([FHO

Q7750A ZONE MANAGER

63(&,),&$7,21'$7$
)($785(6
Š
‡ ,QWHUIDFHV(;&(/ 6\VWHP&%XVWR([FHO
Š Š
(FKHORQ /21:25.6  (%XV QHWZRUN

‡ 3URYLGHVD%3RUWFRQQHFWLRQYLDD3&IRUWKH;,
2SHUDWRU,QWHUIDFH YLD;, &$5(DQG/LYH&$5(

‡ 8VHUDFFHVVRIVXEV\VWHPGDWDYLD&$5(
SURJUDPPHGXVHUGHILQHGSRLQWQDPHV

‡ (QHUJ\PDQDJHPHQWVWUDWHJLHV&$5(SURJUDPPDEOH

‡ &RQWUROLQWHUDFWLRQVWUDWHJLHV&$5(SURJUDPPDEOH

‡ 7LPHSURJUDPV&$5(SURJUDPPDEOH

‡ $ODUPUHSRUWLQJIRU([FHO(%XVQHWZRUN

‡ $SSOLFDWLRQDODUPUHSRUWLQJ

‡ )XOOLQWHUDFWLRQZLWKRWKHUFRQWUROOHUVRQ&%XVXVLQJ
JOREDOGDWD

‡ 9PLQDQG9PD[RI([FHO9$9,,HGLWDEOHYLD;%6

‡ 3DVVLYHEXVZLGHDFFHVVRQ&%XV

*(1(5$/ '(6&5,37,21
The Q7750A Excel 10 Zone Manager is a programmable There are two hardware versions of the Q7750A.
master controller for an Excel 10 subsystem. It provides • 2003-devices have a free topology (FTT) E-Bus
energy management functions and communication interfaces transceiver.
between EXCEL 5000 System products and the Excel 10 • 1005-devices have a twisted pair topology (TPT) E-Bus
Echelon LONW ORKS (E-Bus) network. The Q7750A provides transceiver.
C-Bus (9600 baud and 1M baud) and E-Bus (78k baud)
communication interfaces. It also maps user selectable Excel The Q7750A is delivered with operating system software on
10 subsystem data points into C-Bus points with a full set of EPROMs. The Zone Manager contains all time programs,
point attributes, including user addresses. user addresses and Excel 10 subsystem mapping
information. 0DSSLQJ is the term used to describe the
allocation of Excel 10 subsystem data to Q7750A data points
that are accessible from the C-Bus. This mapping process is
executed using a PC-based software tool (CARE and
E-Vision).

® U.S. Registered Trademark


Copyright © 1999 Honeywell Inc. • All Rights Reserved
74- 2950- 2
4$(;&(/=21(0$1$*(5

E-BUS C-BUS COMMUNICATION NETWORK


SERIAL
ADAPTER

EXCEL 10
Q7750A
PERSONAL COMPUTER TOOLS ZONE
MANAGER EXCEL 500
E-VISION EXCEL BUILDING SUPERVISOR
CARE
LiveCARE
C-BUS TO E-BUS
INTERFACE DEVICE

E-BUS COMMUNICATIONS NETWORK E-BUS COMMUNICATIONS NETWORK

EXCEL 10
FAN COIL UNIT
CONTROLLER

E-BUS
ROUTER EXCEL 10
WALL MODULE

EXCEL 10
W7751H EXCEL 10 W7751F
SMART VAV2 PANEL PLENUM
ACTUATOR MOUNT VERSION
VARIABLE AIR VOLUME
CONTROLLER

EXCEL 10
WALL MODULE

Overvw2
EXCEL 10
WALL MODULE

)LJ([DPSOH4$([FHO]RQHPDQDJHUVXEV\VWHP GHYLFHVVKRZQ 

63(&,),&$7,216
6\VWHP&DSDELOLWLHV
7DEOH6\VWHP&DSDELOLWLHV
&DWHJRU\ /LPLWV5DWHV2SWLRQV
Number of devices on C-Bus Maximum of 29.
Number of Excel 10 devices on E-Bus Maximum of 120 (one Q7751A Router is required for each 60 Excel 10 device
segment).
Number of points supported Maximum of 1000.
C-Bus baud rates 9600 baud, with XD 505 submodule option.
1M baud with XD 508 submodule option.
Dial-up Via XDM506 submodule.

74-2950-2 2
4$(;&(/=21(0$1$*(5

/('6WDWXV,QIRUPDWLRQ
7DEOH4$([FHO=RQH0DQDJHU/('6WDWXV,QIRUPDWLRQ
/('1R ([SODQDWLRQ &RORU /('IXQFWLRQLI2Q /('IXQFWLRQLI2II
1 5V (POWER) Green Power on Power off
2 Contr. (RUN) Green Software is running, watchdog is triggered Watchdog locked, software not working
3 B-PORT (send) Yellow Q7750A sends data on RS232 port* No communication
4 B-PORT (receive) Yellow Data is sent to Q7750A on the RS232 port* No communication
5 C-Bus (send) Yellow Q7750A sends data on the C-Bus * No data sent on the C-Bus
6 C-Bus (receive) Yellow Q7750A receives data from the C-Bus * No data received from the C-Bus
7 E-Bus Yellow E-Bus network activity * (see NOTE) No E-Bus network activity
8 Service LED Red Blinking not configured E-Bus initialized and working correctly
* LEDs 3 through 7 flicker with the frequency of data being transmitted or received (see NOTE).

127( LED 7 is used to display E-Bus network activity. In 1005-devices it flickers with data being transmitted or received, but
in 2003-devices it flickers only with data being received.

