R911335488
Rexroth Inline Block IO for Edition 02
Output Features
• Four universal analog signal outputs for the con-
nection of either voltage or current signals
• Connection of actuators in 2 and 3-wire technol-
ogy
• Four current ranges:
±10 mA, 0 mA to 20 mA, 4 mA to 20 mA, ±20 mA
• Two voltage ranges:
0 V to 10 V, ±10 V
• Resolution 16 bits (15 bits + sign bit)
• Short-circuit-proof outputs
• Parameterizable output values when the bus fails
SSI Interface Features
All standard absolute encoders with SSI interface can
be connected with the following properties:
• Four SSI interfaces
• 8 to 31 bits (configurable)
• Gray code, binary code
• No, even or odd parity monitoring
• Transmission speeds: 67.5 kHz, 100 kHz,
150 kHz, 200 kHz, 250 kHz, 300 kHz, 400 kHz,
500 kHz, 600 kHz, 700 kHz, 800 kHz, 900 kHz,
1 MHz, 2 MHz, 4 MHz
• Encoder resolution: 8 bits ... 31 bits
• Evaluation of waiting cycles (clock-pulse space,
sub-clock)
• Activation/deactivation of SSI interface
• Parameterizable offset
• Parameterizable substitute value in the event of
an error (e.g., open circuit)
Table of Contents
1 Description ............................................................................................................... 1
2 Ordering Data ........................................................................................................... 4
3 Technical Data ......................................................................................................... 5
4 Internal Basic Circuit Diagram ............................................................................. 12
5 Electrical Isolation ................................................................................................. 13
6 Relevant Notes ....................................................................................................... 13
7 Local Diagnostics and Status Indicators ............................................................ 14
8 Connecting SERCOS III, Supply,
Analog Sensors, and Actuators ........................................................................... 15
8.1 Connecting SERCOS III....................................................................................................................15
8.2 Connecting the Supply, Actuators, and Sensors ..............................................................................16
12 SERCOS III.............................................................................................................. 22
12.1 SERCOS III Profiles, Classes and
Function Groups ...............................................................................................................................22
12.2 Electronic Rating Plate .....................................................................................................................22
12.3 Configuration Via the Service Channel .............................................................................................23
12.4 Process Data ....................................................................................................................................26
12.5 Diagnostics.......................................................................................................................................31
12.6 SERCOS Address ............................................................................................................................34
12.7 Password (IDN/S-0-0267) ................................................................................................................34
13 Timing Diagram...................................................................................................... 35
14 SERCOS III Parameters ......................................................................................... 36
15 Reconfiguration Button......................................................................................... 41
15.1 Restart of the Module .......................................................................................................................41
15.2 Restoring the Default Settings ..........................................................................................................41
4/42 Bosch Rexroth AG | Electric Drives R-ILB S3 AI12 AO4 SSI-IN4 | Data Sheet
and Controls
2 Ordering Data
Products
Description Type MNR Pcs. / Pkt.
Rexroth Inline Block IO for SERCOS III with 12 analog inputs R-ILB S3 AI12 AO4 SSI-IN4 R911171949 1
and 4 analog outputs and 4 SSI interfaces
Accessories: Ethernet
Description Type MNR Pcs. / Pkt.
Ethernet cable, 10BASE-T, CAT.5, RKB0007/00,15 R911170146 0.15 m
crosslink, assembled with RJ45 connectors at both ends
Ethernet cable, 10BASE-T, CAT.5, RKB0007/002,5 R911170147 2.50 m
crosslink, assembled with RJ45 connectors at both ends
Ethernet cable, 10BASE-T, CAT.5, RKB0007/005,0 R911170148 5.00 m
crosslink, assembled with RJ45 connectors at both ends
Ethernet cable, 10BASE-T, CAT.5, RKB0007/010,0 R911170149 10.00 m
crosslink, assembled with RJ45 connectors at both ends
Ethernet cable, 10BASE-T, CAT.5, RKB0007/025,0 R911170150 25.00 m
crosslink, assembled with RJ45 connectors at both ends
Ethernet cable, 10BASE-T, CAT.5, RKB0008/002,5 R911170151 2.50 m
assembled with RJ45 connectors at both ends
Ethernet cable, 10BASE-T, CAT.5, RKB0008/005,0 R911170152 5.00 m
assembled with RJ45 connectors at both ends
Ethernet cable, 10BASE-T, CAT.5, RKB0008/010,0 R911170153 10.00 m
assembled with RJ45 connectors at both ends
Ethernet cable, 10BASE-T, CAT.5, RKB0008/025,0 R911170154 25.00 m
assembled with RJ45 connectors at both ends
Accessories: Other
Description Type MNR Pcs. / Pkt.
