Professional Documents
Culture Documents
DR M.zaki Voltage Stability
DR M.zaki Voltage Stability
DR M.zaki Voltage Stability
Stability
Index
A Composite 382
Acting, (fast) 275, 290, 304 Concepts 76, 136
Action 162, 422 Consequencies 38
Active 37, 52 Constants 29, 369, 441
Admissible 20 Continuous 137, 422
Admittance 36 Control 38, 180, 264, 275
Affecting 90, 165 Controller, Controlled 269,317,330
Analysis 23, 242, 250 Converter 230, 234
Angle, phase 26, 28 Cooling 138, 422
Applications 125, 173, 213 Correction 38
Arc furnace 379 Criteria, Criterion 106, 128, 407
Assiut 77, 426 Critical 128
Aswan 426 Current 142
Asynchronous 7 D
Available 90, 372 Damping 435, 439
Average 29, 54 Definitions 3, 15, 90
AVR 150, 152, 422 Depression 24, 27
B Decrease of 101, 103
Back e.m.f. 57 Dip, Dips 386
Base 367 Discharge 419
Behavior 51, 393 Distribution 16
Behind 86, 421 Drops 418
Between 100, 232, 336 Dynamic 53, 141, 399
Block-diagram 327 E
Booster 300, 423 E.m.f. 57, 275
C Effect (of, on) 45, 213, 372, 398
Cables 423 Efficiency 12, 18
Capacitor, Capacitive 347 Electromechanical 65
Causes 101, 414 Electronic 91, 104
Changer, Tap 336, 340, 361 Energy 437, 439
Characteristics 16, 127, 142, 386 Entrance 15, 16
Checking 128 Equations 33, 154
Classification 52, 90 Equivalent, Th 35
Closed – Loop 149, 325 Examples 420
Coefficients 68 F
Collapse 424, 425 Factor, (s) 38, 232, 385
Combination 322, 340, 351 Fast 136, 422
Compensation 38 Flicker 356
Compensators 42, 173, 325 Flora 52, 54
Components 184, 227 Fluorescent 51, 52, 75
566 Index
U - rated 15
Unstable, Unstability 322 - scalar 110
UPS 52, 211 - service entrance 15
Using 225, 317, 340 - steady-state 94, 106, 212, 386
Utility 65 - transient 14, 78, 93
Utilization voltage 16 - utilization 16
V W
V-curves Watt component
VAR 136, 173, 325 Wind-mill generators 52
Variable 130, 290, 309 Winding 5
Voltage Wound-rotor
- collapse 91, 309 Y
- definition 15 Y-matrix 35, 110, 113, 126
- depression 24, 27, 32 Z
- drop 414, 419 Zone 18, 426, 439
- flicker 92, 305, 356
- instability (ies) 90, 106
- load line 101
- oscillations 91, 92
- profile 18
- quality 20
- regulation 28, 48
- relations 23, 111
- requirements 304
- security 19
- sensitivity 23, 41, 42
- spread 16, 17
- stability 1, 51, 78
- stability limit 109
- standards 20
- variations 39, 52, 63
- zone 124
- admissible 20
- base 15, 17
- distribution network 16
- limitation of
- load nodes 32, 45, 398
- maximum 43
- minimum 143
- network 16, 26, 90
- nodes 39, 45
- nominal 69, 110, 128
Contents e
Contents
Chapter 1:
Power Systems Stabilities 1
1.1 Power Systems Instabilities Types 1
1.2 Conditions Leading to Voltage Collapses and Voltage 4
Instabilities
1.3 Voltage Instability Time Scales 4
1.4 Transmission System Participation in Voltage Stability 5
1.5 Generator Participation in Voltage Stability 8
1.6 Load Participation in Voltage Stability 10
1.7 Power Systems Blackouts and Failures 11
1.8 Voltage Collapse Preventive Techniques 11
1.9 Voltage Stability Classifications 12
1.10 Voltage Stability Analysis 13
1.11 System Protection Role in Voltage Stability 14
1.12 Power Systems Islanding 14
1.13 Cold Inrush Current 16
1.14 Voltage and Load Stability 18
1.15 Voltage Stability Limit 20
1.16 Voltage Security 20
1.17 Voltage Standards 20
1.18 Admissible Voltage Drops 21
Problems 21
References 22
Chapter 2:
Voltage/Powers Relations of Two Nodes Systems 23
2.1 Importance of Two Nodes Power Systems Analysis 23
2.2 Two Nodes Systems Elements 23
2.3 Complex Voltage Depression Method 24
2.4 Scalar Voltage Depression Iterative Method 27
2.5 Generalized Constants Method 29
2.6 Load Nodes Short-Circuit Power Method 32
2.7 Load-Flow Gauss Iterative Method 33
2.8 Thevenen's Equivalent of Large Power Systems at Certain
Load Nodes 35
2.9 Load Nodes Reactive Power Characteristics 36
2.10 Load Nodes Active Power Characteristics 37
2.11 Load Power Factor Correction and Load Voltage Control 38
2.12 Load Compensation Theory Principles 38
f Contents
Chapter 3:
Load Representation for Voltage Stability Studies 51
3.1 Introduction 51
3.2 Loads Behavior 51
3.3 Load Window 51
3.4 Stiff and Soft Loads 52
3.5 Classification of Load Types 52
3.6 Traditional Load Modeling in Power Systems Studies 52
3.7 Static and Dynamic Loads 53
3.8 Linear and Nonlinear Loads 53
3.9 Load Representation by Powers/Voltage and Frequency
Formula 53
3.10 Load Representation by Characteristic Coefficients
Power/Voltage and Power/Frequency Relations 68
3.11 Loads Representation by Single Termed Polynomials 70
3.12 New Suggested Load Polynomial Models 72
3.13 Load Modeling for Transient Voltage Stability Studies 78
3.14 Conclusions 87
Problems 87
References 88
Chapter 4:
Voltage Instability Phenomena 90
4.1 General 90
4.2 Available Definitions 90
4.3 Classification of Power-Systems Stabilities 90
Contents g
Chapter 5:
Criteria for Detection of Steady State Voltage
Instability 106
5.1 Introduction 106
5.2 Steady-State Voltage Stability Criteria 106
5.3 Applications to Large Power Systems 125
5.4 Loads With Known P/Q/V Characteristics 127
5.5 Checking of Criteria Numerical Results by Critical Voltage
Criteria 128
5.6 Application of the Six Voltage Stability Criteria to Large
Power Systems of Fixed Loadability 128
5.7 Application of the Six Criteria to Large Power Systems Having
Variable Loadabilities 130
Problems 130
References 134
Chapter 6:
Static VAR Compensators 136
6.1 Introduction 136
6.2 What are Static VAR Compensators 136
6.3 Types of Static VAR Compensators 137
6.4 TCR/FC Voltage / Current Characteristics 142
6.5 Need of Transformers with Static Compensators 144
6.6 SVC's Losses Evaluation 144
6.7 SVC's Harmonics Generation 145
6.8 SVC's Control Techniques 148
6.9 SVC’s Modeling for Stability Studies 161
6.10 SVC Representation in Power Flow and Voltage Stability
Studies 172
6.11 Applications of Static VAR Compensators 173
h Contents
Problems 174
References 175
Chapter 7:
Flexible AC Transmission Systems FACTS 179
7.1 Introduction 179
7.2 What are FACTS? 179
7.3 FACTS Objectives 180
7.4 FACTS Functions and Control 180
7.5 Meaning of Flexibility of Electric Power Transmission 181
7.6 Actual and Proposed FACTS Schemes 183
7.7 Components and Principles of Operation of FACTS Schemes 184
7.8 FACTS Representation in Steady-State System Studies 212
7.9 Static Synchronous Generators Modeling 212
7.10 Future Applications of FACTS 213
7.11 FACTS Effects on Systems Stability and Security 213
7.12 Summary 214
Problems 214
References 215
Chapter 8:
HVDC Systems Operation and Control 219
8.1 Introduction 219
8.2 Historical 219
8.3 AC and DC Transmission Systems 222
8.4 Disadvantages of DC Transmission 225
8.5 Reliability of DC Systems 225
8.6 Necessities of Using DC Transmission 225
8.7 DC Transmission System Connections 226
8.8 Two-Terminals DC Links Components 227
8.9 HVDC Systems Configurations 229
8.10 HVDC Loadability Features 230
8.11 DC to AC Losses 230
8.12 Operation of Converter Circuits 230
8.13 Relationship between AC and DC Quantities and AC Side
Power Factor 232
8.14 Converter Transformer Rating 234
8.15 Multiple Bridge Converters Operation 234
8.16 Basic Rectifier Model 235
8.17 Basic Inverter Model 237
8.18 HVDC Link Operation 239
8.19 Two-Terminal HVDC Link Control 241
8.20 Steady-State Analysis of Two-Terminal HVDC Links 242
Contents i
Chapter 9:
Voltage Control in Power Systems 275
9.1 Introduction 275
9.2 Voltage Control by Acting on Generators Excitation 275
9.3 Voltage Control by Acting on Transmission System Elements
Variables 290
9.4 Voltage Control by Acting on The Load Itself 304
9.5 Using Series Voltage Controllers 317
Problems 318
References 321
Chapter 10:
Voltage Stabilization of Unstable Loads 322
10.1 Aspects of Load Instability 322
10.2 Techniques of Voltage Stabilization of Unstable Loads 322
10.3 Improvement of the Load Power Factors 323
10.4 Using Static VAR Compensators 325
10.5 Using on Load Tap-Changing Transformer at Load Terminals 336
10.6 Using Combination of on Load Tap-Changing Transformer and
Static VAR Compensator 340
10.7 Using Series Capacitors at Load Terminals 347
j Contents
Chapter 11:
Load Representation Effects on Voltage Stability
Evaluation 372
11.1 Available Load Representations 372
11.2 Influence of Load Modeling on Voltage Stability Evaluation 375
11.3 Induction Motor Loads 377
11.4 Arc Furnace Load 379
11.5 Aluminum Smelter Plant Load 379
11.6 Lighting Loads 381
11.7 Practical Composite Loads 382
11.8 General Comments on Effects of Load Representation on
Voltage Stability Evaluation 383
Problems 383
References 384
Chapter 12:
Induction Motor Role in Provoking Voltage
Instability 385
12.1 Introduction 385
12.2 Factors Governing Role of induction Motors 385
12.3 Induction Motor Characteristics During Steady-State 386
Conditions
12.4 Induction Motor Load Characteristics After Sudden Voltage
Dips 386
12.5 Motor Response to Frequency Excursions 389
12.6 Response to Ramp Frequency Variations 391
12.7 Induction Motor Behavior after Opening a Circuit of Double
Circuits Lines Feeding the Motor 393
12.8 Effect of Induction Motor Content in Load Composition 393
12.9 Quantity of Mechanical Loading 395
12.10 Nature of the Mechanical Loading 396
12.11 Inertia's of Motor Rotor and Shaft Load 396
12.12 Effect of Load Node Short-Circuit Levels 398
12.13 Contribution of Generator Dynamics 399
12.14 Induction Motor Load Starting Effects on Voltage Stability 400
Contents k
Chapter 13:
Blackouts Preventive Measures 414
13.1 Causes of Blackouts in Power Systems 414
13.2 Triggering Voltage Instability Leading to Blackouts 420
13.3 Blackouts in Power Systems 420
13.4 Means of Voltage Stability Enhancement 421
13.5 Preventive Measures of Blackouts 423
13.6 Preventive Measures of Blackouts in a Typical Large Power
System 426
13.7 Summary 443
Problems 443
References 444
Appendix A:
Derivation of the Formula of the dZ/dVr Criterion
and the Formula of the dE/dV Criterion 446
Appendix B:
Determination of the Maximum Receiving End Power and Critical
Load Nodes Voltage for Constant Receiving End Qr 452
Appendix C:
Distribution Overhead Lines and Cables Parameters and Typical
Power Systems Data 453
Appendix D:
Required Capacitors Ratings for Improvement of Power Factors of
Electrical Equipment's and Motors 458
Index 465
Preface a
Preface
Power systems planning, operation and control are usually affected by
their stability and power quality. Traditionally this stability has concerned
synchronous machines rotors motion in synchronism during and after small
and large system disturbances. Recently, the stability of loads has been paid
the same importance and attention as it has been found inter-related to voltage
stability. Both of them affects and is effected by the other. Power systems
stability have, recently classified to the known synchronous (or inertial or
angle) stability and voltage (or load) stability.
projects and examination problems for this course during those years. The
book is subdivided into thirteen chapters and some appendices.
system voltage control and stabilization and load provoking the phenomena
and blackouts preventive methods are displayed in chapters 9,10,11,12,
and13.
Chapter 9: deals with methods of voltage control used actually in
practice. The chapter is provided with some practical examples. It was clear
that the more recent and important mean is the thyristorized static VAR
compensator. Its parameters and control elements are given for this purpose.
Chapter 10: gives in detail the more recent research results and
recommendations about voltage stability enhancement methods at load
terminal. Use of combinations of static VAR compensators, on-load tapped
transformers, series capacitors and optimum load shedding are explained.
Chapter 11: is reserved to an important subject in voltage stability
studies, that is the influence of load modeling on voltage stability evaluations.
The chapter shows clearly the importance of having load models based on
experimental results and polynomial models to specified orders for each load.
Special attention is paid to lighting loads, arc furnaces, aluminum smelter
plants, electrolytic loads and rotating motors of all types. Residential,
commercial and industrial general loads are also included.
Chapter 12: is devoted to give in detail the induction motor load role
in provoking voltage instabilities, as it is proved that it provokes this
phenomena and it is the more used loads in all applications. Influence of
voltages on motors powers and reactive powers are explained together with
influences of network frequency excursion on such powers are also given.
Criteria of induction motor load stability are briefly discussed.
Chapter 13: gives an idea about the blackouts and their preventive
measures. Causes of blackouts and counter measures for avoiding them are
explained in this chapter. As an example, a complete analysis of a certain
blackout occurred in a whole country and methods of countermeasure are
presented.
during all these years have effectively participated in the creation and
completion of this work. They discussed actively each part of the course with
me and solved its problems. They raised several questions, which led to
improvements of the quality of its topics and material. They are all heartily
acknowledged. The thesis of my M. Sc. and Ph. D. students has added to the
material of the book. Their contributions are included in the book and largely
appreciated.
An essential and unique textbook for universities students and a tool for
planners, designers, operators and control engineers of power systems.
Chapter 1 1
Chapter 1
Instability may also be encountered without loss of synchronism, but with low
voltage levels. For example a system consisting of a synchronous
generator feeding an induction motor load through a transmission line can
become unstable because of the collapse of load voltage .Maintenance of
synchronism is not an issue in this instance ; instead , concern is voltage
or load stability. This form of stability can also occur in the loads covering an
extensive area supplied by a large system.
The possible consequences of voltage instability in an electric power system
can reach complete failure or blackout. This situation arises when a severe
disturbance is not cleared away fast enough. Harmonic stability arises when
currents with frequencies other than 50/60 HZ flow within the network and
through generators driven by multi stage steam turbines.
Progressive drop in bus voltage can also be associated with rotor angles going
out of step. For example, the gradual loss of synchronism of machines as
rotor angel between two groups of machines approach or exceed 180
degree would result in very low voltages at intermediate points in the
network .Voltage instability is essentially a local phenomenon; however, its
consequences may have widespread impact . Voltage collapse is more
4 Power systems Stabilities
Whether voltage will progressively decrease and the system will become
unstable depends on the load characteristics .With a constant – impedance
static load characteristics , the system stabilizes at power and voltage levels
lower than the desired values . On the other hand with a constant – power load
characteristics, the system become unstable because of the collapse of the
load bus voltage.
From the view point of voltage stability, the relationship between P R and VR
is of interest .Figure (1.3) shows, for the power system of Figure (1.1) , curves
of the VR-PR relationship for different values of load power factor . The
locus of critical operating points is shown by the dotted line in the figure.
Normally , only the operating points below the critical points represent
satisfactory operating conditions A sudden reduction in load power factor or
increase in(QR )can thus cause the system to change from a stable operating
condition to an unsatisfactory, and possibly unstable operating condition
represented by the lower part of the V- P curve .
The influence of the reactive power characteristics at the receiving end (loads
and compensating devices) is shown in Figure (1.4) .The system is stable in
the region where the derivative dQR/ dVR is positive .The voltage stability
limit ( critical operating point ) is reached when the derivative is zero
.Instability is noticed when that derivative is negative.
The characteristics of the transmission systems as impacted by the flow of
the active and reactive powers through the highly inductive elements show
that the principle causes of voltage instability are the following:
(a)The load on the transmission lines is too high.
(b)The voltage sources are too far from the load centers.
(c)The sources voltage is too low
(d) There is insufficient load reactive compensation.
6 Power systems Stabilities
Fig. 1.1 A simple two node system for illustration of voltage stability
phenomena
Fig. 1.2 Receiving end voltage, current and power as a function of load
demand
Chapter 1 7
Fig. 1.3 VR-PR characteristics of the system with different load-power factors
Fig. 1.4 VR-QR characteristics of the system with different load-power factors
8 Power systems Stabilities
however, very slow to cope with the fast transient voltage collapse
phenomena associated with load devices and power electronic controlled
loads especially those of major induction motor content .
The injection of fast variable reactive power near the load centers can prevent
voltage collapse or instability. This can be achieved by shunt capacitors or
reactors, static Var compensators (SVC), thyristor controlled series capacitors
(TCSC), combinations of these elements, flexible AC transmission systems
(FACTS), which can act almost instantaneously within 2 cycles or less. The
need for analyzing the long – term dynamic response following major upsets
and ensuring proper coordination of protection and control systems is also
being recognized for voltage collapse avoidance.
may exist during the ensuing system conditions .The system can thus
deteriorate to the extreme states, the result being the loss of significant
portions of system load. Generally, the actions of control and protective
system dominate the system response during these conditions. The situation is
often aggravated by poorly coordinated protection and control systems.
The electronic circuit shown in the figure(1.7(a)) regulates the inrush current
that arises upon initial application of voltage to capacitors .This inrush
current control circuit is intended principally to be incorporated into an
electronic instrument in which capacitors are used to filter out current
harmonics and noise that would otherwise be impressed on the instrument
18 Power systems Stabilities
power supply bus .In the absence of a circuit like this one , voltage would be
applied to the capacitors abruptly - typically by closing a relay ; the resulting
high inrush current could disrupt the power supply bus and thereby also
adversely affect the operations of other instruments connected to the same
bus.
The task of that circuit is as follows: shortly after turn-on , the inrush current
control circuit causes the voltage on the instrument bus to ramp
approximately linearly up to the full power supply potential , so that the
inrush current is constrained to be an approximately square pulse of
controlled amplitude .In more detail ,the sequence of events is the following:
Before power is applied , all capacitors are discharged .Upon initial
application of power to the input terminals Q 1 becomes turned on , and C1
starts to charge through R1 .The turn on of Q1 causes the charging of C2 to
full power supply voltage .When C1 becomes turned off; this allows C2 to
discharge partially .When the potential on the left side of C 2 threshold
voltage of Q2, the output voltage begins to ramp up toward the full supply
voltage, following initial application of power as shows fig (1.7)(b).
Table (1.1) Loads inrush currents periods and their ratio's to steady state
values.
(*) When the discharge tube, transformers, choke coil, capacitors, ect…
are combined in common in discharge lamp circuits ,the inrush current
may be 20 to 40 times, especially if the power supply impedance is low in
the high power factor type
(**) Conditions become harsher if plugging or including is performed
since state transitions are repeated.
21 Power systems Stabilities
Aspects of voltage instability are: some motors may fail to support the load
torques and can go to stand-still, lighting discharge lamps may experience
blackouts production will decrease, etc. Also loads are then said to be
"unstable loads". From load point of view voltage stability has been defined
in terms of the ability to maintain voltage so that when load increased, load
power will increase, i.e. both power and voltage being controllable, at
different voltage levels.
1.15 Voltage Stability Limit:
For the simplest case of resistive load and a source reactance, we find that
load power increases as its conductance increases until load conductance
equals source susceptance and then decreases as its conductance is further
increased. This defines the power limit. The system voltage will be unstable
beyond that limit. Thus it seems legitimate to call the critical point a stability
limit as well as a power limit. In this simple case the voltage is still
controllable by varying load conductance. In order to increase the voltage
stability limit, the voltage at the load should be maintained by reactive power
compensation if the load bus has no nearby generation.
1.16 Voltage Security:
Voltage security may be defined as the ability not only to operate stable but
also to remain stable following any reasonably credible system disturbance.
Security may be measured either by the increase in load that can be supported,
or by the increase in system impedance through which the load can be
supplied, or by the severity of a temporary major disturbance (e.g. critical
clearing time for a fault) that can be withstood without exceeding the limit of
voltage stability. All of these measures of margin can be calculated but cannot
be measured directly on an operating system. However, an indirect measure
that can be observed is the sensitivity of voltage to the continual changes in
load (dV/dP). As mentioned before, the critical value of (dV/dP) for a
satisfactory margin may vary for different load and system operating
characteristics, and so must be calibrated for the particular system and
operating point in question. The behavior of system voltage is often a very
good indicator of the approach to the boundary of secure operation. As the
limits of voltage stability are approached, voltage may become not only very
sensitive to small changes in load but also more difficult to control.
1.17 Voltage Standards:
There are several standards for voltage magnitudes allover the world. German
VDE standards are:
Low voltages: (D.C): 110, 220, 440 volts
Chapter 1 21
References
[1] B.M. Weedy, B.R. Cox, "Voltage Stability of Radial Power Links", Proc.
of IEE ,London, Vol. 115,No. 4, April 1968,pp528-536.
[2] B.M. Weedy, "Electric Power Systems", Book ,3rd Edition ,New York,
John – Wiley and Sons 1979.chap.8.
[3] C. Concordia, ”Voltage Instability”, Electric Power Energy Systems, May
1989,pp 14-20.
[4] C.W. Taylor, “Power System Voltage Stability”, Book, Mc. Graw Hill,
New York, 1993.
[5] P. Kunder, "Power System Stability and Control", Book, Mc Graw – Hill,
New York, 1994, Chaps.7, 12
[6] W.I. Rashid, “Voltage Stability Enhancement in Power Systems”, Ph.D.
Thesis, Suez Canal University, Port Said, Egypt, 1997.
[7] F.Bouring –G. Testud, B.Heilbronn, J.Versulle, "Present Practices and
Trends on the French Power System to Prevent Voltage Collapse" IEEE Trans
on Power Systems, Vol. 8, No. 3 August 1993. PP778-778.
[8] S.Abe. ,Fukunaga, Isono, B.Kondo, "Power System Voltage Stability"
IEEE Trans on PAS, Vol -101.Oct. 1982, PP3830-3840.
[9]C.C.Lui and F.F Wu.," Steady –State Voltage Stability Regions of Power
Systems"System and Control Letters,Vol. 6, June.1985,PP 23-31.
[10]A.E.Hammad , M. Z. EL-Sadek , "Prevention of Transient Voltage
Instabilities Due to Induction Motor Loads by Static VAR Compensators "
IEEE Trans on Power Systems , Vol 4 , Aug .1989 ,PP 1182-1190.
[11] F. El-Kady, " A Survey of Major Blackouts and Failures of Power
Systems" , Review Paper, Egyptian Universities High Council , Cairo, Egypt,
1997.
[12] M.Z. El-Sadek, “Preventive Measures for Voltage Collapses and Voltage
Failures in the Egyptian Power System ”, Electric Power Systems Research
Journal ,No.44 , 1998, pp 203-211 .
Chapter 2 32
Chapter 2
Voltage/Powers Relations
of Two Nodes Systems
Voltage/powers relations of two nodes equivalent power systems are
presented in several methods based on different mathematical models. The
voltages are given as functions in load active power, load reactive power and
transmission system parameters. Characteristics of two nodes equivalent
power systems receiving end voltages and their behavior at certain generating
end voltages as function of load powers are detailed. Emphasis are made on
maximum transmitted power relations and their corresponding critical
voltages. Compensators gains and system gains influences on load nodes
voltages sensitivity to load reactive power variations are illustrated, taking
into consideration various load nodes short circuit powers levels. Shapes of
load lines with and without compensators are finally displayed.
the Thevenen’s equivalent impedance at the load node. Two port generalized
constants model can be used to represent the former cases or to represent
medium and long lines in series with transformers provided with tap-
changers.
Vs Vr
Rs Xs
Vs Pl + jQl
Pr + jQr
Qc = Qr -Ql
Just at the receiving end of the transmission link, the powers are (P r + jQr).
The load powers are (Pl + jQl). Pr is evidently equal to Pl, while Qr differs
from Ql. The difference between Qr and Ql allows for reactive power
injections or compensation Qc at the load node, i.e. (Qr = Ql + Qc). Although
Vs, Vr are complex quantities, their magnitudes will be the main field of
interest in voltage stability problems as they are determining indicator.
Vx X s I p Rs I q (2.2)
With:
Pr Q
Ip and I q r (2.3)
Vr Vr
Rs Pr X s Qr
Vr (2.4)
Vr
X s Pr Rs Qr
V x (2.5)
Vr
Chapter 2 32
In complex form:
Fig. 2.2 Phasor diagram of two nodes system voltages and currents
2 2
g h
Vs Vr (2.9)
Vr V
r
Or:
Vr4 2 gVr2 g 2 h 2
Vs (2.10)
Vr2
4
2
Vr 2 R P X Q V 2 Vr R2 X 2 P2 Q 2 0
s r s r s s s r r
(2.11)
Then:
32 Voltage/Powers Relations of Two Nodes Systems
b b 2 4ac
Vr (2.12)
2a
Where:
a 1.0
b 2 Rs Pr X s Qr Vs2
c Rs2 X s2 Pr2 Qr2
The receiving end reactive power Qr, which is the sum of the load reactive
power Ql and the compensator reactive power Qc, can be calculated by slight
manipulation in (2.8) as:
Qr is positive for lagging power factor and negative for leading one. The
phase angles difference between Vs, Vr; is given by:
V X P R Q
sin x s r s r (2.14)
V V V
s r s
For ultra high voltage networks, Rs << Xs and the angle is small, (i.e. tan
in radians) and V = 0, therefore the magnitudes of the voltage depression is
approximately given by:
X s Qr
Vr (2.15)
Vr
X s Pr
V x (2.16)
Vr
X s Pr
(2.17)
Vs Vr
Which means that reactive power flow is mainly dependent on nodes voltages
magnitudes and active power flow is mainly dependent on phase differences
of these voltages.
Example 2.1:
A Load center consumes 25 MW and 50 MVARS at peak load period.
It is fed from an infinite 10 kV network through a transmission link of
impedance Zs = (0.0784 + j0.3922) Ohm. Find the voltage depression and the
required compensator reactive power for the following cases:
(a) System without compensation.
(b) When the load power factor is corrected to unity.
(c) For the load node voltage reste equal the source voltage.
Solution:
(a) Having Vs = 10kV, Pr = 25MW, Ql = 50MVAR and Qr = Ql = 50MVAR. Rs
= 0.0784Ohm, Xs = 0.3922Ohm, the load node voltage Vr is given by equation
(2.11) as: Vr = 6.782kV
The voltage depression will be Vr = Vs - Vr= 3.218 kV. and no compensation
exists (i.e. Qc = 0)
(b) For load power factor compensation to unity:
Compensator reactive power Qc = -Ql = -50 MVAR and Qr = 0. Eqn. (2.11)
yields: Vr = 9.748kV. Therefore, voltage depression Vr = 0.252kV.
Noting that power factor correction has improved the voltage level and
reduced the voltage depression from 3.218 to 0.252 kV.
(c) Compensation for equal load and source voltages:
This means that Vr = Vs = 10kV, or zero voltage regulation. Using eqn. (2.13),
Qr = -6.35 or -484 MVAR. Load quantity makes that evidently Qr = -6.35
MVAR will be considered.
Compensator reactive power Qc = -6.35-50 = -56.35 MVAR
No voltage depression in this case on the account of large required reactive
power compensation (-56.35MVAR) at the load end. Practically reactive
power compensation is a fraction of the load reactive power. This is called
load voltage control.
X Q Rs Pr
Vs Vr s r Vr (2.18)
Vr
Having a fixed value for Vs and a specified value for both of Pr, Qr, Rs
and Xs, the load node voltage magnitude Vr can be calculated in an iterative
method. In that method the numerator of eqn. (2.18) is calculated once and
kept constant. The iterative procedure starts by assigning the nominal value
for |Vr| (per phase). Vr is then calculated from eqn. (2.18). The first value of
Vr is afterwards found from |Vr| = |Vs| - |Vr|. The new value of Vr is
substituted in eqn. (2.18) to get a new value for Vr, which is used to
calculate the second iteration of Vr. The process is to be repeated until the
scalar depression Vr rest unchanged. The final value of |Vr| = |Vs| - |Vr| is
taken as the magnitude of Vr. The sending end voltage phase angle can then
be calculated approximately from.
V x X s Pr Rs Q r
(radians) (2.19)
Vs Vs Vr
V V Rs Pr R
Qr r r k s Pr (2.20)
Xs Xs
Where:
K = (Vr.Vr/Xs) and Qr = Ql + Qc.
Compensator reactive power Qc can be calculated from eqn. (2.20), for any
specified load voltage Vr, load power Pl and transmission link (Rs + JXs).
Example 2.2:
Using the scalar voltage iterative method, find the load voltage of a
load consumes constant powers of 1 MW and 0.75 MVARS, independent of
voltage. The load is fed through a line of impedance Z s = (0.66 + j0.66) Ohms
from an infinite network having constant voltage of 3.3 kV.
Solution:
Load node phase voltage 3300/ 3 1900V.
The first iteration of eqn. (2.18) yields:
R P XsQ r
ΔV (1) s r
Vr
Chapter 2 32
Vs AVr BI r (2.21)
23 Voltage/Powers Relations of Two Nodes Systems
Assuming Vr is the reference phasor and the load current I r lags Vr by r. The
transmission system generalized constants are:
A = |A| and B = |B|
Vs s AVr BI r r
2 2 2 2 2
Vs A Vr B I r 2 ABV r I r cos
r
2 2 2 2
Vs A Vr B I r 2 ABVr I r cos cos sin( ) sin
2
r r
(2.23)
G G 2 4 A2 B 2 S 2
Vr (2.25)
2 A2 2 A2
Where:
r
G 2 AB P cos Q sin Vs
r
2
And: S 2 Pr2 Qr2
The critical voltage, which corresponds to the maximum power transfer, can
be found by equating the second term under the root to zero, i.e.
Chapter 2 23
G
Vcr (2.26)
2 A2
b b 2 4ac
Pmax (2.27)
2a 2a
Where:
(a) For constant power factor load (cos r = constant): a, b and c are found
from:
a sin 2 2 cos sin tan r tan 2 r cos2
cos 2 tan r sin 2
b Vs Vs
AB AB
V S4
c
4 A2 B 2
(b) For constant reactive power load (Qr = constant): a, b and c are found
from:
a sin 2
V 2 2 ABQ sin
b cos s r
AB
V 4 Q sin V 2
c
s r s Q 2 cos 2
2 2 AB r
4 A B
Noting that (+) and (-) are used for Qr with lagging and leading power factors
respectively. A, B, and , for a line having total series impedance Z and
total shunt admittance Y, are calculated as follows:
For simple Z = (Rs + jXs) link: A = 10, B = Z.
For section link: A = (1 + YZ/2), B = Z .
For T section link: A = (1 + YZ/2), B = (1 + YZ/4) Z.
For long lines: A = [1 + (YZ/2) + (Y2 Z2 /4) + (Y3 Z3 / 720)+...],
B = Z [1 + (YZ/2) + (Y2 Z2 /120) + (Y3 Z3 /5040) +...]
The first two terms are sufficient for lines lengths less than 500 Km.
23 Voltage/Powers Relations of Two Nodes Systems
S sc Vs I sc
*
Psc jQsc S sc sc (2.28)
Vs2
S sc . (2.29)
Zs
Z s Rs jX s (2.30)
Then:
Vs2 Vs2
Rs Z s cos sc cos sc , X s sin sc (2.31)
S sc S sc
The real and imaginary components of the voltage depression Vr, Vx can
be written in the form:
V P cos Q sin
r r sc r sc (2.33)
V 2 V S
s r sc
V P sin Q cos
x r sc r sc (2.34)
V 2 V S
s r sc
Q
V Vs Vr r V (2.37)
S s
sc
Or:
Q
Vr Vs 1 r
(2.38)
S
sc
Therefore:
Vr
Vs (2.39)
Qr
1
S
sc
This relation gives the slope (-Vs/Ssc) of the voltage characteristic of the two
node link due to receiving end reactive power variation at a node of specified
short- circuit power level, which is shown in fig. (2.3).
S g Ps jQs (2.40)
S r Vr I * Pr jQr (2.41)
22 Voltage/Powers Relations of Two Nodes Systems
Vs Vr I Rs jX s Vr IZ s (2.42)
S*
Vr V r Z (2.43)
s * s
Vr
Having Vs, Sr and Zs, eqn. (2.43) can be solved iteratively to get V r. Gauss
iterative method is usually used with a computer program to perform these
iterations. In this concept Pr is the actual load power and Qr is the net received
reactive power at node r. It is the difference between the load reactive power
demand and the external injected reactive power.
Example 2.3:
For the two nodes power system shown in fig. (2.1), find the load
voltage Vr when its power demand is (8-j5) pu and the generator node voltage
Vs is kept constant at 1pu. The transmission link impedance is Z s =
0.005+j0.03 pu./phase. Use the load flow Gauss iterative technique equations.
Solution:
Having Vs = 1.00, Zs is known, using first Gauss iteration for V r(1) =1.00,
substitute in eqn. (2.43) to get a new value for Vr(1) = 0.810-j0.215. Using this
value a second iteration yields Vr(2) = 0.715-j0.190.
The third one gives Vr(3) = 0.677-j 0.215. Continuation of these iterations up
to the 13th, one gets Vr(13) = 0.618-j 0.215 and the 14th, iteration gets the same
value.
Solution is said to be converged and the load voltage is finally pronounced as:
Vr = 0.618-j0.215 = 0.654-19.18o pu
Current in the link is: I = (8-j5)/(0.654-19.18) = 14.43-51.19 pu, and
Generator input power is given by:
Sg = Vs I* = (1.0 0)(14.43-51.19) = 9.04+j11.24 pu
The voltage depression in then = 0.346 pu
Example 2.4:
Solve example 2.3 for:
(a) Load demand increased to (10+j5)
(b) Equal load and source voltages (Vs = Vr = 1.0 pu).
Find required compensation reactive power.
Chapter 2 22
Solution:
(a) No convergence occurs. No solution, i.e., the system cannot operate with
this heavy loading condition
(b) Assuming the load voltage Vr is the reference values then:
8 j5 jQ c
Vs 1.00 0.005 j0.03
1.00
|Vs| = |1 + (0.005+j 0.03)(8-j 5+jQc)| = 1.0
This gives Qc = 7.41 pu. Therefore: Vs = 1.014.6 pu.
And the generated power is given by: Sg = 8.349-j 0.315 pu.
I G Y GG Y GL V G
L LG (2.44)
I Y Y LL V L
With:
VL, IL vectors of voltages and currents at load nodes.
