POLYCAB INDIA LIMITED


(formerly known as Polycab Wires Limited and Polycab Wires Private Limited)

ROUTINE TEST REPORT


Sample Received On : 2022/06/01
Test Report No : 61245577 Report Date : 2022/06/01
Discipline : Electrical Testing Group : Cables & Wires
Customer : PARADISE ELECTRICAL INDUSTRIES Reference Standard : IS 7098 PART-1/88-1100V
Customer Address : #3815 BABUWALI GALI,MORIGATE,,CENTRAL Test Method : As per Reference Standard
DELHI,DELHI,DELHI,110006 Sample Condition : Good New Cable
Item Code : LVIS09AXSFY23.5C150SA002S
INFORMATION PROVIDED BY CUSTOMER:
PO Number : 1000401710 PO Date : 29-JUL-22
Size : 3.5CX150 SQ MM SO Number : 22232063699
Voltage Grade : 1100V Type : A2XFY
Description : POLYCAB MAKE 1100 V STRANDED SECTOR SHAPED (CLASS 2) ALUMINIUM CONDUCTOR, XLPE INSULATED,
INSULATED CORES LAYING FOR LAID UP, WRAP TAPE I/SH, SINGLE LAYER GALVANISED STEEL FLAT STRIP
ARMOURED AND EXTR UDED ST2 PVC OUTER SHEATHED LV POWERCABLE AS PER IS 7098 PART 1
SR No Drum Nos. Cond Job Lot Core Colour High Voltage
Resistance at Quantity Test
20 Deg C (MTR) at 3 kv For 5
ohm/km(Max) Minute
M=0.206/N=0.4
43
1 2227AFG-109398 0.431 510 BLACK Ok

0.194 510 BLUE Ok


0.199 510 Ok RED
0.195 510 Ok YELLOW

Remarks: Outer Sheath With Anti Termite and Anti Rodent Properties
Note :
1. The cable under test confirms the requirements of reference standard with amendments & data sheet.
2. Test results relates only to item(s) tested &listed in report.
3. Any corrections/ensures invalidates this test report.
4. Any discrepancy in this report should be brought to our notice within 15 days from the date of issue.
5. Report shall not be reproduced except in full without approval of the laboratory.
*END OF REPORT*

Imran Bokda Gaurav Trivedi Tejash Suthar


Prepared By Reviewed By Authorized Signatory

Format No: PCTL/PIL/F/7.8.1 Rev No : 01 Revision Date: 04.06.2021 Issued No : 03 Issue Date: 24.08.2020