Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 7

Transformer inrush 4

When does exciting current inrush occur in power transformer?

Exciting current inrush

When a transformer is initially energized, there is a phenomenon known as exciting current


inrush. Although inrush currents are not generally as damaging as fault currents, the duration
of exciting current inrush is on the order of seconds (as compared to on the order of cycles with
fault currents).

When does exciting current inrush occur in power transformer? (on photo: Two 220kV power
transformers at Bahawalpur and Burhan; credit: ntdc.com.pk)

Exciting current inrush conditions also occur much more frequently than short circuits, so this
phenomenon is worth exploring.

Consider what happens when initially energizing a single phase transformer. Flux in the core is
equal to the integral of the excitation voltage.
If the circuit is closed when the voltage is passing through zero and the initial flux is zero, the
sinusoidal flux will be fully offset from zero. The full-offset flux has a peak value that is twice the
peak value of a symmetrical sinusoidal flux.

In other words, the peak flux for a fully offset wave can approach two times the normal peak
flux, and this is generally sufficient to drive the core into saturation.

At this point, the only thing that limits exciting current is the air-core impedance of the
winding, which is several orders of magnitude smaller than the normal magnetizing impedance.

Therefore, the exciting current is much greater than the normal exciting current during the half
cycle when the core is saturated. During the opposite half cycle, the core is no longer saturated
and the exciting current is approximately equal to the normal exciting current.

This is illustrated in Figure 1.


Figure 1 – Exciting
inrush current for a core having no residual flux

The situation is even more extreme when there is residual flux in the core and the direction of
the residual flux is in the same direction as the offset in the sinusoidal flux wave. This is
illustrated in Figure 2 below.

Note that Figure 1 and 2 are drawn on current different scales, so the peak current plotted in
Figure 2 is actually much larger than the peak current plotted in Figure 1.
Figure 2 – Exciting
inrush current for a core having a residual flux

Let’s find the peak inrush current

To find the peak inrush current, limited only by the air-core reactance, it is convenient to
calculate the inductance of the winding using cgs units:
where:

 N – number of turns in the coil

 Amt – area inside the mean diameter of the coil, cm2

 l – axial length of the coil, cm

 L – inductance of the coil, μH

The flux generated by the inductance φL is equal to the residual flux plus 2 times the normal
flux change minus the saturation flux, since the saturation flux is in the iron. But φL is related to
the inductance and the current:

Therefore, the peak inrush current is expressed in the cgs system of units as follows:

where:

 Ipeak is in amps and

 φr – residual flux

 φn – normal flux change

 φs – saturation flux

Without resistance in the circuit, each successive peak would have the same value and the
current inrush would go on indefinitely. With resistance in the circuit, however, there is a
significant voltage drop across the resistance and the flux does not have to rise quite as high as
the previous cycle.
The integral of the voltage drop represents a net decrease in the flux required to support the
applied voltage. Since the i × R voltage drop is always in the same direction, each cycle
decreases the amount of flux required. When the peak value of flux falls below the saturation
value of the core, the inrush current disappears. The rate of decay is not exponential although it
resembles an exponentially decaying current.

IMPORTANT! For large power transformers, the inrush current can persist for several seconds
before it finally dies off.

The line reactance has the effect of reducing the peak inrush current by simply adding
inductance to the air-core inductance of the winding. There is a definite relationship between
inrush current and short circuit current because both are related to the air-core inductance of
the windings.

Remember that short circuits tend to exclude flux from the core.

RULE OF THUMB! Typically, a rule of thumb is that peak inrush currents are a little over 90% of
peak short circuit currents. The magnetic forces caused by inrush currents are generally much
smaller than short circuit forces, however. Because only one winding per phase is involved,
there is no magnetic repulsion between windings.

The whole problem of analyzing exciting current inrush gets much more difficult when 3-phase
transformers are involved. This is because the phase angles of the exciting voltages are 120°
apart, there are interactions of currents and voltages between phases, and the three poles of
the switching device do not close at exactly the same time.

Nevertheless, it is safe to say that the peak magnitude of inrush current for three-phase
transformers approaches the short circuit current levels.

One of the interesting features of exciting current inrush is that since the current is fully offset,
there are large percentages of even harmonics present. Even harmonics are otherwise rarely
encountered in power circuits.

Sympathetic inrush

There is also a phenomenon known as sympathetic inrush, where a transformer that is


previously energized will exhibit a sudden change in current when a nearby transformer is
switched on. Sympathetic inrush is caused by changes in line voltages from the inrush currents
of the second transformer.

You might also like