Smoke Spill Calculation

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 3

Smoke Spill Calculation

Project :
Specification: BOMBA requirements & MS 1780

Location : Level G - Production 1

Minimum Air Change Per Hour : 10 ACH

Total Area : 2,167.35 M2


23,329.36 FT2

Room Height: 4.80 M


15.74 FT

Room Volume: Total Area x Room Height


10,403.28 M3
367,297.37 FT3

Smoke Spill Exhaust @ 10ACH - 61,216.23 CFM

Suggested Fan Capacity & Quantity - 30,608.11 CFM x2

Smoke Spill Fan Selection: SSF-G1 31,000 CFM @ 1"WG / Class H


SSF-G2 31,000 CFM @ 1"WG / Class H

Make-Up Air : 75% of Smoke Exhaust Air Volume


FAF-G1 23,250 CFM @ 1"WG / Class H
FAF-G2 23,250 CFM @ 1"WG / Class H

Location : Level G - Production 2

Minimum Air Change Per Hour : 10 ACH

Total Area : 1,828.50 M2


19,681.97 FT2

Room Height: 4.80 M


15.74 FT

Room Volume: Total Area x Room Height


8,776.80 M3
309,873.00 FT3

Smoke Spill Exhaust @ 10ACH - 51,645.50 CFM

Suggested Fan Capacity & Quantity - 25,822.75 CFM x2

Smoke Spill Fan Selection: SSF-G3 26,000 CFM @ 1"WG / Class H


SSF-G4 26,000 CFM @ 1"WG / Class H

Make-Up Air : 75% of Smoke Exhaust Air Volume


FAF-G3 19,500 CFM @ 1"WG / Class H
FAF-G4 19,500 CFM @ 1"WG / Class H
Smoke Spill Calculation
Project :
Specification: BOMBA requirements & MS 1780

Location : Level 1 - Production 3A

Minimum Air Change Per Hour : 10 ACH

Total Area : 2,167.35 M2


23,329.36 FT2

Room Height: 4.30 M


14.10 FT

Room Volume: Total Area x Room Height


9,319.61 M3
329,037.23 FT3

Smoke Spill Exhaust @ 10ACH - 54,839.54 CFM

Suggested Fan Capacity & Quantity - 27,419.77 CFM x 2

Smoke Spill Fan Selection: SSF-L1-1 28,000 CFM @ 1"WG / Class H


SSF-L1-2 28,000 CFM @ 1"WG / Class H

Make-Up Air : 75% of Smoke Exhaust Air Volume


FAF-L1-1 21,000 CFM @ 1"WG / Class H
FAF-L1-2 21,000 CFM @ 1"WG / Class H

Location : Level 1 - Production 3B

Minimum Air Change Per Hour : 10 ACH

Total Area : 1,828.50 M2


19,681.97 FT2

Room Height: 4.30 M


14.10 FT

Room Volume: Total Area x Room Height


7,862.55 M3
277,594.56 FT3

Smoke Spill Exhaust @ 10ACH - 46,265.76 CFM

Suggested Fan Capacity & Quantity - 23,132.88 CFM x 2

Smoke Spill Fan Selection: SSF-L1-3 24,000 CFM @ 1"WG / Class H


SSF-L1-4 24,000 CFM @ 1"WG / Class H

Make-Up Air : 75% of Smoke Exhaust Air Volume


FAF-L1-3 18,000 CFM @ 1"WG / Class H
FAF-L1-4 18,000 CFM @ 1"WG / Class H
Smoke Spill Calculation
Project :
Specification: BOMBA requirements & MS 1780

Location : Racking Warehouse

Minimum Air Change Per Hour : 10 ACH

Total Area : 1,434.50 M2


15,440.96 FT2

Room Height: 16.47 M


54.02 FT

Room Volume: Total Area x Room Height


23,627.65 M3
834,195.90 FT3

Smoke Spill Exhaust @ 10ACH - 139,032.65 CFM

Suggested Fan Capacity & Quantity - 34,758.16 CFM x 4

Smoke Spill Fan Selection: SSF-L3-1 35,000 CFM @ 1"WG / Class H


SSF-L3-2 35,000 CFM @ 1"WG / Class H
SSF-L3-3 35,000 CFM @ 1"WG / Class H
SSF-L3-4 35,000 CFM @ 1"WG / Class H

Make-Up Air : 75% of Smoke Exhaust Air Volume


FAF-L3-1 26,250 CFM @ 1"WG / Class H
FAF-L3-2 26,250 CFM @ 1"WG / Class H
FAF-L3-3 26,250 CFM @ 1"WG / Class H
FAF-L3-4 26,250 CFM @ 1"WG / Class H