End clamp for securing the Inline station on the DIN rail for a SUP-M01-ENDHALTER R911170685 2
horizontal mounting position; to the right and left of the sta-
tion
End clamp for securing the Inline station on the DIN rail for a SUP-M01-ENDHALTER/AL R911171035 2
vertical mounting position; above and below the station
Documentation
Description Type MNR Pcs. / Pkt.
“Automation terminals of the Rexroth Inline product range” DOK-CONTRL- R911317021 1
application description ILSYSINS***-AW..-EN-P
“SERCOS III system manual” application description DOK-CONTRL-ILS3*******- R911333512 1
AP01-EN-P
For additional ordering data (accessories), please refer to the product catalog at
www.boschrexroth.com.
Data Sheet | R-ILB S3 AI12 AO4 SSI-IN4 Electric Drives | Bosch Rexroth AG 5/42
and Controls
3 Technical Data
Housing dimensions
156 59
120
141
Fig. 1 Module housing dimensions (in mm)
Housing dimensions with connectors (width x height x depth) 156 mm x 141 mm x 59 mm (with connectors)
General data
Weight 505 g (with connectors)
Operating mode SERCOS III process data mode
Transmission speed 100 Mbps
Connection method for sensors 2- and 3-wire technology (shielded)
Connection method for actuators 2-wire technology (shielded)
Connection data for Inline connectors
Connection method Spring-cage terminal blocks
Conductor cross section 0.08 mm2 ... 1.5 mm2 (solid or stranded), 28 - 16 AWG
Ambient conditions
Regulations Developed according to VDE 0160 / EN 50178 / IEC 62103,
UL 508
Ambient temperature (operation) -25°C ... +60°C
Ambient temperature (storage/transport) -25°C ... +85°C
Humidity (operation/storage/transport) 10% ... 95%, EN 61131-2
Air pressure (operation/storage/transport) 70 kPa to 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Air and creepage distances According to DIN VDE 0110/IEC 60664, IEC 60664A,
DIN VDE 0160/EN 50178/IEC 62103
Housing material Plastic, PVC-free, PBT, self-extinguishing (V0)
Pollution degree according to 2; condensation not permitted during operation
EN 60664-1/IEC 60664-1, EN 61131-2/IEC 61131-2
Surge voltage class II
6/42 Bosch Rexroth AG | Electric Drives R-ILB S3 AI12 AO4 SSI-IN4 | Data Sheet
and Controls
Mechanical requirements
Vibration test sinusoidal vibrations according to 5g load, 2.5 hours in each space direction
EN 60068-2-6/IEC 60068-2-6
Shock test according to EN 60068-2-27/IEC 60068-2-27 30g load for 11 ms, half sinusoidal wave,
three shocks in each space direction and orientation
Broadband noise according to EN 60068-2-64/IEC 60068-2- 0.78g load, 2.5 hours in each space direction
64
Interface
SERCOS III interface 2 x SERCOS III via RJ45 connector;
Shielding via parallel connection of R, C, and VDR
Data Sheet | R-ILB S3 AI12 AO4 SSI-IN4 Electric Drives | Bosch Rexroth AG 7/42
and Controls
Current consumption at US
No-load operation SSI without encoder and encoder supply 38 mA 40 mA
SSI with 4 encoders MBaud without encoder supply 70 mA 80 mA
SSI with 4 encoders MBaud with encoder supply (4 x 200 mA) 890 mA 900 mA
Total current consumption at UL and US
No-load operation of outputs and AI mode 220 mA 240 mA
AO U nominal load/SSI nominal load (UOUT = 10 V with RL = 2 k); 278 mA 305 mA
4 x SSI encoder 1 MBaud without encoder supply
AO I nominal load/SSI nominal load (IOUT = 20 mA with RL = 0 k); 325 mA 350 mA
4 x SSI encoder 1 MBaud without encoder supply
AO I nominal load/SSI nominal load (IOUT = 20 mA with RL = 0 k); 1125 mA 1150 mA
4 x SSI encoder 1 MBaud with encoder supply (4 x 200 mA)
8/42 Bosch Rexroth AG | Electric Drives R-ILB S3 AI12 AO4 SSI-IN4 | Data Sheet
and Controls
Analog inputs
Number 12 differential analog inputs
Measured value resolution 16 bits (15 bits + sign bit)
Measured value representation IB IL (15 bits with sign bit)
Input filter 10 kHz HW filter, mean-value generation via software filter
with adjustable number of values per software
Conversion time 75 µs
Cut-off frequency (-3 dB) of the input filters 10 kHz
Transient protection Yes, via arresters
Connection method of signals 2 and 3-wire connection; shielded,
twisted pair cable
Overload protection Yes, ±30 V DC, minimum
Voltage mode
Input range 0 V to 10 V; ± 10 V
Input resistance ≥ 260 k
Open circuit response Goes to 0 V
Maximum permissible voltage between analog voltage in- ± 30 V DC
puts and analog ground (UCM)
Current mode
Input range ± 10 mA; 0 to 20 mA; 4 mA to 20 mA; ± 20 mA
Input resistance 240
Open circuit response Goes to 0 mA
Maximum permissible current per current input Electronic overload protection
Overload protection at the analog current inputs Yes, ±30 V DC, minimum
Analog outputs
Number 4
Voltage output range 0 V to 10 V, ± 10 V
Current output range 0 mA to 20 mA, ± 20 mA, 4 mA to 20 mA
Measured value resolution 16 bits (15 bits + sign bit)
Measured value representation IB IL (15 bits with sign bit)
Conversion time 75 µs
Resolution 16 bits
Output load
Voltage output RLmin = 2 k
Current output RLB = 0 to 500
Transient protection Yes, internally via arresters
Connection method of signals 2-wire termination; shielded, twisted pair cable
Short-circuit protection
Voltage output Yes, permanent electronic short-circuit protection
Current output Yes, permanent electronic short-circuit protection
Enabling function Yes, internal electronic
Optical indicators 5% output LED, channel-specific
Data Sheet | R-ILB S3 AI12 AO4 SSI-IN4 Electric Drives | Bosch Rexroth AG 9/42
and Controls
The ambient conditions and the local conditions in the system can result in special requirements
for the installation of cables. These must be taken into consideration accordingly.
