VVVF Inverter
SAMCO-NS series
Warning Notification
Rating nameplate
Terminal block
Radiator structure
Grounding terminal
■ Product body:
NS Vector Control Inverter Body (For example: NS-4A017-B):
-1-
The contents of the model
Rating nameplate
-2-
Connection with peripheral device
Draft for the connection with peripheral device
Power Supply
Electromagnetic contactor
AC reactor
Zero-phase reactor
DC reactor
Zero-phase reactor
-3-
■ Installation in the side of left / right :
Pls. assure the space is above 5cm, whatever is between the inside of cabinet and the
outlook frame of Inverter, or between Inverter’s outlook frame while installed in the side of left/right
-4-
■ Installation more layers in the side of up /down:
Pls. assure the distance is above 20cm, whatever is between the inside of cabinent and the outlook frame of Inverter,
or between the Inverter’s outlook frame, and ensure the ventilation and cooling for each Inverter, or will be caused of
being not enough of heat dissipation.
-5-
■ Installment site for ventilation fan in the cabinent:
■ Notification:
◆ When several inverters are set in a control cabinet, be sure to local the ventiliation fans properly
to allow free aire circulation.
◆ Ensure the air in the outside of cabinent flow to the Inverter’s heat dissipation route, take those heat from the
Inverter in operation away in efficient.
◆ If the ventiliation fans are located properly, the ambient termperature will rise and affect the cooling of the Inverter.
(Correct) (Incorrect)
-6-
Removal and Installation of the front cover
◆ Pls. carry out this work during the main circuit wiring、control circuit wiring.
-7-
(2)Changed fan
(3)Installation
-8-
Terminal Connection Draft
DC reactor (optional selection)
Brake Unit
Terminal in Main circuit
(Optional)
Input terminal
Output terminal Braking Resistor (Optional Selection)
Communication terminal
Isolation cable
P1 P PR X
Input Power R U
FR DI1
DO1 Open collector output
Multi-functions terminal
3DF DI4
MBS DI5
Control Circuit Vout
V 0 ~ 10V Voltage output
DCM Iout
4 ~ 20mA Current output
ACM
Digital signal on ground
Analog signal
Outlook dimensions
Dimension
Mode No. Outlook Frame
H H1 W W1 D d t
Ød
NS-4A003-B
E asykW ° C Mp a% r p m skV A H z
DRIV E
ST OP
H1H
NS-4A004-B 130 121 115 106 166 4.5 5
P R OG
C LE A R E NT E R
WARNING
■ Riskofelectricshock.
open whiel
●Readthemanualbeforeinstallationandoperation.
for10
●Donot after
thisco ver isappliedor
minu tes isolatingpo wer.
●En sureproperearthconnection.
危险
■有可 能引起 受伤, 触电。
●安装 运行前 请务必 阅读操 作说明 书并遵 照其指 示。
NS-4A006-B
●请正 确接地 。
W1 t
D
W
Ød
NS-4A009-B
E asykW ° C Mp a% r p m skV A H z
DRIV E ST OP
CPLER OG
AR E NT E R
H1H
NS-4A013-B 225 214 140 129 150 5.5 6
WARNING
■ Riskofelectricshock.
open
●Readthemanualbef whieoper
or ei ns t all ati onand l ati on.
for10
●Donot after
thisco ver isappliedor
minu tes isolatingpo wer.
●En sureproperearthconnection.
危险
■有可 能引起 受伤, 触电。
●
安装 运行前 请务必 阅读操 作说明 书并遵 照其指 示。
通电 时及切 断电源 1 0 分钟 内请不 要打开 前面盖 板。
●
●
请正 确接地 。
NS-4A017-B
W1 t
W D
Ød
NS-4A024-B
E asykW ° C Mp a% r p m skV A H z
DRIV E ST OP
CPLE
R OG
AR E NT E R
WARNING
■ Riskofelectricshock.
open whiel
●Readthemanualbeforeinstallationandoperation.
for10
●Donot after
thisco ver isappliedor
minu tes isolatingpo wer.
