Voltage PCOB-36
Switchgear Outdoor Vacuum Circuit Breaker

Whether for medium voltage distribution networks or industrial


applications, if you’re looking for outdoor circuit breakers
PM 104398

from a name you can trust, look to Schneider Electric and


the PCOB-36. Backed by decades of experience, and with
over 100,000 circuit breakers in operation all round the world,
Schneider Electric is the recognised market leader in the field
of medium voltage switchgear.

Over 30 years experience in the field


First manufactured in the 1980’s, Schneider’s Porcelain Clad
Outdoor Breaker (PCOB) quickly gained acceptance amongst
network designers, public utilities and private industries world-
wide. The PCOB-36 circuit breaker incorporates a minimum
of moving parts, ensuring a high degree of reliability – the
mechanism has undergone exhaustive mechanical, laboratory
and field-endurance testing.

Applications
PCOB-36 is particularly suitable where a reliable power supply is needed
in distribution networks such as:
• Short-circuit protection
• Transformer switching
• Cable switching
Benefits • Over head line switching
• Capacitor bank Switching
• Simple to install and to operate • Load transfer and auto reclosing

• Robust construction Reliability Installation


The low energy requirements and To ensure safe transportation and
• Reliable conception makes it for unique design of the vacuum facilitate installation, the PCOB-36
interrupters make the PCOB-36 is despatched to customers with
long time of service extremely reliable in service. the mounting structure packed
separately to the Circuit Breaker
• Up-to-date vacuum interrupters Quality assembly & operating mechanism.
technology As an option arrangement for
Rigorous quality and service
Current Transformer / Power
standards are maintained
Transformer mounting support
• Maintenance reduced at the throughout the production
process, structure if needed.
minimum
Increased creepage and strength
are provided by the high quality Low maintenance
operating rod. Minimal maintenance requirements
and proven long service life deliver
Out of phase Duty reduced lifecycle costs.
The PCOB-36 is suitable for out-of
phase duty. Environment
The PCOB-36 is designed to
be suitable for heavily polluted
Moisture resistance environments,
Double lip sealing gaskets
The PCOB-36 has been designed
significantly reduce the possibility
in order to be environment-friendly
of moisture ingress.
it does not contain toxic materials.

NRJED315626EN - PCOB 36 - 21-01-2015 V8.indd 1 19/02/2015 13:35:44


Medium
Voltage PCOB-36
Switchgear Outdoor Vacuum Circuit Breaker

Features Pole Assembly

PM 104399
The inclusion of high-performance, robust vacuum interrupters make Top Terminal
the unit suitable for all switching duties in medium voltage electrical
distribution networks. Capable of interrupting over 100 full short-circuit
operations, and more than 30,000 close-open operations at normal load Porcelain Insulator
current, the PCOB-36 is a field-proven solution with broad international
industry acceptance. Vacuum Interrupter

Bottom Terminal

Construction
• Vacuum Interrupters are housed inside hollow porcelain insulators
• Three single-phase assemblies are mounted on a common base frame Insulating Rod
that also supports a mechanical drive linkage
• The main drive rod is actuated by the drive mechanism, rotating the
bell crank which actuates the insulated drive rod assembly and closes
the breaker
• Each vacuum interrupter is connected to a top terminal plate which is
fixed to the porcelain insulator

Reliable operating mechanism Operating mechanism


The robust and reliable PCOB-36 operating mechanism offers the
PM 104400

following features:
• Motor-driven, spring charged
• Automatically charged after each closing operation
• O-C-O operation without recharging
• Mechanical / electrical anti-pumping
• Provision for manual charging
• Manual closing and tripping arrangement
• Mechanical ON-OFF, operation counter and spring-charged indication

NRJED315626EN - PCOB 36 - 21-01-2015 V8.indd 2 19/02/2015 13:35:45


Medium
Voltage PCOB-36
Switchgear Outdoor Vacuum Circuit Breaker

Operating conditions
Ambient conditions in accordance with Standards IEC 62271-1/ IEC 62271-100
Temperature class ≤ 40°C
Minimum / Maximum ambient temperature -10°C/ *55°C degree °C
Average value over 24 hours 35 degree °C
Average relative humidity: 24 hours / 1 month ≤ 95% / ≤ 90%
Installation altitude above sea-level ≤ **1000 m

* De rating of rated continuous current applicable at 55°C


** Please contact Schneider electric

Technical characteristics
Rated Voltage 36 kV
Rated power frequency withstand voltage 70 kV
Rated lightning impulse withstand voltage 170 kV peak
Rated frequency 50 Hz
Rated short time withstand current 25 kA - 3 s
Rated peak withstand current 62 kA peak
Rated continuous current 1250 A / 2000 A
Degree of protection IP55
Standards IEC-62271-100/IS-13118
Operating sequence O-0.3s-CO-3min-CO
Weight (Breaker/HDG structure) 320 Kg / 60 Kg (Aprox.)
Pole Material Porcelain
PM 104401

NRJED315626EN - PCOB 36 - 21-01-2015 V8.indd 3 19/02/2015 13:35:45


Medium
Voltage PCOB-36
Switchgear Outdoor Vacuum Circuit Breaker
Installation
SM 100749

AL Top terminal 1686


700 700

Top insulator
AL bottom
terminal

Bottom insulator

Lifting huck 463


Earth pad

Operating handle for


Arrangement manual charging
for pad lock
3895
3408

Operating height
1497
Operation platform

1871

548

Plinth Plinth

545
300

Ground level

1350

Leg
M16 x 500 «J» Bolt 4-Ø14 Holes
150

Plinth level
300 Plinth
ground level

Grouting material
895

containing M20 or
100
40

above grade concrete


sand & cement mixture
30

Section on «A-A»
4-Ø18 Holes for
© Schneider Electric Industries SAS - All rights reserved

foundation fixing with


M16 «J» foundation bolts 40 30
545 150

Foundation plan Detail of terminal

Schneider Electric Industries SAS As the standards, specifications and designs change from time to time, please ask for
35, rue Joseph Monier confirmation of the information given in this publication.
CS30323
F - 92505 Rueil-Malmaison cedex (France) This document has been printed
on ecological paper
RCS Nanterre 954 503 439
Share capital: €896,313,776 Conception: Schneider Electric Industries SAS
www.schneider-electric.com Photos: Schneider Electric Industries SAS
Printing: Altavia
NRJED315626EN 01/2015

NRJED315626EN - PCOB 36 - 21-01-2015 V8.indd 4 19/02/2015 13:35:46