VG, IG vectors of voltages and currents at generators node.
YGG, YGL, YLG, and YLL are sub-matrices of the system Y-matrix.
22 Voltage/Powers Relations of Two Nodes Systems
Killing all generators of the system means that all generators are
connected to the ground with the result that their self elements |Y GG| will
disappear and |VG| = 0. Their mutual with load nodes |YLG| vanish. This
mutual should be added to the self of the load nodes, which are connected to
the generator buses "G". Fortunately they are already included in |Y LL| of the
load nodes in the elements having mutual with the generators before killing.
Therefore, the above [Y]-matrix becomes:
I L Y LL V L (2.45)
V L Z LL I L (2.46)
With:
|ZLL| = 1/|YLL|
In other words, the feasible power that can be transmitted at each level
of the receiving voltage and the respective needed reactive power at this end.
Chapter 2 22
(a) (b)
That two values of voltage exist for each value of power is evident
from equation (2.24). At the lower voltage a very high current is required to
provide the required power. For loads of lagging power factors the possibility
22 Voltage/Powers Relations of Two Nodes Systems
exists that the operating power may be near the knee where small changes in
load cause large voltage changes and voltage instability can occur. On the
other hand, lagging power factors load works at a low voltage level and a
limited power transfer.
Inserting a capacitor in shunt with the receiving end load i.e. having
leading power factor region at load end, raises the voltage levels, eliminates
the probability of voltage fall and increases the power transfer for each level
of voltage. When the load power and reactive power are independent on its
node voltage, that load is said to be “stiff". Otherwise it is called “soft” load.
(b) The purely reactive power compensator cannot maintain both constant
voltage and unity power-factor at the same time.
(c) Rule (b) has an exception when the load power is zero, it is quite
possible for a purely reactive compensator to maintain both constant
voltage and unity "average" power-factor.
dQc
Kc (2.47)
dVr
Qc
Vr Vk (2.48)
Kc
Within 0 Qc Qc (max).
Therefore, if Kc is infinity, the compensator can generate a reactive power
sufficient to keep Vr = Vk = constant as load varies. For example, a
compensator gain of Kc = 40 VAR/volt means that the compensator reactive
power changes from zero to 1 pu for a change in Vr by Vr =1/40 = 0.025 pu.
Ql Qc Qr (2.49)
Q 1
Vr Vs 1 r Vs Qr (2.50)
S K
sc s
It is the relation of the load node voltage (Vr) with its received reactive power
Qr. Its slope is (-Vs/Ssc) is the inverse of the system gain Ks of units VAR/volt.
As Qr increases, the load voltage falls, by a rate of (Vs/Ssc) Qr, or at a rate
equal to (1/Ks) Qr. Ks is a negative value.
r s
dV V
S (2.51)
dQ sc
r
Fig. 2.8 Load node voltage with load reactive power at different nodes
short-circuit levels
23 Voltage/Powers Relations of Two Nodes Systems
Q Qc
Vr Vs 1 l (2.52)
S sc
Qc K c Vr Vk (2.53)
k c Vk Ql
1
S
sc S sc
Vr Vs k V (2.54)
k V
1 c s 1 c s
S S
sc sc
Equation (2.54) shows how the supply point voltage V r varies with load
reactive power Ql in the presence of a reactive power compensator. Provided
that QcQc (max), the load reactive power is Ql, the compensator gain is Kc
and its knee voltage is Vk, the generator voltage is Vs and the load node short-
circuit power is Ssc. For uncompensated load, eqn. (2.54) tends to (2.50).
Comparing the two terms of eqns. (2.50) and (2.54), the compensator is then
has two effects:
(a) It alters the no-load network voltage from Vs to a new virtual value
given by the first term of eqn. (2.54), which is:
Chapter 2 22
kV
1 c k
Vs
S sc
(2.55)
k cVs
1
S sc
(b) It modifies the sensitivity of the load node voltage to load reactive power
variations, as shown by second term of eqn. (2.54), to the following:
Vs
dV
r S sc
(2.56)
dQ k V
l 1 c s
S
sc
Example 2.5:
For a certain system Vs = 1.00 pu, and Ssc = 25 pu, based on Qc(max),
(a) Find the voltage sensitivity to load reactive power without any reactive
power compensation.
(b) Find that voltage sensitivity to load reactive power variations with
compensator having a gain Kc = 100, for a gain Kc = -100 and for Kc = .
Solution:
(a) Without compensation: (Kc = 0) dVr/dQr = -Vs/Ssc = -0.04
(b) With compensation:
dVr
With Kc =100: From eqn. 2.56, 0.008
dQ l
dVr
With Kc = -100: From eqn. 2.56, 0.013
dQ l
dVr
With Kc =: From eqn. 2.56, 0.0
dQ l
Chapter 2 22
Vs 1
dV
r S sc ks
k (2.57)
dQ k V
l 1 c s 1 c
S k
sc s
Where, the slope or gradient (-Vs/Scs=1/Ks), defines the system gain "Ks",
therefore equals the rate at which reactive power must be absorbed from the
system in order to depress the system voltage by amount of unity. Ks is
therefore analogous to Kc for compensator, Ks is always negative.
The leverage which the compensator has to do in determining the overall
sensitivity of network voltage to load reactive power is a function of the ratio:
(Kc/Ks), for QcQc (max) as seen from equation 2.57. Ks equal the negative of
the load node short circuit current when its voltage is normalized to the source
voltage Vs.
Example 2.6:
A Load node of short-circuit power Ssc = 250 MVA, is fed through a
transmission system from an infinite network of constant voltage V = 1.0 pu,
and loaded by a load of maximum reactive power Ql (max) = 10 MVAR. To
regulate the load voltage, a capacitive static VAR compensator is connected at
that load node. The compensator can generate capacitive reactive power up to
-10 MVAR.
(a) For a load reactive power variation from (0 to 10) MVAR, find the
required compensator reactive power Qc, load node voltage depression
(V) and the system received reactive power at the load end Q r. The
compensator gain Kc = 100 (VAR/volt).
(b) To what range of consumed reactive power overload, the compensator
will be in service.
(c) Repeat (a) when the load is overloaded upto 150% of Ql (max).
Solution:
(a) Application of eqns. (2.54) and (2.57) show that:
22 Voltage/Powers Relations of Two Nodes Systems
Vr f Pr , Qr (2.58)
As all the other system nodes voltages are assumed as infinite buses, The total
differentiation of Vr is:
V V
dV r dP r d Q (2.59)
r P r Q r
r r
dP dQ
dV r r (2.60)
r P Q
r r
V V
r r
X Q R P
V V s r s r (2.61)
s r V
r
Chapter 2 22
Or:
2
V V V X Q R P (2.62)
s r r s r s r
Pr V 2V
s r (2.63)
Vr R
s
And:
Qr V 2V
s r (2.64)
Vr X
s
The latter formula represents the reciprocal of the node voltage sensitivity to
reactive power injection at that node. At no-load Vr = Vs and that sensitivity
equals to:
Qr V
s
(2.65)
Vr X
s
s j
V V
I s (if Rs<Xs) (2.66)
sc jX
s Xs
Problems
2.1 The equivalent Thevenen’s of node # 21 of the IEEE 30 bus power
system is given by: E = 0.9535-14.37o pu, Zs = 0.148675.24o pu. The
node feeds a load having P = 0.106pu, Q = 0.01pu.
(One) Find the load node voltage magnitude, voltage phase angle, and voltage
depression, using the complex voltage depression method, the scalar
voltage depression iterative method, and the generalized constant method,
the load node short–circuit power method, and the load–flow Gauss
iterative method.
22 Voltage/Powers Relations of Two Nodes Systems
(Two) Find the critical load node voltage and the maximum load power for
load power factors: 0.7 lead, unity and 0.7 lagging.
(Three) Plot the critical voltage magnitudes, the maximum power for constant
load power factors of (0.1 up to 0.9) in the leading and in the lagging
ranges, with intervals of 0.1. Repeat these plots for constant reactive
power loads ranging from (0.1 to 0.9) pu in the capacitive and inductive
ranges and for zero load reactive power (Active power is kept constant at
its original value).
(Four)For active load powers equal 100%, 75% 50% 25% 10% and 5 % of the
maximum transmitted power, find the load terminal voltage .The load
power factors are ranging from (0.1 to 0.9) lead and from (0.1 to 0.9) lag
and unity. Plot the power against the load voltage in each case. Repeat this
requirement with constant load reactive powers equals (0.01 to 0.1) pu
inductive and (0.01 to 0.107) pu capacitive and for zero reactive power.
(Five) Plot P/V and Q/V characteristics of the system for both constant load
power factors and constant load reactive powers, for the IEEE 30 bus
system at node #21.
2.2For the six-bus Ward Hall system, repeat (a), (b), (c), and (d). The system
data are Eth = 1.004-3.2o pu., Zth = 0.32375.48o pu., P = 0.3 pu., Q =
0.18 pu. in (d) Q is changed from 0.18 pu up to 0.718 pu., in the inductive
and capacitive ranges. Unity power factor should be included.
2.3 A large load center is fed from a voltage source Vs, through a
transmission system having the generalized constants:
A = 1.00o and B = 0.2589.72o pu. and consumes powers of: Pr = 0.6 pu,
Qr = 0.216 pu. at Vr = 1.0 pu.
Find the load node voltage using all studied methods.
2.4A supply system operates at 11 kV with short-circuit level of 250 MVA
and of Thevenen’s impedance ratio Xs/Rs of 5, supplying a wye-connected
inductive load whose mean power is 20 MW and whose reactive power
changes from (0 to 40) MVARS find:
(One) The voltage depression due to maximum loading using all known
methods
(Two) The required reactive power for unity load power factor compensation.
(Three) The required reactive power for zero voltage regulation and for +10%,
+20%, +50% voltage regulations
(Four)The improvement in load voltage values due to unity power factor
correction in (b) and for voltage control regulations in(c)
(Five) The critical load node voltage and the corresponding maximum power.
(Six) With short-circuit levels of 400, 100, 50 MVA, repeat (a). (b). (c). (d),
and (e)
2.5 For a two-nodes power system having the following data:
Chapter 2 22
References
[1] Elgerd, O., "Electric Energy Systems Theory", Mc-Graw Hill, New
York, 1971.
[2] Gross C. A., "Power System Analysis", Wiley, New York, 1986.
[3] Guile A. E. and Peterson W., "Electrical Power Systems", 2 nd, edition,
Vol.2, Pergamon Press New York, 1977.
[4] Neuenswander, J. R., "Modern Power Systems", International textbook
Co., Scranton, Pennsylvania, 1971.
[5] Weedy B and Cory B. J., "Electric Power Systems", 4 th, edition. John
Wiley & Sons, New York, 1998.
[6] Gonen T., "Electrical Power Distribution System Engineering", Mc-
Graw Hill, New York, 1986.
[7] Gonen T., "Modern Power Systems Analysis", A Wiley-Inter-science
Publication, John Wiley & Sons, 1988.
[8] Grainger J. J. and Stevenson W. D., Jr, "Power System Analysis", Mc-
Graw Hill, international, 1994.
[9] Glover J. D. and Sarma M., "Power System Analysis and Design", 2nd
edition, PWS Boston, Massachusetts, 1994.
[10] Miller T. J. E., "Reactive Power Control in Electric Systems", General
Electric Corporation Company Research and Development Center
Schenectady, New York, 1982.
[11] Ahmed A. A. H., "Control of VAR Flow in Power Systems as
Influenced by System Reconfiguration", M. Sc. Thesis, Assiut
University, Assiut, Egypt, 1993.
Chapter 3 15
Chapter 3
Load Representation for Voltage Stability
Studies
3.1 Introduction:
Voltage stability is tightly related to load characteristics and voltage
magnitudes. It is directly dependent on load behavior with voltage and
frequency variations. It will be shown later that voltage instability can be
detected with several criteria. They are defined by different formula, which
are all function in load node powers, load nodes reactive powers and their
derivatives with voltage and frequency. So, exact detection of the occurrence
of voltage instability phenomena is mainly dependent on the correctness of
the loads power/voltage and reactive power/voltage relations. Recently it has
suggested to represent these relations in polynomial forms to certain orders,
which led to coincidence of results of voltage stability criteria. The load
powers/voltage characteristics have derived from the load/time and
voltage/time characteristics, usually recorded in all power stations and
substations. New models for the loads which represent the heaviest burden on
power systems voltage stability such as: Induction motors, heaters, arc
furnaces, arc welders, aluminum smelters, fluorescent lamps, sodium vapor
lamps, and mercury vapor lamps are presented. The known simple models for
these loads were found to have erroneous results on detection of occurrence of
voltage stability.
days, seasons, and with weathers conditions. Load windows are very difficult
to be defined for substations load busses.
power is consumed, which means unity load power factor. Active power
changes to the nth, power of voltage, Therefore:
Vn
P Po , Q0 (3.1)
Von
The exponent n was found to be 1.50 to 1.6 for modern filament lamps. This
value appreciably independent from the amplitude of voltage reduction. "n"
decreases from initial value of 2 to its final value (1.5–1.6) in a time period
equal the thermal transient time of the lamp.
Po
P V 2 , Q0 (3.2)
Vo2
remains constant and the effective tube resistance "R" is assumed current and
frequency dependent according to the relation:
Ro I o o k '
R (3.3)
I I
Where Ro, Io and o are nominal values of resistance, current and frequency
respectively, and (k' = RoIoo). Also the assumption is made that voltage drop
Vt across the tube remains constant, i.e.
Vt Ro I o const. (3.4)
On the above assumptions, active and reactive power to the circuit were
expressed at voltage V, frequency and choke inductance L as:
0.5
' K '
2
V2
K
P (3.5)
2
L
2
1 K
'
2 1
Q V c (3.6)
L L
V Vi
PP (3.7)
oV V
o i
V V j
QQ (3.8)
oV V
j
Where Po and Vo are rated load power and voltage; Vi and Vj are the values of
the voltage at which the approximated P/V and Q/V linearized characteristic
intersects the axis of the abscissas. These formula were found to be valid if:
Vi > 0.6-0.7 pu, Vj > 0.65-0.7 pu for fluorescent tubular lamps.
Vi > 0.75-0.85 pu, Vj > 0.7-0.8 pu for mercury vapor bulb lamps.
15 Load Representation for Voltage Stability Studies
If the voltage drops below the above limits, even for a short while (0.1 s), the
arc is quenched and current is drawn immediately to zero. The duration of the
voltage drop has only a small influence on the extinction value (10-15%). It
is well known that when the voltage is restored, the mercury vapor bulb lamps
will not reignite during a few minutes.
3 2
Vdo BaEll (3.9)
Since the voltage drop per bridge is I d(3Xc/), with Xc the converter
commutation reactance, and since there are B bridges in series, the controlled
DC voltage of the converter is given by:
3X
Vd Vdo cos I d B c (3.10)
Where Id is the DC converter current and the thyristor firing angle. The DC
output power is given by:
Pd Vd I d (3.11)
6
I l1 BaI d (3.12)
Having the DC power equal the AC input power, the input power factor is
given by:
B=1 from six pulses, B=2 from 12 pulses and B=4 for 24 pulses system, and
so on.
If the voltage va(t) is constant during the voltage depression and equal to a
fraction K of the rated voltage Va (va(t) = Va' = KVa), the DC voltage can be
expressed as:
Where "h" is a constant of the rectifier and is a factor accounting for the
high-speed voltage control, if any (1). If the rectifier has controlled ignition
and o is the delay angle at the occurrence of the voltage dip, the delay angle
will be drawn automatically to zero in the trial to support of voltage; then
from theory of rectifiers it is found =1/coso.
Let us call "I" and "I'" the DC currents circulating in steady condition when
the AC voltage is Va and Va' = KVa. i.e.
The solution of the differential equation of the R-L-E circuit, given later, has
led to the following expression:
Pt Vc' t it KVc I I ' e t I '
Or:
1 K t KVc E
Pt KVc2 e KVc (3.19)
R R
The reactive power is easily calculated when the current and voltage are
known. If the magnetizing power of the transformers is neglected, theory of
Chapter 3 15
rectifiers provides the following expression of the power factor, when the
delay angle = 0, as supposed in the foregoing:
2 IX
cos 1 (3.20)
2Va
2 I t X
Qt Pt tg t qo Pt tg cos1 1 qo
(3.21)
2Va t
the furnace has been charged, usually with steel scrap, the operator energizes
the circuit with the electrodes in the drawn position. They are then lowered
under automatic control until they contact the charge and an arc is ignited, the
control then attempts to maintain constant impedance in the circuit. In some
methods of operation, the furnace transformer secondary voltage is at a high
level during the initial part of the meltdown for maximum power output.
Constant current cannot be maintained until a significant quantity of the
charge has been melted, because of the changing shape of the mass of scrap as
it liquefies. The arc is quite irregular and the load fluctuates. Widely from
short-circuit when the electrodes contact the metal to no-load when the arc is
extinguished. Since scrap is usually bulky, the furnace must be recharged one
or more times during meltdown. Arc resistances are usually unequal.
I (3.22)
3 R2 X 2
Total applied apparent power in the three phases:
V2
S 3VI (3.23)
R2 X 2
Input reactive power:
55 Load Representation for Voltage Stability Studies
3 XV 2
Q 3 XI 2 (3.24)
R X 2 2
Load curves for a 40MVA furnace are plotted in fig. (3.4) with the aid of
equation (3.22) to (3.30) as a function of the electrode current. The furnace
data are X= 2.9m.ohm/phase, I (operating)= 53 K Amps/line, V= 420 volt,
R=0.5m.ohm/phase, arc resistance is variable, I= furnace current ranging from
zero to 80 K Amps. If the current is more than maximum value of 55 K.
Amps, the arc power will decay. While the losses will still increase further. If
the electrical efficiency is taken into account, it is clear that one must keep to
the left of this point. Load power factor at that point is usually around 0.7.
Fig. 3.6 Comparative load curves for two balanced furnaces having
different reactance’s (2.5 m, 5 m)
Chapter 3 51
Fig. 3.7 Load curves for an arc furnace with unbalanced circuit and
equal current control
Tl n (3.31)
Where:
and are constants and "n" is the shaft speed.
2
X
s s 1 X
V 2 X m cr s cr X
m
Q (3.33)
X 2
s
1
s
cr
Critical slip and reactance are frequency dependent but not voltage or current
dependent unless saturation is taken into account. The P-V, Q-V
characteristics may be also determined by the use of the simplified circuit
shown in fig. (3.8). When it is assumed that the mechanical load on the shaft
is constant. The electrical active motor power is:
2 r
P 3I 2 constant (3.35)
s
3I 2 r
s 2 (3.36)
P
2
Q
3V
Xm
3I
2
X 1 X 2 (3.37)
Also, from fig. (3.8), the active motor power is given by:
2r 3V 2 r 3V 2 r s
P 3I 2 2 2 (3.38)
s
s
r2
2 r2
2 sX 2
X2
s
EV X Xq
P sin V 2 d sin 2 (3.39)
X 2X X
d d q
EV X Xq X Xq
Q cos V 2 d V 2 d cos 2 (3.40)
X 2X d X q 2X d X q
d
Where: Xd, Xq are motor parameters. E is the internal voltage and V is the
terminal network voltage. is the internal voltage phase angle.
dP V
P
dP , P P P
(3.41)
dV d o
Q
dQ V dQ , Q Q Q
(3.42)
dV d o
Table 3.1 Formula for dP/dV, dQ/dV, dP/d and dQ/d for various load
types
Load Type dP/dV dQ/dV dP/d dQ/d
Filement lamp nP V 0.0 0.0 0.0
(n=1.55-1.6)
Heaters (n=2) 2P V 0.0 0.0 0.0
1 P Q 1
P V 1 cos 2 t
2Q V
cos 2
P 1 cos t
2
Discharge t 3
or: Po Vo Vi ---
Lamps or: Qo Vo V j
Vi 0.6-0.7 cost: power
Vj =0.65-0.8 factor
P V 1 Q P 2
DC
0.0 Q2 P Q
Converters
Arc Furnaces tVP LQ 2tV L P Q
Induction Q P 1 Q P
2P V P P
Motor 2P V 1 kn kd 2sscr kd kn k2 kd
2sscr k2 kd
(Where) 2 s2
kn scr
2 s2
k p scr kd kn k2k p k2 2 /1 s
E sin E cos
2V 2V
Xd Xd
Synchronous
Xd Xq Xd Xq --- ---
Motor sin 2
2Xd Xq 2Xd Xq
2 2
P Po
V , V
Q Qo (3.43)
2 2
V
o Vo
P jQ
Y Load 2
V
Which is to be added to the system admittance matrix [Y], in shunt at the load
node.
(b) While in load flow studies, they were represented as constant power
loads... i.e.
o o
V
P P , Q Q V (3.44)
oV oV
o o
V
P P , Q Q V (3.45)
oV oV
o o
Where:
P, Q = Load power and reactive power
Po, Qo = Initial powers and reactive powers
V, Vo = Actual and initial load node voltages
Chapter 3 55
n m
V
P P , Q Q V (3.46)
oV oV
o o
Table 3.3 Single termed polynomial models for some typical loads
Voltage Voltage
Type of Load Dependence Type of Load Dependence
P Q P Q
0.05
1-Large I.M V V0.5 7-Fluorescent lamp V 1.0
V3.0
2-Refrigerator V0.8 V2.5 8-Incandescent lamp V1.55 ---
3-Heat pump V0.2 V2.5 9-Arc furnace V 2.3
V1.6
4-Dish washer V1.8 V3.5 10-Aluminum smelter V2.3 V2.7
5-Clothes dryer V2.0 V3.3 11-Induction motor V0.1 V0.6
6-Color TV V2.0 V5.0 12-Mercury vapor lamp V1.0 V1.0
55 Load Representation for Voltage Stability Studies
Recently energy analyzers can get the corresponding values of the three
quantities directly on screens or in prints or on diskettes. Using the published
experimental P/V and Q/V characteristics of some loads, their polynomial
models were found. These models are based on a nominal power of 0.3 pu,
nominal reactive power of 0.18 pu at voltage of 1 pu. Any other load powers
should be normalized to get nominal load power and reactive power at 1 pu
voltage, simply by multiplying these polynomial coefficients by the (load
power/0.3) and (the load reactive power/0.18). The polynomial load models
are displayed below, for various load types:
Fig. 3.13 Fluorescent and mercury vapor lamps P/V, Q/V response
The Assiut cement company bus bar load measured results are selected as
another example. Power, reactive power and voltage time responses are
plotted in fig. (3.17). From these plots, P/V and Q/V characteristics were
derived and the load polynomial representations are derived as follows: That
load active and reactive powers are expressed by the 3rd order polynomials.
Fig. 3.17 P/V, Q/V Assiut cement company bus-bar loads responses
n n
P Pj , and Q Q j (3.70)
j 1 j 1
dP
a1 2a2Vr 3a3Vr2 4a4Vr3 5a5Vr4 ... (3.73)
dVr
dQ
b1 2b2Vr 3b3Vr2 4b4Vr3 5b5Vr4 ... (3.74)
dVr
The dynamics of each element in the fixed axis are transformed to the
synchronous rotating reference frame via Parks transformation. Balance
operation is assumed and the zero sequence dynamics are dropped. Each
capacitor is represented by its terminal voltage components as states and each
inductor is represented by its flowing current components as states. This is
shown in fig. (3.18). The differential equations describing their dynamic
behavior transformed to the network d-q axis are:
For the R-L Load:
R
I d o Vd o I d I q (3.75)
X1 Xl
R
I q o Vq o I q I d (3.76)
X1 Xl
With R, Xl are load resistance and 50Hz reactance. Id, Iq the d and q axis
current components respectively. o is the synchronous angular frequency
and is instantaneous angular frequency. For the shunt capacitors:
Vd o I d Vq (3.77)
Bc
Vq o I q Vd (3.78)
Bc
Where Bc is the 50Hz capacitor susceptance. Vd, Vq are the capacitor voltage
components in the d, q axis. Id, Iq are the capacitor currents components in the
d, q axis. , o previously defined with the R-L load
56 Load Representation for Voltage Stability Studies
di Ri V (t ) E
L (3.79)
dt c
1
ed'
Tqo
' ed' X q X q' id (3.81)
eq'
1
' eq' X d X d' iq V f
T
(3.82)
do
1
Te Tm (3.83)
M
ra ' X q
'
i d e d e ' 1 V (3.84)
D D q D d
Te Vd id Vq iq (3.86)
Tm (3.87)
With:
1
D
ra2 X d' X q'
55 Load Representation for Voltage Stability Studies
P rq Rr irq s o rd (3.91)
T Tm
o Ps e (3.92)
2 o H
Chapter 3 55
With:
Te eq ird ed irq (3.93)
Tm r (3.94)
The motor takes the voltage from the network, which will be:
Vt Vt t (3.101)
The motor injects in the network the negative of the stator currents, which are
given by:
X X m rd
isd sd r (3.102)
X X X2
s r m
sq X r X m rq
isq (3.103)
X X X2
s r m
The active and reactive power consumed by the motor are given by:
P rq o X 7 rq X 4 sq s s rd (3.107)
P Pm
P r o e (3.108)
M
Stator fluxes:
sd a Vsd X 5 Vsq s b rd X 5 rq s (3.109)
Stator currents:
I sd sd X 1 rd X 3 (3.111)
I sq sq X 1 rq X 3 (3.112)
Rotor current:
I rd rd X 2 sd X 3 (3.113)
I rq rq X 2 sq X 3 (3.114)
Pe rq I rd rd I rq (3.115)
Pm r (3.116)
Where:
r
s s , M 2H o , o 2f
s
Vt Vsd jVsq , s 1.0 P.u,
1 X 1
a , b s , C , and d X 6 s2
d d X X X 2
r s m
X 1 CX r , X 2 CX s , X 3 CX m , and X 4 Rr X 3
X 5 Rs X 1 , X 6 X 52 , X 7 Rr X 2 , and X 8 Rs X 3
Chapter 3 51
Vt
is isd jisq (3.118)
Zs ZmZr
ZmZr
Zm
ir ird jirq is (3.119)
Zm Zr
rq o X r irq X m isq (3.121)
s
sd o X s isd X m ird (3.122)
s
sq o X s isq X m irq (3.123)
s
o Pe Pm
P s (3.124)
M
Pm (3.126)
Network powers:
Pin Vsd isd Vsq isq (3.127)
With:
r
o=2, s=314.0 or 377.0 rad/sec, s s
s
Where:
= Supply frequency
Z s Rs jX ss o , X ss X s X m
s
Z r Rr jX rr o , X rr X r X m
s
Z m jX m o
s
The variation of the supply voltage Vt or its frequency varies the motor slip
“s” according to the differential equation of rotor mass motion.
Where:
3.14 Conclusions:
Load characteristics could be given by curves of active and reactive
power against voltage and frequency or by analytical P-V and Q-V relations
or by characteristic coefficients for each load component or by high order
polynomials of powers/voltage expressions. Individual or composite loads at
each node can be represented by such techniques.
Problems
3.1 A load consuming power 1.0+j0.5 pu at 0.95 pu voltage, express that
loads as:
(a) Constant impedance or constant admittance load
(b) Constant power load
(c) Constant current load
3.2 Repeat prob. (3.1),when the voltage phase angle becomes 0, 20, -20
degrees respectively.
3.3 An incandescent lamp consumes 35Watts under 200V, and rated
40Watts at 220V find the load exponent "n"
3.4 A load having nominal power of 1.0+j0.5 pu, write its polynomial form
when it is: Arc Furnace Load–Arc welding transformer Fluorescent
Lamp-Mercury Vapor lamp-Sodium vapor lamp-Aluminum smelter
plant-Induction motor with different mechanical load. For all these
loads find the formula of (dP/dV ) and (dQ/dV) for each load
3.5 A Soda reduction plant has the following data: cells in series 44, E=
136V, R = 0.27m.ohm, L = 0.12 mH, = 0. 45 sec. P = 43MW, I =
220KA, VT =195V. Find the load power and reactive power voltage
formula.
3.6 An arc furnace load circuit has a total reactance = 2.9 m.ohm, loss
resistance r =0.5 m ohm and source voltage 420V. Its maximum current
is 55KA, power factor 0.7. Find the arc resistance, the arc power, and
the arc energy per day and per year, the arc voltage and the circuit
losses. If the arc resistance is halved. What will be the new load power
factor and the corrective capacitor reactive power to avoid penalty in
Egypt and in Europe.
3.7 An induction motor is represented by its L-R. Equivalent circuit with
parameters: Xm = 3pu X = 0.2pu, (r2/s) = (0.04/s)pu, based on 500KW,
6.6kV, and P = 1.0pu, at V = 1pu. Determine the reactive power
consumed at various voltages and plot the P/V and Q/V characteristics
of the motor. Find the critical slip and critical voltage at which the
motor stalls. Assume the mechanical load constant and bus bar voltage
is raised from zero to normal value at intervals of 0.5kV.
55 Load Representation for Voltage Stability Studies
3.8 A load has time recorder plots for power, reactive power and voltage
shown in the following fig. (P3.8). Using the MATLAB extrapolation
technique, find the power/voltage and reactive power voltage
polynomial coefficients up to terms less than 0.001.
Fig. P 3.8 Power, reactive power and voltage time records plots
References
[1] Maurica, H. Kent, Wayne R. Schmus, Francis A. Mccrackin, and
Lauther M. Wheeler, “Dynamic Modeling of Load in Stability
Studies”, IEEE on PAS, PAS-88, No. 5, May 1975, pp.756-763.
[2] G. J. Berg, “System and Load Behavior Following Loss of Generation:
Experimental Results and Evaluation”, Proc. IEE, London, Vol. 119,
No. 10, October 1972, pp.1483-1486.
[3] F. Illiceto, A. Csyhsm, G. Ruckutuhl, “ Behavior of Loads During
Voltage Dips Encountered in Stability Studies Field and Laboratory
Tests”, Paper T72, IEEE PES Winter Meeting, New York, February
1972, pp.2470-2477.
[4] Y. Sundberg, “The Power Circuit of Arc Furnaces”, Elektro Warme
International, 30, b2. April 1972, pp.693-699.
[5] M. Z. EL-Sadek et al, “A Flexible AC Transmission System (FACTS)
For Balancing of Arc Furnace Loads”, Electrical Power Systems
Research Journal, 1997.
Chapter 3 55
Chapter 4
Voltage Instability Phenomena
4.1 General:
This chapter deals with definition, identification and classification of
the phenomena of voltage instability. After displaying the definitions of
voltage instability, its mechanism, causes, types, forms, factors affecting its
occurrence and its consequences are presented. It explains the concepts and
mechanism of steady-state voltage instability and transient voltage instability.
Loads provoking these phenomena are clarified. Their role is explored.
(d) Voltage Flicker: occurs mainly with arc furnaces or arc welding or
repetitive pumping loads. This is shown in fig. (4.4). Voltage flicker has
usually a very slight drop in voltage magnitude, but in a repetitive manner
at frequencies of (5-20)Hz. This type may destroy the eyes retain or may
be annoyant for human eyes. Voltage flicker causes undesirable irritation
for consumers eyes and may destroy there retains.
Chapter 4 19
(f) Voltage Failure: When voltage disappear completely for certain times,
it is called voltage failure. Some times thus occur in the form of spikes.
noticed by Weedy [1] in 1968. Recently, it has found that the phenomena can
occur in seconds or milliseconds. This has early called, in ref. [2], "Transient
Voltage Instability". Opening of one of two circuits feeding large induction
motor loads or clearing short circuits at induction motor load terminals after
certain period recently called in [3] "Critical Clearing Time for Voltage
Stability" or tripping of local generation, near induction motor loads, are
reported to be the three main causes of occurrence of transient voltage
instabilities. They are all related to the presence of induction motor loads.
Other studies showed that these phenomena occur also with repetitively
variable load or with HVDC systems controls failures. In resume, two types
of voltage instabilities are now well known.
(a) Steady-State Voltage Instability: Occurs gradually in minutes,
hours or days and experienced in many countries in the form of voltage
collapses.
(b) Transient Voltage Instability: Occurs suddenly in seconds or
milliseconds, subsequent to network topology variations or short-circuits
at induction motor or tripping of local generators or some parallel lines or
at HVDC terminals with controller failures of either rectifiers or inverters
or at certain operational conditions of repetitively variable loads or due to
presence of arc furnaces loads. This form of instability is the main cause
of several blackouts in the systems worldwide. It occurs in the form of
voltage oscillations or collapse modulated by oscillations or as voltage
flickers.
2 2
2 Pr Qr
2 2 2
Vs A Vr B
2 r r
2 AB P cos Q sin (4.1)
Vr
For each value of generator voltage Vs and load powers Pr, Qr and network
constants A, B, equation (4.1) shows that Vr is of fourth order. Figure (4.6)
shows Vr against Pr for a certain typical system for different constant power
factors. Each value of load power P1 can be consumed at two values of
terminal voltages V1 and V2. The first value V1 is a stable value slightly less
than the no-load voltage Vs. While the latter value V2 is an unstable value.
Consumption of P1 under voltage V2 will be accompanied by drawing
excessive currents and consequently by heavy losses and important voltage
Chapter 4 19
drops and heating of lines, transformers and switchgears. Having the load
operates at a stable voltage V1 and allowing the load power to increase to P2,
its voltage will fall to V3. Increasing the load more and more until the critical
voltage reaches (at which the two values of voltages coincide), critical
situation is attained. No further increase in load power is possible. Any slight
power impact, at this situation will cause the load voltage to move to a value
lower than the critical value. The load power will decrease more and more
and settle at a value P4 in the unstable range determined by system
parameters. No body can find analytically these unstable voltage values,
because of divergence of load-flows at these situations. It is noticed that
heavy load impacts forces the unstable voltage to reach zero (or it looks like a
virtual short-circuit, without any material short-circuit at that load node).
Further partial load shedding may allow the load to restore its stable voltage,
e.g. if P3 is reduced to P1, V3 will go to V1, as shown in fig. (4.6). During
gradual impacts, the voltage may oscillate between stable and unstable values
according to load power value.
Fig. 4.6 P/V Characteristics of a load node with constants load power
factors
If the link of the two nodes system represents two parallel lines and one of
them is tripped out, dashed lines of fig. (4.6) give its new characteristic. At
that time, the maximum power and the corresponding critical voltage
decreased. The same powers P1, P2…etc, will be fed at lower voltages as
shown fig. (4.6). If any of the powers P1, P2 ...Pn is more than the critical
powers of these new P/V characteristic curves, no stable operating point
exists. Thus if the load power does not cope with the system power capacity,
system fails to feed that load, i.e. complete voltage failure will occur or
complete blackout is then experienced, in the steady-state conditions.
96 Voltage Instability Phenomena
In figs (4.7), (4.8) P/Q/V load node system characteristics are plotted
for different constant values of Q= (0, 1.5 and 3) pu. Superimposed on that
network P/Q/V characteristic, the transient power/voltage trajectory of the
load behavior, just after one line opening of the double circuit transmission
link. Figure (4.7) is plotted for 100% constant impedance load and fig. (4.8) is
plotted for 50% constant impedance and 50% induction motor load. When
load reactive power level increases, the maximum static power limit denoted
by the point where voltage/power characteristics reverse direction, decreases.
