Professional Documents
Culture Documents
IGTE2014 Busductreview Formatted 9aug Finial
IGTE2014 Busductreview Formatted 9aug Finial
IGTE2014 Busductreview Formatted 9aug Finial
*J. Faiz, *H. Ehya, *A. M. Takbash, †S. Shojaee, †M. Hamidian and †A. Ghorbani
*Center of Excellence on Applied Electromagnetic Systems, School of Electrical and Computer Engineering,
College of Engineering, University of Tehran, Tehran, Iran.
†
Generator Engineering and Manufacturing Co. (Pars), Mapna Group, Tehran, Iran
E-mail: Ehya@ut.ac.ir
Abstract— Energy resources management dictates the reduction of losses in electrical equipment from energy generation and
consumption point of views. Generally, it is preferred to distribute electrical energy by bus-ducts in the place of cables over all
energy levels due to the lower losses in bus-ducts. Therefore, it is essential to have a wide knowledge about various aspects of
bus-ducts design including electromagnetic, mechanical and thermal. These are addressed in the present paper and attempt is
made to review the most important papers in the field focusing on advantages and disadvantages of the proposed techniques.
(a)
(b)
Fig. 9. Cross section of proposed bus-duct [11]. Fig. 10. Eddy current losses density versus position in: (a) upper layer
and (b) right side of bus-duct layer [1].
Temperature of the outer bus is only 0.5 degree lower
than that of the middle bus. The reason is that heat Mutual heat impacts of two adjacent buses have been
exchange close to the heat exchange surface is better and examined in [10]. Two bus-duct systems in the output of a
it has lower temperature. Fig. 12 shows the temperature medium voltage and very high current generator can have
profile along y-axis for different types of insulations with mutual impacts on the heat exchange. In addition,
different heat conduction. In Fig. 12, k is the heat transfer magnetic field due to a bus-duct can have negative
coefficient. As expected using insulations with higher impacts on the efficiency of adjacent bus-duct. The first
heat conduction results in lower temperature of bus. In step in such analysis is examining the current distribution
addition, there is a good agreement between the test and in the conductors and inspecting the impacts of the
predicted results. conductors‟ current on the bus-duct enclosure [9].
Heat exchange in air-isolated high current bus-ducts
TABLE 2. DIMENSIONS, PROPERTIES AND HEAT TRANSFER COEFFICIENTS has been considered in [13] in which coupling of a 2D
OF MODELED BUS-DUCT [1].
magnetic model has been utilized using two ANSYS-
Dimensions
Bus-bars size (mm) 6×280
Emag and ANSYS-FLOTRAN softwares. In addition, three
Insulation thickness (mm) 0.25 types of three-phase bus-ducts consisting of insulated
Steel thickness (mm) 1.50 three-phase bus-duct, no segregated three-phase bus-duct
Current rating (A) 3000 and segregated three-phase bus-duct have been
Impedance at 60 Hz (μΩm-1) 16.7+j6.45 investigated.
Properties Fig. 13 shows a schematic insulated three-phase bus-
Thermal Electrical Electrical
conductivity conductivity permeability duct. Simulations and tests have been carried out at rated
(W ᵒC-1 m-1) (Sm-1) (μr) current of 8.4 kA, frequency 50 Hz and environment
Bus-bar 386 5.8×107 1 temperature of 16 °C. Fig. 14 shows the thermal analysis
Insulation 0.15 0 1 of the insulated three-phase bus-duct. As shown in Fig. 14
Bottom surface 16.286 1.03×107 200 in such bus-duct systems, mutual impacts between phases
Side surface 0.52 0 1
Heat Transfer coefficients
from electromagnetic and thermal point of views are
Heat transfer coefficients (Wm-2ᵒC-1) minimal because of insulated enclosure. Losses density as
Top surface 3.2363 output of the electromagnetic analysis is the input of
Bottom surface 6.00174 thermal analysis. Fig. 15 shows 2D heat distribution in an
Side surface 4.5003 insulated three-phase bus-duct.
Fig. 13. Schematic of insulated three-phase bus-duct [13].
(a)
(a)
(b)
(b)
Fig. 17. Eddy current in conductor enclosure due to magnetic field due Fig. 18. Current density in cross section of first phase of a bus-duct [8].
to: (a) conductor itself and (b) adjacent conductor [6].
TABLE 5. CURRENT IN DIFFERENT PARTS OF BUS-DUCT AND ITS OHMIC
LOSSES [8].