For the integration of shielded I/O cables in an equipotential bonding concept for the automation
system, the following applies in principle:
Shielded analog I/O cables may only be connected directly to functional earth ground potential
at a single point.This results in the prevention of voltage equalization currents via the analog ca-
ble. Additional information is available on request.
Tolerances at TA = 25°C
AI measuring range Absolute (typical) Absolute (maximum) Relative (typical) Relative (maximum)
0 V to 10 V, ±10V ±20 mV ±30 mV 0.2% ±0.3%
±10 mA, ±40 µA ±60 µA 0.2% ±0.3%
0 mA to 20 mA
4 mA to 20 mA
±20 mA
AO output range Absolute (typical) Absolute (maximum) Relative (typical) Relative (maximum)
0 V to 10 V, ±10V ±10 mV ±15 mV 0.1% ±0.2%
±10 mA, ±20 µA ±40 µA 0.1% ±0.2%
0 mA to 20 mA
4 mA to 20 mA
±20 mA
The data contains the offset error, gain error, and linearity error. All percentage values refer to
the relevant positive measuring range final value. Unless stated otherwise, the values refer to
nominal operation (nominal voltage US = UL = 24 V, preferred horizontal mounting position, "IB
IL" format, default filter setting, the same measuring range setting for the channels, etc.).
Please also take into consideration the values for temperature drift and the tolerances influenced
by electromagnetic interference. The maximum tolerance values represent the worst-case mea-
surement inaccuracy. They contain the theoretically maximum possible tolerances in the corre-
sponding measuring ranges. In the same way, the theoretical maximum possible tolerances of
the calibration and test equipment have been taken into account.
The drift values refer to the relevant measuring range final value.
The data refers to nominal operation with horizontal installation on DIN rail.
Additional tolerances may occur due to the influence of high-frequency electromagnetic interfer-
ence caused by wireless transmission systems in the near vicinity. The specified values refer to
nominal operation. The components are directly exposed to interference without the use of ad-
ditional shielding measures (e.g., steel cabinet).
The tolerances specified above can be reduced through additional shielding for the I/O module
(e.g., use of a shielded control box/control cabinet, etc.). Please observe the measures recom-
mended in the Rexroth Inline system manual for your bus system.
SSI interface
Absolute encoder inputs
Number 4
Encoder signal Clock, clock inverted (according to RS-422)
Data, data inverted (according to RS-422)
The corresponding red Ex LED (x = 1 to 4) lights up when the encoder cable is broken.
Unshielded cables may lead to erroneous results in environments subject to heavy noise.
Encoder
Resolution 8 to 31 bits
Encoding Gray code, binary code (configurable)
Parity monitoring None, even, odd (configurable)
Transmission frequency 67.5 kHz, 100 kHz, 125 kHz, 200 kHz, 250 kHz, 100 kHz,
300 kHz, 400 kHz, 500 kHz, 600 kHz, 700 kHz, 800 kHz, 900
kHz, 1 MHz, 2 MHz, 4 MHz (configurable)
Encoder supply
Nominal voltage 24 V DC
Voltage range 19.2 V DC ... 30.0 V DC
Current carrying capacity 200 mA, maximum
Short-circuit protection Thermic (self-healing)
The corresponding red Ex LED (x = 1 to 4) lights up when the 24 V encoder supply is overloaded
or short-circuited.
Cable length < 30 m for shielded cable (to ensure conformance with EMC
directive 89/336/EEC)
Approvals
For the latest approvals, please visit www.boschrexroth.com.