The other set of curves (a1, b1, c1) in figs. (4.7), (4.8), represent the system
characteristics when one circuit of the transmission line is tripped while
keeping constant the equivalent external network voltage source. It is clear
that tripping one line circuit results in lowering the respective power limit for
each load reactive power level. Also, for the same real and reactive power
loads the terminal voltage drops.
With a purely static load, both load real and reactive powers decrease
as the load voltage drops as shown in fig. (4.9). While, with presence of
induction motor load, fig. (4.10) shows exponential increase of reactive power
when voltage drops, slight decrease of active powers. Therefore, when one
line circuit is tripped in this case a stable dynamic operating point is reached,
however with a lower voltage magnitude as shown by the trajectory (d) in fig.
(4.7). With induction motor loads, fig. (4.8), however, no stable operating
point exists when one line circuit is tripped and both load voltage and power
collapse after some initial oscillations shown by trajectory "d" in fig. (4.8).
This is due to the dynamic characteristics of the induction motors reactive
power, shown in fig. (4.10). The final steady-state condition settles at an
unstable voltage point on P/V curve c 1, although it has firstly oscillates
around several stable points on curves a1, b1, drawn for one line opening case.
Sometimes, no operating point is reached and state of voltage failure is
attained.
Chapter 4 19
Fig. 4.10 Transient P/Q/V response of 50% induction motor and 50%
constant impedance after one line tripping
Chapter 4 11
V Vo e t k sin t (4.2)
With ranges (330-400) sec. and f ranges (5-6) cycles/sec or ranges (36-
40) rad/sec and k ranges (0.003-0.005). Values of =332, =35.9, and
k=0.004 are reported by some authors.
(f) Welding machines of any size can provoke voltage instabilities, as their
loading vary between no-load and short-circuit intermittently. Moreover,
their reactive power demand is very excessive, because of their very poor
power factor (0.2-0.3).
(g) Induction motor load, which is the more familiar load in both domestic
and industrial applications. It is the main source of voltage instabilities
especially when it has no power factor correction capacitors. Induction
motor load consumes heavy reactive power at lower voltages. For any dip
in its terminal voltage, its reactive power increases nearly exponentially.
This process is repetitive for each successive voltage dip. At voltages
lower than 0.8pu, induction motors can go to standstill. The motor will not
provide any mechanical power to its load shaft, i.e. it behaves as a
transformer with air gap between its primary and secondary magnetic
circuit. This is shown in fig. (4.11) for voltage dips of 30% and 50% at
terminals of a typical isolated induction motor
(h) Street lighting lamps of large numbers and without corrective
capacitors (power factors of 0.39-0.58).
100 Voltage Instability Phenomena
(i) Large inductive furnaces and large solenoids used for electric
magnets are important reactive power consumers (p.f 0.15-0.3).
(j) Large electrochemical plants (such as aluminum smelters, soda
chloride reduction plants, and metal coating plants and water analysis
units) are other sources for voltage instabilities.
(a) (b)
Fig. 4.11 Characteristic of induction motor load reactive power and slip
due to voltage dips
(a) 30% voltage dips (b) 50% voltage dips
To sum up, HVDC systems and induction motor loads are reported to be the
severest loads provoking voltage instabilities. Arc furnaces, however, provoke
voltage flickers which is a special sort of voltage instability, which not only
affect the other loads operation but also annoy the human eyes and can
destroy their retains.
other. Unstable loads, such as energized induction motors failed to start (at
stand-still) or HVDC system with partial loss of reactive power compensation
or a large load with partial short-circuits will draw heavy currents and reactive
powers from the system and will trigger voltage instability or lead to voltage
collapse. On the other hand, a system suffering from voltage collapse or
instability due to any reason (such as lowering of generator voltages or
malfunction of their controls) will lead to load instability for all of its loads.
X s Qr Rs Pr
V Vs Vr (4.4)
Vr
P2 Q2
Ploss 2
R
(4.5)
V
P jQ
I (4.6)
V
I p 2
/ V 2 Q 2 / V 2 and V IR2 IX 2 .
Irrespective of the sign of Q, the magnitude of I is function of Q. Therefore
voltage instability is more probable.
Problems
4.1 What are the causes of voltage instability of power systems?
4.2 What are the consequences of voltage instability on power system
operational conditions?
4.3 Explain the mechanism of occurrence of steady-state voltage
instability in power systems.
4.4 Explain the mechanism of occurrence of transient voltage instability in
power systems.
4.5 What are the aspects of occurrence of voltage instability?
4.6 Define both of voltage instability and load instability and give the
interrelation between them.
4.7 What is the difference between voltage or load stability and
synchronous or inertial or angle stability?
4.8 Steady-state voltage stability and transient voltage stability are two
aspects of voltage stability in time spectrum. Give factors
characterizing each of them.
4.9 What are the main factors contributing to voltage instability?
4.10 Explain how voltage instability is initially triggered.
4.11 What are the main systems usually suffering from voltage instability.
4.12 What are the loads, which tend to provoke voltage instability?
4.13 What is the role of reactive power in initiating or alleviating voltage
instability?
Chapter 4 909
References
[1] A. E. Hammad, M. Z. El-Sadek, "Prevention of Transient Voltage
Instabilities due to Induction Motor Loads by Static VAR
Compensators", IEEE Trans. on Power Systems, Vol.4, No.3, pp. 182-
1190, August 1989.
[2] B. M. Weedy, B. R. Cox, "Voltage Stability of Radial Power Links",
Proc. IEE, Vol.115, No.4, pp. 528 - 534, April 1968.
[3] M. Z. El-Sadek, "Prevention of Repetitive Blackouts in the Egyptian
Power System", Middle East Power System Conference, MEPCON'92,
Assiut University, Egypt, January 1992, pp. 14 - 19.
[4] F. N. Abdelbar, "Control of Dynamic Over-Voltages Due to Load
Rejection and Prevention of Voltage Instability Using Shunt Static
VAR Compensators”, M. Sc. Thesis Assiut University, Egypt 1987.
[5] F. Bourgin, G. Testud, B. Heilbronn, J. Versulle, " Present Practices
and Trends on The French Power System to Prevent Voltage Collapse",
IEEE Trans. on Power Systems, Vol. 8, No. 3, August 1993, pp. 778 -
788.
[6] C. Barbier, J. Barret, "An Analysis of Phenomena of Voltage Collapse
on a Transmission System", Revue General Electric, RGE, Paris, July
1980, pp. 3 - 21.
[7] C. W. Taylor, "Power System Voltage Stability", Book, McGraw Hill,
Inc., New York, 1994.
[8] W. I. Rashed, "Steady-State Voltage Stability Enhancement of Power
Systems", Ph. D. Thesis, Suez Canal University, Port Said, Egypt, 1997
[9] Moneer M. Abu El-Nagaa, "Major Blackouts and Failures of Power
Systems: Main Causes, Consequences and Preventive Measures", 7th
International Middle East Power Systems Conference Ain Shams
University, Egypt, MEPCON’ 2000. March 2000, Vol. 2, pp. 702 - 713.
106 Criteria for Detection of Steady State Voltage Instability
Chapter 5
Criteria for Detection of Steady State Voltage
Instability
5.1 Introduction:
Detection of steady-state voltage instabilities is performed through load
flow techniques or through certain mathematical criteria. Among these
derived criteria: dE/dV criterion, dZ/dV criterion, L-indicator criterion, dP/dV
criterion, critical voltage criterion, load flow formula criterion, modal
eigenvalues criterion and ZLoad/Zsystem criterion. The mathematical formulas of
these criteria are displayed for simple two nodes power systems, to represent
all of the possible power systems configurations. The results of these criteria
can be checked by using the critical voltage value for each case, detection of
transient voltage instabilities call for differential equations models and
eigenvalues or time simulations techniques and is beyond the scope of this
chapter.
In evaluation of the dEs/dVr for the basic two nodes system in fig. (5.1), the
following symbols are used:
Chapter 5 701
It is shown that voltage stability holds when a factor k 'c>0 where k'c is
obtained from dEs/dVr and is defined as:
Q 2V
k c' cos 12 r r cos
Vr Zl
(5.1)
P 2V E
sin 12 r r sin s 0
Vr Zl Zl
Critical steady-state node voltage stability arises when k 'c = 0 and instability
appears when k'c<0. The criterion depends mainly on the partial
differentiation of both load power and reactive power with respect to its
terminal voltage magnitude. Noting that E s/Zl equals the load node short-
circuit current (Isc).
' Q 2V P E
k cos r r sin r s 0 (5.2)
c 12 V 12 V
r X r X
From which:
Q
r 2Vr Pr
I
sc V tan 12 (5.3)
V cos
r 12 X r
As (Isc = Es/X):
108 Criteria for Detection of Steady State Voltage Instability
' Q 2V E
K cos r r s 0 (5.4)
c 12 V
r X X
Qr Es 2Vr
(5.5)
Vr X cos 12 X
Qr I sc 2Vr
(5.6)
Vr cos 12 X
Qr 2Vr
cos
12 V
I
sc
(5.7)
r X
This gives a relation between the short circuit current (I sc = Es/X) at the load
point and the other parameters, at this particular load case, eqn. (5.7) is
rewritten as follows and the voltage will be stable, when:
Qr 2Vr
cos 12 I sc (5.7)
Vr X
Noting that (EsIsc) is the short circuit power level Psc of the concerned load
node. For a composite load, Pr and Qr can be represented by polynomials in
Vr, and:
n
1 P n
1
Pr
k
a V and r ka V k 1 (5.9)
k r V k r
k 0 r k 0
n
2 Q n
2
k
Qr b V and r kb V k 1 (5.10)
k 0
k r V k r
r k 0
Which can be substituted into eqn. (5.1) or (5.8) to give k 'c in terms of Vr, X,
Z1, Es, 12 and , and in ak, bk which are system constants. n1, n2 which are
the load powers polynomial orders.
E
k z 2Vr3 Vr E s2 3Vr2 E s cos 12 s Vr2 E s Vr3 cos 12
Vr
12 Vr4 Vr2 E s2 2Vr3 E s cos 12
Vr E s sin 12
3
(5.11)
Pr Qr
2 2
r
V
P Qr
p r r Qr 0
V r V r
Example 5.1:
Check the voltage stability of a power system represented by its
Thevinen's equivalent (E and X) at one of its nodes loaded by a load of
voltage characteristics:
P=3.5V3, Q = 2.0V
The equivalent generator voltage E is calculated at the nominal voltage V=1.0
pu and is kept always constant (E=constant). Use (dZ/dV or dX/dV criterion).
If E is allowed to change, check the voltage stability using the exact (dE/dV)
(or Kc>0 criterion), R is negligible.
Solution:
Using the scalar voltage drop formula:
XQ RP X Q
EV as (R=0.0)
V V
2
EV V 2 EV V E V
X
Q 2V 2 2
E constant: dZ/dV = dX/dV = (-0.5) (system voltage is stable)
X constant: dE/dV = 1.0 (system voltage is stable)
Example 5.2:
A load is supplied from a 275kV distribution bus bar through a link of
reactance per phase to neutral of 70 (ohm) and X/R ratio =5.0. The load
consists of a constant power demand of 200MW, and reactive power demand
which is related to the load voltage (V) by the polynomial: Q = 4 - 8V+5V2
(a) Check the above system voltage stability using the dE/dV criterion
(PL=200MW, at 0.78 p.f lag.)
(b) Check also the above system voltage stability using the dZ/dV
criterion .
(c) If the load power is doubled, check the system voltage stability for
cases (a) and (b)
Take bases of 275kV and 200MVA.
Solution:
Base impedance (2752/200), and X = 70 x (200/2752) = 0.185 pu, R = X/5 =
0.037 pu., E=10 pu. (Assumption). But, P = 1.0 pu at p.f = 0.78 lag.
1.0
I cos1 0.78 1.27 38.74 pu.
1.0 0.78
Chapter 5 777
Example 5.3:
A general nonlinear load having the following load/voltage relations:
Pr Po Vrn and Q r Q o Vrm
The load is fed from an infinite network through a link having a generalized
constant A = 10, B = 0.2389.72o, when the load power vary from zero to
1.0 pu at 0.8 power factor lagging. Initially E = 1.00.0o pu.
Derive a formula for dE/dV, then plot the value of dE/dV r with Vr when it is
changed from zero to unity at the following cases:
(a) m = n = 0 (constant MVA load)
(b) m = n = 1 (constant current load)
(c) m = n = 2 (constant impedance load)
From m = n = 0, Pr = 1.0 pu. Plot dE/dVr for different power factors from 0.7
to 0.9.
Solution:
Having; Pr Po Vrn , and Q r Q o Vrm
Pr Q r
nPo Vrn 1 , and mQ o Vrm1
Vr Vr
dE/dV is given by differentiation of E w.r.t. V r in the eqn. relating E, Vr, A,
B, , , Pr and Qr given in chapter 2, therefore,
112 Criteria for Detection of Steady State Voltage Instability
dE
dVr
2A 2 Vr B 2 2n 2Po2 Vr2n 3 2m 2Q o2 Vr2m3
2AB nP V
o
n 1
r cos β α mQ o Vrm1sin β α /2E
Substitution in the above equation for dE/dV r, by the appropriate values of m,
n and by the different values of powers and load voltage V r, fig. (5.2) shows
dE/dV for (m = n = 0), and for different powers and voltages Vr . fig. (5.3)
shows the same values for (m = n = 1), while fig. (5.4) for (m = n = 2). Noting
here that it was easier to differentiate E w.r.t. Vr than using the formula of the
criterion.
Voj Sj
L j 1 (5.12)
Vj Y jiV j2
Where:
Voj Thevenins equivalent voltage at node j
Sj Node complex power of node j
Vj The larger voltage amplitude or the feasible solution
Yji Admittance between nodes i and j
F jiVi
L max J L Li max J L 1 (5.13)
i V j
G
1 1
Z LL Y LL , and F LG Y LL Y GL F ji
FLG or Fji is a hybrid matrix can be obtained from the following analysis:
V L I L Z LL F LG I L
G H G GL
GG G
(5.14)
I V K S V
114 Criteria for Detection of Steady State Voltage Instability
V L Z LL I L F LGV G (5.18)
Where:
1 1
Z LL Y LL , and F LG Y LL Y GL (5.19)
I G Y GGV G Y GLV L
1 L 1
I G Y GGV G Y GL Y LL I Y GL Y LL Y GLV G
I G K GL I L S GGV G (5.20)
Where:
1
K GL Y GL Y LL
1
S GG Y GG Y GL Y LL Y GL
With:
VL, IL Vector of voltages and currents at consumer nodes
VG, IG Vector of voltages and currents at generator nodes
ZLL, FLG, KGL, SGG Sub-matrices of the H-matrix
Chapter 5 771
The Sub-matrices of the matrix are generated from the Y-matrix by a partial
inversion. For any consumer node, i, j L an equation for Vi can be derived
from the matrix.
Vj Z ji I i F jiVi (5.21)
i L iG
Where:
1
Z LL Y LL Y GL
1
F LG Y LL Y GL
Vs Z S
L 1 s (5.22)
Vr Vr
With:
S = the apparent power.
Z = the transmission series impedance.
Vs, Vr = voltage at generator node, and load node respectively.
Therefore:
L = 0, when Vr = Vs, and L = 1, when Vr = 0.5Vs, and L >1, when Vs > Vr.
P J p J pv
Q J J qv V
(5.23)
q
Where:
P = Increment change in bus real power
Q = Increment change in bus reactive power
= Increment change in bus voltage angle
V = Increment change in bus voltage magnitude
116 Criteria for Detection of Steady State Voltage Instability
Jp, Jpv, Jqv, Jq are the Jacobian matrix elements. At each operating point keep
P (real power) constant, therefore the value of P = 0. Then the eqn.(5.23)
becomes:
0 J p J pv
Q J
(5.24)
q J qv V
0 J p J pv V
J pv J 1
p V
Q J q J qv V
Q J qv J pv J p1 J q V
Q J r V
J r J qv J pv J p1 J q
Jr is a reduced Jacobian matrix of the system. Eigenvalues of this reduced
Jacobian matrix is used as indicator of voltage stability. If all the eigenvalues
of Jr are positive, the system is considered voltage stable. The system is
considered voltage unstable if at least one of eigenvalues is negative. At each
operating point we keep the real power P constant and evaluate voltage
stability by considering the incremental relationship between the reactive
power Q and the magnitude of the bus voltage "V".
Vs
I
Z
2
Z
Z s 1 1
Zs
2 1 cos
12
Zs
I sc
I
2
Z
1 Z 1 2 1 cos
12
Zs Zs
Vs
I sc (5.26)
Zs
According to above equation, the collapse of the system at load bus (i) occurs
when the impedance of the load is equal to the equivalent impedance looking
into the port between bus i and the ground, i.e. Z1 = Zs (or = ZThevenin’s). For a
secure system at bus (i), we must have ZThevenin’s/Zload1, therefore,
ZThevenin’s/ZLoad can be taken as a measure of voltage stability at node (i)
ZThevenin’s/ZLoad = 1 is the critical value. If this value violate unity system
voltage becomes unstable.
1
Pmax
2a
b b 2 4ac (2.27)
1
Vcr 2 K E s2 (2.28)
2A
Where:
K 2 ABPr cos Qr sin (2.29)
And a, b, c are parameters given below for two loading cases: constant
reactive power loads and constant power factor loads. A load having voltage
less than the node critical voltage or having a power more than the node
maximum power corresponding to its critical voltage announces a state of
voltage instability.
(a) (b)
E s2 Ar2Vr2
B2
P r
2
Qr2 2 ABPr cos Qr sin (5.30)
Vr2
Where:
A=A and B=B are the line generalized line constants. Multiply
both sides of Eqn. (5.30) by Vr2, we get:
Vr2 Es2 Ar2Vr4 B 2 Pr2 Qr2 2 ABVr2 Pr cos Qr sin (5.31)
Let:
Chapter 5 771
1
Vr21,2 2 K E s2
2 A
K E 2 2
s
4 A 2 B 2 Pr2 Qr2 (5.33)
Corresponding to Pmax there is one value of Vr, as the two values are
coincident, then the term under the root must vanishes i.e. the term under the
root become zero. The two equal values of the voltages Vr21,2 are thus the first
part only of eqn. (5.33) i.e.
K E 2 2
s
4 A2 B 2 Pr2 Qr2
Or:
2 AB Pr cos Qr sin Es2 2
4 A2 B 2 Pr2 Qr2 (5.34)
Pr in Eqn. (5.35) is Pmax of the node under study. Solution of Eqn. (5.35)
results in two values of Pr, one of them is negative and the other is positive.
Evidently the positive value should be considered.
Therefore:
1
2 a
Pmax b b 2 4ac (5.36)
Where:
a sin 2
cos 2
b
AB
E s 2 ABQr sin
E 4 Q sin E s2
c 2s 2 r Qr2 cos2
4A B AB
Qr Pr tan r
The previous analysis will be valid as:
cos 2
sin 2 Pr2
AB
E r 2 ABQr sin Pr
E 0
(5.37)
4
4 ABQr sin 2 E s2 4 A 2 B 2 Qr2 1 sin 2
s
4 A2 B 2
cos 2
sin 2 Pr2
AB
E r 2 ABPr tan r sin Pr
E s4 4 ABPr tan r sin 2 E s2
(5.38)
2 2
4 A B
4 A 2 B 2 Pr2 tan 2 r 1 sin 2
0
2 2
4A B
2 sin 2 cos tan r sin
2
tan r 1 sin
Pr
2 2
(5.39)
cos 2 tan r sin 2
E s4
0
Pr Er Er
AB AB 2 A B
2 2
Pr in (5.40) is Pmax of the node under study. Solution of eqn. (5.40) results in
two values of Pr, one of them is negative and the other is positive. Evidently
the positive value should be considered. Therefore:
1
Pmax b b 2 4ac
2a
(5.41)
Where:
a sin 2 2 cos sin tan r tan 2 r cos 2
cos 2 tan r sin 2
b Es Es
AB AB
Chapter 5 727
E s4
c 2 2
4A B
Example 5.4:
For the Ward-Hale 6-bus power system, the Thevenen’s equivalent at
node #5 is calculated as: Eth5 = 0.9815-3.1987o pu, Zth5 = 0.08125+j0.31277
pu, the load power at node #5 is kept constant (at 30MW = 0.3 pu), while its
reactive power is varied between 0.18 pu and 0.692 pu. Check the system
voltage stability for these two cases using dE/dV, dZ/dV and L-criterions (P
& Q are constants in each case).
Solution:
For node #5:
Vr5 E th5 IZth5
P jQ (5.42)
E th5 5 * 5 Z th5
V
r5
Application of criteria, we find:
For Q5 = 0.18 pu:
(dE/dV) or Kc = 2.4497, (dZ/dV) or Kz = - 0.036747, V = 0.9 pu
L = 0.2785, (Pmax = 1.3205 pu, Vcr = 0.5136)
So, the system voltage is stable.
This is clear from the voltage, which dropped to 0.49075 pu, it's lower than
Vcr and its phase angle which increased suddenly to -41.8, instead of -13.114
in the stable case. While in the first case the load node voltage is greater than
its critical one.
Example 5.5:
For the IEEE 30 bus system, the load power of a certain node is fixed at
21.88MW (0.2188 pu), while its reactive power was 14MVAR (0.14 pu). The
voltage is then stable. If the load reactive power of that node is changed
122 Criteria for Detection of Steady State Voltage Instability
Vr2 E 2 A2Vr4 B 2 Pr2 1 tan 2 r 2 ABPr cos tan r sin Vr2 (5.46)
Let:
K = cos + tanr sin and S = 1 + tan2r
Thus:
Vr2 E 2 A2Vr4 B 2 Pr2 S 2 ABPr KVr2 (5.47)
Or:
A2Vr4 2 ABPr K E 2 Vr2 B 2 SPr2 0 (5.48)
dV
4 A 2Vr3 r
dV
2 2 ABPr K E 2 Vr r
2 ABKVr2 2 B 2 SPr 0
dPr dPr
4 A V 4 ABP K 2E V dV
2
r
3
r
2 ABKV
dP
2
r
r
r
2
2 B 2 SPr 0 (5.49)
r
Regarding the slope of the voltage/power plot, the voltage is stable when:
2 ABKV r
2
dP
2 B 2 SPr r 4 ABKVr Pr 4 A 2Vr3 2 E 2Vr 0 (5.52)
dVr
2 ABKV r
2
dP
2 B 2 SPr r 2Vr 2 ABKPr 2 A 2Vr2 E 2 (5.53)
dVr
Regarding the slope of the power/voltage plot, the voltage is stable when:
dPr 2Vr 2 ABKPr 2 A 2Vr2 E 2
0
(5.54)
dVr
2 B KVr2 BSPr
From eqns. (5.54), (5.50) dVr/dPr is known by the sensitivity of receiving
voltage w.r.t receiving power, dPr/dVr defines the limit of receiving power
w.r.t receiving load voltage. Regarding to the load node voltage/power
characteristics, the voltage will be stable when dVr/dPr is negative and dPr/dVr
is positive, it will be unstable when dV r/dPr is positive and dPr/dVr is
negative. Using this new concept of voltage instability, dP r/dVr and dVr/dPr
criterion are plotted for a certain system for a 0.9 lagging power factor
(fig.5.7) and for a power factor 0.9 leading (fig.5.8). dV r/dPr are drawn for
different power factors in the lagging and leading ranges (0.7 to 0.9), for the
same system. The figure shows bifurcation of that slope at the critical voltage
and illustrates clearly the stable and unstable voltage zones. Noting that
Vs=1.0 pu and is constant, and the criterion describes the slope of the Vr/Pr
curve for constant power factors. Figure (5.9) shows the dP/dV characteristics
of that system.
Fig. 5.9 dPr/dVr Characteristics of the system for lead, lag and unity
power factors
For the unstable voltage cases, the load flow diverges i.e., load node
voltage Vr cannot be known. Upon separation of the concerned load powers,
load flow may converge and Eth can be obtained. Together with Zth, the load
node voltage Vr can be calculated, using simple formula given in chapter 2,
relating Eth, Zth, Pr, Qr and Vr as a fourth order equation in Vr. The
determination of Thevenen’s equivalent of a large power system can be
summarized in the following steps:
Disconnect its load
With the load node separated, perform a load- flow for the system.
The obtained voltage at the load node represents its Thevenen’s voltage
Eth.
Arrange the system nodes so that all generators are at the top of
nodes.
Kill all generators.
I G Y GG Y GL V G
L LG (5.55)
I Y Y LL V L
Killing all generators of the system means that all generators are connected to
the ground with the result that their self elements Y GG will disppear and
VG=0. Their mutual with load nodes vanish. These mutual should be added to
the self of the load nodes, which are connected to the generator buses "G".
Fortunately they are already included in YLL of the load nodes in the form of
mutual with the generators, before killing.
Therefore, the above Y-matrix become:
I Y V
L LL L
(5.56)
V Z I
L LL L
(5.57)
Where:
Chapter 5 721
Z Y
LL LL 1
Z th V L I L Diag. Z LL , (corresponding to node i) (5.58)
In order to have the same results of all criteria, the following technique is
proposed for calculating the new Zth at each load node. The new proposed
technique can be summarized in the following steps:
(a) Evaluate the admittance matrix [Y] and perform a load-flow solution
to obtain the voltage at each bus.
(b) Disconnect the load at the node at which Zth is to be calculated.
(c) Convert all other loads to constant impedance loads using the
formula:
P jQ
Yii Load i 2 i (5.59)
V
i
Where:
Pi, Qi Load power and reactive power at node (i).
|Vi| The magnitude of the voltage at node (i).
Yii(Load) Equivalent load admittance at node (i).
(d) Modify the system admittance matrix [Y] diagonal elements as:
Yii Yii old Yii Load (5.60)
(e) Eliminate lines and columns corresponding to generator buses to
obtain Ybus (new).
(f) Invert the new reduced Ybus (new) matrix, to get Zbus (new).
(g) The diagonal elements of Zbus(new) which corresponds to node (i) is
the new Zth corresponding to node (i).
(h) All the previous 6 steps should be repeated for any change in the ith,
node loading conditions (Pi or Qi), as the voltage level at all nodes will be
changed and the equivalent Yii (load) will be certainly changed.
loads, which should be known for each load node. Generally special recorders
in all load centers can record the time response of the power, reactive power
and voltage. The P/V and Q/V characteristics can then be found from these
time records at discrete intervals or by using the energy analyzers available
nowadays. Extrapolation technique can determine polynomial orders of these
relations.
P Po a1V a2V 2 a3V 3 a4V 4 a5V 5 ...... (5.61)
dP
a1 2a2V 3a3V 2 4a4V 3 5a5V 4 ...... (5.63)
dV
dQ
b1 2b2V 3b3V 2 4b4V 3 5b5V 4 ...... (5.64)
dV
If the loads are considered as constant power loads, all of the coefficients (a 1,
a2...ai), (b1, b2...bj) vanish and both dP/dV and dQ/dV become zero. Recent
studies gave these coefficients for known individual loads and for some
typical loads. They were displayed in chapter 3.
The six bus Ward-Hall system is selected to illustrate the concept of the
above criteria for detection of degree of steady-state voltage stability of large
power systems. The Ward-Hale 6-bus system, generally used for testing the
new developed techniques in comparison to the known ones, is shown in
fig.(5.10). The system has two generators, 6 nodes, 5 lines and 2 transformers
with tap-changers. For the 6-bus Ward-Hall system, Thevenen’s equivalent at
each load node, with its load separated, is firstly calculated. The Thevenen’s
pu. Voltage and impedance for the load nodes (nodes 3-6) of the 6-bus system
are found in pu to be as follows:
The L indicator, dE/dV, dZ/dV modal analysis and Z th/ZL criterion are
applied for each node and the results are given in table (5.1), for the base case
state. The table shows complete agreement of the results with the six criteria.
Also, it shows the value of the critical voltage for each load node and its
corresponding consumed maximum power Pmax. Lj are all less than unity,
dE/dV are positive, dZ/dV are negative, Zth/ZL are less than unity and all
eigenvalues are positive, for all load nodes (node 3 to 6), which indicate that
all load nodes voltage are stable, and complete agreement of the six criteria is
obtained. The same study was performed in [8] for the IEEE-30 bus system.
Problems
5.1 A large power system is loaded by a load of 0.3 pu power at a load
node has a Thevenen’s equivalent of Eth=1.004-3.20pu,
Zth=0.32275.23opu. Check the system stability for load reactive powers
of 0.18 pu, 0.36 pu, 0.69 pu and 0.72 pu.
5.2 Thevenen’s equivalent of node # 21 of the IEEE 30-bus system is
Eth=0.9535-14.3658 pu, Zth = 0.1485875.24 pu. Its load is p = 0.10 pu.
Find the node critical voltage, then check the system voltage stability for
reactive loads of Q = 0.019 pu, 0.057 pu, 0.107 pu.
5.3 A generator is feeding a load of (1+j1) pu, through a double circuit line,
each has a reactance of 0.185 pu, the resistance is negligible, on 200 MVA,
275 kV base.
Chapter 5 717
(a) Assuming the load power is kept constant at 1.0 pu and the reactive
power is stressed. Find this value of reactive power at which voltage
instability starts to occur.
(b) If the reactive power is kept constant at 1.0 pu and the active power
is increased. To what value the system voltage will remain stable?
(c) Use all known criteria and compare your results.
5.4 A 6-nodes power system is loaded by a load of (0.3 + j0.18) at node #
5. The system Thevenen’s equivalent at that node is V th5=1.004-3.2o pu,
Zth = 0.32375.43o pu.
(a) Check the system voltage stability at that node using all known
criteria.
(b) If the load is doubled, is the voltage stability holds?
(c) What will be the critical load voltage at that node and what will be
its maximum delivered power?
(d) If the load has a leading power factor of the same value, what will be
the new critical load voltage and the new maximum delivered power.
(e) If the load power is kept constant at 0.3 pu and its reactive power is
stressed, what will be the value at which voltage instability starts.
5.5 A 275 kV infinite system feeding a load through a line of 70 ohm
reactance and negligible resistance, Taking a 200 MVA base power
(a) Check the system voltage stability when its load reactive power
varies according to: Q=5V2-8V+4 and the load power factor is varied
between 0.1 and 0.9 by intervals of 0.1
(b) Check the system voltage stability, when its load reactive power
varies according to Q = 5V2 - 8V + 4 and the power factor is varied
between 0.1 and 0.9 leading at intervals of 0.1. What will be the situation
at unity power factor?
(c) Check the system voltage stability when its load power varies with
voltage as P = 2V2 and Q is kept constant.
(d) Repeat (a), (b) when P and Q are doubled.
5.6 The Thevenen’s equivalent of a 6 nodes power system at a certain
operation condition is calculated at node #5 as: Eth = 0.9815 - j3.1987 pu,
Zth = 0.08125 + j0.31277 pu (on 100 MVA base). Node # 5 is loaded by a
load of 30 MW and a reactive power of 18 MVAR
(a) Find the load voltage V.
(b) Check the load voltage stability, using the exact (dE/dV) criterion,
dZ/dV, L-criterion, modal criterion and ZL/Zthev criterion.
5.7 A power system has four load nodes. The Thevenen’s equivalent at
these nodes are found by:
Eth3 = 0.9753-1.023 pu Zth3 = 0.27375.64o pu
Eth4 = 0.9540-9.93 pu Zth4 = 0.22174.81o pu
Eth5 = 1.004-3.20 pu Zth5 = 0.32375.43o pu
Eth6 = 0.9873-3.20 pu Zth6 = 0.23775.54o pu
132 Criteria for Detection of Steady State Voltage Instability
Check the node voltage stability of that system for the following loading:
P3 + jQ3 = 0.55 + j1.3 P4 + jQ4 = 1.0 + j1.0
P5 + jQ5 = 0.6 + j0.36 P6 + jQ6 = 0.5 + j0.05
5.8 For each of the nodes, of problem 5.7, find the load at which the
voltage becomes unstable when:
(a) The load is purely resistive (Q = 0)
(b) The load is purely inductive (P=0,Q positive)
(c) The load is purely capacitive (P=0, Q negative)
5.9 Find the critical nodes voltages for the nodes of problem (5.7) when the
load power factors are 0.7 lead, 0.9 lead, unity, 0.7 lag, and 0.9 lag. Plot
critical voltage values with power factors.
5.10 Assuming negligible link resistance, find critical value of X for
voltage instability for a general two nodes system in the following cases:
(a) A load, which drives a constant power P and a constant reactive
power Q from an infinite bus network through a line of variable reactance
XL (variable length and a short line).
(b) If the load power P is constant and equal 1.0 pu at V = 1.0 pu and
load reactive power in pu varies with terminal voltage according to: Q =
5V2 - 8V + 4.0.
(c) If 90%, 70%, 50%, 25%, 5% of the line reactance XL is compensated
successively by a series capacitor of reactance Xc, determine the critical
voltages in each case and plot them with series compensation percentage.
5.11 A 66KV load of 100 MW at 0.9 power lagging is fed from a 66 kV
supply through a 132 kV line, stepping-up and a stepping-down
transformer. The total impedance of the transmission line and the two
transformers is (2.5 + j66) ohm. Taking a 100 MVA base:
(a) Check the load voltage stability when the load is represented by its
impedance at nominal voltage
(b) Check the load voltage stability when the load is composed of 50%
constant power, 20% constant impedance and 30% constant current.
(c) Check the load voltage stability when the load is composed of 50%
constant power, 20% constant impedance and 30% constant current.
5.12 A load of (0.8 + j0.5) pu, based on 100 MVA base, is fed from a
generating source through a stepping-up transformer of reactance 0.15pu,
double circuits transmission line, each circuit has a reactance 0.4 pu and a
negligible resistance and a stepping-down transformer of reactance 0.1 pu.
Find the load voltage and its maximum power and check its voltage
stability, when the generator is:
(a) With constant excitation voltage( E = 2.52 pu and Xs = 1.5 pu).
(b) With non-continuously acting AVR (E’ = 1.59 pu, X’ = 0.4 pu).
(c) With continuously acting AVR (constant terminal voltage, V t =
1.28).
Chapter 5 711
References
[1] B. M. Weedy, B. R. Cox, "Voltage Stability of Radial Power Links",
Proc. IEE, Vol. 115, No. 4, April 1968, pp. 528-536.
[2] B. M. Weedy, "Electric Power Systems", Book, John Wiley and Sons,
Third edition, 1979, (chapter 8)
[3] A. A. Ahmed, "Control of VAR Flow in Power Systems as Influenced
by System Configuration", M. Sc. Thesis, Assiut University, Assiut
Egypt, 1993.
[4] M. Z. EL-Sadek, M. M. Dessouky, G. A. Mahmoud, W. I. Rashed,
"Improvement of the Steady-State Voltage Stability Criteria Results",
in Fifth International Middle East Power Conference, MEPCON’97,
January 1997, Alexandria University, Egypt, pp. 426-430.
[5] M. Z. EL-Sadek, M. S. Abdel-Salam, A. A. Ibrahim, A. A. Hussien,
"Criteria for Detection of Steady-State Voltage Stability of Power
Systems", Electric Power and Machines Journal, Vol. 25, 1997, pp.851-
864.
