Design Services For Power and Telecommunication Networks

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Kingdom of Saudi Arabia

Royal Commission for Jubail and Yanbu


Royal Commission in Jubail

JOB NO. 027-T36


DESIGN SERVICES FOR POWER AND TELECOMMUNICATION NETWORKS

CONTRACT NO. 139-C04


PRIMARY INFRASTRUCTURE OF JUBAIL 2, STAGE 4 – PHASE 1

E Oct 2022 Issued for Bid Syed Mohsin Eqbal Javid Ashraf Ghoneim Michail Flessas

Rev. No. Date Revision(s) Prepared By Reviewed By Submitted By Approved By

INSTRUMENTATION Job No. 027-T36 Contract No. 139-C04

DATA SHEET – PRESSURE TRANSMITTER Doc. No. 139-C04-DATA-20UT-EA-101 Rev. E


(SWW LIFT STATIONS) Page 1 of 4
The design parameters/requirements are to be confirmed by the Contractor.

SL. No. Design Data Requirements Vendor’s Data


GENERAL

1 Instrument Tag See table below

2 Service description See table below


139-045-20UT-PE-200 &
3 P & ID number
PE-201
TRANSMITTER
Piezoresistive/
4 Sensing element
Capacitance
5 Mounting Direct

6 Power supply 24 VDC


7 Conduit connection type ¾ inch NPT
8 Enclosure class EExd Gr IIA, B & IP-66
Polyurethane coated
9 Housing material
Aluminium
10 Output signal 4-20 Ma +HART
11 Element type Diaphragm
15 Element material SS 316 L
16 Body material SS 316
¾ inch ANSI 150# FF
17 Process connection
Flanged Diaph.seal
18 Flush kit Required
19 Mounting bracket *
20 Calibration range See table
21 Span limits *
SERVICE CONDITIONS
22 Fluid Sewage water
23 Max. Pressure 6 bar G

Doc. No. 139-C04-DATA-20UT-EA-101, Rev. E Page 2 of 3 Contract No. 139-C04


The design parameters/requirements are to be confirmed by the Contractor.

SL. No. Design Data Requirements Vendor’s Data


Operating Temperature / Max.
24 32 °C / 46 °C
Temperature
ENVIRONMENTAL CONDITIONS
25 Maximum temperature 55 °C
26 Humidity 10 - 95%

* Vendor to specify
Note:
1) The enclosed product data sheet is illustrative example of the minimum level of
quality and performance of the product which the Contractor is required to provide
and install. The actual final products provided and installed must be at least the
equivalent of or exceed the examples given in both quality and performance.
2) Process connection flange shall provide flushing port inbuilt.
TABLE-1

S.l. No Tag Range Service description Lift Station

1. PIT-101 0-8 BAR G Pump P-01 discharge


pressure
Pump P-02 discharge SWW-LS-1
2. PIT-102 0-8 BAR G
pressure
3. PIT-201 0-8 BAR G Pump P-01 discharge
pressure
Pump P-02 discharge SWW-LS-2
4. PIT-202 0-8 BAR G
pressure

Doc. No. 139-C04-DATA-20UT-EA-101, Rev. E Page 3 of 3 Contract No. 139-C04

You might also like