12/42 Bosch Rexroth AG | Electric Drives R-ILB S3 AI12 AO4 SSI-IN4 | Data Sheet
and Controls
SPI SPI
SSI SSI
SPI SPI
ADC
# DAC
#
MUX
FPGA 9
AI ...
4x 4x
1,2 V ±5 V
2,5 V ±15 V
3,3 V
24 V 24 V
U/I U/I U/I U/I U/I
+24 V
+5 V
US
UL
GNDUL GNDUS
FE
Amplifier
Optocoupler
Electronic fuse
FPGA FPGA (field programmable array)
5 Electrical Isolation
Logic area
UL (3.3 V DC / 2.5 V DC /
1.2 V DC)
(24 V DC)
FPGA, Switch
Analog I/O
Analog inputs (4 x 3)
...
(5 V DC / +-15 V DC)
DAC, ADC, ... Analog outputs (1 x 4)
...
Supply of the SSI channels (4 x 1)
US Initiator supply UIS
initiator supply US UIS1
(24 V DC) SSI interface (24 V DC) UIS2
(24 V DC) UIS3
UIS4
FE potential 8013B003
6 Relevant Notes
Shielding
Shielding ground of the connected
twisted pair cables is electrically con-
nected to FE. When connecting net-
work segments, avoid ground loops,
potential transfers, and voltage equal-
ization currents via the braided shield.
Electrostatic discharge
The module contains components that
can be damaged or destroyed by elec-
trostatic discharge. When handling the
module, observe the necessary safety
precautions against electrostatic dis-
charge (ESD) according to
EN 61340-5-1 and IEC 61340-5-1.
Housing
Only personnel authorized by Bosch
Rexroth are permitted to open the
housing.
14/42 Bosch Rexroth AG | Electric Drives R-ILB S3 AI12 AO4 SSI-IN4 | Data Sheet
and Controls
S3 LNK1 SF E1 E2 E3 E4 1
ACT1 US 2
LNK2 UL 3
ACT2 4
PWR SSI1 SSI2 SSI3 SSI4 AI1-3 AI4-6 AI7-9 AI10-12 AO1-4
RJ45
Pin 8
Pin 7
Pin 6
Pin 5
Pin 4
Pin 3
Pin 2
Pin 1
1 2
3 4
1-4
AO
-12
AI10
AI7-9
E4 AI4-6
E3 AI1-3
E2 SS
I4
E1 SS
I3
SF US
I2
SS
K1
UL
I1
LN CT1 SS
A
S3
LN
K2
A CT2
PW
R RECONF
X7E1
X7E2
AI10 ... 12
AO1 ... 4
AI1 ... 3
AI4 ... 6
AI7 ... 9
PWR
SSI1
SSI2
SSI3
SSI4
1 2 3 4 5 6 7 8 9 10
RECONF
US US T /T T /T T /T T /T UI1+UI1- UI4+UI4- UI7+UI7- UI10+UI10- U1 AGND
PWR X7E1 UL UL D /D D /D D /D D /D UI2+UI2- UI5+UI5- UI8+UI8- UI11+ UI11- U2 AGND SSI, AI, AO
1 2 GND GND24VGND 24VGND 24VGND 24VGND UI3+UI3- UI6+UI6- UI9+UI9- UI12+UI12- U3 AGND 1 2
UL US
1.1 1 1
2.1 1.1 1 1
2.1
FE U4 AGND
9 Connection Notes
The module has an FE spring (metal Always connect the analog sensors,
clip) on the bottom of the electronics actuators, as well as SSI encoders, us-
base. This spring establishes an electri- ing shielded, twisted-pair cables.
cal connection to the DIN rail. Use The conductor cross section of these
grounding terminals to connect the DIN cables must be 0.25 mm².
rail to protective earth ground. The Connect the shielding to the module us-
module is grounded when it is snapped ing the shield connection clamp. The
onto the DIN rail. clamp connects the shield to FE on the
To ensure reliable functional earth module side. Avoid connection to FE
grounding of the module even when from both sides.
the DIN rail is dirty or the metal clip This shield connection clamp does not
is damaged, always ground the exist for the connector for the analog
module additionally via the FE ter- outputs AO (connector 10), therefore
minal point. connect the shield of the analog outputs
externally.
AI 10 ... 12
AO 1 ... 4
AI 1 ... 3
AI 4 ... 6
AI 7 ... 9
Power supply Sensor
SSI 1
SSI 2
SSI 3
SSI 4
PWR
24 V DC
AI + - + - SI
1 2 3 4 5 6 7 8 9 10 1 2
U/I+ U/I-
U/I+ U/I-
U/I+ U/I-
U Sensor
Power supply
-
OUT2
SERCOS III - 24 V DC
+
UL US AI + - + SI
U/I+ U/I-
U/I+ U/I-
Voltage measurement
-
+
OUT2
General actuator
Fig. 10 Current measurement 4 mA ... 20 mA, 2-wire
connection method
(SI = current signal)
1 2
U/I+ U/I-
U/I+ U/I-
U/I+ U/I-
10.2 Connection Example for the SSI Interfaces 11 Configuration Using a Configuration
Software
The module can be configured in two ways:
• Configuration with a configuration software, e.g.,
Rexroth IndraWorks, in connection with the as-
sociated SDDML file.