Chapter 5 711
Chapter 6
Static VAR Compensators
6.1 Introduction:
Earlier static VAR compensators were saturated reactors shunted by
fixed capacitors or DC–controlled saturated reactors. They were applied since
the mid of the sixteenth. Recent power electronic devices based static VAR
compensators were known and applied since the beginning of the seventeenth.
They were extensively used in the beginning of the eighteenth to replace the
conventional rotating synchronous condensers, in most networks. Several
versions of these compensators are now in service worldwide, others are in
the planning stages. Over 20 applications are already known for these
compensators. They have fast response and offer effective control to power
systems during normal operation conditions and during disturbances.
on the task of the SVC in the system. The control is either switching out and
in or continuous control. So these devices are called switched devices or
controlled devices respectively.
I 2 X
Bc (6.1)
V2
(
b)
With: : thyristors firing angle, and =2-2. The losses with a TCR include
the step-down transformer cooling system, filters and TCR. The firing angle
ranges from 90o to 180o.
(a) (b)
Fig. 6.3 TCR/TSC static VAR compensator
(a) Configuration (b) V/ I Characteristics
6.3.6 Combination of TCR, TSC and TSR’s:
TCRs can be combined with TSCs and TSRs to form static VAR
systems, which have continuously variable outputs from reactive limit to
capacitive limit. The losses for the combined systems are the sum of the
components. TCR provides continuous voltage regulation while it has losses,
harmonics and cost. TSR, TSC assume the frequent requirements of systems.
fig. (6.3) represents also this version of SVC’S but with several reactors with
anti parallel-connected thyristors, instead of one.
(a) (b)
Chapter 6 747
(a) (b)
Example 6.1:
A TCR/FC static VAR compensator is connected to a 138 kV load bus
to improve the network voltage stability. The short circuit-level of the load
bus is 4000MVA and the network frequency is 60Hz. Load flow studies show
Chapter 6 743
that the voltage can be maintained at 1.0 pu at both no load and peak load, if
reactive power of 15MVAR (inductive) and 45MVAR (capacitive) are
injected respectively. The slope of the static VAR compensator is adjusted to
(Vc=0.2%). Find the maximum and minimum load voltage within the
control range. Draw the compensator steady-state characteristics.
Solution:
X (of the system)
kV 2
1382
4.761
MVA sc 4000
138000
Vl n 79674 volt
3
Maximum capacitive current of the compensator = Ic max
Maximum inductive current of the compensator = I l max
Qc 45 106
I c max 188.27 Amp. TCR/FC
3Vl l 3 138000
Q - Qc 60 - 45 106
Il max 62.76 Amp.
3Vl l 3 138000
δVc 0.2 138000
slop But, Vc 159.35 volt
Ic max 3 100
159.35
slop 0.846 volt/Amp.
188.27
VT min 138000 3 0.846 188.27 79515 volts
VT max 138000 3 0.846 62.76 79727.4 volts
Then: VTmin and VTmax are equally 137.724kV and 138.092 kV respectively.
Voltage and current characteristic is shown in fig. (6.6), below.
144 Static VAR Compensators
Fig. 6.7 Losses versus reactive power for different SVC types
Fig. 6.8 Voltage and current waveforms of a TCR at certain firing angle
V 1 π
If π 2α sin 2α 0α (6.3)
ωL π 2
The Fourier analysis gives harmonic current component the nth, by the
expression:
V 4
sin cosn n cos sin nα
In 3
ωL
n n π
(6.4)
Figure (6.9) gives the percentage of the harmonics orders as influenced by the
thyristor firing angles. The Figure shows the percentage amplitudes of the
fundamental component and the odd harmonic currents with respect to the
maximum reactor current against the firing angle, which is calculated from
eqns. (6.3), (6.4).
The principle of controlling the conduction period of the thyristors means that
harmonics generated are 3rd, 5th, 7th, 9th, and 11th, 13th, and so on. The
maximum amplitudes of the 3rd, 5th, 7th, 9th, 11th, 13th, and 17th, harmonics are
13.78%, 5.0%, 2.5%, 1.57%, 1.05%, 0.75% and 0.57% of the fundamental
current of the reactor at full conduction, respectively. With balanced control,
the reactor branches may be connected in delta or if they are connected in
star, their transformers should be connected in delta so as to eliminate the zero
sequence components (or triplen harmonics); that are, the 3 rd, 9th, 15th, ... etc.,
and will not feed into the power system. Only very small parts of these
harmonics will be present in the line current owing to various bridge
asymmetries. Table (6.1) gives the maximum amplitudes of harmonic in
phase and line currents up to the order 37. Noting that triplen harmonics do
Chapter 6 741
not appear in line currents and these maximum amplitudes do not occur at the
same firing angles.
reactors (TSRs), each has "mL" Henry. Since the TCR inductance is increased
to "mL" Henry, then, from eqn. (6.4) the amplitude of each of the odd
harmonics are reduced by a factor "m". Therefore, the amplitudes of the 5 th,
7th, 11th, and 13th, harmonics of the splitted TCR's SVC’s became very small
than those resulting from a single TCR version. A third method, which also
requires two thyristor-controlled reactors, is the 12-pulse connection. This
means that two similar thyristor controlled reactors are used, one being
connected to a star connected secondary winding and the other to a delta–
connected secondary winding of a feeding transformer. Owing to the phase
shift (30 degree) between the voltages in the two windings, the 5 th, 7th, 17th,
and 19th, harmonics are reduced or theoretically eliminated, while the 11th and
13th remain the same as for single large reactor. Reduction of lower-order
harmonics is made also by using (TCR/ TSR/FC) or (TCR/ TSR/TSC) types
static VAR compensators, although (TCR/ FC) and (TCR/TSC) versions are
the more applicable.
feeds this to the priority logic circuit unit which determine the priority of
operation of the SVC, which are either: voltage balancing or load currents
balancing or power factor correction or others. The output of the priority logic
circuit unit is fed to the firing angle calculation stage. Its output is sending to
the firing angle pulses generators for each gate of thyristors. Individual inter-
phases ’s: ab, bc, ca are calculated in this stage. Phase-locked loop or PLL
circuits are used to synchronize the controller to the positive sequence
reference voltage and to control the sequencing program. It synchronizes also
the controller sinusoidal functions outputs to the network voltages and
currents waves. As the programmable controllers run allover the hour,
synchronizing timing circuits are provided to synchronize the inputs with the
outputs in time spectrum.
Figure (6.11) shows the block diagram of a closed loop control system
for a thyristor controlled shunt SVC compensator. The input signal to its
automatic voltage regulator AVR is the terminal voltage V on the HV side of
the transformer. It is measured by conventional voltage transformer, one in
each phase, and converted to a direct-voltage signal in a signal converter #2.
This signal converter consists essentially of a voltage-matching transformer, a
6-pulse rectifier and a low-pass filter having a time constant of about 1.5 ms
to reduce rapid transients in the network voltage.
distribution A/D unit #5 to digital signals (on/off order signals for TSC and
TSR) and an analog signal (control signal to TCR firing angles) whose
magnitude is such that the effective susceptance for the shunt SVC
compensator exactly corresponds to the susceptance reference B ref. It may be
desirable in certain applications to have a certain slope of the current/voltage
characteristics of the shunt compensator. This may be accomplished in the
way shown in, for example, in fig. (6.11), by means of a feed-back of the total
compensator current It (inductive current Ir plus the capacitive current Ic).
This current is then measured with conventional current transformer and
converted in a signal converter unit #1 to a direct current signal V 1. This
signal, which has different signs for inductive and capacitive current, is fed to
the summing junction of the regulator in such a way that it corresponds to an
increase or a decrease of the voltage reference for inductive and capacitive
current, respectively. The control system also include a synchronizing unit #3,
which ensures that the regulator signals are updated and that firing pulses are
given exactly the right instant. A linearization block may be added at the
output of Bref. Recent artificial neural network signals or adaptive self tuning
signals or fuzzy-logic signals or neuro-fuzzy signals or adaptive pole
placement or pole assigned signals may be added at the input summer of the
regulator in order to improve SVC effectiveness in improving power system
stabilities.
152 Static VAR Compensators
Fig. 6.12 Time response of a typical existing SVC compensator for a step
change in network voltage
A typical system time response of a large power system, provided by
TCR/TSC-SVC, for a step change in the SVC node voltage, for 0.25 sec is
shown in fig. (6.12). A substantial reduction in the network node voltage has
been brought about by switching of a 100 MVAR inductive load at the SVC
node. After 0.25 s the inductive load was switched out again so that the
conditions return to normal. From the oscillogram record it can be seen that
the total time response for both the voltage reduction and the subsequent
increase, is about 2 cycles (0.04 s). The oscillogram of fig. (6.12) shows also
the shape of variation of the virtual equivalent TCR reactance B ref, the shape
of the error signal V, together with the total compensator current It, the
TCR inductive current Ir, the TSC capacitive current Ic and the SVC node
voltage V.
V kH
H (6.5)
VT 1 STH
1 slop 1 ST2
G1 (6.6)
1 ST1 1 ST3
Slop is the droop slope of the voltage regulator, (T 2, T3) are time constants of
the lead-lag regulator compensation circuits. The controller output is fed to
the firing angles circuits represented by a gain Kd and delay Td with transfer
function.
Chapter 6 713
kd
G2 k d e STd (6.7)
1 STd
Vt Vo (6.8)
Vt Vs Vr Vt H GX (6.9)
1 GX
Vt Vs Vr (6.11)
1 GXH 1 GXH
1 GX
Vt Vs Vr (6.12)
1 GXH 1 GXH
Vt 1
(6.13)
Vs 1 GXH
Chapter 6 711
slop 0
0
X
Vt 1 slop
0.5
slop (6.14)
Vs X 1
1 slop
X 0
1
Vt Vs (6.15)
The no-load SVC node voltage after compensator connection is given by the
equation (6.9):
Vt Vs Vr Vt H GX (6.16)
This means that the controlled SVC alters its no-load node voltage. Eqn.
(6.14) decides that when the SVC characteristic slope is zero, its terminal
voltage will be constant irrespective on its current variations (Vt=0). The
SVC creates an infinite bus at its node. If the slope is very large, no control
exists and the controller input is nearly zero. All variations in system voltages
will completely appear at compensator node (Vt = Vs). If the system
equivalent series reactance X equals the controller droop slope, any variations
in system voltage at the compensator node will drop by 50% due to presence
of its controller. According to the ratio of the equivalent Thevenen's system's
reactance at compensator node to its controller’s droop slope, the compensator
terminal voltage variations sensitivity to system voltage variations ranges
from 0% to less than 100%. Without compensator, it becomes 100 %.
Example 6.2:
A static VAR compensator is connected to a 138kV (1.0 pu) load bus to
improve the network voltage stability. The short circuit-power of the load bus
is 4000MVA and the network frequency is 60Hz. Load flow studies show that
the voltage can be maintained at 1.0 pu at both no load and peak load, if
reactive power of 15MVAR (inductive) and 45MVAR (capacitive) are
injected respectively. The slope of the static VAR compensator is adjusted to
3. The time constants of the voltage regulator ate T 1 = 0.02sec, T2 = T3 = T4
=1.0 sec. The feedback time constant is 0.0008 sec. and its gain is 0.99 pu.
156 Static VAR Compensators
The reference voltage is 1.01pu. The delay of the gate circuit is 2.777 x 10 -3
sec. The controller gain is adjusted to 1.0. Find:
(a) The compensator node voltage variations as a percentage of the system
no load voltage. (Sensitivity of compensator terminal voltage to system
voltage variations (Vt/Vs)), with and without the controlled compensator.
(b) What will be this sensitivity when the equivalent network reactance is
very small and very large?
(c) What is the no-load voltage of the SVC node before and after
connecting the compensator?
(d) What will be these values when the slop is 0.846
Solution:
X (of the system)
kV
1382
4.761
MVA sc 4000
G1=1/slop, and G2=1.0; Then: G=G1G2=0.333
ΔVt 1 1
0.389
ΔVs 1 X/slop 1 4.761 0.333
ΔVt 100% of ΔVs (without the controlled compensator)
ΔVt 38.9% of ΔVs (with the controlled compensator)
(b) ΔVt 100% of ΔVs if X 0
ΔVt 0.0 % of ΔVs if X
(c) V(no-load)=0.61 pu. (if there is no SVC connected)
V(no-load)=Vs+(Vr-VtH)GX=0.86 pu (when SVC is connected)
1 1
(d) G G1G 2 1.182 ; Then:
slop 0.846
ΔVt 1
0.15
ΔVs 1 4.761 0.846
ΔVt 15% ΔVs if slop 0.846
This means that at no-load conditions, the SVC node terminal voltage
variations will be only 38.9% of the node voltage variation without presence
of that controlled compensator. It will be 50% if the controller droop slope
equal the node equivalent reactance. It will be 15% of system voltage when
the slop goes to one-tenth its original value. The SVC node voltage variation
vanishes completely if the TCR/FC slope is zero. All system voltage variation
appear at the SVC node when there is no SVC controller (slope = infinity)
Therefore, the compensator rating will equal to B comp in pu at V=1.0 pu. Bcomp
equals the physical susceptance of the fixed uncontrolled capacitors and
equals to the equivalent Bref.
For the controlled TSC or TCR-controlled SVC, the rating of the controlled
SVC is given by:
XQ RP
Bcomp Bref Vref H Vs I s X s G (6.18)
Vt
I s Bref Vt Vref HVt G (6.19)
For the fixed uncontrolled capacitors, the rating required to maintain certain
voltage is given by:
Vt Vs
X Q Bcomp Vt 2 RP
(6.20)
Vt
From which:
XQ RP
Vs Vt
Vt
Bcomp
XV (6.21)
t
Studies have proved that for maintaining the voltage at the same value, the
controlled SVC requires less rating than the uncontrolled fixed capacitors.
The rating is proportion to the gain G or to the inverse of the droop slope of
the compensator.
Example 6.3:
A power system is represented by its Thevenen’s equivalent at certain
node. It was E=1.004-3 pu, Zs=0.3275 pu. The system is loaded by a load
P+jQ = 0.3+j0.7 pu at that node and is provided by a static VAR compensator
whose G =1/8.9, KH =0.99, Vref =1.0 pu. Find the compensator rating when it
158 Static VAR Compensators
Therefore, the controlled SVC needs less rating than the uncontrolled
capacitor for the same voltage maintenance purposes.
2 2 (6.22)
Where is the firing angle required to get certain Bl (); which is given by:
sin sin
Bl Bl . max (6.23)
X l
Where: Xl represents the fixed reactance X of the TCR compensator, B lmax its
reciprocal. is the conduction angle. Therefore, the compensator current at
fundamental frequency still be:
sin
I l V Bl V (6.24)
X l
Chapter 6 711
V Vk jXI (6.25)
sin
Bl Bl . max (6.26)
Which has a nonlinear relation with the voltage, i.e. the characteristic V/I will
not be linear or straight characteristic as shown in fig. (6.3). In order get a
straight linear relation of V with I, a linearizer circuit should be incorporated
in the control circuit, just after the conduction angle calculator, its transfer
function will be: K2/(-sin). This will leave:
sin K 2
Bl Bl . max K 2 Bl . max (6.27)
sin
Or it will be certain linear fraction of Bl.max (rated fixed value of the TCR at
V=1 pu). Therefore the current I will be:
Where:
K K1 K 2 Bl. max
Where K1 is the regulator gain and BV is the variation in the reference SVC
susceptance multiplied by the TCR terminal voltage V.
160 Static VAR Compensators
The system short circuit level at compensator node affects its response
that is as the system short circuit level is low; the compensator response will
be faster, but less stable. On the other hand, with high short circuit levels,
compensator response will be slower or it will be not effective. Addition of
current control loop to the basic voltage control loop (fig.6.10), improves the
accuracy. If the gain of this loop is very high, then the current error is
negligible and the controlled reactive power will be proportional to the
voltage error, independent of the values of the TCR, TSC reactance’s and
independent of the gains of conduction angles calculators and the linearizing
networks and the gating pulse generation. The slope of the control
characteristic is determined by the gain K1. The current error amplifier K2
may be an integrator so that the current error is essentially zero.
This model is most suited for modern techniques of direct solution of power
system networks. If Et is greater than V, then it will represent a static VAR
generator or later static synchronous generator. For this model:
V Et
I (6.29)
jX
162 Static VAR Compensators
For TCR:
2 sin 2
E t Vf V 1 (6.30)
For other types Et should be defined as a function of the device control
system.
The basic feature of this model is that the SVC size (or rating) can be
represented in the linearized, as well as the nonlinear, systems models
implicitly in the fixed reactance X, which is the inverse of the SVC size at 1
pu rated voltage QSVC=V2B=B at (V=1pu), X=1/B, moreover the model can
represent all known types by simply changing its parameters. f(h) is usually
multiplied by a linearizing transfer function to get unity and f(h) block
vanishes.
Fig. 6.15 Controlled TCR/FC with equivalent power system and load
The relation of the SVC terminal voltage V and the currents balance at
the SVC node gives the following relation which interrelates the system
Chapter 6 763
parameters, the load admittance (Gl +jBl), the TCR parameters (or rating Bd),
the controller action represented by the factor K, and the fixed capacitor
susceptance Bc, together with the system. Thevenen’s equivalent voltage Es
and susceptance Bs. The TCR static VAR compensator is represented by an
admittance Bd behind an ineritaless voltage source Ec=KV. K represents the
thyristor control action. K should be always less than one. K = 1 represents
the thyristor turn-off state. The actual TCR reactor fundamental current (Ic) is
given by:
V Ec
I c jBd V KV (6.31)
max
jX
Where:
Bd=1/Xmax
V 1 K
Ic
jX max
jBd V 1 K jBref V j Vref VH GV (6.32)
Vref
HV G
K 1 (6.33)
Bd
2 K
2
2
Gl B s Bl Bd 1 Bc V B s E s
2 2
(6.34)
V
For TSC, Bc vanishes and K will be greater than one. The problem will be in
the value of K, as TSC enters in service in discrete manner and not has
continuous control. This model although seems simple, it presents a large
advantage for power system analyst and offer a good relation between system
parameters and control actions, for certain node voltages V and load
variations requirements.
Q K1V 2 K 2V (6.35)
The constants K1, K2 must be calculated so as to obtain Q=0 at initial voltage
conditions. The load must be changed to a constant reactive load in the region
outside the control limits. For studies of system dynamics in the period of (0.1
to 5) seconds, the control circuitry are represented by block diagrams showing
all necessary functions and nonlinearties, such that shown in fig. (6.16),
which is a general of the SVC.
The output of the block diagram is the per unit admittance B of the
reactor where the per unit base is defined using the reactor’s maximum
output. The output is also shown multiplied by the voltage giving the
absorbed current of the SVC,. The nonlinear block specifies the maximum
and minimum admittance values. CIGRE gave typical values of (100 to 400)
for K and (40 to 150) m.sec for T. For this general model, CIGRE suggested
typical parameters as:
consideration in this model through the value of B max and Bmin, which are the
nonlinear limits of the controller output. In linearized models, the limits are to
be omitted; therefore the size of the SVC cannot be represented explicitly in
the variables of the model. Moreover, taking the admittance of the SVC the
instantaneous value of B, as a system state, complicates the formulation of the
system equations, especially when the network is to be represented by its
passive elements and to be eliminated with the system auxiliary algebraic
variables.
(a) (b)
slope) and 100 per unit (1% slope) on the SVC base. The time constant,
TR, is usually between 20 and 150 milliseconds.
The Lead-Lag Terms: They are often zero. For preliminary
simulations, phase lead can be used to improve damping of oscillations (at
the expense of synchronizing support). The leading terms can also be used
to provide adequate phase and gain margins when high steady state gain is
used.
Integrators: Should be non-windup and provided to feed integrated
signals over certain period instead of instantaneous signals.
The Measurement Circuits: (Fig. 6.19(c))Which convert three
phase voltages and currents to a quasi-dc control signal that is proportional
to the amplitude of the positive sequences and fundamental frequency
content of the measured variable. This is done by instrument transformers,
A/D conversion and computation, and filtering. For fundamental
frequency simulation, the model is a single low pass filter with a time
constant of 1-8 milliseconds. The time constant depends on the actual filter
used. If the network exhibits strong resonance’s near fundamental
frequency, more elaborate filters can be required to maintain SVC control
stability; the low-frequency response of such filters should be modeled if
significant. Because of the small time constants, they are not considered
part of basic models.
Thyristor Firing Circuits: Transfer function fig. 6.19(d) shows the
model for the delays associated with thyristor firing T d is the gating
transport delay with a value of about one millisecond and T b represents
the effect of thyristor firing sequence control with a value between three
and six milliseconds. It illustrates that SVC control has short
characteristics which, when combined with variation in power system
circuit can lead to control instability.
The Thyristor Susceptance: Control module, fig.6.19(d),which can
be modified to represent discontinuous switching of TSC and TSR types of
SVCs.
Linearizing Function: The nonlinear relationship between Bref and
the TCR firing angle is compensated by a linearizing function in the
thyristor susceptance control. Since firing angle is not represented
explicitly in fundamental frequency models, the linearizing function is not
represented explicitly.
Damping Signals: Various local or remote input signals (with
appropriate phase compensation) can be used for damping .Possibilities
include line power or current, bus frequency or voltage, apparent
resistance, and speed or frequency differences from remote locations can
be included. They are called damping signals.
Network Interface: The SVC interface with the network can be
either of two methods. The variable susceptance, B, can be used to update
168 Static VAR Compensators
(a) (b)
Fig. 6.20 IEEE model 2 of closed loop controller
(a) General Structure (b) Voltage regulator
6.9.6 Data Required For IEEE Models 1 and 2:
Data required for such controllers are: Qmax (Inductive) and Qmin
(Capacitive) in MVAR at one pu high-side voltage to selecting Bmin and Bmax
respectively. Total SVC MVAR is required beside the voltage regulators
parameters KR, TR, T1 and T2 for IEEE model 1 and KSL, K1 , Kp and Tp for
model 2. Correspondence of parameters of the two models can be made by
assuming Tm=T1=T2=Tp=Td=Tb=Ts=Kp=0 the KR=1/KSL and TR=1/(KSL K1).
Typically a gain of KR=33.3 per unit on the SVC base and a time constant of
TR=100 milliseconds may be used for a moderately strong system. All other
time constants may be neglected. The gain corresponds to a 3% slope. Line
outage disturbances may be simulated, and the time constant adjusted to
provide a fast, well-damped SVC response. Slope values in the range 1-5%
are usually used.
Fig. 6.22 Detailed model of a TSC system with closed –loop voltage
regulation
an equivalent special sampling interval equal to one sixth of one cycle of the
network voltage (T/6, where T is the time for one cycle).
Figure (6.23) shows an approximate model. A device connected to the
bus concerned and having a linear and continuously controllable susceptance
B represents the main circuits. The control circuits are approximated
accordingly. The model can accept the dead time due to the filter time
constant (1/f) and the dead zone. This dead time may be short or long. For
small error signals, the average voltage is quite sufficient to be used. For very
large error signals, such as those appearing on network faults or load
rejections, the maximum time required to switch on or off all the capacitors
approaches one cycle of the network voltage. Based on the simulations shown
by many authors, the conclusion was drawn that the approximate model is
satisfactory for most transmission systems simulations for the fundamental
frequency effects.
Fig. 6.24 SVC models with slope representation using conventional power
flow PV bus
Problems
6.1 What are the main components of static VAR compensator?
6.2 What are the CIGRE and inertialess SVC models features?
6.3 State the types of static VAR compensators in use in industry.
6.4 Give the IEEE modeling of static VAR compensators controls?
6.5 What is the need for existence of transformers with static VAR
compensators?
6.6 State the practical application of static VAr compensators in power
systems
6.7 Static VAR compensators are important source of harmonics
generation. Quantify the maximum percentage of each harmonic order
generated from TCR type?
6.8 A static VAR compensator is connected to a 132kV-load bus to
improve the network voltage stability. The short circuit power of the load
bus is 5000MVA and the network frequency is 50Hz. Load flow studies
showed that the voltage can be maintained at 1.0 pu at no load and peak
load is reactive power of 100MVAR (inductive) and 40 MVAR
(capacitive) are injected. The slope is adjusted to 3%. The time constants
of the voltage regulator are T1 = 0.02 sec, T2 = T3 = T4 = 0. The feedback
time constant is 0.0008sec. The delay of the gate circuit is 2.777 X 10 -3
sec. Find:
(a) The maximum and minimum load voltage within control range. Draw
the compensator steady-state characteristics, when the compensator is
TCR/FC type and of TCR/TSC type.
Chapter 6 711
References
[1] M. Z. El-Sadek, "Optimization of Static VAR Compensators Parameter
for Damping Power Systems Oscillations", Ph. D. Thesis, Swiss
176 Static VAR Compensators
Chapter 7
Flexible AC Transmission Systems
FACTS
7.1 Introduction:
Flexible AC Transmission Systems abbreviated by FACTS forms a
new domain in power system control engineering, using power electronic
devices and circuits and the more recent available technologies in automatic
control and valves. Some of these FACTS are pure power electronic devices,
others are power electronic elements applied to conventional electrical
circuit's elements and connected to the electrical networks. Some devices are
to be connected in series; the majorities are shunt-connected devices. Few
versions of these FACTS are now in use. Numereous concepts are suggested
in the literature. They were named FACTS, as early as the beginning of the
1990’s. Recent IEEE convention gave definitions and a specific name for
each type of these FACTS so as to have unified terminology worldwide.
Static VAR compensator known since 1970’s was its first element. This
chapter aims to present briefly these new devices and to illustrate their
components, jobs, functions and role in power systems control. Their actual
and future possible applications in control of power systems electronically
and statically are clarified. Utilities will use extensively these devices and
new other concepts may appear in the near future, following to the progress in
power electronics and control engineering developments.
zero time or with time delay of thyristor operation. In these devices the
reactors are linear air-cored reactors connected in series with thyristor. The
amount of the inductive reactive power can be adjusted by changing the firing
angle of the thyristors. In switched versions, of reactors or capacitors
thyristors firing angles are zero and 180o.
I2X
Bc (7.1)
V2
Chapter 7 989
a
b
c
Icb Ia Ib Ic
Icc c c
Bcab Bcbc
B bc B ab
Ica
Bcca
Control
Bcca system
jX tr jX a jX b (7.2)
VS V R
Pmax (7.3)
X tr
jXa jXb
Load
P+jQ
XS jBC() XR Load
P+jQ
(a) (b)
Thus if BC() is capacitive, X'tr will be less than Xtr, the maximum power of
eqn. (7.3) will be more than without FACT element. On the other hand if
BC() is inductive (or negative), the transfer reactance X 'tr will be more than
Xtr and the maximum transmitted power is less than that drawn without
FACTS. The network configuration is changed by addition of X S and XR at
the source and load terminals respectively. This will change the current
distribution and changes the load voltage VR, if VS is kept constant, according
to:
P jQ VR
VR VS jX tr' (7.5)
* jX
V R R
P jQ
VR VS j X a X b (7.6)
*
VR
MSC MSR
Control
System
Measurement of
voltage and current
Control Qref
Firing angles
186 Flexible AC Transmission Systems FACTS
P
At DC Terminal
Idc + Vdc - DC Terminal
Energy
-Vdc -Idc Idc Vdc
Source
Energy Storage
Absorbs P Supplies P
reactive power flow, the three-phase inverter output voltage E1, E2, E3 should
be in phase with the system bus or the three-phase terminal voltages V1, V2,
V3. By controlling the inverter output three-phase voltages E1, E2, E3 the
reactive power flow can be controlled; increasing E above the amplitude of V,
for any phase of the system phases, causes leading current to be drawn from
the AC system. Where as decreasing E below V produces a lagging current
flow from the system.
io
+
V1 i1
V2 i2 Vo
V3 i3
_
(a)
(b) (c)
source inverter may be fed either from a DC voltage supply as shown in fig
7.8 (a) or from a fixed capacitor C as shown fig 7.8 (b)
V1 V2 V3
io1 E1 iDC
io2 E2 Static DC
Inverter Voltage 3-phase
io3 E3 VDC
Supply
AC lines
3-phase
Inverter
DC
Phase
Capacitor
io1 E1 iDC shifting
Transformer
io2 E2 Static
Inverter VDC C
io3 E3 Harmonic
Filter
(a) (b)
rating of the converter is one half of the maximum leading or lagging output
provided. This is simply done by simple connections of the converters with
the supply in a feedback manner, as shown in fig. 7.9(b). The power doubling
circuit diagram using three-phase, 6-pulse bridge type frequency changer is
given fig. 7.9(c).
V1 V2 V3
VL1 IL1
io1 E1
io2 E2 Static VL2 IL2
AC to AC
io3 E3 Changer
VL3 IL3
AC system
0
V1 V2 V3 1
I01 L E1=kV1 VL1=V1
Static
I02 L E2=kV2 Frequency VL2=V2
I03 L E3=kV3 Changer
(L=-0) VL3=V3
I01 V1 L kV1 V1
Static
I02 V2 L kV2 Frequency V2
Changer
I1 I03 V3 L kV3 (L=-0)
V3
I2
IL1
I3 IL2
IL3
(b) (c)
Fig. 7.9 (a) Static voltage source using AC/AC frequency changer
(i) Conventional arrangement with separate high-frequency AC source
(ii) Self-sufficient operation from LC tank circuits (HF base)
(b) Power doubling arrangement
Chapter 7 919
+
Vo,a i1
Vo,b i2 Vdc
Vo,c i3
_
(a)
Coupling
Transformer
Magnetic structure
for multi-pulse waveform fabrication
multi-pulse inverter
+Vdc
(b)
192 Flexible AC Transmission Systems FACTS
Similarly, the real power exchange between the inverter and the system
is made by phase shifting the inverter output voltage with respect to the AC
system voltage by a special control system. That is, the inverter supplies real
power to the AC system, from its DC energy storage, if the inverter output
voltage is made to lead the corresponding AC system voltage. By the same
way, the inverter absorbs real power from the AC system to its DC energy
storage, if the inverter output voltage is made to lag the AC system voltage.
part in the generation of the reactive power. In other words, the inverter
simply interconnects the three output terminals in such a way that the reactive
output currents can flow freely between them. Viewing this from the
terminals of the AC system, one could say that the inverter establishes a
circulating power exchange among the phases, although reactive power is
internally generated by the action of the solid-state switches, it is still
necessary to have a relatively small DC capacitor connected across the input
terminals of the inverter, to cover the SSG losses or to provide active power
to the AC system.
Coupling
Transformer
Magnetic structure
for multi-pulse waveform fabrication
(a) (b)
synchronous condenser. For this reason that specific SSG arrangement which
generates only reactive power, is called static synchronous compensator
(SSC) or static compensator (STATCOM) or static condenser (STATCON) or
advanced static VAR compensator (ASVC).
AC system VT At the AC terminal
Iq Supplies Q
Coupling V1>VT Vac
Q Transformer
V1 V1<VT Absorbs Q
Iq
Multi-pulse
At the DC terminal
inverter
Idc=0 +Vdc
Vdc
Idc=0 - DC Terminal
+
0
(a) (b)
Fig. 7.13 Static synchronous compensator or static compensator or static
condenser (a) Configuration (b) Modes of operation
junction temperature at which the devices are operated. The ability of the
STATCOM to produce full capacitive output current at low system voltage
also makes it highly effective in improving the transient or first swings
stability. The characteristics of the STATCOM are superior to those attainable
with the conventional thyristor-controlled static VAR compensator (SVC).
Transient
Transient Rating
Rating VT
Transient
VT
Rating 1.0
1.0 0.9
0.9 0.8
0.8 0.7
0.7
0.6
0.6
0.5 0.5
0.4 0.4
0.3 0.3
IC ICmax ILmax IL
0 ICmax 0 ILmax IL
IC
(a) (b)
Energy I*qR
External Control
Storage
The basic control loop of the external control is set up to regulate the
terminal voltage by means of controlling the reactive component of the output
current is shown in fig (7.15). The amplitude VT of the terminal voltage is
measured by the voltage measuring and processing circuits. This measured
voltage amplitude is compared with the reference voltage V R. The difference
between these two, the error signal V is amplified and processed in the error
processor and amplifier to provide the reference signal Q R for the reactive
output current. Power oscillation damping and the minimization of the first
rotational swing can be accomplished by the modulation of the reactive
component of output current, or by the modulation of the real component of
output current, or by the modulation of both. The control of the real power
exchange between the SSG and the AC system is done by modulating the real
component of the output current around zero (or around a fixed real power
reference). If the SSG is set to absorb from, or supply to, the AC system real
power during disturbances.
(a) SSC or the static synchronous compensator acts like an ideal controlled
static condenser. It is able to maintain the maximum capacitive output
current at any system voltage down to zero. Its V-I characteristic is superior
to that obtainable the thyristor-controlled static VAR compensator whose
maximum capacitive output current decreases linearly with the system
voltage.
(b) Because of this V-I characteristic, the VA rating of the static
compensator, used for voltage support and transient stability improvement,
can be reduced significantly below that required for a static VAR
compensator.
(c) If the static compensator is equipped with a suitable energy storage
device, it can also be used for load leveling and the minimization of power
outages.
(a) (b)
Fig. 7.16 Series static synchronous generator
(a) Configuration (b) Possible operating modes
Vpq Va
V0 +V0 VC
V0 VC V0 Va
V0
V0 Vpq
V0 V0
V0 V0
V0 +V0+VC V0 +V0+Va
I
V jKXI (7.7)
V jIKX c (7.8)
Where: Xc is the impedance of the series capacitor, and V/I is the voltage drop
by the capacitor current.
The series reactive compensation scheme based on this principle is shown in
fig. (7.18). The effect of this compensation on the transmittable power can be
seen from the expression for a simple two machine:
V2
P sin
(7.9)
X 1 K
With K is a continuous variable (0<K<1), V is the terminal voltage, is the
load angle, X is the inductive reactive series line reactance. For normal
capacitive compensation, the output voltage must lag the line current by 90
degrees, as illustrated in fig. (7.18), in order to directly oppose the inductive
voltage drop of the line impedance. However, the output voltage of the
inverter can be reversed by simple control action to make it lead the line
current by 90o. In this case, the injected voltage is in phase with the voltage
developed across the inductive line impedance and thus the series
compensation has the same effect as if the reactive line impedance was
increased. This capability can be exploited to increase the effectiveness of
Chapter 7 101
power oscillation damping and, with sufficient inverter rating; it can also be
used for fault current limitation.
VC
i CT Vac
Transmission
Line
Vac PT
I
VC
impedance input ZR and the RMS amplitude of the line current I obtained via
the current measuring and processing circuits.
I L
CT
Z()
PT
Pm
IL VT
V,
Current Frequency
Measuring Variation
and or Power
Internal Processing Flow
AC Power System Inverter Circuits Measuring
Control Circuits
IL
+ Z*R f or
∫Pdt
+ - V*qR X
Energy V*dR
External Control
Storage
Fig. 7.19 Basic control scheme for static synchronous series compensator
Vpq
Input Transmission line I
Supply transformer Series transformer V0 V/0
Inverter 1 Inverter 2
DC Link
Cap.
