Project name: Teatro JEG | Project ID: 001

Customer: IDEARTES | Location: Bogotá Colombia


Generated with LPU Selection Tool 1.2.18 on Thu, 26 Oct 2023 23:10:07 GMT | PUID: ----

HI-FOG® Land pump unit


Pump unit ID: ----
Sales Data Sheet for Special LPU
This pump unit has special design requirements. Data sheet information can be used only for
reference. Not to be used for detailed design.

LPU system type code: LPU05+00/Vd/SB/140/140

Pump module 1 type code: MELPU3+0M/0C0B5/1FA/00E

Pump module 2 type code: MELPU2+0S/0C0B5/1FA/00E

Pump controller type code: CLPU05+0F/3M1/1F3A1/B0E0E

Description

The pump unit is the main part of a HI-FOG® high-pressure water mist fire protection system. It supplies the pressurized
water to the system.
The HI-FOG® Land Pump Unit (LPU) is a modular pump unit, available in nine sizes. The pump unit consists of a control
cabinet and 1–9 motor-pump modules. The number of motor-pump modules defines the size of the pump unit. The
motor-pump modules are stacked on base modules, forming together 1–3 towers that are called LPU modules. The LPU
modules can be positioned freely in the pump room, to any locations that meet the service area requirements. An LPU module
consists of 1–3 motor-pump modules and the base module. In the pump unit, there is always one primary LPU module called
the Master LPU module, which is equipped with sensors and manual valves. In pump units of more than three motor-pump
modules, there are also slave LPU modules without those features.
The control cabinet operates the pump unit automatically with programmable logic controllers (PLC).

The LPU has several methods of activation. The pump unit activates automatically or is activated manually, both locally or by
a remote start signal. The LPU is designed to start the motor-pump modules sequentially upon activation, thus not creating as
high electric current peaks as if started at the same time.

Customer: IDEARTES
Location: Bogotá Colombia
Project name: Teatro JEG
Project ID: 001

SENSITIVE Contains no technical data subject to the EAR or the ITAR.


1/6
Project name: Teatro JEG | Project ID: 001
Customer: IDEARTES | Location: Bogotá Colombia
Generated with LPU Selection Tool 1.2.18 on Thu, 26 Oct 2023 23:10:07 GMT | PUID: ----

General

Unit type LPU5+0

Number of HP motors (including redundant) 5

Motor manufacturer Brook Crompton (ATB)

Motor #1 start type & standby pumping ETO - M1 with FC (no elec. Standby pump)

Motor start type & power (kW) Direct On Line (DOL) / 27

Amount of power supplies Main supply only

Feed water supply type Pressurized water feed (feed water pump)

Water treatment unit control No

Feed water pump control and supply Start signal for FWP (power supply not by Marioff)

Feed water pump motor power No FWP

Design pressure, bar 140

Pump panel user language English (EN)

User manual document number 0000069482

Classification VdS certified

Pump skid operation temperature 4-45°C

Cabinet operation temperature 0-40°C

Maximum altitude of operation 3000m; Gravity fed units shall meet the NPSH requirement

Pump skid painting Default color (RAL3020)

Control cabinet painting Default color (RAL7035)

Enclosure rating (IP) IP54

Pump unit connection sizes

Inlet type and dimension DN65 DIN2642 flange

Water inlet pressure 2 - 10 bar (excludes filter losses)

High pressure outlet type and dimension Ø38S DIN2353

Test outlet and bypass outlet type and dimension Ø38S DIN2353

Water output pressure and flow

Working pressure, bar 140

Maximum flow @ 140 bar, l/min 473

Drain flow @ 0 bar, l/min 500

Customer: IDEARTES
Location: Bogotá Colombia
Project name: Teatro JEG
Project ID: 001

SENSITIVE Contains no technical data subject to the EAR or the ITAR.


2/6
Project name: Teatro JEG | Project ID: 001
Customer: IDEARTES | Location: Bogotá Colombia
Generated with LPU Selection Tool 1.2.18 on Thu, 26 Oct 2023 23:10:07 GMT | PUID: ----

Power requirements

Power consumption (kW) 145*

Rated Current of Assembly, InA (A) 400*

Nominal current, Ie (A) 221*

Motor start current, Is (A) 519*

Short circuit current, Icc (kA) 0-10

Power supply (VAC/Hz) 440 / 60


* - Power and current values are preliminary and may change during the design phase.
Electrical design drawings will indicate the final values.

Control cabinet dimensions & weight

Width (mm) 1200

Height (mm) 2000

Depth (mm) 500

Weight (kg) TBD

Electrical cabinet service area

Customer: IDEARTES
Location: Bogotá Colombia
Project name: Teatro JEG
Project ID: 001

SENSITIVE Contains no technical data subject to the EAR or the ITAR.


3/6
4/6
Contains no technical data subject to the EAR or the ITAR.
Product code: ----M1
Unit weight: 777 kg
Unit code: MELPU3+0M/0C0B5/1FA/00E

SENSITIVE
Location: Bogotá Colombia
Project name: Teatro JEG
Customer: IDEARTES

Project ID: 001


Generated with LPU Selection Tool 1.2.18 on Thu, 26 Oct 2023 23:10:07 GMT | PUID: ----
Customer: IDEARTES | Location: Bogotá Colombia
Project name: Teatro JEG | Project ID: 001
5/6
Contains no technical data subject to the EAR or the ITAR.
Product code: ----M2
Unit weight: 535 kg
Unit code: MELPU2+0S/0C0B5/1FA/00E

SENSITIVE
Location: Bogotá Colombia
Project name: Teatro JEG
Customer: IDEARTES

Project ID: 001


Generated with LPU Selection Tool 1.2.18 on Thu, 26 Oct 2023 23:10:07 GMT | PUID: ----
Customer: IDEARTES | Location: Bogotá Colombia
Project name: Teatro JEG | Project ID: 001
6/6
Contains no technical data subject to the EAR or the ITAR.
Mandatory water tank monitoring

SENSITIVE
Generated with LPU Selection Tool 1.2.18 on Thu, 26 Oct 2023 23:10:07 GMT
Customer: IDEARTES | Location: Bogotá Colombia
Project name: Teatro JEG | Project ID: 001