This way is described in the following.
• Configuration via the service channel
See “Configuration Via the Service Channel” on
page 23.
If you use a configuration software, the values for con-
figuration will be displayed on the interface.
Configurable are:
Fig. 12 Typical connection with 24 V encoder supply • SSI interfaces
• Analog outputs and inputs
Absolute encoder The values in bold are default settings.
20/42 Bosch Rexroth AG | Electric Drives R-ILB S3 AI12 AO4 SSI-IN4 | Data Sheet
and Controls
Analog Inputs
Since three analog inputs have been assigned to
every structure instance, the configuration bytes for
the three inputs must be specified one after the other.
For configuration one byte for "Measuring range" and
one byte for "Filter" is required for every input. This re-
sults in six configuration bytes for every function group
instance.
S-0-1505.1.20 Byte
(Connector 6) 0 1 2 3 4 5
AI 1 measuring AI 2 measuring AI 3 measuring AI1 filter AI2 filter AI3 filter
range range range
S-0-1505.2.20 Byte
(Connector 7) 0 1 2 3 4 5
AI 4 measuring AI 5 measuring AI 6 measuring AI4 filter AI5 filter AI6 filter
range range range
S-0-1505.3.20 Byte
(Connector 8) 0 1 2 3 4 5
AI 7 measuring AI 8 measuring AI 9 measuring AI7 filter AI8 filter AI9 filter
range range range
S-0-1505.4.20 Byte
(Connector 9) 0 1 2 3 4 5
AI 10 measur- AI 11 measur- AI 12 measur- AI10 filter AI11 filter AI12 filter
ing range ing range ing range
Bit Value Description Remark I/O Control Word (IO control, IDN/S-0-1500.0.1)
1 New data New producer data Bit Value Description Remark
Toggle • Initial value of the bit is 0 15 Outputs
in CP4
0 Outputs inactive Substitute values en-
• This bit must be abled
switched when changes
1 Outputs enabled
occur.
14-0 Reserved
• New data is generated in
the connection each Output Data
time this bit is switched (Container OutputData, IDN/S-0-1500.0.5)
and the data between
connection and applica- Container OutputData assignment
tion is exchanged. That IDN Length (in
means that the expected bytes)
value for this bit in the
consumer must also be PDOUT AO1 S-0-1504.1.5 2
switched for the next PDOUT AO2 S-0-1504.2.5 2
communication cycle PDOUT AO3 S-0-1504.3.5 2
when the data of a cer-
PDOUT AO4 S-0-1504.4.5 2
tain producer cycle have
not been received.
• For a cycle synchroniza-
tion connection, this bit
should always be
switched in the associ-
ated SERCOS cycle.
• This bit causes a moni-
toring for an asynchro-
nous connection. After
this bit has been
switched, for example,
the monitoring always
starts with the monitoring
time (tPcyc)
• This bit should be
switched once for every
transmission time (tPcyc),
after the producer readi-
ness (bit 0) was set to
the value 1.
0 Producer
readiness
0 Not ready The producer does not gen-
erate data in this connec-
tion.
1 Ready The producer generates
data in this connection. The
recipient can process the
connection data when the
producer has switched the
new data (bit 1). The pro-
ducer readiness bit should
only be evaluated in CP4.
28/42 Bosch Rexroth AG | Electric Drives R-ILB S3 AI12 AO4 SSI-IN4 | Data Sheet
and Controls
Output Data
Significant values for output voltage and output cur-
rent can be taken from the following table:
Input Data
Significant values for input voltage and input current
can be taken from the following table:
12.5 Diagnostics
Analog Outputs (IDN/S-0-1504.SI.17)
SI has a value from 1 to 4, depending on the analog
output at connector 10.
The diagnostics IDN for an analog output is 16 bits
wide. The meaning of the individual bits is shown in
the following table:
Input 3
1 Above voltage/current
Bit Des. Description Meaning range
0 Voltage monitoring 0 -15 V OK 14 Open circuit 0 Input OK
of the negative 15 V 1 -15 V below permissi- (no open circuit)
supply ble level 1 An open circuit was
1 Voltage monitoring 0 -5 V OK detected at the input
Input 1, 2, 3
1 Above voltage/current
range 3 Parity 0 Check OK
error 1 Check not OK
6 Open circuit 0 Input OK
(no open circuit) 4 Initiator Power status 0 PTC fuse has not
1 An open circuit was supply feedback for the blown
detected at the input initiator supply of 1 PTC fuse has blown
(current <3.2 mA) the correspond-
ing channel.