GTO GTO
AC AC
DC DC
Fig. 7.20 Basic circuit of the unified power flow controller (UPFC)
753 A
150 MVA Load
T1 T3 T7 T5
TS TS
115 kV
Exciting Transformer
(As element can also be WYE connected)
energized. If they are fully off, the segment is denergized. Figure (7.22)
shows a schematic diagram of such TLTCT arrangements.
Tapped
Transformer Load
b VB2
VsA
c
Generator
Varistor
Field
Armature
Varistor
(a) (b)
Spark gap
Chapter 7 101
VLoad
Zload Zload Zload
Firing angles
Normally off
AC Rectifier
DC/AC Inverter
Main
Supply
Static
Switches Critical
Load
Batteries
Super-
conductive
coil
Three-phase
system
212 Flexible AC Transmission Systems FACTS
VT
ْjBs GL ْjX
BL
Es kV
7.12 Summary:
Implementation of static synchronous generators, static synchronous
compensators, static synchronous phase shifters and unified power flow
controllers will result in a significant reduction in equipment size and
installation labor, as well as in eliminating the reactors and power capacitors
associated with losses and heating. Furthermore, the uniform all electronic
devices can greatly reduce manufacturing cost and time by allowing the use of
standard, pre-fabricated power inverter modules for different applications.
The static electronic series devices offer fast responses and damp power
system oscillations and counter measure the harmful subsynchronous
resonance problems initiated by traditional series capacitors or of HVDC
systems in AC networks.
Problems
7.1 What are the meanings of flexible AC systems?
7.2 What are the elements of any flexible AC transmission system?
7.3 What is the difference between controlled and switched elements?
7.4 What will be the future of applications of the FACTS?
7.5 Static synchronous generators will soon replace static VAR
compensators. Explain?
7.6 What are the main differences between static VAR generators and static
VAR compensators and static synchronous generators?
7.7 Describe all known schemes of FACTS
Chapter 7 191
References
[1] Y. A. Mubarak, "HVDC System Performance with New Controls",
M.Sc. Thesis, Aswan High Institute of Energy, Aswan, Egypt, 2001.
[2] J. Arrillaga, "High Voltage Direct Current Transmission", Book,
London Peter Peregrinus, 1983.
FACTS (General-Definitions –Concepts):
[3] N. G. Hingorani, "High power electronics and Flexible AC
Transmission System", Joint APC/IEEE Luncheon Speech, April 1988,
American Power Conference 50th Annual Meeting, Chicago, IEEE
Power Engineering, July 1987.
[4] N. G. Hingorani, "FACTS-Flexible AC Transmission Systems", IEEE
International Conf. on AC and DC Power Transmission, London,
Publication No. 345, pp. 1-7, 1991.
[5] FACTS Overview, "Published by CIGRE and IEEE PES", 1995,
Reference IEEE 95 TP 107.
[6] A. A. Edris, "Proposed Terms and Definitions for Flexible AC
Transmission system (FACTS)", IEEE Transaction on Power Delivery,
Vol. 12, No. 4, October 1997.
[7] M. Z. El-Sadek et al, "A Flexible AC Transmission System (FACTS)
for Balancing Arc Furnace Loads", Electric Power System Research,
Vol.41, 1997, pp. 211-218.
[8] M. E. Ahmed, "Improvement of Power Systems Operation Quality
Using Flexible AC Transmission Systems (FACTS)”, M.SC. Thesis
Assiut University, Assiut, Egypt, 2000
SSG-SCC (or STATCOM or STATCON or ASVC):
[9] Y. Sumi, Y. Haramu, T. Hasegawa, M. Yano, K. Ikeda, T. Matsuura,
"New Static VAR Control Using Forced Commutated Inverters", IEEE
Transactions on PAS, PAS-100(9), 4216-4224,1981.
[10] P. M. Bhagwat, V. R. Stefanovie, "Generalized Structure of a
Multilevel PWM Inverter", IEEE Transactions on Indusrial
Applications, Vol. IA-19, No.6, Nov/Dec 1983, pp. 1057-1062.
[11] LUIS T. Moran et al, "Analysis and Design of a Three-Phase
Synchronous Solid State VAR Compensator", IEEE Transaction on
Industry Applications, Vol. 25, July/August 1987.
216 Flexible AC Transmission Systems FACTS
Chapter 8
HVDC Systems Operation and Control
8.1 Introduction:
High voltage direct current HVDC systems are widely used in power
systems transmission industry. They solve most of power system synchronous
stability with long distance transmission of electric power from waterfalls
hydraulic generation stations to large load centers. They are the only means of
power transmission in the cases of connection of different frequency areas,
connection of areas having different control systems philosophies and
connection of areas with under sea connections between their countries and
Islands. Also, DC transmissions save conductors, towers and eliminate
inductance and virtual capacitances from transmission links calculations.
Recent progress of industrial electronic devices, circuits and controls
encouraged strongly the use of HVDC systems. The ease of power control of
HVDC systems by firing angle variations is another important factor. The
progress of power electronics will also solve the problem of the DC circuit
breakers and large power capacities will be available in the near future.
8.2 Historical:
Initial applications of electricity were lighting and traction, utilizing
DC in relatively confined geographical locations that did not required
transmission distances. The early designed lighting supply stations installed
by Edison on 1882 in London (80kW at 110V), in New York (600kW at
110V), and the London underground supply of 600kW at 500V. They were all
DC power stations. In 1890 since 1891 and invention of AC transformers, the
three-phase AC transmission lines were built every where. While it seems
obvious to us now that AC should be the predominant means of power
transmission, this was not so obvious in the 1890’s. Edison’s Pearl street
station which was indeed 110V DC, and the Edison-Westing-House debates
between DC and AC transmission a forward by the invention of AC power
transformer. Concurrently, the thury system of series connected DC machines
found acceptance in Europe-at least 19 of these were installed between 1880
and 1911.
220 HVDC Systems Operation and Control
(d) The fourth one: starts from Zaier to republic of Middle Africa
to Chad to Sudan and back to the first line at Aswan in Egypt.
Egypt will be connected to Libya to Tunisia to Morocco. Three
connections between Africa and Europe: The first between Morocco and
Spain, the second between Tunisia and Italy and the third between Egypt to
Jordan to Syria to Turkey and Europe. Three other DC lines will transmit a
projection of that power to the southern countries of Africa, to form a multi-
terminal African DC network by three circuits.
(a) The first through: Zaier to Angola to Namibia to South Africa.
(b) The second is through Zaier to Uganda to Kinia to Tanzania to
Mouzambiek to Zimbabwe to Zambia to South Africa (Britoria).
(c) The third one is through Zaier to Zambia to Zimbabwe to
Botswana to South Africa (Britoria). Africa will be connected to Asia
by the interconnection Egypt to Jordan, to Iraq and Iraq to Iran and
Jordan to Saudi Arabia to Golf Emirate from the Asian extensions.
Break-even
AC
Distance Distance
AC (+) AC
System System
Optional
(a)
(+)
AC AC
System ( ) ( ) System
(-)
(b)
(-)
AC
(+) (+) AC
System
System
(-)
(c)
Chapter 8 992
8.8.1 Converters:
They perform AC/DC and DC/AC conversion, consist of valve bridges
and transformers with tap changers. Converter transformers connected in
star/star and star/delta arrangements feed the converter. The ratings of a valve
group are limited more by the permissible short circuits than steady state load
requirement.
AC power AC power
system #1 DC DC system #2
smoothing smoothing
reactor reactor Circuit
Converter breaker
Id
Y/Y Y/Y
Transformer Transformer
Earthling Electrodes
Y/ /Y
DC line
AC filter DC filter Inverter
Rectifier DC filter AC filter
static VAR static VAR
compensator compensator
(SVC) (SVC)
228 HVDC Systems Operation and Control
Valve firing signals are generated in the converter control at ground potential
and are transmitted to each thyristor in the valve through a fiber-optic light
guide system. Rectifier and inverter are controllable by firing circuits
generation.
8.8.6 Electrodes:
The connection to the earth requires a large surface area conductor to
minimize current densities and surface voltage gradients. If it is necessary to
restrict the current flow through the earth, a metallic return conductor may be
provided as part of the DC line.
8.8.7 DC Lines:
Overhead lines or cables, DC lines are very similar to AC lines, except
for the number of conductors and spacing required as well as insulators
numbers. Towers are different than those with AC lines.
8.8.9 Controllers:
Both rectifiers and inverters are provided with sophisticated control
systems. P, PI, and PID controllers are used. Recent control systems include
voltage dependent current order limits (VDCOL), compensators and firing
angles calculators in sinusoid forms cos or cos . DC current controllers are
also used. Local controllers are provided for each side. A master control
controlling the two sides simultaneously is a must.
While Back-to-Back systems are used mainly for adjacent systems with
different frequencies or adjacent systems with different control techniques
8.11 DC to AC Losses:
A DC transmission system when compared with a three phase AC
system transmitting the same power and having the same size of conductor.
The ratio of AC line loss to the corresponding DC loss is 1.333, assuming
equal power transfer and equal peak voltages for both options.
t
A
0 3
A0
Fig. 8.6 Voltage waveforms showing the effect of overlap during
commutation
Chapter 8 921
The transfer of current from one phase to another requires a finite time, called
the commutation time or overlap time. The corresponding overlap or
commutation angle is denoted by , shown in fig. (8.6). During each
commutation period, the current in the incoming valve increases from (0 to
Id), and the current in the outgoing valve reduces from (Id to 0).
In normal operation, the overlap angle is less than 60; typical full load
values are in the range of (15o to 25o). If (60o 120o), an abnormal mode
of operation occurs in which alternately three and four valve conduct. In
fig.(8.6) the effect of the overlap is measured by subtracting an area A from
the area Ao, once every 60o (/3rad). The voltage reduction due to
commutation overlap, the corresponding average voltage drop (due to
overlap) is given by, Vd=3A/ then:
Vdo
Vd cos cos (8.1)
2
3
Or: Vd Lc I d (8.2)
With commutation overlap and ignition delay, the direct voltage is given by:
I lm 2 3 I d (8.4)
I l1
6 Id (8.5)
With losses in the converter neglected, the AC power must equal the DC
power. Therefore:
3Ell I l1 cos Vd I d (Vdo cos ) I d
Substituting for Vdo from above and for Il1 from equation (8.5) we have:
3Ell
6 I d cos 3 2 Ell I d cos
The term cos is referred to by some authors as the (vector power factor) or,
(displacement factor). The converter thus operates as a device that converts
alternating to direct current (or direct to alternating current) so that the current
ratio is fixed but the voltage ratio varies with the ignition delay caused by grid
or gate control.
cos cos
Vd Vdo cos Vd Vdo (8.7)
2
3 2 cos cos
Vd
Ell
2
With losses neglected, AC power is equal to the DC power: Pac = Pdc, hence,
Chapter 8 922
3Ell I l1 cos Vd I d
3 2 cos cos
Ell I d
2
6 cos cos
I l1 cos
(8.8)
2
With =0o, I l1 6 I d denoting this value of Il1 when =0o by Il1o,
equation (8.8) can be written as:
cos cos
I l1 cos I l1o (8.9)
2
Where:
I l1o 6 Id
As an approximation Il1 may be considered equal to Il1o:
I l1 I l1o
6 Id (8.10)
The converter has essentially fixed current ratio (Id/Il1), the variation with load
being only a few percent. It follows that the power factor is given by:
cos cos
cos (8.11)
2
Hence:
V
cos d (8.13)
Vdo
The power factor cos, depends on load in addition to ignition delay angle ,
from rectifier DC voltage (equation 8.3), hence:
234 HVDC Systems Operation and Control
Rc I d
cos cos (8.14)
Vdo
3 2
Vd Ell cos
(8.15)
2
I trms Id (8.16)
3
Ell Vdo (8.17)
3 2
transformer connections required are more complex than those for 12-pulse
converters are. Therefore, it is more practical to use 12-pulse converters and
provide the necessary filtering.
3 2
V do BaEll
(8.19)
Since voltage drop per bridge is (3Xc/)Id and there are (B) bridges in series,
the DC voltage is given by:
Where: B, and a are the number of converter bridges, and off nominal tap
ratio of transformers respectively. The average DC output voltage of a 12-
pulse bridge is twice that of a 6-pulse bridge converter, the RMS value of the
fundamental frequency component of the total alternating current and the
power factor are given by:
I L1
6 BaId (8.22)
AC system Smoothing
reactor
+
Ld
DC system Vd
Y-Y -
(a)
AC system
Smoothing
reactor
Y-
Ld
+
DC Vd
system
-
Y-Y
(b)
Fig. 8.7 Six and twelve-pulse bridge converter
(a) Six pulse (b) Twelve pulse
236 HVDC Systems Operation and Control
Rcr
+ Id +
Vdor cos Vdr
- -
The main assumptions made in the development of the basic rectifier model
are: Control action on delay angle is considered to be instantaneous, no tap
changing takes place during or after the disturbance, the DC current is
smooth, and There is no harmonic distortion. The output voltage is thus
obtained:
Example 8.1:
The transformer primary line voltage to a three phase connected
rectifier is 220kV, and the off nominal tap ratio is 0.8, the rectifier delay angle
is 15o. Calculate:
(a) The direct voltage output for: Overlap commutation angle (=0o,
=20o, and=40o)o.
(b) The effective reactance XC if the rectifier is delivering 1000A, AC
voltage is 250kV, (=20o, and =0o)o.
(c) Repeat parts (b) for (=30o).
Chapter 8 922
Solution:
(a) Given that, Vll = 220kV, and a = 0.8,then we have equation:
Vdo 3 2 π aVll , then Vdo 237.68 kV
Using equation:
V
Vd do cosα cosα μ
2
Then: for =0o, Vd 229.58 kV , =20o, Vd 212.14 kV , and =40o,
Vd 182.95 kV .
(b) For equation:
Vdor 3 2 π aVll 270.09 kV
V
Vd do cosα cosα μ , then Vd 261.95 kV
2
And rectifier equation is:
Vdr Vdor cosα 3X cr π I d , then X cr 8.52 Ohm
(c) For =30o. Vdr 203.75 kV , and then; X cr 31.57 Ohm
V
Vd Vdo cos do cos cos
2
V
Vd do cos cos (8.24)
2
The transitional value of the ignition delay angle, t beyond which inversion
takes place is given by: cos t cos t 0 , or t t t , thus
the delay angle corresponding to start of inversion is:
t (8.25)
2
This angle is less than 90o. The effect of the overlap is thus to reduce t from
90o to (90o -/2). Since valves conduct in only one direction, the current in a
converter cannot be reversed. A reversal of Vd results in a reversal of power,
238 HVDC Systems Operation and Control
an alternating voltage must exist on the primary side of the transformer for
inverter operation. The direct voltage of the inverter opposes the current, as in
a DC motor, and is called a counter voltage or back voltage, shown in fig.
(8.9) for description of rectifier operation, we use the following angles:
Rectifier Inverter
Iac
Id
t
r
i
Fig. 8.9 Angles used in the description of rectifier and inverter operations
cos cos
Vd Vdo
2
Based on the above equations, the inverter may be represented by the two
alternative equivalent circuits shown in fig. (8.10).
Rci - Rci
+ Id + + Id +
Solution:
(a) For inverter equation is
Vdi Vdoi cosγ 3X ci π I d
Vdoi 3 2 π aVll 261.45 kV
Then: γ cos1 0.911 24.35o
The overlap angle for equation
V
Vd do (cosγ cos(γ μ))
2
cos(γ μ) 0.6188 and μ 27.416o
(b) The output inverter DC power and power factor are:
Pdi Vdi I d 160 MW
V
cosφ i d 0.765o
Vdo
(c) The magnetizing VAR input to the inverter
Q i Pdi tanφ i 134.71 MVAR
For the relations is:
240 HVDC Systems Operation and Control
The direct current Id that flows from the rectifier to the inverter and, the
sending end power can be expressed as:
V Vdi
I d dr (8.28)
Rdc
+ +
Id
Vdr Vdi
Vdor Vdoi cos Vdoi
Vdor cos
- -
CC Control CC Control
Id Id
Rectifier
Id
Imarg
Inverter
3
Vdi Vdoi cos min X Ci I d
Iordr
Id Id
Vr CIA Phase Phase CEA Vi
Control advance advance control
CC CC
control control
Fig. 8.14 Schematic control diagram of HVDC with CIA, CC and CEA
control
Vdr Vdi
ISr ISi
Vr Vi
Vdr 3 2 Br a r Vr cos r 3Br X cr I d (8.33)
I sr 6 I d
Where:
I sr I r a r
Then:
I r ar 6 I d
Here r is the rectifier’s delay angle, and Xcr is its commutating reactance per
bridge. The application of KVL in the DC link gives:
Vdi 3 2 Bi aiVi cos i 3Bi X ci I d (8.35)
Here i is the inverter’s extinction angle, and Xci is its commutating reactance
per bridge. The power relations are given by:
The base AC and DC current can thus be calculated, we concluded that the
base DC current is 3 times the base AC current.
I dc B 3I ac B (8.38)
This system enables us to write the condition that power in AC side is equal
to the power on the DC side in a computationally simple way.
Vd I d 3Vll I l cos
Then:
Vd pu V B I d pu I dc B 3Vll pu V B I l pu I ac B cos
3I ac B
Or: Vd pu I d pu V I l cos
I dc ll pu pu
B
Vd pu I d pu Vll pu I l pu cos
I l pu
3 2 I d pu (8.39)
Example 8.3:
246 HVDC Systems Operation and Control
A HVDC link has the following parameters: Xcr = 45 ohms, Rdc = 4.5
ohms, and Xci = 42 ohms. The transformer primary AC line voltage terminals
to a three-phase connected rectifier is 260 kV, and the off nominal tap ratio
for rectifier, inverter side are 1.05, and 1.03 respectively. When delivering
400MW at 300kV DC. The inverter operates with an extinction angle of 24 o.
Calculate:
(a) The delay angle of the rectifier.
(b) The AC line current and power factor at the rectifier terminals.
(c) The power factor at the inverter terminals.
(d) The extinction angle at 0.25 full load current.
Solution:
(a) The DC current Id is obtained as:
400 10 3
Id 1333.33 Amp.
300
The rectifier equation is applied. Thus,
Vdr 3 2 π a r Vr cosα r 3X cr π I d
As a result, the delay angle is r =14.275o
(b) The AC line current is related to the DC current by
I l 6 π I d , thus I1 = 1039.59Amp.
The AC power at the rectifier satisfies
Pac 3a r Vl I l cosφ r , then cosr =0.8137
(c) The voltage equation of the DC line is:
Vdr Vdi I d R dc , then Vdi=294.0kV
The inverter equation is applied. Thus,
Vdi 3 2 π a i Vi cosγ i 3X ci π I d , then Vi=273.44kV
The AC line current is the same as that for the rectifier. The power at the
inverter is given by: Pdi Vdi I d , then Pdi=358.565MW
For a loss-free inverter, the AC line power is Pac=392.0 MW
The power factor at the inverter AC terminals is obtained as:
cosi 0.773
(d) The extinction angle at 0.25 full load current is obtained from:
V cosα r Vdoi cosγ i
I d dor then; =21.1o
R cr R dc R ci
These results are shown in figure 8.16(a) the curve between the extinction
angle and DC load current
Example 8.4:
Chapter 8 942
Solution:
(a) From the data at the inverter we have
500 10 3
Il 1167.78 Amp.
3 1.03 0.8 300 10 3
Thus:
I d π 6 I l 1497.73 Amp.
The DC voltage at the inverter terminals is calculated using
Pdi Vdi I d
Vdi 333.83 kV
The inverter voltage equation is
Vdi 3 2 π a i Vi cosγ i 3X ci π I d
As a result, γ i 19.27
The rectifier voltage is now obtained using
Vdr Vdi I d R dc , then Vdr 340.57 kV
The rectifier voltage equation is
Vdr 3 2 π a r Vr cosα r 3X cr π I d
As a result, Vr 288.37 kV
This is the required line voltage at the rectifier AC terminals. The power input
to the rectifier is obtained from
Pdr Vdr I d , then Pdr 510.09 MW
The line current at the rectifier is the same as that at the inverter, and for a
loss-free rectifier,
Pac Pdc , then cosφ r 0.8328
(b) The delay angle of the rectifier when half load is passed through that
link is obtained from equation,
V cosα r Vdoi cosγ i
I d dor
R cr R dc R ci
α r 12.37
These results are shown in figure 8.16(b) the curve between the firing delay
angle and DC load current.
n angle[Deg]
30 20
angle [Deg.]
25 16
12
20
248 HVDC Systems Operation and Control
(a) (b)
Fig 8.16 The effects of DC load currents on the extinction, and firing
delay angle (, and )
(a) Extinction angle () (b) Firing delay angle ()
8.23 Multi-Terminals HVDC Systems (MTDC Systems):
A multi-terminal DC (MTDC) system has more than two converter
stations, some of them operating as rectifiers and others as inverters. The
simplest way of building a MTDC system from an existing two terminals
system is to introduce tapping some where in the DC line. Parallel operation
of converters and bipolar can also be viewed as multi-terminal operation. The
complexities of control and operation increase considerably. The specific
areas of applications for MTDC systems: bulk power transmission from
several remote-generating stations to several load centers, asynchronous
interconnection between adjacent power systems, and reinforcing of an AC
network which is heavily loaded.
1 2 1 2
3 4 3 4
AC system
AC system
(a) (b)
Fig. 8.17 Simple diagram of the MTDC bipolar scheme connection
(a) Parallel (b) Series
DC system
Vd3 side Vd4
a3 Inverter a4
Ac system
(3) side (4)
V4
V3
The rectifier (1) voltage and inverter (1) voltage on the DC part of the system
are related by:
The model of the inverter (1) is similar to that of the rectifier (1). Thus the
following equations apply:
The rectifier (2) voltage and inverter (2) voltage on the DC part of the system
are related by:
Vd 2 Vd 4 R24 I d 4 (8.56)
The model of the inverter (2) is similar to that of the rectifier (2). Thus the
following equations apply:
The rectifier (1) voltage and rectifier (2) voltage on the DC part of the system
are related by:
Vdsp3 Vd 3 0 (8.61)
Vdsp4 Vd 4 0 (8.62)
Vd 3I d 3 Pdsp3 0 (8.67)
Vd 4 I d 4 Pdsp4 0 (8.68)
(1) V1 V2 (2)
Rectifier
AC system
I1 side I2
a1 a2
R24 Id
R13 Id DC system
side
a3 Inverter a4
Ac system
(3) side (4)
V4
V3
Then the direct current from the DC voltage on the system side of the rectifier
(1) can be obtained by:
Where, (Id) is the DC current related from the rectifier #1, and constant of the
all network. The DC voltages of all the other rectifier and inverter are related
from the DC line equations and related by:
Vd1 Vd 2 R12 I d
Vd 2 Vd 4 R24 I d
Vd 3 Vd 4 R34 I d
Vd 3 Vd1 R13 I d
Then the summations of the DC voltages are equally zero, or related by:
V d 1 V d 2 V d 3 Vd 4 0 (8.71)
From the models of the rectifier and the inverter, the firing angles and the
extinction angles are obtained from the following equations:
From the direct voltage of all DC sides of the converters and the active power
balance between the AC and DC sides the following equations apply:
256 HVDC Systems Operation and Control
Vd 4 Vdsp3 I d R34
Vd 2 Vdsp3 I d R31 R12 (8.79)
Vd1 Vdsp3 I d R31
Vd 3 I d Pdsp3 0 (8.84)
Start
Solve AC equations
No
cos 1, and cos 1
Yes
Stop
Fig. 8.20 Flow chart AC/DC load flow for MTDC systems
Example 8.5:
Figure (8.21) shows a single line diagram of a four terminal HVDC
system. Assuming that the current generated from rectifier station #2 is
divided equally between lines (2-1) and (2-4). Find:
(a) The extinction angle of inverter station # 3.
(b) The extinction angle of inverter station # 4 when its AC voltage is 100
kV, 200 kV, and 300 kV and the power of this inverter.
(c) The total system losses.
258 HVDC Systems Operation and Control
I1 I2
a1 = ? a2 =1.04
Vd3 Vd4
P3 = ? Xc3 = 25 XC4 = 20 P4 = ?
3= ? 4= ?
I3 I4
a3 =1.03 a4 = 1.04
Solution:
(a) We start at the rectifier labeled #2. The DC current is related to the voltage
by: Vd2Id2 500 103
As a result, the rectifier is voltage equation is written as:
500 103 Id2 3 2 π 1.04 300cos14.3 3 25 π 103 Id2
Solving the quadratic equation, we get Id2 1328.24 A
From which,
500 103
Vd2 376.44 kV
1328.2347
The current Id21 is equal to the Id24 .As a result:
Id21 Id24 Id2 2 664.12 A
Vd1 Vd2 Id21R 21
Then Vd1 363.16 kV
` Vd4 Vd2 Id24R 24
Then Vd4 363.16 kV
The current Id1 is obtained from: Pd1 Vd1Id1
Chapter 8 952
Example 8.6:
Solve example 8.5, when the system is operated as series multi-
terminal HVDC system. The converter #2 controls the system DC voltage and
current. Converters #3, #4 are connected with line has R 34 = 10 ohms, the DC
current flows from station #2 towards station #1. Assume that a 1=1.02,
1=19.085o and 2=26.835o. and all other data are the same. Find the stations
AC voltages V1, V3, V4 and the power factor at inverter #4.
Solution:
The DC voltage and currents of station #2 are the same as in example
8.5, then: Vd2 = 376.44 kV, Id = 1328.24 Amp.
Then:
Vd1 = Vd2 - 20 Id/1000 = 349.875 kV
Vd3 = Vd2 - 30 Id/1000 = 336.593 kV
Vd4 = Vd2 - 40 Id/1000 = 323.310 kV
Then the AC voltages are calculated from:
3 2
V1 Vd1 R c1Id a1cosα1 275.19 kV
π
3 2
V3 Vd3 R c3Id a 3cosγ1 280.28 kV
π
Similarly:
3 2
V4 Vd4 R c4 Id a 4cosγ 2 278.32 kV
π
To get power factor of inverter #4:
6
I4 Id 1035.6 Amp.
π
Pd4 Vd4Id 429.433 MW
This method is very slow to be practical. Whereas the delay angle can
be controlled very fast by using the grid or gate control system. However, this
method causes the converter to consume an excessively large amount of
reactive power. Therefore, it is usual to operate the rectifier with minimum
delay angle and the inverter with minimum extinction angle in order to
achieve the control with minimum amount of reactive power consumption.
Figures (8.22), (8.23) shows the elements of a recent converter controller.
+Idmar
K
1 STr
V V
cos o
cos
Eo
0
Current regulator +Vcea -1
Delay angle
determination
Vd Vd Rectifier E operating
Inverter CEA E operating CIA Point
Point
min Inverter
1 Inverter CEA
2 CC
Rectifier
Rectifier 3 CC
CC
Id Id
Imarg
Most schemes used to date have used the above modes of operation for
the rectifier and the inverter (fig. 8.14). However, there are some situations
that may warrant serious investigation of a control scheme in which, the
inverter is operated continuously in current control mode and the rectifier in
(min) control mode. Each DC converter operates in the required mode of
control: constant current (CC), constant ignition or delay angle (CIA), or
constant extinction angle (CEA).
CC CC CC CC
I1 I2 I3 I4 Id
(a)
Vd
Combined
rectifier C/C.
Combined
Imar
inverter C/C.
I2 I3+ I4 I1+ I2 Id
(b)
Fig. 8.25 Control characteristics of parallel connected MTDC system
(a) Individual converter characteristics (b) Overall characteristics
Vd
CIA
CC
Vd Combined
Vd I1
rectifier C/C.
CIA
Combined
inverter C/C.
CC
Vd I2
CEA Imar
CC Id
I3 I4 I2 I1
I3
Vd
CEA
(b)
CC
I4 Id
(a)
Fig. 8.26 Control characteristics of series connected MTDC system
(a) Individual converter characteristics (b) Overall characteristics
266 HVDC Systems Operation and Control
Iord Id Iord Id
(a) (b)
Vd Recent characteristics
CIA
Operating points
(c)
Qi Pi tan i
268 HVDC Systems Operation and Control
Since min and Iord are known, for equations (8.43), (8.45), and (8.42) the
rectifier equations are:
Vdr Vdi Rdc Iord
Then:
V K B X I
r cos 1 dr 2 r cr ord
K1arVr K1arVr
Pr Vdr Iord
Qr Pr tan r
Vdr K1arVr cos min K2 I ord I m arg Br X cr 0
Pr Vdr I ord I m arg (8.88)
Qr Pr tan r
With (Vr) known from AC solution, the inverter equations are the following:
Vdr Vdi Rdc I ord I m arg
V
i cos 1 di
K 2 Bi X ci I ord I m arg
K1aiVi K1aiVi
Pi Vdi I ord I m arg
Chapter 8 962
Qi Pi tan i
K a B V cos K1ai BiVi cos
* 1 r r r
Id min
3 3
Br X cr Rdc Bi X ci
Pr Vdr I d* (8.90)
Pi Vdi I d*
Qr Pr tan r
Qi Pi tan i
Read
desired , min , Iordr, Imarg, and min
min
desired Iordr min Imarg
Vr Iac Id
r min Vi
i min i min
r min
r Pr AC system solution Pi i
Pr Vdr I d
Qi Qr i Pr tanQ
Q r
i
Qr Pi Vdi I d Mode
Mode Qi
Mode
1
Qi Pi tan i 1 Mode
2 3
Mode (1):
i min , Id=Iord
Mode (2):
r min , Id=Iord-Imarg
Mode (3):
r min ,Iord>Id>Iord-Imarg
Problems
8.1 An HVDC system having rectifier commutation reactance Xcr=60
ohm, transformer off nominal tap ratio ar=1.03, inverter commutation
reactance Xci=55 ohm, and transformer off nominal tap ratio a i =1.01,
the DC line resistance Rdc=5 ohm. The AC voltage at rectifier side is Vr
= 220kV, while the AC voltage at the inverter side Vi = 225kV. Find the
DC flowing current when the rectifier firing angle is =14o and the
inverter extinction angle =21o.
8.2 For problem 1 plot the DC current when the rectifier firing angle is
varied from zero to 90o by intervals of 10o.
8.3 For problem 1 plot the DC current when the inverter extinction
angle is varied between 5o to 90o.
8.4 Repeat problem 1 for ar and ai are changed between 0.8 to 1.2 for
each.
8.5 Solve example 8.5 when inverter #4 is totally separated together
with line R24. Find the rectifier-firing angle when the AC voltage at
rectifier #2 is 100kV, 200kV, and 300kV.
8.6 Solve example 8.5 with unknown firing angles and AC voltages
100, 200, 200, 400kV.
8.7 The curves shown in Figure (Prob.7) are for a simple single-bridge
rectifier-inverter link. Assume that the rectifier and inverter stations
have identical apparatus and parameters and that the steady state
operating point at the rectifier terminal voltage Vdr is 100kV. Assume
that the DC line has a total loop resistance of 5.0 ohm, a pole-to-pole
capacitance of 0.01 F/m, and a loop inductance of 3.2 mH/m. Use
dimension one-bridge equations.
(a) Determine the rectifier commutating resistance Rc.
(b) Determine the inverter DC average terminal voltage Vdi.
(c) Determine the rectifier-firing angle ( ) at the operating point E.
Vdr
15
120kV
110kV
E
100kV
Id
1000A 1200A
Figure Prob.7
Chapter 8 922
Imarg
References
[1] J. Arrillaga, Amold C. P. and Harker B. J., "Computer Modeling of
Electrical Power Systems", Book, John Wiley & Sons, New York,
1983.
[2] M. E. El-Hawary, "Electrical Power Systems Design and analysis",
Book, Reston, Publishing Company, 1983.
[3] B. M. Weedy, B. J. Cory, "Electric Power systems", Book, John Wiley
& Sons, New York, 1997.
[4] B. J. Cory, "High Voltage Direct Current Power Converters and
Systems", Book, London: Mc-Donald, 1965.
[5] C. Adamson and N. G. Hingorani, "High Voltage Direct Current Power
Transmission", Book, London, Garraway, 1960.
[6] S. K. Gandhi, "Semiconductor Power Devices", Book, Jhon Willy &
Sons, New York, 1967.
[7] B. Jayant Baliga, "Modern Power Devices", Book, John Wiley & Sons,
New York, 1987.
[8] P. Kundur, "Power System Stability and Control", Book, Mc-Graw.
Hill, New York, 1994.
[9] E. W. Kimbark, "Direct Current Transmission", Book, Wiley-Inter-
Science, New York, 1971.
[10] K. R. Padiyar, "HVDC Power Transmission Systems Technology and
System Interactions" Book, Wiley Eastern Limited, 1993.
[11] E. Uhlmann, "Power Transmission by Direct Current", Book, Berlin
Springer-Verlag, 1975.
274 HVDC Systems Operation and Control
Chapter 9
Voltage Control in Power Systems
9.1 Introduction:
Generator internal e.m.f.s are the source of voltages in power systems.
Loads active and reactive powers demand together with network parameters
determine both of load and generators terminals nodes voltages. Control of
power system nodes voltages can be achieved either:
By acting on generators excitation.
Or, By acting on transmission system elements or variables.
Or, By acting on loads operational conditions.
Or, By combinations of them.
An inherent voltage control is also accompanied with three-phase load
balancing and harmonics minimization. Analyses displayed in this chapter are
devoted to voltage control during steady state or quasi steady-state conditions.
The techniques are used in all conditions.
P2 Q2
Ia (9.1)
Va2
Other inputs are signals to be added to reinforce the system stability, through
power systems stabilizers (PSS), such as generator speed, acceleration,
incremental power or reactive power, rotor angle or derivatives of these
quantity deviations.
Va K g
Gg (9.2)
V fd 1 STdo
'
Where:
Kg Generator gain (Operational variable around 1.04)
Parametric and operational variable (around 0.7)
T'doOpen-circuit field circuits time constant (in the range of 0.02-5sec)
S Laplace transform coefficient
Formula for Kg and will be given later. For unloaded generator, this transfer
function tends to be:
Va 1
Gg (9.3)
V fd 1 STdo
'
Chapter 9 279
1
G E (9.4)
K E STE
With KE = 1.0 for separately excited generators, KE = -0.1 for self excited
generators, TE is in the range (0.5 to 1.0) sec.
To account for the saturation, a virtual feedback signal of the exciter output
voltage is added with gain SF (Efd) which accounts to the difference of the
machine air gap line and the actual load-saturation curve.