Value Current (A) Power losses (W/m)
Phase L1 4603.26<-1.3ᵒ 293.23
Phase L2 4604.39<-238.7ᵒ 293.34
Phase L3 4603.45<-118.7ᵒ 292.82
__.Shield 8.62<-22.6 287.97____
Shield part___________________________________
Bottom side 97.92<-32.4ᵒ
Top side 97.92<-32.4ᵒ
Left-most side 1038.38<180.4ᵒ
Right-most side 1120.90<-59.3ᵒ
Left separation partition 989.20<130.9ᵒ
Right separation partition 1009.73<18.8 .
(a)
(a)
(b)
Fig. 20. (a) A bus system and its eddy currents and (b) heat exchange of
system [14].
(a)
(b)
Fig. 22. Two horizontal (a) and vertical (b) structures of buses [17].
T (t ) T1 t
1 e (1)
T2 T1
(a)
(b)
Fig. 29. (a) Magnetic flux lines and (b) flux density in IPB cross section
[16].
Fig. 31. Force exerted on conductors at time of short circuit fault [16].
Fig. 30. Induced eddy current in bus-duct enclosure during short circuit
fault [16] Fig. 32. Electromagnetic force in middle phase conductor at two phase
angles of current [16].
in the middle phase conductor at two phase angles of
current [16]. As shown in Fig. 32, amplitude of the
electromagnetic force varies by variations of the current
phase angle, but these variations has no influence on the
force amplitude. Fig. 33 shows the electromagnetic force
at the time of short circuit fault in the enclosure with two
different materials [22]. As shown in Fig. 33, the
maximum force for two materials is almost the same. In
the steel, this force reaches its peak earlier and damps
quicker and therefore it applies less stress on the supports.
Application of aluminum enclosure makes it possible to
break the circuit by protection devices before the Fig. 33. Electromagnetic force at time of short circuit fault in enclosure
maximum force reaches [16]. Impact of distance between with two different materials [16].
phases on the electromagnetic force due to short circuit TABLE 11. SHORT CIRCUIT CURRENT FOR DIFFERENT CONDUCTORS IN
fault is shown in Fig. 34 [23]. DIFFERENT BUS SYSTEMS [24].
Increasing distance between the phases has influence Ph.no. R1 S1 T1 R2 S2 T2 R3 S3 T3
3 33.1 41 42.5 42.2 43.1 42.4 42 45.3 33.6
on the volume and affects seriously the electromagnetic 3 &N 29.8 40 43 42.3 42.7 42.8 42.2 43.3 41.6
force as such that the force decreases largely, but at the 3& 32.9 39.5 42.6 42.4 42.8 42.6 42.2 44.4 36.9
time fault occurring it has no impact on the maximum PE
3& 33.3 39.2 42.8 42.4 42.6 42.8 42.4 43.2 41.4
force. Effect of the enclosure material on the short circuit N, PE
force has been shown in Fig. 35. As shown in Fig. 35, 2- RS 32.8 36.6 2.8 37.6 36.1 2.8 37.6 35.3 5.6
aluminum alloy having larger resistivity leads to lower 2-RT 25 2.4 37.1 36.7 0.2 37.1 36.7 2.5 24.1
2-ST 35 35 37.8 2.7 35.9 37.9 2.7 36.8 32
amplitude of the electromagnetic force [23]. In [21], a
[8] P. Sarajcev, R. Goic “Power loss computation in high current
generator bus ducts of rectangular cross section” Electric Power
Component and Systems, Vol. 38, pp. 1469-1485, 2010.
[9] A. Canova, L. Giaccone, “ Numerical and analytical modeling of
busbar systems” IEEE Trans. On Power Delivery, Vol. 24, No. 3,
pp. 1568-1578, July 2009.
[10] R T. Coneybeer, W. Z. Black, R. A. Bush, “Steady state and
transient ampacity of bus bar” IEEE Trans. on Power Delivery,
Vol. 9, No. 4, pp. 1822-1829, October 1994.
[11] M. Imamura, M. Nakahara, T. Yamaguchi and S. Tamura, “
Analysis of magnetic fields due to three phase bus bar currents for
the design of an optical current transformer”, IEEE Trans. on
Magnetics, Vol. 34, No. 4, pp. 2274-2279, July 1998.
[12] R. Nageswara Rao, “ Effect of particle size on particle movement
in a single phase gas insulated bus duct”, International Journal of
Fig. 34. Impact of distance between phases on electromagnetic force Engineering Research and Applications”, Vol. 2, No. 3, pp. 544-
due to short circuit fault [23]. 549, May-June 2012.
[13] T. Bachorec, J. Hosek, and M. Saska, ″Heat transfer simulation
and experimental verification of the high-voltage air-insulated bus
ducts″, 2007,ASME DC, United States of America, Jan 2004.
[14] J. K. Kim, S. C. Hahn, K. Y. Park, H. K. Kim and Y. H. Oh, “
Temperature rise prediction on EHV GIS bus bar by coupled
magnetothermal finite element method” IEEE Trans. on
Magnetics, Vol. 41, No. 5, pp. 1636-1639, May 2005.
