DC Inverter 5 Toneladas
DC Inverter 5 Toneladas
Light Commercial
Trouble Shooting
Contents
I. Outdoor unit error code
II. Troubleshooting
III. Indoor unit error code
IV. Troubleshooting
E3 Reserved
E5 reserved
E7 Reserved
E8 Reserved
H1 Reserved
Repower on to clear
H4 There are 3 times P6 protection in 30 minutes.
the error code.
Repower on to clear
H5 There are 3 times P2 protection in 30 minutes.
the error code.
Repower on to clear
H6 There are 3 times P4 protection in 100 minutes.
the error code.
H7 Reserved
H8 Reserved
Repower on to clear
H9 There are 2 times P9 protection in 10 minutes.
the error code.
Repower on to clear
H10 There are 3 times P3 protection in 60 minutes.
the error code.
P12 >
T3 24℃ more than 5 min in heating mode
L3 Reserved
No
No
Correct
direction?
Check chip in the outdoor Yes Reinstall or
Well touch?
PCB replace the chip
Any pin broken?
No
OK
1. Check the outdoor unit phase sequence and the power supply phase
sequence are the same.
No
Communication
wiring
Solutions: If there is open circuit in the wire group, replace the wire group; if
there is open circuit in the terminal block, then replace the terminal block;
otherwise go to next step.
OK
25 5
35 3.5 Check chip or
outdoor PCB
OK
OK
There is Air or N2
in the system
OK
Solutions: If heat exchanger is too dirty or something blocks it, then clear the
dirty or blocking things; otherwise go to next step.
,
1 Low-voltage protection
When the voltage is below 172V will display low voltage
fault
,
2 High-voltage protection
When the AC voltage ≥ 265V and lasted 30 seconds, the
machine shut down and alarm;
When the AC voltage ≤ 256V and lasted 30 seconds, recover
:
Note Voltage detection accuracy ±3%.
E9:AC high voltage protection
,
1 Power input
Check whether the voltage between A-N is higher than 265V
Please contact the electric sector if voltage is high
If all voltages above is normal, you need to replace main control board.
E9:AC low voltage protection
,
1 Power input
Check whether the voltage between A-N is higher than 172V
Please contact the electric sector if voltage is low
If all voltages above is normal, you need to replace main control board.
Troubleshooting
It will display this error when the EEPROM parameters is not right.
Troubleshooting
:
H0 Communication malfunction between DSP and 0513
Solution: If the resistance measured OL, replace the wire group; if displayed
0Ω, go to the next step
CHIGO New Generation DC Inverter VRF System
Troubleshooting
:
H0 Communication malfunction between inverter module and chip 0513
Solutions: If the power light is ON, replace the main control board or inverter
module board; If the power light is off, go to the next step
Solutions: If the plug contact bad, re-connect; otherwise go to the next step.
Solutions: If the voltage is 300V, replace the inverter module board; if the
measured voltage is 0V, replace the power filter board.
7. If the fault is still the same after doing above steps, replace the
main control board.
Charge additional refrigerant Lack refrigerant Error Repair the leakage &
correctly? Refrigerant leakage? Charge refrigerant;
OK
Gas pipe is blocked?
Gas valve is not opened
High temp. of discharge and Check gas side of system Error Remove the dirty;
suction, low operation current, Open the valve
low pressure is low?
OK
Check
pressure
switch or
PCB
CHIGO New Generation DC Inverter VRF System
Troubleshooting
H5, P2: Low-pressure Protection
4. Pull out the low pressure switch and measure its resistance (normal
0)
Check sensor,
chip or outdoor
PCB CHIGO New Generation DC Inverter VRF System
Troubleshooting
H6, P4: High discharge temperature
Resistance
decrease
when
temperatu
re
increase
Error
Use this module in another Module is broken Replace the module
outdoor unit to check
OK
There is Air or N2
in the system
OK
Short circuit of strong
power part? Too much refrigerant in the
system
Compressor malfunction? OK
The normal resistance between Error Replace the compressor
Compressor or strong
any two terminals of compressor or other damaged part.
power part is abnormal
is 1~3Ω
OK
low temp. of discharge, low Too many refrigerant in the Error Discharge some
pressure and high pressure is system refrigerant from system
high? Big current?
OK
Check sensor,
chip or PCB
Solutions: If heat exchanger is too dirty or something blocks it, then clear the
dirty or blocking things; otherwise go to next step.
2. Pull out the high pressure switch and measure its resistance (normal
0)
:
P10 Typhoon protection
:
P11 T2 high temperature protection in cooling mode
:
Note Under normal condition, T3 outdoor pipe temperature in the
heating mode will not higher than 24 degrees for a long time, maybe
the temperature sensor is not accurate or is measure ambient
temperature.
Troubleshooting
Display H4,outdoor
unit H4, P6: Inverter module protection
Must Repeat power on.
Compressor malfunction?
OK
Check chip
or PCB
L3 reserved
P6.
Check the compressor
L4 And direction of DC current
wire
L8/L9
Change the chip or change
the compressor
CHIGO New Generation DC Inverter VRF System
Troubleshooting
L0: Inverter compressor malfunction
、
3 Over heat protection (auto-recover): Lights flash 5 times every 3s.
Check if the module heat sink is cooled properly, check if the thermal
silicone on module is coated evenly.
Solution: If voltage is not 220V, then replace the main control board,
otherwise go to next step.
CHIGO New Generation DC Inverter VRF System
Troubleshooting
L1: DC generatrix low voltage protection
Solution: If not 0V, then replace the contactor, otherwise replace the
inverter module board.
CHIGO New Generation DC Inverter VRF System
Troubleshooting
L2: DC generatrix high voltage protection
Indoor coil outlet temp. Check the connection port Well connected the
Error
sensor T2B between sensor and PCB is sensor and PCB
loosed or not?
No
Check IU
chip or PCB
Replace IU
chip or PCB
EE: Water level alarm error
2. Pull of the connector, and use one short circuit wire instead, if the error
disappear, replace the water level switch, otherwise replace the PCB
E7: EEPROM error
NO
Component damaged?
Check PCB Error Replace the PCB
Wet?
wrong selection of refrigerant pipe, indoor EXV or
branch joint, the refrigerant distribution among the
indoor units is quite imbalance;
OK
Indoor EXV jammed?
Indoor fan doesn’t run?
Check low pressure Error Clean the indoor unit; Fix
Filter or coil of indoor unit is the broken part
too dirty?
OK
When the indoor units are Error Resume the power for
running, if power failure Check Power supply of
indoor units these indoor units
happen, the indoor EXV will
keep open.
OK