Test report

Supervisor:

Operator: Shobin

Note:

Signature
Type Serial no.

Test report

General data

Project data
Project name
Execution date
Report ID
Report issue date
Company information
Company name
Address
Country
Department
Station name
Contact
City
Phone number
Fax number
E-mail
Environment conditions
Temperature
Humidity
Pressure
Transformer data
Serial number 22JC205080002
Test object bar code
Manufacturer ABB
Rated power 750 kVA
Rated current 39 A
Rated voltage 11 kV
Connection
OLTC type

Test lab Date Test engineer Page 2 of 3


Type Serial no.

Turns ratio 1

Sequential 3~

HV/LV
Date and Time 12/23/2023 5:31:00 AM
Vector Group Dyn1
Test Voltage 40 V

Turns ratio
Tap Turns Turns Turns Ratio Ratio Ratio
Name plate
Positio Min Max ratio ratio ratio deviation deviation deviation Pass/Fail
ratio
n phase A phase B phase C phase A phase B phase C
11550 /
1_ - - 48.074 48.072 48.071 -0.03 % -0.04 % -0.04 % Pass
416
11275 /
2_ - - 46.94 46.939 46.937 -0.01 % -0.01 % -0.02 % Pass
416
11000 /
3_ - - 45.806 45.805 45.803 0.01 % 0.01 % 0.01 % Pass
416
10725 /
4_ - - 44.672 44.671 44.669 0.04 % 0.04 % 0.03 % Pass
416
10450 /
5_ - - 43.538 43.536 43.535 0.07 % 0.06 % 0.06 % Pass
416

Excitation current [mA]


Phase Phase Phase
Tap Position Min Max Pass/Fail Min Max Pass/Fail Min Max Pass/Fail
A B C

1_ - - 1.669 - - - 1.2032 - - - 1.2989 -

2_ - - 1.7552 - - - 1.248 - - - 1.3559 -

3_ - - 1.8294 - - - 1.2962 - - - 1.3964 -

4_ - - 1.9003 - - - 1.3488 - - - 1.4534 -

5_ - - 1.9854 - - - 1.3948 - - - 1.5093 -

Phase angle [°]


Tap Position Min Max Phase A Phase B Phase C Pass/Fail

1_ - - -0.05 -0.05 -0.04 -

2_ - - -0.04 -0.04 -0.04 -

3_ - - -0.04 -0.04 -0.04 -

4_ - - -0.04 -0.04 -0.04 -

5_ - - -0.04 -0.04 -0.04 -

Test lab Date Test engineer Page 3 of 3