1
e STd (9.5)
1 STd
G g 0 K g (9.6)
Both |Va| and Efd are being constant values related by:
Va G g 0E fd K g E fd (9.7)
With:
K g Z K Z K d2 K q2
For a load impedance of |Z| = |R+jX| = ( R 2 X 2 ) and for a generator
having resistance r and reactance’s (Xd, Xq), the coefficient is defined by:
282 Voltage Control in Power Systems
1 r R 2 X X d' X X q
1 X d X d' K d r R 2 X X d X X q
(9.8)
X Xq
Kd
r R 2 X X d' X X q
Kq
r R
r R 2 X X d' X X q
K K d jK q , K K d2 K q2
But:
Va rI a r Z I a r R jX I q jI d e j
Or:
Ea' r R I q X d' X I d j r R I d X q X I q (9.10)
And:
Va I a Z Z I q jI d e j Z K q jK d Ea' e j (9.11)
Thus:
Va Z K Ea' K g Ea'
Then:
Kg Z K (9.12)
K g Va
Gg S (9.13)
1 STdo
'
E fd
For a non-salient pole generator loaded by a pure resistive load and without
AVR, the generator terminal voltage at steady-state conditions may be
expressed as:
Va G g 0E fd K g E fd (9.14)
R
K g
R 2 X q2
And:
R
Va E fd (9.15)
R
2
X q2
Efd is assumed to remain fixed at the value giving |Va| = 1 at no-load, i.e. at
R = . This means that Efd = 1. Therefore;
R
Va for (0 < R < ) (9.16)
R
2
X q2
Va 1
Ia (9.17)
R R 2
X q2
Which gives:
2 2
R2 Ia X q2 I a 1 (9.18)
But:
I a R Va
Then:
2 2
Va X q2 I a 1 (9.19)
This means that when the generator loading current Ia increases, its terminal
voltage falls rapidly. At Ia =1/Xq, the terminal voltage will vanish totally.
Noting that Xq is in the range of 0.6 to 1.0 pu for hydraulic units and of 1.0 to
1.66 pu for thermal units, |Va will reach zero at Ia between 1.0 to 1.66 pu.
for hydraulic units and between 0.6 to 1.0 pu for thermal units, without any
control. The voltage will be between 60% to 70% of its no-load voltage at
nominal current loading, as shown in fig. (9.6).
K A K g
1 K R
Va Vref
A
Vref (9.20)
1 GH K E K A K g
R X q K E K A R
2 2
The reference is chosen so that the generator terminal voltage equal to unity at
no-load condition, or |Va| = 1 when R = . Therefore eqn. (9.20) yields:
KE KA
Vref (9.21)
KA
(K E K A )R
Va (9.22)
2 2
R X q K E K AR
Va ( KE K A )
Ia (9.23)
R 2 2
R X q KE K A R
KE KA
Ia (at R = 0, |Va|=0)
XqKE
Ia 0 (at R = , Ia = 0)
Example 9.1:
Plot V/I characteristic of a non-salient pole generator having Xq = 0.6.
The excitation system amplifier gain is KA = 47, and its exciter gain KE = 1,
with and without automatic voltage regulator. Find the reference voltage
value.
Solution:
(a) Without AVR:
Va =1 pu at Ia =0
Va =0 at Ia =1/Xq =1/0.6 =1.66
(b) With AVR:
Va = 1 pu at Ia = 0
Va =0 at Ia = (47+1)/Xq = 48/(10.6)=80
Noting that the normal range of operation is: Ia = 1 pu only.
(c) Vref = (KE+KA)/KA = (1+47)/47 = 1.02128 pu.
The V/I characteristic is shown in fig. (9.8).
Chapter 9 287
Normally the generator full load current does not exceed 135% of its rated
designed current at nominal voltage and frequency. However, the above
example shows that with controlled excitation of the generator, the voltage
drops to zero at 80 times of the full load current which practically
unattainable and the voltage remains constant in the physically possible
generated current range. The control of the excitation system tends to damp
system voltage oscillations during and after disturbances and prevents the
system from going to the unstable zone.
(a) Operation with fixed excitation and constant no-load voltage (E), i.e. no
regulator action. The generator can be simulated by an equivalent circuit of E
in series with Xs.
(b) Continuously acting regulator i.e. operation with the terminal voltage
varies with load changes in very narrow range. The generator can be
simulated by E and a reactance smaller than the synchronous value,
suggested by experience in practice that a reasonable value would be the
transient reactance (X). Some authors suggest taking half of the
synchronous reactance. This mode is usually applied to most modern
regulators.
(c) Very fast-acting regulators i.e. operation with terminal voltage constant.
The nearest approach to it exists in the forced-excitation regulators used on
generators supplying very long lines. In this type E increases and increases
to keep V = constant, will be beyond 90o. The generator terminals will be
represented by a constant voltage source, irrespective of loading conditions.
(a) (b)
The AVR force up the voltage and consequently increases the power output of
the machine so that instead of power falling after = 90o, it's maintained and
dP/d is still positive. This is shown in fig. 9.9(b) for a machine infinite bus
system.
Example 9.2:
A generator is feeding an infinite bus system through a stepping-up
transformer, transmission line and a stepping-down transformer. Generator
synchronous reactance Xs=1.5 pu and its transient reactance X=0.4 pu.
Stepping-up transformer reactance is 15% while that of the stepping-down
transformer is 10%. Transmission line reactance is 0.2 pu, its resistance is
negligible. All are given on 100MVA base. Normal power is P+ jQ =0.8+j0.5
pu. Find the system transfer reactance, the maximum transferred power and
the generator e.m.f, when the generator operates:
(a) With no AVR
(b) With continuous acting AVR
(c) With fast acting AVR
Solution:
(a) With no AVR: constant excitation voltage, generator reactance is
represented by Xs, therefore:
(X) Transfer = 1.5 + 0.15 + 0.2 + 0.1 = 1.95 pu
0.8 j0.5
E 1.00 o j1.95 2.5838.3o
1.0
And generator maximum power:
Pmax =EV/X=(2.581)/1.95=1.29 pu.
(b) Using non-continuously acting AVR: Generator is then represented by
its transient reactance X and E, therefore:
(X) Transfer = 0.4 + 0.15 + 0.2 + 0.1 = 0.85 pu
0.8 j0.5
E ' 1.00 o j0.85 1.5925.5o
1.0
Generator maximum transferred power:
Pmax =E'V/X=(1.591)/0.85=1.87 pu.
(c) With fast acting AVR: The generator terminal voltage will rest constant
irrespective of generated power. E and both will increase to keep Vt always
constant.
(X) Transfer = 0.15 + 0.2 + 0.1 = 0.45 pu
0.8 j0.5
Vt Constant 1.00 o j0.45 1.2816.4 o
1.0
Pmax =(1.281)/0.45=2.85 pu.
290 Voltage Control in Power Systems
Table (9.1) gives a resume of these three cases and shows numerically the
increase in transferred power with voltage control and the virtual transferred
reactance decrease with that control.
Vs, Vr are the source and load voltages respectively. On the other hand,
in low and medium voltage networks, the voltage difference depends on both
the active load power P and its reactive power Q and is given by:
XQ RP
V V s Vr (9.25)
Vr
Vr V RP
Q (9.26)
X
This equation decides also that for a fixed specified voltage drop |V|, and
load voltage Vr, reactive power injection can compensates for any
changement in load power "P". For example, variation of P to P1 and keeping
|Vr|V = constant, requires variation of drawn Q to:
RP P1
Q1 Q (9.27)
X
It suggests also that even if the load power "P" is kept constant, and the
network elements (R, X) are unchanged, reactive power Q is required to
compensate for keeping any constant voltage drop "V" or to keep Vr
constant.
Moreover, the equation decides that reactive power Q can also compensate for
network elements variations (R, X) which occur during lines opening or
reclosing. Correct sign of injected Q is necessary for the appropriate
compensation.
292 Voltage Control in Power Systems
V1 V2 10 (9.28)
j 2 10
V2 0.894 26.6 (9.29)
1 j 2
Voltage of node #2 dropped by 10.6% from its no-load value, which is
unacceptably low. Now adding shunt admittance B of pure reactive element in
parallel with the load can alleviate this problem, as follows.
Fig. 9.10 Two nodes system with shunt reactance (B) in parallel with load
1 2
V2 (9.30)
1 2 B
2
Noting that, for B = 2 pu, the voltage raises in the capacitive range and
is lower than the nominal no-load voltage. To raise V2 to be equal to V1 then:
1 1 2 B 2 , then B=0.268 pu or 3.732 pu, B=0.268 is selected.
Therefore, any load bus (or connection bus) voltage can be controlled to any
value using shunt reactive element (inductor or capacitor). Also, the degree of
the compensation depends on system reactance B s or on the load node short-
294 Voltage Control in Power Systems
circuit level (Bs). Increasing the short circuit level to certain extent makes
the reactive power compensation is not necessary.
9.3.1.2 Practical Means of Shunt Reactive Power Injection at
Network Busses:
Reactive power injections or absorption’s at network busses can be
achieved either by:
(a) Mechanically switched shunt fixed reactors.
(b) Mechanically switched shunt fixed capacitors banks.
(c) Synchronous compensator (no-load synchronous motor).
(d) Thyristorised static VAR compensators or systems.
(e) Recent proposed static synchronous generators.
(f) Flexible AC Transmission Systems (FACTS)
Vr
1 2
2
t s V s t s t s2V s2 4RP XQ
0.5
(9.31)
Two values of Vr for each value of ts are obtained. One of them is stable, the
other is unstable or undesirable, for corresponding values of t s and tr.
Xs Xt Rs
Q 2 P
Vs t2 t
V Vt (9.32)
t Vt
Vt2 t 2 Vt Vs t Rs P X s X t Q 0 (9.33)
Or:
aVt2 bVt c 0 (9.34)
V sVt V sVt 2 4Vt 2 R s P X s X t Q 0.5
t1
(9.35)
2Vt 2
V sVt V sVt 2 4Vt2 R s P X s X t Q 0.5
t1
(9.36)
2Vt 2
Using eqns. (9.35), (9.36) the off nominal tap ratio of that tap-changing
transformer with various load powers and reactive power are plotted at
different load voltages in figs (9.14), (9.15) respectively, for a certain system.
Figure (9.14) shows the load powers corresponding to load voltages between
Vt=0.8 and Vt=1.2 p.u at different off nominal tap ratios between zero and 1.2
and at constant reactive power.
The figure shows that at lower load voltages, the transformer off-
nominal tap-ratio should be more than 0.75 for stable voltage operations. This
value will be 0.5 for higher voltage cases. Moreover, the maximum allowable
load power is the same for all load voltage levels. The figure decides that
lower off nominal tap ratio are not preferable from voltage stability point of
Chapter 9 297
view and the transformer tapping variations do not affect the maximum power
to be transmitted.
With a certain constant load power, fig. (9.15) shows the reactive
power response at different tapping. Once more, off nominal tap ratios less
than 0.45 will lead to unstable operations of the power system. The maximum
allowable (critical) reactive power is the same for all cases. Transformer
tapping does not affect this value. The range of the off nominal tap ratios is
wider than that with constant reactive power case, for the same voltage levels.
The observed fact that maximum load power is the same at any value of V t
can be explained regarding the values of "t", which are coincident, up on
vanishing the terms under the roots of eqns. (9.35), (9.36).
Fig. 9.14 Off nominal tap ratio/load power at different load terminal
voltages
298 Voltage Control in Power Systems
Fig. 9.15 Off nominal tap ratio/load reactive power at different load
terminal voltages
Example 9.3:
A 132kV-transmission system consists of 132kV line, an 11/132kV
step-up transformer and a 132/11kV step-down transformer, both are provided
by tap-changers. The line and transformer impedance’s amount to
(0.14+j0.33) pu on base 100 MW. The tap ratio (ts tr) equals to unity. The load
in pu is (1+j0.483) pu.
(a) Calculate the setting of the tap-changers required to maintain the
voltage of the load bus bar at 11kV (1 pu).
(b) Find the required reactive power in pu to be injected if the tap ratio
exceeds the limits 20 %.
Solution:
(a) Line voltage is to be completely compensated or:
Vs = Vr = 132kV = 1 pu and (ts tr = 1). In pu, the load is (1 + j0.483)
on 100 MVA base. Application of (9.30) gives:
1
2
1 t s2 1 t s t s2 40.14 1 0.38 0.483 , then t s 1.21
0.5
(b) These setting are more than the limits, to obtain the required reactive
power injection, apply (9.31) with ts = 1.2 and Q as unknown as follows:
1
2
1 1.21 2 1 1.21 1.21 2 40.14 1 0.38 Q
0.5
From which Q = 0.436 pu (-) sign. And compensator Qc = Q - Ql = 0.436-
0.483 = - 0.047 pu. (Capacitive)
(
b)
Vs XQt
Vr (9.37)
t Vr t 2
t 1 t V Q
2
t (9.38)
X
But, the short circuit level at the node "r" is given by:
V2
S sc (9.39)
X
t 1 t S sc Qt (9.40)
Example 9.4:
For the tag-stagger arrangement shown in fig. (9.17), if the voltage at
the bus bars A, B are kept constant at 1 pu. Reactance of both transformers is
18%. Off-nominal tap ratio of T1, T2 are 1.15, 0.85 respectively. Base power
is 120 MVA. Find the net reactive power flow at bus B.
Solution:
Referring to fig. (9.17)
1.15 1 1 0.85
I1 j0.833 pu. and I 2 j0.833 pu.
j0.18 j0.18
Due to I1: At bus A QA = 0.833 x 1 x 120 = 100MVAR
At bus B QB = 0.833 x 1.15 x 120 = 115MVAR
Due to I2: At bus A QA = 0.833 x 1 x 120 = 100MVAR
At bus B QB = 0.833 x 0.85 x 1 x 120 = 85MVAR
Therefore net reactive power at bus B: QB=115 - 85 = 30MVAR. Net reactive
power at bus A: QA = 0.
Noting that changing T1, T2 will change their reactive powers and both of Q A,
QB.
Chapter 9 301
Example 9.5:
Two generators feed local reactive loads each 12MVAR's. They are
interconnected by a line having a reactance of 0.061pu, a transformer
(X=10%) and a booster transformer of (X=10%). If the voltage at the
machines buses is kept constant at V1=V2=1pu, and no power or reactive
power are transmitted on the line, booster transformer voltage is raised by
8.75%, in order to avoid formation of ice by circulation of currents in lines.
Find the new reactive power demand from each generator? (Take base
MVA=20).
Solution:
As there is power transmit on the line, therefore initially each generator
feeding its own local load (12MVAR). Injection of 0.0875 pu voltage at the
booster transformer is equivalent to a superposition of such voltage in a
circuit as that shown in fig. (9.20). Current due to booster transformer voltage
0.08750
is: I1 j0.336 Amp.
j0.1 0.061 0.1
This current results in reactive powers at bus A:
302 Voltage Control in Power Systems
(a) (b)
X l X c Q RP
V Vs Vr (9.41)
Vr
Table 9.2 Required reactive power for a 1kW load at different power
factors and total load KVA
Arc furnaces loads operate at nearly 0.7 power factors and consume
several tenth of MW’S, while aluminum smelter plants consume several
hundreds of MW’S and reache 1000 to 2000 MW’s with power factors of
Chapter 9 305
V IZ
Z 2 P2 Q2 (9.43)
V2
Fig. 9.23 Block diagram of power system and SVC for voltage control
9.4.4 Simplified Representation of a Power System,
TCR/FC Static VAR Compensator and a Load:
In voltage control studies of load nodes, a simple two nodes system is
quite sufficient. The system is represented by its Thevenen’s equivalent
voltage E and its Thevenen’s impedance Bs (or its short-circuit capacity at
unity pu voltage) as shown in fig. (9.24). The load is represented by a shunt
reactance (Gl+jBl). The TCR static VAR compensator is represented by an
admittance Bd behind an ineritaless inphase voltage source E c=KV. K
represents the thyristor action. K should be always less than one, (K=1)
represents the thyristor turn-off state, (K=0) represents the thyristors fully on
state. Ec is inphase with the SVC terminal voltage V. The actual TCR reactor
fundamental current (Ic) is given by:
V Ec
Ic jBd V KV (9.44)
jX max
Where:
Bd=1/Xmax
V 1 K
Ic
jX max
jBd V 1 K Vref VH GV (9.45)
Vref
VH G
K 1 (9.46)
Bd
Application of Kirchoffe's current law to circuit of fig. (9.24), yield a relation
relating all system parameters (network, load and compensator and its
controller) which is found by equating real and imaginary parts:
2 Ec
2
Gl B s Bl B d 1 Bc V 2 B s2 E 2 (9.47)
V
That compensator model can then be used to represent either of the following:
(a) A synchronous condenser with Ec is the internal voltage, Bd is the
effective susceptance (in general Ec V), or K >1.
(b) The reactor of a static VAR controller with Ec the critical voltage at
which the reactor is turned off or saturation disappears and Bd is the effective
slope of the current/voltage relation for (V Ec). For (V Ec) the current is
zero, i.e. the branch is not present, or Ec represents the drawn inductive
current as Ic = (V-Ec) Bd, Ec = KV, where K represents the function of the
control system, in regulating the TCR current magnitude.
(c) Static VAR Generator with inductive or capacitive B d and internal
voltage Ec, which supply or absorb reactive power, since, E c is kept in phase
with V, 0 < K < 2.
The parameters of our simple circuit are represented by admittance's other
than impedance’s, in order to facilitate the analysis.
2 n2
V V
P Po , Gl Glo
Vo Vo
(9.48)
Chapter 9 309
m m2
V V
Q Qo , Bl Blo
Vo Vo
Where: Po, Qo, Glo, and Blo are the steady-state load values at the initial
voltage Vo. (Gl, Bl) are their values at the actual voltage V.
From the standpoint of voltage stability, reactive power compensation at load
terminals or very close to them is very important. In order to get maximum
power transfer, controlled compensation (e.g. SVC or synchronous
condenser) is essential. In addition, this circuit and these simple relations give
the change of the quantitative effects of load power factor, system reactance,
load P-V, and Q-V characteristics, and the required reactive power Q on load
node voltage magnitude which define its stability state.
dP dP
P Glo Blo (9.49)
lo
dG lo
dB
dP dP Blo
0 (9.50)
lo lo
dG dB Glo
310 Voltage Control in Power Systems
To calculate the values of dP/dGlo, dP/dBlo we start from the circuit equation,
expressed as voltage magnitude.
2 Ec
2
2
Gl Bs Bl Bd 1 Bc V Bs E
2 2
(9.51)
V
From which:
1 dV
l
G
(9.52)
V dGlo D
E
Bs Bl Bd 1 c Bc
1 dV V
(9.53)
V dBlo D
1 dV 1 dV
(9.53)
V dBc V dBlo
dV B dV
d (9.54)
dEc VdBlo
E
Bs2
dV V
(9.55)
dE D
E
Bs2
1 dV 1 dV
V (9.56)
V dBs D V dBlo
Where:
E
D n 1Gl2 Bs Bl Bd 1 c Bc Bs m 1Bl Bd Bc
V
Note that if (Bd, Ec) represents a TCR, or saturated reactor, of a SVC, both B d
and Ec disappear completely from the equations when V E.
dP dV 2 dG
nGlV V lo (9.57)
dX dX dX
Or:
dP 1 dV 2 dG
nP V lo (9.58)
dX V dX dX
With similar relations for Q. The equation for dP/dGlo and dP/dBlo are derived
from these equations by replacing X by Glo and Blo respectively.
9.4.8 Active and Reactive Powers Limits/Voltage
Exponents Relations:
The active power limit P = 0 in terms of voltage and load exponent n
occurs when:
dV B dV 1 V
lo (9.59)
dGlo Glo dBlo n Gl
dV Blo dV 1 B V
lo (9.60)
dGlo Glo dBlo m Glo Bl
These two powers limits equations suggest that the presence of a reactive
component in the load expressed by Bl reduces the power limit.
n m
V V
P Po and Q Qo (9.61)
Vo Vo
The load node voltage sensitivity to compensator susceptance (or rating)
variation is derived as:
1
1 dV Bs2 n 2Gl2 Bd Ec
m 2 (9.62)
s
V dBc B 2 G 2 0.5
l Vo
D Bs2 Gl2 Bs2 Gl2
0.5 Bd Ec
V
1
1 dV 2
Bs Gl2
V dBc
0.5 E E
d c
V
(9.63)
Chapter 9 313
Thus for Gl Bs the load voltage is controllable even without the employment
of controlled reactive power compensation, i.e. with only shunt capacitance
Bc, However, the control gain may become intolerably large, resulting in
instability.
(b) For constant power load, we have m=n=0, then (9.63) becomes:
1
1 dV B 2 2G 2
s l
(9.64)
V dBc
Bs Gl
2
2 0.5
Bd Ec 2Gl2 Bs2
2 n m Bl (9.65)
V
Bs Gl
2
2 0.5
Bd 0 , Bc Bs Bl Bs2 Gl2
0.5
(9.66)
314 Voltage Control in Power Systems
(c) If m = n = 0 (with Blo = 0.5Glo and Bd = 0), the power limit is attained at
Glo = 0.523Bs just as it was for voltage control dV/dB c. By comparing
equations (9.62) and (9.65), it can be seen directly that if n = 0, the power
and voltage control limits are the same, regardless of the value of m, while
for any positive n, the power limit is reached first before the voltage limit
and that this conclusion holds even when controlled reactive power
compensation (represented by Bd Ec/V) is present.
(d) Therefore voltage stability studies in terms of voltage behavior for
changes of load from an initial normal condition, corresponds more closely
to the above forementioned definitions and behaviors. This will might be
observed in a real power system. Naturally lead to the demonstration of the
significance of load power/voltage characteristics and of the controllable
reactive power compensation effects on system voltages and sensitivities. It
is to be noted that the above analysis and the presented figures are derived
for V = E. If V is controlled to other value other proportions are to be found.
E
C Bc Bd 1 c Bs Bl Bs2 Gl2
0.5
(9.67)
V
Chapter 9 315
V
Bc Bco K 1 (9.70)
Vo
D Bs2 n 2Gl2 Bs2 Gl2 m 2Bl
Bd Ec
V
K (9.72)
Example 9.6:
A load is fed from a large power system, which is represented by its
Thevenen’s equivalent at the load node (Es, Bs). The load is given by its shunt
admittance (G1+jB1). A TCR/FC static VAR compensator is used to control
the load voltage. It is represented by Bc, Bd and Ec = KV. System data are:
System: Es = 1.02 pu, Bs = 1.0 pu
Load: P = 1.0 pu, pf = 0.8 Lagging and V = variable
316 Voltage Control in Power Systems
Solution:
Es = 1.02 pu, Bs = 1.0 pu, Bc = 0.2 pu, Bd = 0.5 pu
P = Po = 1.0 pu, Q = 40 = 0.75 pu
Gl= Po = 1.0 pu, Bl = Qo = 0.75 pu
Using relation of equation:
BsEs 2 V2 Gl2 Bl Bc Bs Bd 1 K 2
Then:
Bs Es
V
G l2 Bl Bc Bs Bd 1 K 2
With K = 0 (TCR is fully on), then V = 0.584 pu.
While with K = 0.95, then V = 0.639 pu.
Noticing that inserting shunt reactors depress the node voltage.
Example 9.7:
A load of admittance Yl=Gl+jBl is fed from a large network represented
at the load node by its Thevenen’s equivalent E behind its Thevenen’s
reactance (or admittance Bs). Its resistance is neglected. A TCR/FC
compensator is installed in shunt at the load bus represented by a shunt
capacitive susceptance Bc for the FC and a shunt inductive susceptance B d
behind voltage source Ec, for the TCR.
Find the required static VAR compensator susceptance required to keep the
load voltage at 0.95 pu. When the source voltage E is 1.0 pu and the voltage is
at the power limit for voltage stability. The load is a constant impedance load
(m=2, n=2). Its initial value was Pl+jQl =1.0+j0.5 at V = 1.0 pu. Compensator
controller equivalent total gain K = 0.98 and Bs =1.0 pu.
Solution:
Po=1.0pu, Qo=0.5pu, Vo = E = 1.0pu, V = 0.95pu, K=0.98, Bs=1.0pu, n=m=2.
Therefore:
V n 2 Po
G l Po n 2 1 pu.
Vo Vo
BsEs 2 V2 Gl2 Bl Bc Bs Bd 1 K 2
Then; Bc = 0.892 + 0.0004 Bd
Assuming Bd = 1.2 Bc.
Then:
Bc = 0.8924 pu and Bd = 1.071 pu.
Chapter 9 317
Example 9.8:
A load having the following voltage dependence relations
P = Po and Q = Qo (V2/Vo2)
Is connected to a large power system, which can be represented by its
Thevenen’s equivalent voltage E in series with its Thevenen’s reactance jX s.
A compensator of TCR/FC type is used to control the load voltage. It consists
of a fixed shunt capacitor of admittance jB c and thyristor-controlled reactor
represented by a fixed reactor of admittance (-jBd) in series with an e.m.f.
(Ec=KV), K is the regulator gain, V is the load terminal voltage. What is the
controller factor K required to fulfil the following conditions.
Solution:
Po = 0.6pu, Qo = 0.5pu, V = Vo = 1.0pu then: P = 0.6pu, Q = 0.5pu.
P jQ
But: G l jB l l 2 l
V
2
Gl =2/V = 0.6pu and Bl = 0.5pu.
Having: Bs = 1.0pu, E = 1.04pu, P = 0.6pu, Q= 0.5pu, Rs=1pu and Bc=0.8pu
Assuming: Bd = 1.2Bc = 0.96pu
Then eqn. (9.60) gives:
Bs E2 V 2 G l2 Bl Bc Bs Bd 1 K 2
Bs E 2 V 2 G l2
2
B l B c Bs B d 1 K 2
V
Then; K=0.85
V Vm cos (9.73)
(d) With the controlled system case, find the value of reference voltage.
9.3 An AC synchronous generator feeding a load of (1.6 + j1.0) pu on 100
MVA base through a stepping-up transformer (X=0.10 pu), a double
circuit transmission line (each one has Xl = 0.2 pu, Rt is negligible) and a
stepping down transformer (X = 0.1 pu), the generator data are:
Xs = 1.5 pu, X' = 0.4 pu
Find the maximum generated power, for three cases of voltage regulation
(a) No control (constant excitation voltage)
(b) With non-continuously acting AVR
(c) With continuously acting fast AVR
9.4 A 132kV line is fed through 11/132kV transformer from a constant
11kV supply. At the load end of the line the voltage is reduced by another
transformer of nominal ratio 132/11kV. The total impedance of the line
and transformers at 132kV is (25+ j66). Both transformers are equipped
with tap-changing facilities which are so arranged that the product of the
two off-nominal settings is unity. If the load on the system is 100MW at
0.9 p.f lagging.
(a) Calculate the settings of the tap-changers required to maintain the
voltage of the load bus bar at 11kV. Use a Base of 100MVA.
(b) If the settings of the tap-changer are within 10%, what will be the
required injected reactive power, which required to maintain the load voltage
at 11kV (state whether inductive or capacitive).
9.5 Two 110kV power stations A and B are inter-connected by a line
having negligible resistance and a reactance of 10. The voltages are 110
10o kV and 1100o kV at A and B respectively. If a power of 30MW at
unity power factor is to be received by station B from station A, find the
required inphase and quadrature voltage boosts at station B and find the
capacity of the required booster transformers for the inphase and
quadrature boosts.
Use exact method for calculations.
9.6 A transformer is equipped with a tap-changer and connects two infinite
busbars of equal voltages. The transformer is rated at 500MVA and has a
reactance of 0.15 pu. Calculate the reactive power flow, from one busbar
to the other, for a tap setting of:
(a) 0.85:1 1.10:1
(b) Draw the reactive power flow with the tap setting from 0.8 to 1.2, (each
step is 0.1)
9.7 A 132 kV transmission line has a series impedance of (25 + j66) ohm.
It is fed through a 11/132 kV transformer from 11kV constant voltage
supply and feeds its load through 132/11 kV transformer. Both
transformers are equipped with tap-changers, with the product of their off
nominal setting is always unity. Calculate:
320 Voltage Control in Power Systems
(a) The tap-changer setting required for a load of 50MW at 0.9 P.F. lagging
and that required for another load of 200MW, 0.9 P.F. lead. The load voltage
in each case is kept at 11kV .
(b) The maximum load which can be drawn at 11kV with the maximum
possible off nominal setting 20%).
9.8 A 520 km, 500kV transmission system composed of three parallel
similar lines, connected to an infinite bus at one side and to a 2000MW 0.9
P.F. lagging load through a transformer of negligible reactance at the other
side. Each line has series inductive reactance of O.385 /km and shunt
capacitive admittance of j0.24 Mho/km and of negligible resistance
calculate:
(a) The rating of the static VAR compensator required at no load to keep
the load side at its nominal voltage .
(b) The load voltage with the three lines in parallel.
(c) The required compensator rating required for keeping the load voltage
at 0.95 pu at full load condition .
(d) The receiving end node sensitivity and the compensator rating required
for raising the voltage to 1.00 pu, at full load condition.
(e) Repeat (a), (b),(c) with one line opened.
9.9 A three-phase transmission line has resistance and inductive reactance
of 25 and 90 respectively. The voltage at the sending end is 145 kV
and 132 kV at the receiving end; transformers tapping at both ends are
20%. If these voltages are to be kept constant, find the compensator
reactive power and its sign (inductive or capacitive) required at the
following conditions:
(a) System operation at no load
(b) System is loaded by 50MW at 0.8 power factor at receiving end
9.10 Two substations are connected by two lines in parallel of negligible
impedance, each containing a transformer of reactance 0.18 pu. and rated
at 120MVA. Calculate the net absorption of reactive power when the
transformer taps are set to 1:1.15 and 1:0.85 respectively (i.e. tap stagger
is used). The pu. Voltages are equal at the two ends and are constant in
magnitude. What will happen when the latter one ratio become 1:1.1
9.11 A 400 kV transmission line is connected to an infinite bus system and
feeds a load of 1000 MW, 400 MVAR. The line has a series impedance of
(7+j70) ohm and the load stepping down transformers has maximum tap
ratio of 0.9:1. IF the maximum allowable voltage drop is 10% and the
maximum taps are fully used, find the reactive power required from that
compensator at the load side.
9.12 A simplified power system is represented by a system voltage E,
reactance Bs and loaded by a load having 0.9 power factor or B Lo = 0.5
GLo. When the load power (p = GL V2) is changed gradually from 0.6 P.U.
Chapter 9 321
References
[1] Carson W. Taylor, "Power system voltage stability", ERPI Power
Engineering series, book, MC Graw-Hill, Inc, New York, 1994.
[2] S. M. L. Kabir, R. shuttleworth, "Brushless Exciter model", IEE Proc,
Gener, transm, Distrib, Vol. 141, No1, January 1994, pp 61-67.
[3] Excitation System Models for Power Systems Stability Studies, "IEEE
Committee Report, IEEE Trans., PAS, 1981, PAS-100 (2), pp 494-509.
[4] A. R. Bergen, "Power Systems Analysis", book, Prentice-Hall series in
Electrical and Computer Engineering, New York, 1986.
[5] B. M. Weedy, B.J. Cory "Electric Power Systems", Book, John Wiley
& Sons, New York, 4th edition, 1998
[6] C. A. Gross, "Power Systems Analysis," Book, 2nd edition John Wiley
& Sons, 1986, New York.
[7] C. Concordia, "Voltage Instability", Electric Power and Energy, pp. 14-
19, 1988.
322 Voltage Control in Power Systems
Chapter 10
Voltage Stabilization of Unstable Loads
Load instabilities usually occur due to lack of reactive powers or due to
heavy loadabilities or due to high reactance’s of lines or due to mal
distribution of reactive power allover the system. Load/voltage nose curves
are good means to illustrate voltage stability situations. Several means of
enhancement of voltage stabilities are displayed in this chapter. Their
parameters, limitations, and variables are derived in order to keep load
voltages at certain stable levels at various operational conditions. Static VAR
compensator, shunt fixed reactors and capacitors, series capacitors, tapped
transformers and combinations of them are used. Voltage Flicker
phenomenon is also included as a new aspect of load/voltage instability.
Load power factors should not be lower than certain specified values,
which are 0.86 in Europe and 0.9 in Egypt. Penalty must be paid to electrical
facilities when load power factor becomes less than these limiting figures.
The shunt capacitors for loads power factors corrections are mainly specified
by their nodes terminal voltages, rated capactive reactive powers, and
capacitors capacitance in micro-farads. Sometimes ambient temperature
ranges and voltage harmonic contents should be also specified. If the load is
connected to a high voltage network through a stepping down transformer,
these capacitors should be connected to the high voltage side of entrance
transformer. For a load consuming active power "P" with a power factor "
pf1", its power factor is desired to be improved to " pf2", the capacitor voltage
"V" is firstly specified and its capacitive reactive power rating is given by:
Qc
C (10.2)
V 2
XQ RP
V Vs Vr (10.3)
Vr
324 Voltage Stabilization of Unstable Loads
Lower voltage drop means higher load voltage level and less tendency to load
instability. Besides load currents will be less as the load current is given by:
P2 Q2
I load 2 2 (10.4)
Vr Vr
P2 Q2
Ploss 2
I load R R 2 R 2
(10.5)
Vr Vr
Decrease of Q results in less load terminals currents, less losses, less heating
and in less requirement of feeders cross sections as the new required feeders
cross section a2 equal to:
I
a 2 a1 2 (10.6)
I1
Assuming that the self-load current is I1 and the feeder current after power
factor correction is I2. The original feeder cross section is a 1 and the new
lower feeder cross section is a2.
In the Egyptian power system load power factors less than 0.4 are not
allowed. Power factors from 0.4 to 0.6 should pay a penalty of the difference
(0.9-load power factor) multiplied by the billed KWhr and half of this value is
paid for power factors from (0.6 up to 0.9). For pf = (0.4-0.6):
0.9 pf
Penality kwh £/kwh (10.9)
2
Chapter 10 325
Fig. 10.1 Block diagram of power system and SVC with voltage control
V KH
H (10.10)
Vt 1 STH
1 slop 1 ST2
G1 (10.11)
1 ST1 1 ST3
Slop is the droop slope of the regulator, shown in fig. (10.2), (T 1, T2, T3) are
time constants of regulator circuits. The controller output is fed to the firing
circuit which may be completely defined by a transfer function consists of a
gain Kd and delay Td in the form:
Kd
G 2 K d e STd (10.12)
1 STd
The output of this block refers to the compensator admittance B, which upon
multiplication by Vt, yields the compensator inductive reactive current
(Is=BVt), which when multiplied by the system impedance Z s gives the
voltage drop (Vc which will be added or subtracted from Thevenen’s voltage
Vs) due to the compensator current flow through Z s. The load node voltage Vt
is given by the Thevenen’s equivalent voltage V s minus the link voltage drop
(RsP+XsQ)/Vt and the voltage drop due to the SVC current flow through the
link. Therefore, the system equivalent can be represented by the transfer
function block diagram of fig. (10.3). For steady-state analysis, it can be
simplified to that of fig. (10.4), "S" is the Laplace operator, it vanishes in
steady-state analysis. The limiter is included to represent the control range of
the SVC equivalent virtual admittance "B".