7 Reserved
5 Logic Power status 0 Power supply OK
8 Underrange 0 Voltage/current value voltage feedback for the 1 Power supply failed
OK error input and output
1 Below voltage/current drivers of the
range corresponding
9 Overrange 0 Voltage/current value channel.
OK 6 Global Group message 0 Power OK
Input 2
13 Timing Diagram
IDN Name Function Unit Default values Min. value Max. value Scaling
S-0-0014 Interface status Parameter – – – – 1
S-0-0017 IDN-list of all opera- Parameter – – – – 1
tion data
S-0-0021 IDN-list of invalid Parameter – – – – 1
operation data for
CP2
S-0-0022 IDN-list of invalid Parameter – – – – 1
operation data for
CP3
S-0-0025 IDN-list of all proce- Parameter – – – – 1
dure commands
S-0-0095 Diagnostic message Parameter – – – – 1
S-0-0099 Reset class 1 diag- Process – – – – 1
nostic command
S-0-0127 CP3 transition Process – – – – 1
check command
S-0-0128 CP4 transition Process – – – – 1
check command
S-0-0187 IDN-list of configu- Parameter – – – – 1
rable data in the AT
S-0-0188 IDN-list of configu- Parameter – – – – 1
rable data in the
MDT
S-0-0192 IDN-list of all backup Parameter – – – – 1
operation data
S-0-0264 Backup working Parameter – – – – 1
memory procedure
command
S-0-0265 Language selection Parameter 1 – – – 1
S-0-0266 List of available lan- Parameter – – – – 1
guages
S-0-0267 Password Parameter – PW71949 – – 1
S-0-0279 List of password Parameter 1 – – – 1
protected data
S-0-0390 Diagnostic number Parameter – – – – 1
S-0-1000 SCP type & version Parameter – 0x0201 – – 1
0x0301
0x0401
0x0501
0x0A01
S-0-1002 Communication Parameter µs – 250 000 65 000 000 0.001µs
cycle time (tScyc)
S-0-1003 Allowed MST losses Parameter – – – – 1
in CP3/CP4
S-0-1005 Minimum feedback Parameter µs 90 000 – – 0.001µs
processing time (t5)
S-0-1006 AT0 transmission Parameter µs – 0 65 000 000 0.001µs
starting time (t1)
S-0-1007 Feedback acquisi- Parameter µs – 0 2000 000 0.001µs
tion capture point
(t4)
S-0-1008 Command value Parameter µs – 0 2000 000 0.001µs
valid time (t3)
Data Sheet | R-ILB S3 AI12 AO4 SSI-IN4 Electric Drives | Bosch Rexroth AG 37/42
and Controls
IDN Name Function Unit Default values Min. value Max. value Scaling
S-0-1009 Device control (C- Parameter – – – – 1
Dev) offset in MDT
S-0-1010 Lengths of MDTs Parameter – – 0 – 1
S-0-1011 Device status (S- Parameter – – – – 1
Dev) offset in AT
S-0-1012 Lengths of ATs Parameter – – 0 – 1
S-0-1013 SVC offset in MDT Parameter – – – – 1
S-0-1014 SVC offset in AT Parameter – – – – 1
S-0-1015 Ring delay Parameter µs – – 1 048 575 0.001µs
S-0-1016 Slave delay (P/S) Parameter µs – – – 1
S-0-1017 NRT transmission Parameter µs – – – 1
time
S-0-1019 MAC address Parameter – 00-60-34-xx-xx- – – 1
xx
S-0-1020 IP Address Parameter – 149.208.18.209 – – 1
S-0-1021 Subnet mask Parameter – 255.2550.0 – – 1
S-0-1022 Gateway address Parameter – 0.0.0.0 – – 1
S-0-1023 SYNC jitter Parameter µs – – – 1
S-0-1024 SYNC delay mea- Parameter – – – – 1
suring procedure
command
S-0-1026 Version of commu- Parameter – – – – 1
nication hardware
S-0-1027.0.1 Requested MTU Parameter – – 46 1500 1
S-0-1027.0.2 Effective MTU Parameter – – 46 1500 1
S-0-1028 Error counter MST Parameter – – – – 1
P/S
S-0-1031 Signal assignment Parameter – – – – 1
port 1 & port 2
S-0-1035 Error counter port 1 Parameter – – – – 1
& port 2
S-0-1040 SERCOS address Parameter µs 1 0 511 1
S-0-1041 AT command value Parameter µs – 0 65 000 000 0.001µs
valid time (t9)
S-0-1044 Device control Parameter – – – – 1
(C-Dev)
