TEST CERTIFICATE
Report No.: ASTRAL/D-Rex/ 904909A Date: 22.12.2023
200 mm (DN/ID) Double Wall Corrugated (DWC) DRex
Description of Product
HDPE pipes with RR property.
Invoice No. 1/23/Dec/325 861370343782
Name of Buyer KESHRI PIPE & FITTINGS
Quantity 276.00 (Mtrs)
Standard referred IS 16098 (Part 2): 2013
Designation DN/ID Series & SN 8

Cl. No./ Table No. of Results/


Sr. No. Test Particulars Requirement
IS 16098 Part 2 Remarks

Material Characteristics
I.
of Pipes (PE)
Cl. No. 5.1
i) Base Density ≥ 0.930 g/cc Conforms
and (Table 1)
Melt Flow Rate Cl. No. 5.1
ii) ≤ 1.6 g/10 min. Conforms
0
(at 190 C and 5 Kg Mass) and (Table 1)
DN/ID dim min
Cl. No.6.3
II. Dimensions of Pipes 200 195 Conforms
and Table 5
mm mm
The length of pipe shall not be less
III. Lengths of Pipes Cl. No. 6.3.1 than that specified by the Conforms
manufacturer.
e4 min e5 min
Minimum Wall Thickness Cl. No.6.3
IV. 1.5 1.1 Conforms
of Pipes and Table 5
mm mm

The structured outer layer of


finished pipes shall be uniformly
corrugated. The inner layer shall be
smooth and plain. Both layers shall
be free from any visual defects such
V. Visual Appearance CL. No.7.1 as cracks. Blisters, foreign Conforms
inclusions and any other visual
irregularities which may cause
harm to its construction integrities.
The inner surface may reflect slight
shallow undulation.

Resistance to Heating, The pipe shall show no


VI. Table 6 Conforms
Oven Test (At 110 °C) delamination, cracks or bubbles.

F-01:QAP-8.6-KP-01-A Rev. No. 00 Rev. Date: 01.10.2021


≥8
VII. Ring Stiffness Table 10 Conforms
KN/m2
No shattering or any crack or no
split on inside surface of the test
piece. & TIR ≤ 10 %
Impact Strength
VIII. Table 10 Conforms
at 0°C Mass of D90 Fall Height of
Striker (Kg) Striker (mm)
1.6 2000

1. There shall be no decrease of


measure force.
2. There shall be no cracking in any
part of wall structure.
3. There shall be no wall de-
lamination except possible de-
lamination between the outside and
inside wall of double-wall pipes
occurring in reduced welding zone
Ring Flexibility
IX. Table 10 in the ends of the test piece. Conforms
(At 30 percent of dem)
Process aiding profile of material
other than the pipe material is not
subjected to this requirement.
4. There shall be no other types of
rupture in the test piece.
5. Permanent buckling in any part
of the structure of the pipe wall
including depression and craters
shall not Occur in any direction.

Tested By,

(ASTRAL LIMITED)

F-01:QAP-8.6-KP-01-A Rev. No. 00 Rev. Date: 01.10.2021