Considering the load powers P and Q, the terminal voltage Vt is given by:
R P X sQ
Vt V s s Vc (10.14)
V t
Or:
R P X sQ
Vt V s s Vr Vt H GZ s (10.15)
V t
Chapter 10 327
Fig. 10.4 Simplified transfer function block diagram of power system and
static VAR compensator (SVC)
328 Voltage Stabilization of Unstable Loads
From which:
b b 2 4ac
Vt1, 2 (10.18)
2a
Where:
a 1 GHZ s
b Vs GZ sVr
c Rs P X s Q
G
V V V
t
2
t s R s P X s Q
(10.19)
Z sVt HVt Vr
Vt2 1 GHZ s Vt V s R s P X s Q
Vr (10.20)
Vt GZ s
Kd
G (10.21)
slop
Therefore, for any loading conditions (P, Q), the load voltage can be
maintained at certain value of Vt by changing Vr or slop or Kd according to
eqns. (10.19) to (10.21). Three cases of system equivalent impedance are
considered. For UHV networks Rs 0. For medium voltage networks Rs = Xs
and in low voltage networks Xs 0. Therefore,
Chapter 10 329
G 'Z
Slop Vr Vt H s
(10.25)
BcVt
G'
Or: Slop AK (10.26)
Bc
Where:
Z
AK Vr Vt H s
Vt
And:
B
G ' Slop c (10.27)
AK
1
Xc (10.30)
Bc max
(a)
(b)
(c)
Fig. 10.7 Required SVC controller gains and reference voltages for
maintaining leading power factor load voltages constant
(a) P/V characteristics (b) Gain/load plot (c) Reference voltage/load plot
Chapter 10 333
The three cases are plotted in fig. (10.8) for the above typical system
and the gains, which are capable for keeping the load node voltage constant at
0.99 pu are plotted for a typical system. Very high gains are required when R S
>> XS and vice versa when XS >> RS. Intermediate values are obtained when
XS = RS. This is due to the absence of system damping and the need of high
gains to compensate for the existence of the resistance in the system. This
result is very important for applications of compensators in HV, MV and LV
transmission systems. The figure decides that it is not judicious and
uneconomic to use the SVC in LV distribution networks for load voltage
stabilization purposes. It should only be used in UHV or in MV networks
only.
Fig. 10.8 Required SVC controller gains with different feeder equivalent
impedance’s RS >> XS, XS >> RS and XS RS
(a)
(b)
E s E s2 41 X s Bc Rs P X s Q
Vt1
21 X s Bc
(10.32)
Es E s2 41 X s Bc Rs P X s Q
Vt 2
21 X s Bc
Bc
V
t
2
E sVt Rs P X s Q (10.33)
2
X sVt
(a)
(b)
Two cases are considered: Constant power load and constant reactive load,
using the simplified voltage drop relation of voltage the system equations are:
Xs Xt Rs
Q 2 P
V
Vs
Vt t 2
t (10.34)
t Vt
t1
VsVt VsVt 2 4Vt2 Rs P X s X t Q 0.5
(10.36)
2
2Vt
t2
VsVt VsVt 2 4Vt 2 Rs P X s X t Q 0.5
(10.37)
2Vt 2
Using equs. (10.36), (10.37), the off nominal tap ratio of tap-changing
transformer with load powers can be plotted at different load voltages.
Fig. 10.12 The variation of dE/dV criterion results with various off
nominal transformer tap ratios
338 Voltage Stabilization of Unstable Loads
Xs Xt Rs
Q 2 P
Vs t 2
t
V Vt (10.42)
t Vt
The block diagram shown in fig. (10.16) is the same as figures (10.3), (10.4)
but Vs is replaced by (Vs/t), Xt is replaced by Xt/t2 in power voltage relation.
Also Zs is replaced by (Zs/t2). The regulator transfer function is given after fig.
(10.16) by:
Z V Z R X X
Vt2 1 G 2s H Vt 2s G 2s Vr 2s P s 2 t Q 0
t t t t t
(10.43)
Chapter 10 341
2
Vs Z Vs Z Z R X Xt
G 2s V r G s Vr 4 1 G s H s P s Q
t t t t 2
t 2
t 2
t2
Vt1
Z
2 1 G 2s H
t
(10.44)
2
Vs Z Vs Z Z R X X
G 2s Vr G 2s Vr 4 1 G 2s H 2s P s 2 t Q
t t t t t t t
Vt 2
Z
2 1 G 2s H
t
(10.45)
And the compensator controller gain is given by:
Vs Rs X X
Vt 2 Vt 2 P s 2 t Q
t t t
G (10.46)
Zs
Vt HVt V r
t2
Z V R X X
Vt 2 1 G 2s H Vt s 2s P s 2 t Q
t t t t
Vr (10.47)
Z
Vt G 2s
t
G AK
Bc (at Vt=1.0pu) (10.48)
Slop
Where:
Zs
AK Vr Vt H
t 2V t
342 Voltage Stabilization of Unstable Loads
(a)
(b)
(c)
(d)
Fig. 10.16 Load fed through tapped transformer and provided with static
VAR compensator
(a) Equivalent circuit (b) Block diagram
(c) Transfer functions (d) Simplified transfer functions
Chapter 10 343
(a)
(b)
(c)
(d)
Table 10.1 P.U compensator rating at various gains and various off
nominal transformer tap ratios
(a)
(b)
(c)
Fig. 10.18 (a) Gain/Power relation with different transformer tap ratio's
(b) Gain/SVC Reactance with different transformer tap ratio's
(c) Gain/SVC Rating (Bc) with different transformer tap ratio's
Chapter 10 347
In summary:
(a) Presence of only tap-changing transformers does not improve voltage
stability significantly. They do affect the voltage levels and slightly the
critical voltages, but does not affect the maximum powers corresponding to
these critical voltages. Therefore, tap-changing transformer at the load
terminals can slightly contribute to its voltage stability.
(b) Presence of static VAR compensator with different controller gains can
increase the maximum load powers several times its original value without
static VAR compensator and replace using series condensers.
(c) There is an interaction between the transformer off nominal tap ratio and
the compensator controller gains and reference voltages, in order to keep the
load node voltage constant at all loading conditions
(d) The compensator ratings are affected with presence of tap changing
transformer, the fixed reactance of the TCR type compensator changes
significantly with the presence of tap-changing transformer. Certain
transformer off nominal tap ratio's minimize the SVC needed ratings or in
other words:- in the presence of tap-changing transformer, the SVC rating
required to keep the load voltage constant is reduced significantly.
(a)
(b)
(c)
Eqn. (10.52) shows the compensation percentage for the same SVC gain, the
load power increases as the series capacitor percentage increases. Eqn.
(10.52) shows the gains required when the resonance case occurs (at 100%
series compensation). It indicates that very large quantities are required
comparable with those at the other percentages (0% to 75%). The gains when
shunt capacitor resistance (Rsh) is increased by value at which the gains
become in the same order as those with the lower capacitance percentages. R sh
should be increased to certain value in order to have the same gains. The
shunt capacitor resistance Rsh, which must be introduced by the spark gap
during the resonance period, is found by:
Rsh jX c
Z Rs jX s (10.54)
Rsh jX c
R X2 R2 X
Z Rs sh c j X s sh c (10.55)
Z1 Z1
Where:
Z1 Rsh
2
X c2
350 Voltage Stabilization of Unstable Loads
(a)
Chapter 10 351
(b)
(a)
(b)
Fig. 10.21 Load power/SVC controller gain required to keep load voltage
constant in the presence of series capacitor of various compensation
percentages: (a) With 25%, 50%, 75% and (b) With 100%
Chapter 10 353
Vc
Slop (10.57)
Is
1
I s BcVt , Bc (10.58)
Xc
Where Bc is obtained from the feedback block diagram of figs. (10.3), (10.4).
First of all the required SVC compensator rating to keep the load voltage
constant at various loadabilities (0 to 3)pu shows that presence of series
capacitors has led to less SVC rating for same loading and voltage conditions.
At the resonance condition (series compensation = 100 %), fig. (10.22) shows
the required SVC ratings. Impracticable values are required for keeping the
load voltage constant for a heavy load of 3 pu, SVC rating of 80 pu is
required. In order to study the influence of the series compensation on the
SVC ratings with different SVC controller gains, fig. (10.23) is plotted. The
Figure shows minimum ratings at higher series compensation percentages.
Moreover, lower gains are accompanied by lower SVC rating and vice versa.
Steep decrease of SVC ratings with increasing the series compensation
percentage is noticed.
354 Voltage Stabilization of Unstable Loads
Fig. 10.22 SVC rating required stabilizing the load voltage at different
load powers in the presence of series capacitor of various percentages
(a)
(b)
Fig. 10.25 SVC controller gains versus ratings with different series
compensation percentage at constant reactive power
V Q
(10.60)
V S sc
Where Q is the reactive power fluctuations at the PCC (largely equal to the
reactive power fluctuations of the furnace) and Ssc is the network short-circuit
level at the PCC node.
The illustrated flicker for a furnace loaded for 0.12 second and then
unloaded for 0.05 second to produce a flicker rate of six cycles per second
(f=35Hz). The resulting voltage change is about 0.4 percent. For about 1.4
seconds there is a general voltage sag of approximately 0.4 percent during this
state of operation, for two seconds. The no-load voltage at the load node can
be expressed as:
Vs Eth et 305 0.004 sin 35t (10.61)
Where: t is the time, Eth is the Thevenine's voltage at the load node.
X s Xt Rs
Q 2 P
V
Vs
Vt t 2
t (10.62)
t Vt
Vt2 1 GHZ s Vt Eth et 305 0.004 sin 35t GZ sVr Rs P X sQ 0
(10.63)
G
Vt2 Vt Eth e t 305 0.004 sin 35t Rs P X s Q
(10.64)
Z sVr HVt Vr
In order to have constant Vt, i.e. the voltage flicker is totally eliminated an
adaptive gain defined by eqn. (10.64) should be applied. For a typical load,
these adaptive gains G are plotted in fig. (10.27) for 2.0 sec. that the critical
loads node power. This has nearly the image of the voltage flicker shape in
the upward direction.
Chapter 10 359
Fig. 10.27 Adaptive static VAR compensator controller gain required for
keeping the load voltage constant and eliminating the voltage flicker
Fig. 10.28 Load node voltage shape using static VAR compensator of
fixed controller gains within the adaptive gains range values G = 78
360 Voltage Stabilization of Unstable Loads
Vr
Vt2 1 GHZ s Vt Eth et 305 0.004 sin 35t Rs P X sQ
(10.65)
Vt Z sG
Fig. 10.29 Adaptive reference voltage for the SVC regulator controller
and load voltage for totally eliminating the voltage flicker
E e T
Vt2 th
305
0.004 sin 35T V R
2s
X X
P s 2 t
Q
t t
t t
G
Zs
2 Vt HVt Vr
t
(10.66)
Z s Eth e T
Vt 1 GH 2
2 305
0.004 sin 35T V R
s
P
Xs Xt
Q
t t
t t
2
t2
Vr
Zs
Vt G
t2
(10.67)
Figure (10.30) shows the static VAR compensator gain time response
and the SVC gain rating relations required to eliminate totally the voltage
flicker, when tapped transformer is used in combination with the SVC.
(a)
(b)
Fig. 10.30 Flicker voltage elimination with static VAR compensator and a
tap-changing transformer having several off nominal tap ratio’s
(a) SVC gains time response (b) SVC gain/rating relation
Chapter 10 363
F jiVi
i G
Lj 1 (10.68)
Vj
L MAX j L L j and 0 L 1 (10.69)
Where:
L is the set of consumer nodes
G is the set of generator nodes
Vj is the voltage at load node
Vi is the voltage at generator bus
Fji is submatrix of the hyprid-h matrix Fji = | Fji|ji and this matrix is
determined by:
C jiVi
i G
Bj 1 (10.71)
Vj
[BLL]-1 is the imaginary part of the matrix [YLL]-1 and [BLG] is the imaginary
part of the matrix [YLG].
F ji Vi cos i ji j
i G
LRj 1 (10.73)
Vj
F ji Vi sin i ji j
i G
LIj 1 (10.74)
Vj
LI F1 , V
(10.75)
LR F2 , V
C ji Vi cos i j
i G
B Rj 1 (10.76)
Vj
C ji Vi sin i j
i G
B Ij 1 (10.77)
Vj
Chapter 10 365
B I F1 , V
(10.78)
B R F2 , V
A simplification of that method assuming only the B’S of the Y matrix exist
or neglect the resistances of all system elements so (10.76), (10.77) can be
written as:
B I 1 P P
R T V T J S (10.79)
B Q Q
The amount of power (P) and reactive power (Q) to be shed is given by:
P 1 B
L
Q S R (10.80)
B
Where:
1 I
B Ij
Vj i
ji i i
j i j j
C V cos B R 1 B j V
Vj j
G
(10.81)
1 B Rj 1
B Rj
Vj
i
I
C ji Vi sin i j i B j j
Vj j
V
G
(10.82)
The partial derivative of eqns. (10.73), (10.74) with respect to voltage angle
and magnitude changes can be determined as:
LI LI
LI
V
R R T V (10.83)
L L LR V
V
366 Voltage Stabilization of Unstable Loads
Matrix [T] is the sensitivity matrix between indicator changes and voltage
angle and magnitude changes. From eqn. (10.83) changes of the real and
imaginary parts of the indicator corresponding to bus j can be determined as:
1 I
LIj
Vj i
ji i i ji j i j
j
F V cos LR 1 L j V
Vj j
G
(10.84)
1 LRj 1
LRj
Vj
i
I
F ji Vi sin i ji j i L j j
Vj j
V
G
(10.85)
Using eqns. (10.84), (10.85) and the linear relation between changes in
voltage phases/magnitudes and active/reactive power injections, we obtain a
relationship between real and imaginary parts of indicators and the powers
(P, Q), which should be rejected or shed at node j:
LI 1 P P
R T V T J Q S Q (10.86)
L
The amount of power (P) and reactive power (Q) to be shed is given by
eqn. (10.86) as:
P 1 L
I
Q S R (10.87)
L
Using the simplified method assuming only the B's of the Y matrix exist or
neglect the resistance's of all system elements equations, so equations (10.86),
(10.87) can be written as:
B I B I
B I
V P
R R T V S Q (10.88)
B B B R V
V
With [S]=[T][J]-1, J is the Jacobian matrix and [S] is the sensitivity matrix
between indicator changes.
Chapter 10 367
The active /reactive power changes or the load powers to be shed are:
P 1 B
I
Q S R (10.89)
B
These are the same values which get before with simplified admittance's.
Example 10.1:
The 6-bus Ward-Hall system is used as a test system. Two cases are to
be considered. The base case (Case 1) and the case at which the reactive
power at bus # 5 is stressed up to reaching voltage instability state (Case 2).
Solution table 10.3 shows the voltage, indicators and errors between L j and Bj
for the base case (case 1). Table 10.4 shows the same parameters for (case 2).
Examination of tables (10.3), (10.4) shows that:
For (Case 1), the maximum value of indicators Lj, Bj are 0.27518, 0.27585 at
bus 5, while for (Case 2), the maximum value of indicators Lj, Bj are 0.99919,
0.96594 occur at bus 5 also. Therefore the load shedding should occur at node
# 5.
Table (10.5) shows, the active and reactive powers to be shed at node
#5 and the resulting indicators calculated from voltage angles and magnitudes
from a load flow calculation, after load has been shed. Taking minimum value
of the indicator to be 0.5. The error between the two techniques is small. Only
368 Voltage Stabilization of Unstable Loads
5 iterative steps are required to determine the load to be shed at the optimum
node, which is found to be always node #5.
Table 10.3 Voltage, indicators and errors between Lj and Bj in load buses
for case 1
Table 10.5 The active and reactive powers to be shed and the resulting
indicators at load 5, after load successive shed (Lj, Bj minimum = 0.5)
The amount of load to be shed is calculated by eqn. (10.66) and new value of
Lj and Bj are calculated with shedding these quantities. The process is
Chapter 10 369
repeated until Lj, Bj become less than specified values (0.5 in this analysis).
The last values refer to the load quantities, which must be shed.
Problems
10.1 What is meant by load stability and what is its relation with voltage
stability?
10.2 Give the formula for the compensator rating required to stabilize the
load unstable voltage?
10.3 What are the limitation of series capacitor percentage compensation
and why?
10.4 What are the effects of combining static VAR compensator and tap-
changing transformer on compensator rating required for load voltage
stabilization?
10.5 What is voltage flicker and what is its mechanism and how can be
stabilized or eliminated. Show how compensator rating and controller
gains and time constants can be calculated?
10.6 Give formula for static compensator rating, gain and reference
voltage required to stabilize load voltages?
10.7 Give formula for the load to be shed in order to stabilize unstable
loads?
10.8 Give algorithm, which define load location to be shed?
10.9 Prove that combination of compensator and tap-changing
transformer or series capacitor and static VAR compensator is more
efficient and more beneficial from economical point of view?
10.10 Show that series capacitor is not preferable for stabilization of low
voltage networks .It is only for use with ultra and extra high voltage
networks?
10.11 What will be the load stabilization effects of load power factor
correction and what will be the available kW for other consumers due to
that correction?
10.12 A large power system is represented by its Thevenen's equivalent
E=0.99-3.2 pu., Z=0.23775.45 pu. At certain node which is loaded by a
load of 0.5+j0.05 pu. Find the load voltage, the node critical voltage and its
maximum power. Check its voltage stability. If the load is doubled does
the stability will be kept? If the reactive power is stressed to 0.5 pu. What
will be the system voltage stability state?
10.13 In problem (10.12) if a series capacitor is connected in series with
the load. Find the load node maximum power, critical voltage and its
voltage with 25%, 50%, 75%, 90% and 100% compensation percentages.
What will be the voltage stability situation when the load is doubled and
when only its reactive power is stressed to 0.5 pu. In both cases what will
370 Voltage Stabilization of Unstable Loads
be the series capacitor percentage to keep the load voltage equal to the
source voltage and just to stabilize the voltage.
10.14 In problem (10.13) if a static VAR compensator is provided in
shunt with the load and the series capacitor. Find its gains required for
stabilizing the load node voltage at 0.98. H=0.95, Vref=1.0, Vt=0.98.
10.15 For the system of problem (10.13), if only SVC is shunt with the
load. Its Vref=1.0 pu, H=0.95. What will be the load voltages for gains G of
5, 10, 15, 20 and 50. What will be the node maximum power and critical
voltages with these compensator gains.
10.16 In problem (10.15) if the gain is kept constant at G =10, what will
be the reference voltages required to maintain the load voltages at 0.98,
when H=0.95. What will be the maximum node power and critical voltages
with these new reference voltages.
10.17 A combined series capacitor and shunt static compensator is used
with certain power system, find the compensator gains at 50% and 100%
compensation ratio required to stabilize the voltage at 0.99 pu. Load
powers = 0.5 + j0.5, Vref =1.0 pu, H=0.95, E=0.99-3.2, Z=0.23775.45
pu. Find the node maximum power and critical voltage with and without
series capacitor. Find the static compensator gain, which yields the same
maximum power as that with 25%, 50%, 75% and 100% series
compensation ratio respectively. Prove that percentage of 75% is a limit.
10.18 A system is represented by E=0.99-3.2 pu, Z=0.23775.45 pu is
loaded by a load of 0.5 + j0.5 pu.
(a) Find the load voltage (b) Find the compensator gain to raise that voltage
to 0.98 (Vref =1.0 pu, H=0.99)
(c) Find the compensator reference voltage to maintain the load voltage at
0.99 (G=10, H=0.99)
(d) Find the series capacitor ratio required to raise the voltage to 0.99 pu.
(e) Find the static compensator rating required to raise the voltage to 0.99 pu
when G=10, H=0.95, Vref=1.0 pu. If the compensator is replaced by shunt
fixed capacitor what will be its rating and what will be the saving in rating
due to using controlled static VAR compensator.
10.19 Repeat problem (10.18) when a tapped transformer with off
nominal tap ratio of 0.8, 1.0 and 1.2 is used in combination with each case.
10.20 Find the off nominal tap ratio of a transformer connected in series
with the load of problem (10.12) in order to raise the load voltage to 0.95
and 0.99. The load powers are P+jQ=0.5+j0.5 pu.
10.21 In problem (10.12) if the original load was 1.0+j0.5 pu and the
system voltage is unstable, what is the percentage of the load to be shed in
order to maintain the load voltage stability? (Use the node critical voltage
criteria).
Chapter 10 371
10.22 A 2.2MW, 0.7 power factor, load is fed from a 11kV, 50Hz source
through a link which has impedance of 1+j1 ohms and 120mm2 cross
section. It is aimed to raise the load power factor (pf) to 0.95.
(a) Find the load currents before and after pf correction
(b) The load voltage before and after pf correction
References
[1] M. Z. El-Sadek, M. M. Dessouky, G. A. Mahmoud and W. I. Rashed,
"Enhancement of Steady State Voltage Stability by Static VAR
Compensators", Electric Power Systems Research Vol.43, 1997, pp.
179-185.
[2] M. Z. El-Sadek, M. M. Dessouky, G. A. Mahmoud and W. I. Rashed
"Combined Use of Tap Changing Transformer and Static VAR
Compensator for Enhancement of Steady State Voltage Stability",
Electric Power Systems Research, Vol. 45, 1998, pp. 47-55.
[3] M. Z. El-Sadek, M. M. Dessouky, G. A. Mahmoud and W. I. Rashed,
"Series Capacitors Combined With Static VAR Compensator for
Enhancement of Steady State Voltage Stabilities", Electric Power
Systems Research No. 44, 1998, pp. 137-143.
[4] M. Z. El-Sadek, M. M. Dessouky, G. A. Mahmoud and W. I. Rashed,
"Enhancement of Steady State Voltage Stabilities Due to Voltage
Flicker", JIEEEC'98, Amman, Jordan, April, 1998, pp. 176-181.
[5] M. Z. El-Sadek, G. A. Mahmoud, M. M. Dessouky and W. I. Rashed,
"Effect of Control Systems on Compensator Rating Needed for Voltage
Stability Enhancement", Electric Power Systems Research,
Switzerland, No. 50, 1999, pp. 139-145.
[6] M. Z. El-Sadek, M. M. Dessouky, G. A. Mahmoud and W. I. Rashed,
"Optimum Load Shedding for Avoiding Voltage Instability", Electric
power Systems Research Journal, No. 50, 1999, pp. 119-123.
[7] M. Z. El-Sadek, M. M. Dessouky, G. A. Mahmoud and W. I. Rashed,
"Improvement of the Steady State Voltage Stability Criteria Results",
5th, MEPCON’97, Alexandria University, Egypt, 1997, pp. 426-430.
[8] M. Z. El-Sadek, G. A. Mahmoud, M. M. Dessouky and W. I. Rashed,
"Tap Changing transformer Role in Voltage Stability Enhancement",
Electric Power Systems Research, No. 50, 1999, pp. 115-118.
[9] M. Z. El-Sadek, M. M. Dessouky, G. A. Mahmoud and W. I. Rashed,
"Load Representation for Steady State Voltage Stability Studies",
Electric Power Systems Research, No. 43, 1997, pp. 187-195.
[10] M. Z. El-Sadek, A. A. Ibrahim, M. E. Ahmed, "Effects of Load
Representations on Steady State Voltage Stability, "Engineering
Conference, Port Said, 1999.
372 Voltage Stabilization of Unstable Loads
Chapter 11
Load Representation Effects on Voltage
Stability Evaluation
This chapter presents the effects of the new polynomials load models
on evaluation of degree of voltage stability in power systems. These
polynomial models were derived from the available measured characteristics
of the power system loads. Comparisons between the known single term
polynomials load models and the new models effects approzed the necessity
of using these developed models and showed that erroneous results are
obtained using the known available single term models in voltage stability
studies.
2 2 2
V V P V Q
Z R jX
P jQ P 2
Q2 j P 2
Q2 (11.1)
Or:
V2 V2
Z R // X , R , X (11.2)
P Q
In load flow studies, the available analysis are based on constant power loads
i.e. (P + jQ = constant). In synchronous stability studies, combination of
constant impedance loads and constant power loads led to another constant
current load given by:
I
P jQ = Constant (11.3)
V
The available litterateur presented approximated single termed models of
loads powers as functions in voltages to certain exponents. Resumes of such
models for some known loads are displayed in table (11.1). They are based on
researcher notices, and primitive load characteristics.
Chapter 11 373
Voltage Dependence
Type of Load
P Q
0.05
1- Large IM V V0.5
2- Refrigerator V0.8 V2.5
3- Heat pump V0.2 V2.5
4- Dishwasher V1.8 V3.5
5- Clothes dryer V2.0 V3.3
6- Color TV V2.0 V5.0
7- Fluorescent V1.0 V3.0
lamps
8- Incandescent V1.55 ---
lamp
9- Arc furnace V2.3 V1.6
Recently polynomial (P/V), (Q/V) load models are developed, based on time
records (P/t), (Q/t), (V/t) available in nearly all power stations and substations
and at important loads feeding points, with (t) denotes time. The order of the
polynomials of these models are found based on voltage stability criterion
results as it will be shown later. These polynomials can be summarized for
known loads as follows:
Using the same system and the load is replaced successively by various types
of loads, of the same powers, such as: Large IM, small IM, clothes washer,
incandescent light, heat pump, refrigerator, fluorescent light lamps and using
376 Load Representation Effects on Voltage Stability Evaluation
the available models given in table (11.1). Figure (11.2) depicts the
loadabilities which corresponds to the commencement of voltage instability.
These plots show clearly that the induction motor load is the heaviest load on
steady-state voltage instability while the incandescent lamps (or filament
lamps) is the lightest one. To reach voltage instability, incandescent lamp
loading by 50% over that of the induction motor load is required. Effect of
other loads on voltage stability lie in between of these loads.
11.3 Induction Motor Loads:
Having seen that the induction motor load is the more dangerous load
which fastly threaten voltage stability, special attention is paid to detect its
exact model for voltage instability studies, using polynomials with different
powers as given in chapter 3.
On the same plots, the known simple single termed models results are given
in figs. (11.3), (11.4) and (11.5). Oncemore erroneous results when using such
simple single termed models are clear.
378 Load Representation Effects on Voltage Stability Evaluation
sodium vapor lamps. Figure (11.10) shows the available model stability
results as well as the order of the polynomial model, over which, the results
will coincide. It was found to be 4. Polynomial of lower orders lead to
erroneous results. The model is given by equations of chapter 3.
Problems
11.1 What are the advantages of representing the loads by polynomial
(P/V), (Q/V) models based on experimental characteristics?
11.2 Why the single-termed available known models led to erroneous
voltage stability evaluation results?
11.3 Give reasons; why induction motor load is the more heaviest
load on voltage stability and the pure resistive load is the lightest one?
11.4 Give reasons; why 5th, order model is needed for arc furnace
load, while arc light lamps (florescent, mercury and sodium vapor)
need only 3rd order models?
11.5 To which reasons; polynomial model of 7 th, order is needed for
an induction motor having constant load torque and a 5 th, order model
is sufficient with motors having load proportional to its speed or to the
square of its speed?
11.6 Constant power representation is widely used in load flow
studies, while constant impedance and constant current loads were
largely used with synchronous stability studies, but it is proved that
polynomial representation with different order is the more correct
384 Load Representation Effects on Voltage Stability Evaluation
References
[1] W. I. Rashed, "Enhancement of Voltage Stability in Power Systems",
Ph.D. Thesis, Faculty of Engineering, Port Said, Suez Canal University,
Port Said, Egypt, 1997.
[2] M. Z. El-Sadek, M. M. Dessouky, G. A. Mahmoud, W. I. Rashed,
"Load Representation for Steady-State Stability Studies", Power
System Research Journal, Lausanue, Switzerland, No. 43, 1997, pp.
187-195.
[3] P. Kundur, "Power System Stability and Control", Book, McGraw Hill,
New York, 1994, Chapter 7 and Chapter 11.
[4] F. Illiceto, A. Csyhsm, G. Ruckutuhl, "Behavior of Loads During
Voltage Dips Encountered in Stability Studies: Field and Laboratory
Tests", Paper T72, IEEE PES Winter Meeting, New York, February
1972, pp. 2470-2477.
[5] G. J. Berg, "System and Load Behaviour Following Loss of
Generation: Experimental Results and Evaluation", Proc. IEE, London,
Vol. 119, No. 10, October 1972, pp. 1483-1486.
[6] M. Z. El-Sadek, E. H. Badawy, and A. I. Hussien, '' Optimum Future
Requirement of VAR Compensation in Developing Countries
Transmission and Distribution Networks'', 26 th, Universities Power
Conference, Brighton, England, September 1991.
[7] M. Z. El-Sadek, N. H. Fetih, and F. N. Abdelbar, ''Static VAR
Compensator Application for Minimizing the Surge Arrestor Rating at
Aluminum Smelter Electrolysis Plant Terminals'', Proc. of the 23rd,
Universities Power Engineering Conference, (UPEC), Nottingham
England, September 1988, pp.1-4, Session C12.
Chapter 12 583
Chapter 12
Induction Motor Role in Provoking Voltage
Instability
12.1 Introduction:
Induction motor loads are very important in industrial, commercial,
agriculture, and domestic applications. Power system operation is
characterized by sudden voltage and frequency variations due to continuous
load changes, switching, faults, and sometimes generators in and out of
service. Both of the synchronous stability and voltage stability of power
systems are affected by load-voltage and load-frequency characteristics. The
first affects the synchronizing torque's among generators while the latter
affects the active power flow and consequently the system damping. They all
affect voltage stability.
Table (12.1) shows the percentage of the powers and reactive power
after 0.6 sec with different mechanical loading and sustained 0.3pu voltage
dip. For =0, Q is nearly doubled and P increased by 10%, while for =2, P
decreased by 6.15% & Q increased to 1.35 times the initial value. Thus, with
the constant load torque (=0), reactive power increased to 192% and the
active power increased very slightly (110%) as the voltage falls.
Close examination of table (12.1) and fig. (12.3), shows clearly that the
reactive component of the input power to the induction motor, which is
loaded by any type of mechanical loads, increases as the supply voltage
decreases. This can provoke steady-state voltage instability phenomena, since
increased reactive demand causes more voltage drops and a voltage collapse
scenario can follow. For constant torque loads (=0), the voltage collapse can
be augmented and reach very fast by the increase of the active power demand
as the voltage falls as shown in table (12.1) and fig. (12.2).
Table 12.1 Power and reactive power and their % of the initial values for
different mechanical loading after 0.6 seconds, of a voltage dip of 30%
Fig. 12.2 Induction motor power response for a 30% voltage dip and with
three mechanical loads having =0, 1 and 2
Fig. 12.3 Motor reactive power response for a 30% voltage dip and with
three mechanical loads having =0, 1 and 2
Chapter 12 583
1
f inst (12.1)
2 t
The positive half wave of the power and the negative half wave are not
similar. On the other hand, it is noticed that the wavelength of the power is
longer with =2 than that with =0 and the power demand leads the
frequency variation. Studies showed that with 5% sinsoidal increase of the
frequency, leads to 21-26% increase in the active power and to 16-26% in the
reactive power. For a 1% increase of frequency (0.5) Hz, an increase in P=13-
17% and in Q of 15-22% are recorded
Table 12.2 Peak values of the induction motor active and reactive power
and their percentage of their initial values for = 0, 1 and 2 with 5%
siusoidal supply frequency variations increase
Fig. 12.4 Motor active power response for a sinusoidal supply frequency
variations using mechanical load having =0
Table 12.3 Peak values of active and reactive power with ramp frequency
variation of supply (Pinitial =1.04 pu, Qinitial = 0.52 pu)
of load Active Power "P" Reactive Power "Q"
Value pu Value pu
=0 105.8 1.10 109.0 0.600
=1 110.8 1.15 104.0 0.596
=2 114.0 1.20 114.0 1.200
Note: (pu): of the initial value
Table 12.3 shows that the values of power and reactive power for =1
lies in between those of =0 and =2. Figures (12.4), (12.5), (12.6) and (12.7)
show clearly that the variation of system frequency, which occurs normally
during system disturbances, and even during normal operation, affects the
motor power and reactive power consumption, especially with =2 i.e. with
centrifugal pumps and fans which are the popular loads of induction motors.
For example, a 1% increase in frequency (0.5 Hz) results in 5% increase of
active power "P" and about 15% in reactive power "Q". This new factor in the
power balance should be taken into consideration in voltage stability studies.
533 Induction Motor Role in Provoking Voltage Instability
Fig. 12.6 Motor active power response for a ramp supply frequency
variations using three mechanical loads having = 0, 1 and 2
Fig. 12.7 Motor reactive power response for a ramp supply frequency
variations using three mechanical loads having = 0, 1 and 2
Chapter 12 535
When the load is firstly pure constant impedance and the transmission
line consists of two circuits in parallel. The load voltage, load power and load
reactive powers are plotted in fig. (12.8) for one second after one line
opening. The figure shows voltage fall to the steady-state value in less than
10-m.sec. The plots show that constant impedance loads does not contribute
to voltage instabilities, as the power demand drops in the same time with
voltage fall.
Fig. 12.8 Load voltage, active and reactive power responses after one line
opening of feeders to a pure constant impedance load
Fig. 12.9 Load voltage, active and reactive power responses for a pure
after one line opening of feeders to an induction motor load
Chapter 12 533
The figure suggests that the presence of the constant impedance load in
parallel with the induction motor load tends to stabilize the voltage during
normal daily maneuvers. Certain proportions can prevent the collapse and
offset the motor destabilization effects. The pure induction motor content
leads to voltage collapses or voltage instabilities.
Fig. 12.12 Induction motor load voltage response with various types of
mechanical shaft loads
Fig. 12.13 Induction motor load voltage response for different values of
motor inertia constants (H)
538 Induction Motor Role in Provoking Voltage Instability
Fig. 12.14 Induction motor load voltage response with different load node
short-circuit levels due to successive lines tripping
Chapter 12 533
Fig. 12.15 Induction motor load Voltage response with and without
inclusion of synchronous generator dynamics
333 Induction Motor Role in Provoking Voltage Instability
Tmm Tmo Tm 2 m (12.2)
o
Where Tmo is the stand-still load torque, Tm2 constant selected so that
the motor delivers rated torque at rated speed, (m, o) are the motor
asynchronous and synchronous angular speeds respectively. Figure (12.16)
shows the motor starting characteristics without any starting means. The
electromagnetic torque Tem oscillates and settle at its steady-state at 0.6
second while the load torque Tmm shown in broken line nearly constant and
inferior than that electromagnetic torque. This means that till 1.5 second no
starting is reached. The steady-state operating point cannot be obtained. The
rotor slip "S" attains 0.6 and still far from the steady-state value and both the
voltage drop and the initial inrush current, of phase C, are still constants and
state of voltage instability is attained. Not shown on the figure, this situation
is the same for phase's (b) and (a) and continued after 2 seconds.
(a) (b)
(a) (b)
Following a 3-phase fault at the induction motor load bus, fig. (12.19)
shows the load voltage response for 50 and 100 m.sec fault clearing times and
total simulation time of 1sec. 100Motors, each rated 1MW are considered
with similar rated constant impedance load. The post-fault network is kept as
the pre-fault one. The figure shows appearance of state of voltage instability
when the fault clearing time is increased to 100m-sec, at which the voltage
collapses after clearing the fault and settled at 0.74 pu. For a 50 m.sec
clearing time the voltage is retained to 1.0 pu after 1.2 sec. The voltage
instability is confirmed by the plots of the motor load slips shown in fig.
