJ3-5
Protection functions Phase loss, phase sequence protection Phase loss, phase sequence protection,
three-phase voltage imbalance 7%~10%
Sampling mode Voltage sampling Voltage sampling
Protective contact One set of normally open contacts, one One set of normally open contacts, one set of
set of normally closed contacts normally closed contacts
Contact capacity AC 220V 3A (resistive) AC 220V 3A (resistive)
Operating voltage Three-phase voltage (50/60Hz) 380V Three-phase voltage (50/60Hz) 380V,
unbalance less than 7%
- 1 -
III. Technical Features
3.1 Rated insulation voltage Ui: AC380V
3.2 Rated impulse withstand voltage UimP: AC1.5kV
3.3 Rated operating voltage Ue / Rated operating current Ie under the usage category:
AC-15 Ue/Ie: AC380V/0.95A;
AC240V / 1.5A; AC120V / 3A
3.4 Resistive current Ith: 5A
3.5 Rated operating voltage: AC380V three-phase
3.6 Pollution level: 3
3.7 Three-phase imbalance: 7%~10%;
3.8 Mechanical life: ≥1 million times
3.9 Electrical life: ≥100,000 times
3.10 Cooperation with the short circuit protective device (SCPD): The RT16-00, 6A fuse with “1” type basic
protection is recommended as SCPD; that is, the relay shall not cause danger to the persons or equipment in case
of short circuit, and it is not allowed to work continuously before the repair or replacement of parts. If the fuse
protective device of the different model is selected, the original cooperation may fail.
Relay
Operating voltage
three-phase 380V
Standard:
GB/T14048.5
- 2 -
Unit: (mm)
Relay
Operating voltage
three-phase 380V
Standard:
GB/T14048.5
V. Wiring Diagram
Stop
Start
Electric signal
Note: If the start motor cannot run please check whether the AC contactor contact works normally or conduct the
inspection according to the requirements of item 7; do not start the machine forcibly for a long time.
KM: AC contactor, with coil voltage AC380V
- 3 -
VII. Precautions
7.1 If the motor cannot start when the XJ3 relay is installed in the original control circuit according to the
drawing,, this indicates that the identification of the phase sequence of the XJ3 relay is valid, at this time,
exchange any two wires of the power input pins 1, 2 and 3 to start the machine normally, indicating that the phase
sequence has been identified. In the later operation, the XJ3 relay will work to provide protection as long as any
phase of the power supply is changed.
7.2 Shockproof and moisture-proof measures shall be taken for relays during transport.
7.3 The relay is fixed to the base with a buckle. Before pulling out the relay body, first open the buckle, and then
slowly pull out the relay.
7.4 The equipment that may cause major economic losses or personal safety is designed to make the technical
characteristics and performance values have sufficient allowance, and safety measures such as double circuit
protection should be taken.
X. Ordering Notice
Please specify the model and specification of the product when ordering. For Any special requirement. please
contact the manufacturer.
- 4 -
(1) Improper operation. maintenance. or storage;
(2) Modified without permission or improper repair;
(3) Damage due to falling off or caused during installation after purchase;
(4) Force majeure such as earthquakes. fires. lightning strikes. abnormal voltages. and secondary disasters;
(5) The electrical life of the product exceeds 100.000 times; The mechanical life is more than one million times.
If you have any question. please contact the dealer or our company’s customer service department.
Customer Service Hotline: 400-826-8008
Name: Relay
Model: XJ3
www.delixi-electric.com
The second edition of this User Manual was issued in Aug. 2021.