S-0-1045 Device status Parameter – – – – 1
(S-Dev)
S-0-1050.x.1 Configuration of the Parameter – – – – 1
connection
S-0-1050.x.2 Connection number Parameter – – 0 65 535 1
S-0-1050.x.3 Telegram assign- Parameter – – 0 0x3DD4 1
ment
S-0-1050.x.4 Max. length of con- Parameter – – 2 1484 1
nection
S-0-1050.x.5 Actual length of con- Parameter – – – – 1
nection
S-0-1050.x.6 Configuration list Parameter – – – – 1
S-0-1050.x.8 Connection control Parameter – – – – 1
(C-Con)
S-0-1050.x.10 Producer cycle time Parameter µs – 250 000 65 000 000 0.001µs
S-0-1050.x.11 Allowed data losses Parameter – – 1 65 535 1
S-0-1050.x.12 Error counter data Parameter – – – – 1
losses
S-0-1051.0.0 Image of connection Parameter – – – – 1
setups
38/42 Bosch Rexroth AG | Electric Drives R-ILB S3 AI12 AO4 SSI-IN4 | Data Sheet
and Controls
IDN Name Function Unit Default values Min. value Max. value Scaling
S-0-1300.0.1 Component name Parameter – SERCOS 3 – – 1
block 4 axis I/O
module
S-0-1300.0.2 Vendor name Parameter – Bosch Rexroth – – 1
S-0-1300.0.3 Vendor code Parameter – 100 – – 1
S-0-1300.0.4 Device name Parameter – R-ILB S3 AI12 – – 1
AO4 SSI-IN4
S-0-1300.0.5 Device ID Parameter – R911171949 – – 1
S-0-1300.0.6 Connected to sub- Parameter – – 0 511 1
device
S-0-1300.0.7 Function revision Parameter – – 0 9999 1
S-0-1300.0.8 Hardware revision Parameter – – – – 1
S-0-1300.0.9 Software revision Parameter – – – – 1
S-0-1300.0.10 Firmware loader Parameter – – – – 1
revision
S-0-1300.0.11 Order number Parameter – R911171949 – – 1
S-0-1300.0.12 Serial number Parameter – 171949-xxxxx – – 1
S-0-1300.0.13 Manufacturing date Parameter – – – – 1
S-0-1300.0.14 QS date Parameter – – – – 1
S-0-1300.0.20 Operational hours Parameter h – 0 – 1h
S-0-1300.0.21 Service date Parameter – – – – 1
S-0-1300.0.22 Calibration date Parameter – – – – 1
S-0-1300.0.23 Calibration due date Parameter – – – – 1
S-0-1300.0.128 FPGA register Parameter – – – – 1
BORAR-ID
S-0-1300.0.129 FPGA register Parameter – – – – 1
SYSID-ID
S-0-1300.0.130 FPGA register Parameter – – – – 1
SYSID time stamp
S-0-1300.0.131 Configuration data- Parameter – – – – 1
set identification
S-0-1300.0.132 Firmware checksum Parameter – – – – 1
S-0-1300.0.133 Firmware filename Parameter – – – – 1
S-0-1300.0.134 INI block content Parameter – – – – 1
S-0-1300.0.135 Slave communica- Parameter – – – – 1
tion stack
S-0-1300.0.136 Application build Parameter – – – – 1
info
S-0-1301.0.0 List of GDP classes Parameter – 0x0101 – – 1
& version
S-0-1302.0.1 FSP type & version Parameter – 0x00010001 – – 1
S-0-1302.0.2 Function groups Parameter – S-0-1500.0.0 – – 1
S-0-1504.1.0
S-0-1505.1.0
S-0-1515.1.0
S-0-1504.2.0
S-0-1505.2.0
S-0-1515.2.0
S-0-1504.3.0
S-0-1505.3.0
S-0-1515.3.0
S-0-1504.4.0
S-0-1505.4.0
S-0-1515.4.0
S-0-1302.0.3 Application type Parameter – Axis – – 1
S-0-1303.0.1 Diagnostic trace Parameter – – – – 1
configuration
Data Sheet | R-ILB S3 AI12 AO4 SSI-IN4 Electric Drives | Bosch Rexroth AG 39/42
and Controls
IDN Name Function Unit Default values Min. value Max. value Scaling
S-0-1303.0.2 Diagnostic trace Parameter – – – – 1
control
S-0-1303.0.3 Diagnostic trace Parameter – – – – 1
state
S-0-1303.0.10 Diagnosis trace Parameter – – – – 1
buffer no1
S-0-1303.0.11 Diagnosis trace Parameter – – – – 1
buffer no2
S-0-1303.0.12 Diagnosis trace Parameter – – – – 1
buffer no3
S-0-1305.0.1 SERCOS current Parameter – – – – 1
time
S-0-1500.0.1 IO control Parameter – – – – 1
S-0-1500.0.2 IO status Parameter – – – – 1