(12.19), for fault clearing times of 100 m.sec. Motors stall as voltage recovery
is insufficient to reaccelerate the motors. This aggravates the situation since
more reactive power demand is required and consequently voltage instability
state result. For lower clearing time, motors reaccelerate and voltage is
retained. Voltage fall in the case of fault clearing time of 100 m.sec and
higher can be explained by the motor current response for fault clearing times
of the 50 m.sec and 200 m.sec. shown in fig. (12.20). A critical clearing time
is found to be 75m.sec. in this case.
Excessive current in the second case, which are clear in fig. (12.20),
leads to excessive voltage drop and consequently lower air gap torques than
the fixed static shaft load torques and consequently deceleration of the motor
rotor motion. In addition to the high voltage drops in the feeding network,
75m.sec fault clearing time is termed critical clearing time for voltage
instability or ''collapse'', as the voltage remains stable for only lower values
than these critical clearing times. Higher short-circuit periods lead surley to
voltage collapses or instabilities.
(a)
(b)
Fig. 12.19 Voltage and slip response for 100 motors case after different
Clearing periods of a 3-phase short-circuit fault at load bus
(a) After 50 m.sec (b) After 100 m.sec
Chapter 12 333
(a) (b)
Fig. 12.20 Motor input current response after recoveries of 3-phase short
circuit of different periods
(a) After 50 m.sec (b) After 200 m.sec
(
b)
Fig. 12.21 Response of rotor voltage angle behind transient reactance for
different fault clearing times
333 Induction Motor Role in Provoking Voltage Instability
load will be extended to 175 m.sec when only 30% of the original motor load
is in service. This is shown in fig. (12.23).
(a)
(b)
Fig. 12.23 Motor rotor slip and voltages response for 30 motors case after
different clearing times
(a) For 100m.sec (b) For 200m.sec
there is no field voltage. The stability of the induction motor is usually judged
by three criteria [4,5].
(a) Angles of Motor Voltage behind Transient Reactance
Response with Time:
The motor stator voltage behind transient reactance is given by:
'
1 eq
r tan
ed'
rq
Or: r tan 1
(12.4)
rd
response is very useful, and these two later indicators are used jointly to judge
the motor stability.
12.16.1 Typical Cases:
Figure (12.24) shows the phase angle of the motor voltage behind
reactance, for stable and unstable cases, while fig. (12.25) shows the
induction motor slips for stable and unstable cases. Figure (12.26) shows the
induction motor input active and reactive powers for stable and unstable
motors loads. Figure (12.27) gives the motor rotor angle during motor
successful and failed starting (stable and unstable) cases.
(a) (b)
(a) (b)
333 Induction Motor Role in Provoking Voltage Instability
Fig. 12.25 Induction motor slip, for stable and unstable load cases
(a) Stable case (b) Unstable case
(a) (b)
Fig. 12.26 Induction motor power for stable and unstable load cases
(a) Stable case (b) Unstable case
(a) (b)
References
[1] M. Z. El-Sadek, "Behavior of Induction Motor Loads During Voltage
Dips and Frequency Excursions Encountered in Transient Stability and
Voltage Stability Studies", Bulletin of the Faculty of engineering,
Assiut University, Egypt Vol.16, July 1987, pp.193-212.
[2] B. M. Weedy, B. R. Cox, "Voltage Stability of Radial power Links",
Proc. IEE, Vol.115, No.4, April 1968, pp.528-535.
[3] M. S. Chen et al., "Determination des Caracteristiques Statiques et
Dynamiques des Charges des Reseaux Electriques", CIGRE Report,
31-11-1978, pp.1-12, (In French).
[4] D. F. Shankle, C. M. Murphy, R. M. Long, and E. L. Harder,
"Transient Stability Studies 1- synchronous and Induction Machines",
AIEE Transaction, Vol.73, Part III-B, 1954, pp.1563-1580.
333 Induction Motor Role in Provoking Voltage Instability
Chapter 13
Blackouts Preventive Measures
This chapter deals with the factors contributing to voltage instabilities
leading to blackouts and the conditions of triggering these phenomena. A
brief idea about blackouts occurred in power systems and means of
prevention of voltage instability in order to avoid their initiation. Preventive
measures of partial or complete blackouts in distribution systems, in
transmission systems and in large networks are briefly displayed. Analysis of
a blackout experienced in a typical large power system is presented, together
with the preventive measures effects on various system conditions. Emphasis
is made on reactive power compensation by static VAR compensators, as they
are the more recent means of prevention of voltage instabilities in large power
systems and in industrial firms.
(a) (b)
Fig. 13.3 Motor load current after three phase short circuit recovery at
its terminals
(a) For 50 ms short-circuit (b) For 200 ms short-circuit
Chapter 13 417
At this collapse, the voltage reaches to 0.7 or 0.8 pu. It can be reflected
in fall of machines output power (the load powers are proportional to V 2) and
may trigger inertial transient instability. Other consumer's loads will become
unstable and suffer from low service power quality. Lamps blackouts and
motors standstills may be experienced.
Motors:
Scattered domestic, industrial and residential small induction motors
can be regarded as a single large induction motor. Starting of such small
motors simultaneously can be represented by the start-up of a large motor, of
several MVA rating connected to the UHV load node. The voltage response
of the load node is shown in fig. (31.4) for two cases: successful motor starting
and-failed motor starting conditions of a 100MVA motor rating. Without
starters, voltage dips to 0.88pu are experienced, which even with successful
starting will last for 3 seconds, which is sufficient to cause a state of voltage
and inertial instability, besides the other loads instability. Use of controlled
TSC static VAR compensators can alleviates these problems.
(a) (b)
Limits:
Large machines cannot deliver their full-load capacity, when they are
operating near their steady-state stability limit. Increasing the load demand
causes load angle to increase and output power to fall to zero value. A case of
pole slipping may occur. This state may be regarded as a virtual short-circuit
at the machines terminals as the power reaches zero value, which results in
loss of its synchronism with the system, and in unstable voltages. Figure
(13.5) shows the voltages of the four loads of a three machines four loads
system during pole slipping.
P2 Q2
V I Z Z (31.1)
V2 V2
Chapter 13 419
These drops add to a large value at the UHV nodes and are reflected in
voltage problems at the generator nodes. The presence of several inductive
elements in the network such as: Otto-transformers, voltage stabilizers,
induction motors at running or at standstill state, small power transformers,
actuators operated with motors, irrigation pumps motors, welders,
refrigerators, gas discharge lamps, arc furnaces, and general purposes
machines, increase drastically the reactive power demand. In turn this leads to
excessive voltage fall in network lines and generator terminals, if these
reactive powers are uncontrolled during different operational conditions.
(d) Generators are too far from loads: this results in higher transmission
system reactance’s "X" and, higher "IX" voltage drops.
(e) Separation of some generating units through their protection systems
caused by standstill of their auxiliaries motors, due to low terminal
voltages.
(f) Excessive load power demand: which forces the system to operate near
it's critical voltage. The risk is biggest, when the reactive power
consumption is greater than expected.
(g) Low generation voltages: high voltage at the generating end increases
transmissible power, while low voltage brings the operating points near the
critical point.
(h) Existence of induction motors loads: as they demand heavy reactive
power when voltage falls.
(i) Operation of large electric welding factories near heavily loaded
networks.
(j) Presence of highly rated arc-furnaces at the middle of radial networks.
(k) Presence of excessive power factor correction capacitors in networks
polluted by currents and voltage harmonics.
(l) Presence of repetitive unbalanced 3-phase loads, such as arc-furnaces
and electric single-phase trains and single-phase induction motors.
.2 Triggering
31 Voltage Instability Leading to
Blackouts:
The instability of the voltage is usually triggered by some forms of
disturbances resulting in changes in the reactive power situation. Lines
opening or tripping of local generators or addition of new important loads
during peak load periods are all examples for such forms of disturbances.
Additional loads during peak period or sudden impacts of loading or sudden
reloading of large consumers are other causes. Malfunction of control or
protection systems can also trigger voltage instability. Repetitive loading of
trains, furnaces, lifts or welding machines can trigger such voltage
instabilities.
Having known that the voltage drop between two nodes, connected by a link
of impedance Z=R+jX, Generator node voltage is E, load powers are P+jQ
and load node voltage is Vr, is given by:
XQ RP
V E Vr (31.2)
Vr
According to this simple equation, the voltage drops, which leads to voltage
instability are, function in P, Q, R, X and E, together with V r, which is
governed by load nature, type and powers/voltage relations. Therefore, the
avoidance of occurrence of voltage instability can be achieved by:
.4.2
31 Minimization of Transmission Circuits
Impedances:
(a) For Lines:
Use of several circuits in parallel. This is an expensive solution .
Use of superconducting lines or cables, but this is in experimental stage.
Use of series capacitor to minimize the reactance of the line, but it can
cause subsynchronous resonance, which can damage generator rotors .
Fig. 31.9 Voltage magnitude shape before, during and after the blackout
of April, 24, 1990 in the Egyptian network
factors improved to 0.9 and to unity at these UHV level nodes. The results
indicate voltage level increase to the extent that with unity power factors,
voltage levels lie within the 5% limits of their nominal values without any
external means of voltage control. This can be achieved by forcing customers
(domestic and industrial) to improve their loads power factors to nearly unity
at all voltage levels. Compensation should be at all transformation
substations. For the same load power, improvement of the load power factor
raises the operating point to a new V/P curve at positions far from the critical
values of the nose curve of all system nodes.
Table 31.1 Egyptian Network voltage levels with different loads power
factors with and without reactive power injection.
Bus Voltages with (*) Voltages with (**) Voltages with (***)
Actual loads P.F Unity P.F loads 0.9 P.F loads
Number B. INJ. A. INJ. B. INJ. A. INJ. B. INJ. A. INJ.
3 0.000 3.000 3.000 3.000 3.000 3.000
2 3.011 3.011 3.011 3.011 3.011 3.011
1 0...0 0...0 0...0 0...0 0...0 0...0
4 0...0 0...0 3.00. 3.00. 0...0 0...0
5 0.... 0...0 3.0.3 3.0.3 0...0 3.003
6 0..10 0...0 3.01. 3.01. 0..1. 0...0
7 0..01 0..0. 0.... 0.... 0...3 0...1
8 0.... 0.... 0.... 0.... 0.... 0...0
9 0.... 0...1 3.010 3.010 0..0. 0...1
31 0.... 3.00. 3.0.3 3.0.3 3.00. 3.00.
33 3.000 3.001 3.03. 3.03. 3.001 3.001
32 0..0. 0.... 3.03. 3.03. 0...1 0....
31 0...3 3.003 3.0.. 3.0.. 0.... 3.00.
34 3.00. 3.00. 3.011 3.011 3.00. 3.033
(*) Injected reactive power = 73 MVAR at node # 6 NH 500.
(**) No injection of reactive power is required.
(***) Injected reactive power = 38.37 MVAR at node # 6 NH 500.
B. INJ. Before reactive power injection
A. INJ. After reactive power injection
900 km length costs today nearly 200 million dollars while one 220kV circuit
costs nearly 130 million dollars. Usually, there is deficiency in available ways
to install such towers and lines. These reasons make this solution expensive.
Secondly, system dynamics are considered. Aswan zone bus (node #8)
is assumed to be subjected to a 3-phase short-circuit, cleared by opening one
circuit of the two 500 kV circuits between Aswan (8) and Nag-Hammady (9).
Exactly this is the official announced fault on April 24, 1990. The short
circuit is assumed to be lasted only for the circuit-breaker opening time i.e.
for 120-m sec. The assumed short-circuit may be due to solid lines connection
at Aswan or due to a voltage failure resulting from reaching the critical
voltage point at the peak-load period, i.e. a state of virtual internal system
short-circuit due to load instability at any node on the 500kV line. Figure
(31.11) shows the machines terminal voltages after fault clearing. Machines
pole slipping is occurred. Injection of rapid controlled reactive power
generated by static VAR compensator can stabilize such voltage.
Fig. 31.11 Machines terminal voltage response after 120 m sec short-
circuit duration at node # 8 recovered by single line of two circuit
Figure (13.12) shows that the minimum rating of all these minimums is
obtained when the compensator is connected to node #9 (Nag-Hammady).
The figure shows that this rating amounts to 73MVARs, when the short
circuit period is 120 m.sec. This coincides with the linear programming
results obtained with the steady-state conditions. Figure (13.13) shows the
machines angular speeds deviations with 120 m sec fault at Aswan node #8
cleared with one line opening between (8-9), while fig. (13.14) shows the
machines angular terminal voltages response. In these two figures the fault
recovery was made after 120 m.sec and by using a static VAR compensator of
73MVAR rating at nodes #8, #9, #10, and #15 successively.
Figure (31.13), (31.14) show that the compensator stabilizes the system
if, and only if, it is connected to node #9 (Nag-Hammady). Moreover, they
indicate that connecting the compensator to node #15 (northern zone bus)
increases the system instability. This can be explained regarding the voltage
response of the 500kV nodes and Cairo nodes after using 73MVAR static
VAR compensator successively at these nodes as shown in fig. (1 1.14). The
figure shows that voltage instability in the form of voltage oscillations lasts
when SVC was connected to Aswan node #8), or to Sammallout node (#10)
or to Cairo and Delta node (#15).
432 Blackouts Preventive Measures
Fig. 31.12 Minimum required compensator rating for just stabilizing the
system subjected to different short-circuit recovery times when it is
located at different nodes
Network
Fig. 13.17 Neuro-Fuzzy controller applied to excitation system and to
static VAR compensator
Table (13.2) The critical clearing time for short-circuits at different nodes
(a)
(b)
Table (13.6) presents the saving in Egyptian pounds (equal to 0.2 $) when
applying the proposed adaptive NFL-PSS stabilizer.
(a)
(b)
Fig. 13.19 Machines speed deviation response after a sudden 6% load
jump at node # 15 with and without PSS
Fig. 13.20 Damping ratio with SVC at various locations and with
adaptive controls
(a)
K=100
K=47
K=25
K=40
(b)
Increasing the gain to 100, the system loci moves towards the unstable
region. Different controller time constants ranging from 0 sec to 2 sec are
used. Figure (13.21) shows the results for range between 0.02 to 0.1 sec. at
different controller gains k. Maximum damping to the system at controller
gain of 47 is clear. On the other hand it was known that lower time constants
give better damping but fig. (13.21) shows clearly that time constants lower
than 0.04 sec and higher thin 0.07 sec. yield lower damping. This result is
new in this domain. Also, damping will be nearly constant for time constants
ranging 0.04 up to 0.07 sec, upon using adaptive controls.
Figure (13.22) shows the needed SVC rating to get certain damping
ratio between 0.59 and 0.64 in the system when SVC is provided by a
conventional controller and by an adaptive (pole placement) controller. The
figure shows a very important result that the SVC rating is reduced by a ratio
between 20% and 37% in some cases. This means that using the modern
controller (Pole Placement Controller PPC) saves about (1/5 to 1/3) the SVC
rating, which means that SVC price will be lower and cost of the adaptive
control implementation can be compensated by the saving in the SVC rating.
On the other hand, fig.(13.23) shows that the saving in the SVC rating due to
the adaptive controller use is limited. Very low rating will not be effective
even if adaptive controllers are used. The SVC effective ratings range is
shown in fig. (13.23). Clearly lower ratings are used but the band of effective
ratings is as shown in that figure.
Fig. 13.22 SVC ratings for certain damping ratio’s of the system
oscillations
(a) Without adaptive controller (b) With adaptive controller
.7 Summary:
31
Problems
13.1 Voltage instability can lead to synchronous instability. Explain?
13.2 Synchronous instability is frequently associated with voltage
instability. Illustrate?
13.3 What are the general measures for avoiding voltage instability in power
systems?
13.4 What are the techniques, which can be used for prevention of voltage
instability in distribution systems?
13.5 What are the means of preventing transient voltage instability?
13.6 Explain how load power factors correction can effectively participate in
voltage instability alleviation in developing countries power systems?
13.7 Explain how voltage instabilities can be limited by providing
generators with automatic voltage regulators .
13.8 Minimization of transmission systems impedance’s can improve
voltage stability. Explain?
13.9 Use of cables excessively improve voltage stability to great extent .
Illustrate?
444 Blackouts Preventive Measures
13.10 What are the means of controlling reactive power at load terminals?.
What are the advantages of the recent electronic devices ?
13.11 Booster transformers and tap-changing transformers can alleviate
voltage problems and improve voltage stability. In what conditions?
13.12 Voltage collapse is experienced in several systems. What are the
methods of its elimination?
13.13 Voltage failure or complete blackouts were experienced in many
countries in developed and under developing ones. What were the main
causes of the blackouts and what are the countermeasures taken for
avoiding them in future?
13.14 Recent flexible AC transmission systems (FACTS) are new means for
limitation of chances of voltage instability. Explain?
13.15 Distribution systems suffer from certain voltage stability problems.
Which are?
13.16 Voltage instability creates invisible virtual short circuits at certain
critical nodes. Explain this effect in triggering voltage instability. Was
they led to the complete blackouts of the Egyptian power system?
13.17 What are the effects of the recent adaptive controls in preventing
voltage and synchronous stabilities.
References
[1] M. Z. El-Sadek, "Preventive Measures for Voltage Collapse and
Voltage Failures in the Egyptian Power System", Electric Power
System Research, Vol. 44, No. 3, 1998.
[2] M. Z. El-Sadek, "Voltage Instabilities Subsequent to Short-Circuit
Recoveries", Electric Power Systems Research Journal, Lausanne,
Switzerland, Vol.21, No.1, pp. 9 - 16, 1991.
[3] M. Z. El-Sadek, "Optimization of Static VAR Systems Parameters for
Stabilizing Power System Oscillations", Ph. D. Thesis No. 446, Swiss
Federal Institute of Technology Lausanne, Switzerland, 1982.
[4] M. Z. El-Sadek, N. H. Fetih, F. N. Abdelbar, "Starting of Induction
motor by Static VAR Compensators", IEE Publication No. 291,
London, pp. 444 - 447, 1988.
[5] M. Z. El-Sadek, and F. N. Abdelbar, "Effects of Induction Motor Load
in Provoking Transient Voltage Instabilities in Power Systems",
Electric Power Systems Research Journal, Lausanne, Switzerland, Vol.
17, No. 2, pp. 119 - 127, 1989.
[6] R Macaw, "The Great Blackout", Power Engineering, pp. 36a -36c,
Dec. 1965.
[7] Federal Power Commission Report, "Northeast Power Failure", Report
Submitted to the President of USA, Dec. 1965
Chapter 13 445
jX tr jX a jX b (7.5)
VS V R
Pmax (7.6)
X tr
jXa jXb
Load
P+jQ
XS jBC XR
Load
P+jQ
(a) (b)
Thus if BC() is capacitive, XSR will be less than Xtr, the maximum power of
eqn. (7.6) will be more than without FACT element. On the other hand if
BC() is inductive (or negative), the transfer reactance X'tr will be more than
Xtr and the maximum transmitted power is less than that drawn without
FACTS. The network configuration is changed by addition of X S and XR at
the source and load terminals respectively. This will change the current
distribution and changes the load voltage VR, if VS is kept constant, according
to:
P jQ VR
VR VS jX tr' (7.8)
VR
* Z R
P jQ
VR VS j X a X b (7.9)
*
V R
4.3
FLC in (Rec.)
FLC in (Inv.)
4.1
FLC in (Rec. & Inv.)
Id c in p .u
3.9
3.7
3.5
0 0.1 0.2 0.3
Time in sec.
(a)
40
alpha in deg.
30
20
FLC in (Rec.)
10 FLC in (Inv.)
FLC in (Rec. & Inv.)
0
0 0.1 0.2 0.3
Time in sec.
(b)
(c)
20
18
g ama in deg.
16
14 FLC in (Rec.)
FLC in (Inv.)
12 FLC in (Rec. & Inv.)
10
0 0 .1 0 .2 0 .3
Time in sec.
444 Appendix A
Appendix A
Derivation of the Formula of the dZ/dVr Criterion and
the Formula of the dE/dV Criterion
The major parameter to be considered is the impedance Z between the
supply-end infinite busbar and the load. Voltage stability is judged by the sign
of the derivative dVr/dZ. The development of the dZ/dVr, for a two nodes
power system, is as follows: For a system consists of a source E s feeding a
load S=P+jQ, through a short line having Z=Rth+jXth, then:
_
Es Es 1 c jd Es cos 1 jEs sin 1 (A.1)
_
Vr Vr 2 a jb Vr cos 2 jVr sin 2 (A.2)
_ _ _
S P jQ Vr I *
_
_ S *
Pr jQr
I
_ a jb
Vr*
_ _
_
Z
E s Vr
c jd a jd a jb c a k d ba jb
_ Pr jQr Pr jQr
I
_
Z
Pr ac db a 2 b 2 Qr ad bc j Pr ad bc Qr ac db a 2 b 2 (A.3)
Pr2 Qr2
Having:
_
Z Rth jX th
Hence, after substitution from Eqn. (A.1) for a, b, c and d into Eqn. (A.3) and
separation of Rth and Xth, we obtain:
Rth2
Pr2 ac bd a 2 b 2
2
Qr2 ad bc 2 2 Pr Qr ac bd a 2 b 2 ad bc
P r
2
Qr2
2
Rth2
Pr2 E sVr cos 12 Vr2
2
Qr2 E sVr sin 12 2 2 Pr Qr E sVr cos 12 Vr2 E sVr sin 12
P r
2
Qr2 2
Appendix 444
And:
X th2
Qr2 E sVr cos 12 Vr2
2
Pr2 E sVr sin 12 2 2 Pr Qr E sVr cos 12 Vr2 E sVr sin 12 2
P r
2
Qr2
2
Z
2
Pr Qr
2
V
V r
4
E s2Vr2 2Vr3 E s cos 12
Vr P r
2
Qr2
Z 1
Vr P 2 Q 2 V 4 E 2V 2 2V 3 E cos
r r r s r r s 12
E
2Vr3 VEs2 s Vr2 E s Vr3 cos 12
Vr
(A.5)
12 Vr3 E s sin 12 3Vr2 E s cos 12
Vr
Vr4 E s2Vr2 2Vr3 E s cos 12 Pr Qr
- P
r V Q r
Pr2 Qr2 r V r
z
K 2V 3 V E 2
r r s V
Es
V 2 E V 3 cos
r s r
12
12 3
V
V E sin
r s 12
r r
V 4 E 2V 2 2V 3 E cos P 4
12 P Q
r
V 2 E cos r s r r s
r s 12 r V Qr V 0
r
2
P Q 2
r r r
(A.6)
444 Appendix A
Qr is positive for leading power factor and negative for lagging power factor,
in this analysis.
Ps 12
, are calculated from the load powers/voltage characteristics.
Vr Vr
Ps 12
, can be derived as follows:
Vr Vr
The real and reactive power flows in this circuit may be written as a function
of the circuit variables as follows:
Note that all voltage values are "scalar" quantities. For small increments,
P P P
Pl l Vr l E s l 12
Vr E s 12
Q Q Ql
Ql l Vr l E s 12
r
V
sE
12
P Q
Pr r 12 and Qr r 12
Vr Vr
Using: Pl Pr and Ql Qr
Gives:
Pl P P P
E s l 12 r l Vr
V
E s 12 r Vr
(A.7)
Ql Ql Qr Ql
E s 12 Vr
s
E
12
r r
V V
From Eqn. (A.7), by writing in determinant from the expression for Vr, the
equation for Es/Vr can be obtained:
Pl Pl
E s
12 E s
Ql Ql
E s
12 E s
12
Pl Pl
E s
12 E s
Ql Qr Ql
12 r V V r
Appendix 444
Therefore:
E s K
(A.8)
Vr Pl Ql Pl Ql
s 12 12 s
E E
Where:
K is the denominator determinant.
For steady-state stability, Eqn. (A.8) has to be positive and the sign of the
numerator and denominator of Eqn. (A.8) will be considered. From fig. (6.1),
the equation for real and reactive power may be written as:
E V V 2
P s r
l Z 12
sin δ α r sinα
Z
l l
EsVr V 2
Q
l
12
cos r cos
Z
Zl l
Pl Vr
sin 12
E s Z l
Pl E s 2V
sin 12 r sin
Vr Z l Zl
Pl E V
s r cos 12
12 Z l
Ql Vr
cos 12
E s Z l
Ql E s 2V
cos 12 r sin
Vs Z l Zl
Ql E sVr
sin 12
12 Z l
Ql E s 2V
cos 12 r cos
Vr Z l Zl
Therefore:
Pl Ql Pl Ql E sVr2
E Z 2 (A.9)
sE 12 12 s l
E s K
Vr Pl Ql Pl Ql
sE 12 12 E s
E s Z l 2Vr 2V E
cos cos 12 r sin sin 12 s (A.11)
Vr Vr Z l Zl Zl
Or:
E s Z l '
K C A.12)
Vr Vr
Appendix 454
From Eqns. (A.7), by writing in determinant from the expression for 12, the
equation for Es/12 can be obtained:
Es
12 Vr 2 Z1 V E
E V
cos sin r
s cos sin
Vr Es s r E V2
12 12
s r
12
(A.14)
Appendix B
Determination of the Maximum Receiving End Power
and Critical Load Nodes Voltage for Constant Receiving
End Qr
The sending end voltage for two nodes system is given by:
E
2
s
2 2 B
A V
r r
V
2
2 r r
r
P 2 Q 2 2 AB P cos Q sin
r
(B.1)
r
_ _
Where: A A and B B are the line generalized line constants.
2
Multiply both sides of Eqn. (B-1) by Vr , we get:
0E
2
s r r r r
2
r r
r
A V B P 2 Q 2 2 ABV P cos Q sin
2 4 2
(B.2)
Let:
K 2 ABPr cos Qr sin
Eqn. (B.2) will be in the form:
2 4 2
2
A Vr V K E 2 B P 2 Q 2 0
r s r r
(B.3)
From Eqn. (B-3) Vr21, 2 is calculated by:
Vr
2
1,2
1.0
2 K E s
2 A
2 K Es2 2 4 A2 B 2 Pr2 Qr2 (B.4)
Corresponding to Pmax there is one value of Vr, as the two values are
coincident, then the term under the root must vanishes. i.e, the term under the
root become zero. The two equal values of the voltages Vr21, 2 are thus the first
part only of Eqn. (B.4), i.e
K Es2 2 4 A2 B 2 Pr2 Qr2
Or: r
2 AB P cos Q sin E 2
r s
2 2 2
4A B P2 Q2
r r
(B.5)
Eqn. (B.5) can be rewritten in the general form:
The voltage corresponding to Pmax is the critical voltage, which is given by:
Vcr
1
2A
2
K E s2 (B.6)
Appendix C
Distribution Overhead Lines and Cables Parameters and
Typical Power Systems Data
Table C.1 Impregnated paper insulated power cables parameters
10 1.786 0.435
Copper 16 1.123 0.410
25 0.738 0.400
35 0.525 0.395
Condition Ambient temperature 20C & Frequency 50Hz
Reference German standard taken A base of our calculation
Load data
Bus Load Bus Load
No. MW MVAR No. MW MVAR
1 0.0 0.0 16 3.5 1.8
2 21.7 12.7 17 9.0 5.8
3 2.4 1.2 18 3.2 0.9
4 7.6 1.6 19 9.5 3.4
5 94.2 19.0 20 2.2 0.7
6 0.0 0.0 21 17.5 11.2
7 22.8 10.9 22 0.0 0.0
8 30.0 30.0 23 3.2 1.6
9 0.0 0.0 24 8.7 6.7
10 5.8 2.0 25 0.0 0.0
11 0.0 0.0 26 3.5 2.3
12 11.2 7.5 27 0.0 0.0
13 0.0 0.0 28 0.0 0.0
14 6.2 1.6 29 2.4 0.9
15 8.2 2.5 30 10.6 1.9
Generation data
Bus Voltage Generation MVAR Limits
No. Mag. MW Min. Max.
1 1.06 --- --- ---
2 1.043 40.0 -40.0 50.0
5 1.01 0.0 -40.0 40.0
8 1.01 0.0 -30.0 40.0
10 1.082 0.0 -6.0 24.0
13 1.071 0.0 -6.0 24.0
354 Appendix C
Appendix D
Required Capacitors Ratings for Improvement of Power
Factors of Electrical Equipment's and Motors
Table D.1 Three-phase transformers to British Electricity Boards
specification T1 (1958)
KVA 7.2/12/17.5/23 kV 24 kV 36 kV
rating Off load On load Off load On load Off load On load
VAR VAR VAR VAR VAR VAR
16 1080 1360 --- --- --- ---
25 1500 2130 1740 2470 1950 2980
40 2020 3170 2320 3680 2520 3880
63 2500 4460 3020 5300 3480 5760
80 2760 5340 3560 6540 4280 7260
100 3600 6920 4160 7960 5080 8880
125 4500 8760 5000 9860 6140 11000
160 5000 10580 6050 12390 7500 13840
200 6300 13550 7160 15160 8900 16900
250 7800 16950 8620 18970 10700 21050
315 10000 21700 10300 23800 12600 26100
400 10800 25700 13200 30000 15200 32000
500 13500 32300 15800 36800 18000 39000
630 17000 40700 18800 43600 21200 46000
Appendix 854
Table D.4 Capacitor size required to improve power factor to 0.86 and
showing extra powers available by improving the power factor
Table D.7 Recommended capacitor ratings for use with typical single-
phase single operator arc-welding transformers
Table D.9 Rating of capacitor banks for power factor correction of arc
furnaces
Appendix
Motor 3000 1500 1000 750 600 500 375
rated Reactive power in KVAR for
Load % F. L. Load % F. L. Load % F. L. Load % F. L. Load % F. L. Load % F. L. Load % F. L.
(hp) 100 75 50 100 75 50 100 75 50 100 75 50 100 75 50 100 75 50 100 75 50
1 0.8 0.7 0.6 0.9 0.8 0.7 1.1 1.1 0.8 1.2 1.1 1.0 --- --- --- 1.5 1.5 1.4 --- --- ---
2 1.2 1.1 1.1 1.5 1.4 1.4 1.5 1.3 1.3 2.1 2 1.9 --- --- --- 2.8 2.8 2.5 --- --- ---
3 1.7 1.6 1.5 2.1 1.8 1.7 2 2 2 2.8 2.5 2.4 3.4 3 2.8 3.9 3.7 3.5 --- --- ---
5 2.6 2.3 2.1 3.2 2.8 2.5 3.2 2.9 2.7 4.4 4.2 3.8 5 4.7 4.4 5.6 5.3 4.9 --- --- ---
7 3.3 2.8 2.5 4.3 3.7 3.6 4.3 3.9 3.6 5.6 5.5 5.1 6.4 5.8 5.6 7.1 6.9 6.5 --- --- ---
10 4.4 3.9 3.3 5.7 4.9 4.5 5.6 5 4.5 7.4 7 6.7 8.2 7.1 6.4 8.6 7.5 6.6 --- --- ---
15 6.7 6 5.2 8.4 7 6 8.2 6.9 6.3 10 9.7 8.7 11 10 9 13 11 10 --- --- ---
20 9 7 6 10 9 7 10 8.8 7.8 12.4 11.9 10.8 15 13 11 16 14 13 --- --- ---
30 13 10 9 14 12 11 15 13 11 18 17 15 20 18 16 22 21 18 --- --- ---
40 16 14 12 17 16 14 19 16 15 21 20 18 26 23 20 27 24 20 --- --- ---
50 20 17 14 21 20 17 23 19 17 29 27 22 31 27 24 32 29 25 36 32 28
60 20 17 16 24 20 17 24 21 19 30 28 25 33 29 25 40 35 30 41 34 31
70 21 17 16 26 22 19 27 25 22 33 28 25 39 35 29 44 37 33 47 40 36
80 24 20 18 30 24 21 31 29 25 37 32 26 41 36 31 50 43 37 53 45 39
90 27 22 21 33 30 26 37 33 28 40 34 29 46 40 35 51 44 38 60 51 44
100 30 25 23 37 33 29 44 38 33 44 38 32 51 44 38 57 49 42 62 54 47
120 --- --- --- 44 39 34 47 41 34 53 45 38 58 51 43 61 53 45 --- --- ---
140 --- --- --- 48 43 37 52 46 38 61 52 42 64 57 47 71 62 52 --- --- ---
160 --- --- --- 56 44 40 59 52 42 66 54 47 69 59 52 84 75 62 --- --- ---
180 --- --- --- 63 50 45 66 59 47 70 58 51 78 67 58 --- --- --- --- --- ---
200 --- --- --- 63 55 46 68 58 48 82 68 58 87 74 62 --- --- --- --- --- ---
464
220 --- --- --- 68 61 50 75 64 53 90 75 64 --- --- --- --- --- --- --- --- ---
250 --- --- --- 77 69 57 86 68 57 103 85 73 --- --- --- --- --- --- --- --- ---
On-Load Tap Changing Transformer
On changing transformers taps, it’s not allowed to interrupt customer
service so, on-load tap changing transformers are used to regulate the
voltage and to keep its level within limits without interrupting the load.
This is actually done by changing the transformation ratio automatically by
a control system. Tap are frequently installed on the high transformer
voltage side since the current on this side is smaller and the current-
carrying parts of the tap changing gear are therefore less bulky and less
difficult to handle, and the tapping on the low voltage side may not give
sufficiently close control of voltage. The block diagram of transformer tap
changing control system is shown in Fig (F-1)
Microcomputer for
Motor calculating Δ t by
linear programming
a
a’
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
1 0 0 0 0
2 0 0 0 0 0 0
3 0 0 0 0 0 0
4 0 0 0 0 0 0
5 0 0 0
A 0 0 0 0 0 0 0 0 0
B 0 0 0 0 0 0 0 0 0
C 0 0 0 0 0 0 0 0 0 0
D 0 0 0 0 0 0 0 0 0
R 0 0 0 0 0 0 0 0 0 0 0 0 0
S 0 0 0 0 0 0 0 0 0 0 0 0
T 0 0 0 0 0 0 0 0 0
Table (F-1)
1
T
Transformer
winding S
2
Auxiliary
winding
To illustrate the idea of the required steps of the tap changing, the steps
required to change, for example from tap position (1) to another position (2)
of a two-tap transformer of fig (F-2) are given in table (F-2)
In the first step (initial state), contact 1 and switches R and T are close, and
2, S are open. In the second step, contact 2 is close. Afterwards, switch T is
opened in the third step. Then, switch S is turned to the close position. The
fifth step includes the opening of switch R. Finally, in the sixth step, contact
1 is open and switch T is close. The transformer tap is then changed from
position 1 to position 2 without interrupting the load.
On-load tap changing transformers are generally designed for 15%--
20% voltage change, but in steps, each of 1-2%. These steps are
automatically changed by a control system.
Table (F-2) steps required for changing from one tap to anther of 2 tap
transformers
1 2 3 4 5 6
1 C C C C C 0
2 0 C C C C C
R C C C C 0 0
S 0 0 0 C C C
T C C 0 0 0 C
“C” denotes closing a contact or switch and “O” denotes opening a contact
or switch.
i t : 1 j
Y
Node i Node j
Y/t
Y(t-1)/t2 Y(t-1)/t
Auto-transformers
The auto transformer is a two winding transformer with the secondary
winding is tightly connected to primary as shown in fig. (F-9)
Ideally
V1I1= V2I2
Which agrees with the current-flow directions shown in figure (F-5) the
apparent power delivered to the load may be written as
And