&RPPXQLFDWLRQV The maximum C-Bus network length is 3900 ft


E-Bus: The Q7750A uses a transformer-coupled (1200 m), but with the addition of an XD509 Excel
communications port with encoded data presented to High Speed Repeater, the C-Bus can be extended
controllers and devices on the E-Bus at 78K bits per (an additional 3900 ft (1200 m) for each XD509).
second. The E-Bus is insensitive to polarity,
eliminating installation errors due to miswiring. The maximum number of controllers or devices per
C-Bus is 29.
The maximum number of nodes per E-Bus is 60. With
the addition of a Q7751A Router, the maximum 0HPRU\
number of nodes increases to 120 or 60 per E-Bus The operating system EPROMs contain 768 Kbytes of space.
segment. There are also 240 Kbytes of RAM and 1 Kbyte of EEPROM
space available for software use.
The recommended wire for the E-Bus will level IV, 22
AWG (Belden part number 9D220150) or plenum &RQQHFWLRQV
rated Level IV, 22 AWG (Belden part number There are two connectors available on the Q7750A Excel 10
(H2201504) nonshielded, twisted pair, solid conductor Zone Manager:
wire. Honeywell E-Bus cable is available. See 1. Connector 1; power, C-Bus and E-Bus network.
Installation Instructions, form number 95-7509. 2. Connector 2; B-Port (RS-232) compatible with a PC for
the XI581 Operator Interface and, via XI584, E-Vision,
Additionally, Echelon approved shielded cable can be CARE, and LiveCARE.
used. Contact Echelon Corp. Technical Support for
the recommended vendors of Echelon approved +DUGZDUH
cables. The CPU is based on an INTEL 80C188XL Microprocessor
® ®
and also uses an Echelon 3120 Neuron Chip.
GHYLFHV
An FTT network can accommodate bus, star, loop or 3RZHU6XSSO\
any combination of these topologies. This simplifies 24 Vac with a valid range (of 19.4 to 28.8 Vac) at 50/60 Hz.
system installation and makes it easy to add nodes
should the network need to be expanded. 3RZHU&RQVXPSWLRQ
6 VA maximum at both 50 and 60 Hz.
GHYLFHV
The TPT E-Bus is a daisy chain topology — the bus %DWWHU\%DFNXS
needs to go serially from one controller to another The back-up battery, used for RAM and the Real Time Clock,
without branching. is a 3-volt Lithium (type CR 1/2 AA, VARTA number 6127 or
2003-devices can be used to replace 1005-devices equivalent). The backup time for a new battery is 30 days
using a TPT/FTT router. Maximum length of an FTT with a minimum of 72 hours after the first battery empty
network is dependent on a number of factors, see (voltage falls below 2.5 volts) alarm is detected.
E-Bus Wiring Practices, form 74-2865 for details.
0RXQWLQJ2SWLRQV
C-Bus: The C-Bus transmits data between EXCEL 5000 The Q7750A can be mounted in a ring cabinet or attached to
System Controllers, Devices and Building Supervisors 1-3/8 by 9/32 (35 by 7.5 mm) EN 50 022 DIN rail.
at 9600 baud or 1 Mbaud (921 600 baud).

3 74-2950-2
4$(;&(/=21(0$1$*(5

0HFKDQLFDO $FFHVVRULHV
Dimensions in in. (mm) HWD: The following accessories are available:
9-11/16 x 7-9/16 x 2-19/32 (246 x 192 x 66).
Weight in lb (kg): 7DEOH$FFHVVRULHV
2.6 (1.2).
(TXLSPHQW 'HVFULSWLRQ
+RXVLQJ0DWHULDO XI582 Operator terminal with menu-controlled data
ABS plastic. access

(QYLURQPHQWDO5DWLQJV XW565 16 ft 6 in. (5 m) cable for B-Port to XI582


Operating Temperature: connection
32° to 122°F (0° to 50°C). XW566 49 ft 6 in. (15 m) cable for B-Port to XI582
Shipping Temperature: connection
–29.2° to 140°F (–34° to 60°C).
XW567 8 ft 3 in. (2.5 m) cable for PC to B-Port
Relative Humidity:
connection
5% to 90% noncondensing.
XD505 9600 baud C-Bus interface card
$SSURYDO%RGLHV XD508 921 600 baud C-Bus interface card
The Q7750A1xxx is listed under UL 916, File Number S4804
XD509 C-Bus repeater
(QVAX, PAZY) and is being listed by CSA. The Q7750A
meets FCC part 15 class B requirements. XDM506 Modem submodule
Protection Class: IP30.
Electromagnetic: EN 50081-1, EN 500 82-1. $VVRFLDWHG'RFXPHQWDWLRQ

)RUP1R 'HVFULSWLRQ
95-7509 Q7750A Installation Instructions

+RPHDQG%XLOGLQJ&RQWURO +RPHDQG%XLOGLQJ&RQWURO +RPHDQG%XLOGLQJ&RQWURO3URGXFWV

Honeywell Inc. Honeywell Limited-Honeywell Limitee Honeywell AG


Honeywell Plaza 155 Gordon Baker Road Böblinger Straβe 17
P.O. Box 524 North York, Ontario D-71101 Schönaich
Minneapolis, MN 55408-0524 M2H 3N7 Germany
USA Canada
http://www.honeywell.com http://www.honeywell.ca http://europe.hbc.honeywell.com

74-2950-2 Rev. 09/99 Printed in U.S.A. Subject to change without notice