Damper Resistor For LV Motor
Damper Resistor For LV Motor
Damper Resistor For LV Motor
SUPPLY FREQUENCY (f ) = 50 Hz
P Amps
MOTOR LOAD CURRENT I = (√3* V *Cos ϴ)
page 1 of 14 715897856.xls
Acceleration time calculation
This calculates the time that the motor will take to accelerate from one speed to another specified speed (typically calculated in 10% increments of motor full load speed).
The total acceleration time (from standstill to full load speed) is the sum of all incremental speed steps.
Soft starters can limit start current to any desired level. However, the minimum level of start current for a successful
start depends on the motor and load.
To start successfully, the motor must produce more acceleration torque than the load requires, throughout the start.
Reducing the start current also reduces the torque produced by the motor. The start current can only be lowered
to the point where the torque output remains just greater than the load torque requirement.
The likely start current can be estimated from experience, but more precise predictions require analysis of motor
and load speed/torque curves
page 2 of 14 715897856.xls
MOTOR
MOTOR
CURRENT
TORQUE as MOTOR CURRENT MOTOR MOTOR
MOTOR TORQUE as MOTOR as in % of ACCELERATION
MOTOR SPEED as in in % of rated as in % of rated Motor LOAD LOAD ACCELERATNG ACCELERATION
S. NO in % of rated Motor LOAD rated TIME FOR
% of rated Speed Motor FLT for FLC for 3.5 x FLC soft CURRE CURRE TORQUE TIME FOR DOL
FLT for DOL starter TORQUE Motor FLC SOFT STARTER
3.5 x FLTsoft starter NT IN % NT IN %
for DOL
starter
starter
1 0% 240.00% 80.00% 17.00% 700.00% 380.00% 0.00% 47.60% 63.00% 0.35 1.04
2 15% 230.00% 76.67% 5.00% 670.00% 360.00% 0.00% 14.00% 71.67% 0.36 1.09
3 30% 230.00% 76.67% 15.00% 620.00% 340.00% 0.00% 42.00% 61.67% 0.36 1.09
4 45% 230.00% 76.67% 20.00% 580.00% 320.00% 0.00% 56.00% 56.67% 0.36 1.09
Q= P (tanϴ1-tanϴ2)
ƞ
where,
Q = CAPACITY OF CAPACITOR BANK POWER (kVAr)
P= RATED POWER OF MOTOR (kW)
ƞ = motor efficiency
ϴ2= PHASE ANGLE FOR MOTOR POWER FACTOR
ϴ2= PHASE ANGLE FOR TARGET POWER FACTOR
page 3 of 14 715897856.xls
page 4 of 14 715897856.xls
page 5 of 14 715897856.xls
page 6 of 14 715897856.xls
page 7 of 14 715897856.xls
OUTPUT CHARACTRICS WAVEFORM OF SOFTSTARTER
800.00%
CURRENT IN % FLC & TORQUE IN %FLT
700.00% 700.00%
670.00%
STAND STILL POINT
MOTOR TORQUE as in % of rated
620.00% Motor FLT for DOL starter
600.00%
MOTOR TORQUE as in % of rated
580.00% Motor FLT for 3.5 x FLTsoft starter
Linear (Column E)
420.00%
400.00% MOTOR LOAD TORQUE
380.00%
360.00% Linear (MOTOR LOAD TORQUE)
340.00%
MOTOR CURRENT as in % of rated
320.00% Motor FLC for DOL starter
300.00% 300.00% 300.00%
280.00% MOTOR CURRENT as in % of rated
Motor FLC for 3.5 x FLC soft starter
260.00%
240.00% 240.00%
230.00% 230.00% 230.00% 230.00%
200.00% 200.00%
100.00% 100.00%
93.33%
86.67% 90.00%
80.00% 76.67% 76.67% 76.67% 76.67% 80.00%
65.00%
50.00%
35.00%
17.00% 15.00% 20.00%
0.00% 5.00% 0.00%
0% 20% 40% 60% SPEED IN %
80% 100% 120% 140%
The reproduction,transmission or use of this document or its contents is not permitted without express written authority Offenders will
be liable for damages.All rights,includingrights created by patent grant or registration of a utility model or design,a
Consultant : Item No :
PR No. : W.O. No :
Date 30.04.09
Description : 66kV SWITCHYARD
Prep. JSD
Doc.No :
page 9 of 14 715897856.xls
page 10 of 14 715897856.xls
PROJECT: VADODARA LIGHTING FACTORY EXPANSION DOCUMENT NO DATE
30.04.09
DESIGNED CHECKED SHEET
TITLE: 66/11 KV BUS FAULT LEVEL CALCULATION JSD SO 1 of 2
INPUT DATA
UP STREAM FAULT LEVEL = 1600 MVA (As Per Customer given data)
66kV DOG CONDUCTOR RESISTANCE = 0.272 Ω/Km (As Per Conductor data sheet)
page 11 of 14 715897856.xls
= 2.723 Ω
GMD
EQUIVALENT SPACING FOR 3PH LINES (D) = √Dry*Dyb*Dbr
3
Dry = √52+22
= 5.385
Dyb = √5.22+22
= 5.571
Dbr = √0.22+42
= 4.005
EQUIVALENT SPACING FOR 3PH LINES (D) = (5.385*5.571*4.005)^1/3
GMD = 4.935 m
= 4934.62 mm
page 12 of 14 715897856.xls
PROJECT: VADODARA LIGHTING FACTORY EXPANSION DOCUMENT NO DATE
30.04.09
DESIGNED CHECKED SHEET
TITLE: 66/11 KV BUS FAULT LEVEL CALCULATION JSD SO 1 of 2
= 7.5*(10/8)
= 9.375 %
= (2.384*100*10)/(66*66)
= 0.547 %
= (100*10)/1600
= 0.625 %
= 94.811 MVA
= MVA/(√3 X KV)
= 94.811/(1.732*11)
page 13 of 14 715897856.xls
= 4.976 kA
page 14 of 14 715897856.xls