[15] S. L. Ho, Y. Li, E. W. C. Lo, and X. Lin, ״Analysis of three-
dimensional eddy current field and thermal problems in an
isolated phase bus, ״IEEE Trans. on Magnetics, Vol. 39, No. 3,
pp. 1515-1518, May 2003.
[16] A. H. Isfahani, S. Vaez-Zadeh, A. N. Khodabakhsh, “ Calculation
of maximum short circuit electromagnetic forces in the IPB using
time stepping finite element method” Electrical Review, Vol. 85,
2009.
[17] R. M. Del Vecchio, “ Eddy current losses in a conducting plate
Fig. 35. Effect of enclosure material on short circuit force [23]. due to a collection of bus bars carrying currents of different
magnitudes and phases”, IEEE Trans. on Magnetics, Vol. 39, No.
IV. CONCLUSION 1, pp. 549-552, January 2003.
[18] D. Tasic, “ A procedure for analysis of non stationary heating
This paper reviewed different types of bus-ducts from states of acsr conductors” NIS, Electrics and Energetics, Vol. 13,
used materials, voltage level and insulation types point of No. 1, pp. 83-94, April 2000.
views. Bus-duct modeling methods were proposed and [19] H. Hedia, F. Henrotte, B. Meys, P. Dular, W. Legra, “
Arrangement of phase and heating constraints in a busbar” IEEE
their resultant signals were investigated. Bus-duct design Trans. on Magnetics, Vol. 35, No. 3, pp. 1274-1277, May 1999.
must be based on electromagnetic, thermal and [20] S. Xu, X. Jin, F. Pang, “ Analysis of vibration and acoustic
mechanical considerations and all dominant factors upon radiation characteristics of busbar bridge system under
these analyses were introduced in the paper. electromagnetic force” Electric Power Component and System,
Vol. 35, pp. 1317-1330, 2007.
ACKNOWLEDGEMENTS [21] D. G. Triantafyllidis, P. S. Dokopoulos, D. P. Labridis, “
Parametric short circuit force analysis of three phase bus bars- A
fully automated finite element approach”, IEEE Trans. on Pwer
The authors wish to thank Mapna Company in Iran for Delivery, Vol. 18, No. 2, pp. 531-537, April 2003.
financial support of the bus-duct design project. [22] S. L. Ho, Y. Li, E. W. C. Lo, K. W. E. Cheng and K. F. Wong,
״Calculation of eddy current, fluid and thermal fields in an air
REFERENCES insulated bus-duct system״, IEEE Trans. on Magnetics, Vol. 43,
[1] C. Hwang, J. J. Chang, Y. H. Jiang, “ Analysis of electromagnetic No. 4, pp. 1433-1436, April 2007.
and thermal fields for a bus duct system”, Electric Power System [23] A. Hassanpour, and S. Vaezzadeh, “Transient finite element
Research, Vol. 45, pp. 39-45, 1998. analysis of short circuit electromagnetic forces in isolated phase
[2] Technical note “ Medium and high voltage busway system” buses”, Electromagnetics, Vol. 28, No. 6, pp. 590-600, July 2008.
WETOWN BUSWAY Co. htto://wetownbusway.com [24] M. Chiampi, D. Chiarabaglio, M. Tartaglia, “ A general approach
[3] P. Sarajcev, “Analysis of electromagnetic influences concerning for analyzing power busbar under A.C. conditions” IEEE Trans.
two adjacent parallel high current bus ducts” Electric Power on Magnetics, Vol. 29, No. 6, pp. 2473-2475, September 1993.
Component and Systems, Vol. 40, pp. 829-844, 2012. [25] D. P. Labridis, P. S. Dokopoulos, “ Electromagnetic forces in
[4] A. B. Niemoller, “ Isolated phae bus enclosure currents” IEEE three phase rigid busbars with rectangular cross sections”, IEEE
Trans. on Power Appratus and Systems, Vol. Pas-S7, No. 8, pp. Trans. On Power Delivery, Vol. 11, No. 2, pp. 793- 800 , April
1714-1718, August 1968. 1996.
[5] Techno-commercial bid (Part I), “Technical Specifications for
sandwich bus duct for power conditioning system” Raja Ramanna
Centre for Advanced Technology, Indore (MP).
[6] Z. Piatek, D. Kusiak, T. Szczegielniak, “ Electromagnetic filed
and impedances of high current busducts” Modern electric power
systems210, Wroclaw, Poland.
[7] P. Sarajec, “ Numerical analysis of the magnetic field of high-
current busducts and GIL systems” Energies, Vol. 4, pp. 2196-
2211, 2011.