S-0-1500.0.3 Module type code Parameter – 0x424C000000 – – 1
000110
0x424C000000
000111
0x424C000000
000112
0x424C000000
000113
0x424C000000
000114
S-0-1500.0.5 Container output Parameter – – – – 1
data
S-0-1500.0.9 Container input data Parameter – – – – 1
S-0-1500.0.19 Parameter channel
receive
S-0-1500.0.20 Parameter channel Parameter – – – – 1
transmit
S-0-1500.0.32 IO diagnostic mes- Parameter – – – – 1
sage
S-0-1500.0.33 Current IO diagnos- Parameter – – – – 1
tic message
S-0-1504.x.1 Name of IO_FG Parameter – – – – 1
S-0-1504.x.2 Configuration of Parameter – – – – 1
IO_FG
S-0-1504.x.3 Channel quantity Parameter – 1 – – 1
PDOUT
S-0-1504.x.4 Channel size Parameter – 16 – – 1
PDOUT
S-0-1504.x.5 PDOUT Parameter – – – – 1
S-0-1504.x.15 Channel quantity DI- Parameter – 1 – – 1
AGIN
S-0-1504.x.16 Channel size Parameter – 16 – – 1
DIAGIN
S-0-1504.x.17 DIAGIN Parameter – – – – 1
S-0-1504.x.19 Parameter channel Parameter – – – – 1
receive
S-0-1504.x.20 Parameter channel Parameter – – – – 1
transmit
S-0-1504.x.22 Fallback value out- Parameter – – – – 1
put
S-0-1504.x.23 Min. delay time Parameter NS – – – 1 ns
S-0-1504.x.24 Max. delay time Parameter NS – – – 1 ns
S-0-1505.x.1 Name of IO_FG Parameter – – – – 1
40/42 Bosch Rexroth AG | Electric Drives R-ILB S3 AI12 AO4 SSI-IN4 | Data Sheet
and Controls
IDN Name Function Unit Default values Min. value Max. value Scaling
S-0-1505.x.2 Configuration of Parameter – – – – 1
IO_FG
S-0-1505.x.7 Channel quantity Parameter – 3 – – 1
PDIN
S-0-1505.x.8 Channel size PDIN Parameter – 16 – – 1
S-0-1505.x.9 PDIN Parameter – – – – 1
S-0-1505.x.15 Channel quantity DI- Parameter – 1 – – 1
AGIN
S-0-1505.x.16 Channel size Parameter – 16 – – 1
DIAGIN
S-0-1505.x.17 DIAGIN Parameter – – – – 1
S-0-1505.x.19 Parameter channel Parameter – – – – 1
receive
S-0-1505.x.20 Parameter channel Parameter – – – – 1
transmit
S-0-1505.x.23 Min. delay time Parameter NS – – – 1 ns
S-0-1505.x.24 Max.delay time Parameter NS – – – 1 ns
S-0-1515.x.1 Name of IO_FG Parameter – – – – 1
S-0-1515.x.2 Configuration of Parameter – – – – 1
IO_FG
S-0-1515.x.7 Channel quantity Parameter – 1 – – 1
PDIN
S-0-1515.x.8 Channel size PDIN Parameter – 32 – – 1
S-0-1515.x.9 PDIN Parameter – – – – 1
S-0-1515.x.15 Channel quantity DI- Parameter – 1 – – 1
AGIN
S-0-1515.x.16 Channel size Parameter – 16 – – 1
DIAGIN
S-0-1515.x.17 DIAGIN Parameter – – – – 1
S-0-1515.x.19 Parameter channel Parameter – – – – 1
receive
S-0-1515.x.20 Parameter channel Parameter – – – – 1
transmit
S-0-1515.x.128 Offset for SSI input Parameter – 0 – – 1
S-0-1515.x.129 Feedback value in Parameter – – – – 1
error case
Data Sheet | R-ILB S3 AI12 AO4 SSI-IN4 Electric Drives | Bosch Rexroth AG 41/42
and Controls
DOK-CONTRL- Bosch Rexroth AG All rights reserved. No part of this document may be reproduced or stored,
S3AI*AO*SSI-DA02-EN-P Electric Drives and Controls processed, duplicated, or circulated using electronic systems, in any form or
Postfach 13 57 by any means, without the prior written authorization of Bosch Rexroth AG,
97803 Lohr, Deutschland Electric Drives and Controls. Violations shall give rise to claims for damages.
Bgm.-Dr.-Nebel-Str. 2
The data specified above only serve to describe the product. They do not in-
97816 Lohr, Deutschland
Tel. +49 9352 18 0 dicate any specific condition or suitability for a certain application. It must be
Fax +49 9352 18 400 remembered that our products are subject to natural wear and ageing.
8013_en_01
www.boschrexroth.com/electrics