●En sureproperearthconnection.
危険
H1H
取付け、 運転の 前に必 ず取扱 説明書 を読み 、そ
■けが、感 電のお それあ り。 の 指示に 従うこ と。
●
確実 に接地 を行う こと。
危险
■
有可 能引起 受伤, 触电。
●
安装 运行前 请务必 阅读操 作说明 书并遵 照其指 示。
通电 时及切 断电源 1 0 分钟 内请不 要打开 前面盖 板。
●
●
请正 确接地 。
NS-4A038-B
-9- -9-
Composition of Main Circuit Terminals
R,S,T Input Power Terminals Terminals connected to 3 phase commercial power supply
-10-
Distribution Terminal For Main Circuit
1.NS-4A003-B、NS-4A004-B、NS-4A006-B
-11-
2.NS-4A009-B、NS-4A013-B、NS-4A017-B
-12-
3.NS-4A024-B、NS-4A032-B、NS-4A038-B
-13-
Main circuit terminal connection draft
Shorten Plate
DC
Reactor
Motor
Optional Accessory
Power Supply
Braking Resistor
NS-4A003-B 5 7 20
NS-4A004-B 5 7 20
NS-4A006-B 15 7 20
NS-4A009-B 20 7 20
NS-4A013-B 30 7 20
NS-4A017-B 30 17 32
NS-4A024-B 50 25 50
NS-4A032-B 60 25 50
NS-4A038-B 70 32 60
-14-
Recommend Wire Size
Main Circuit
2
Recommended wire size[mm ] Tightening Max.
Screw
P、P1 Torque Wire size
Input Wire R、S、T U、V、W Grounding wire diameter 2
PR、X N·m mm
Note 1: The value for wires in the main circuit are for 600V IV PVC-insulated wires (60℃) When the
inverter ambient temperature is 40℃
The value in( )are for 600V bridged-polyethylened insulated wires(90℃)
Note 2: The maximum wire size indicates the maximum wire cross-sectional are that can be used with
the terminal block
-15-
External brake resistor(Recommend) External brake resistor (limit value)
Model No.
Resistor value Capacity ※ 1 Resistor value Capacity ※ 1
※1 The above brake resistor is selected by the max. use rate 10%ED.
-16-
Composition of Control Circuit Terminals
Wire size
Terminal screw diameter:M3
Tightening torque:0.5[N•m]
■ Most Attention:
▲ Don’t input stronger voltage to the control terminal! Or control board burnt
▲ Pls. move the control calbe far away to power cable in avoid of intevenue or noise.
-17-
Function of control circuit terminals
Type Terminal
Terminal Name Function Description Rated Specification
Symbol
Digital signal common Common terminals for digital input and
Total current consumed:
Multifunctional collector
Sending signals for function through Open collector output
DO1
output terminals selected fuction code. Allowable loading: DC48V
DOE
、50mA
-18-
LCD Operation Panel
Status Display Inverter status during operation /stop
<Frequency> <Output Current> <Roatation Speed> <load factor>
<Output Voltage> <Pressure Value>
Inverter Condition
Information
Seconda ry scree n
Primary screen
Units
Direction Key
Description:
Primary Screen 5 digit 7 segment LCD : Shown the following data through changing Left/Right direction key or
parameters setting, “Current operation frequency、Output current、RPM、Load factor、Output voltage、Voltage value、
Set value and warning content”.
Secondary Screen 5 digit 7 segment LCD: Shown the data of “Current output voltage、DC Voltage、Active power、Apparent
power、Radiator temperature and the others content” by setting parameters.
“Units” is only for primary screen, mainly display “Frequency(Hz)、Output current(A)、Speed roation(Rpm)、Load factor(%)、
Output voltage(V)、Pressure value(MPa)”.
-19-
Function Code Display Code No. and data
For example: Push【PR/CL】Key, secondary screen shown F1001, and
Primary screen show the value of F1001
Push【ENTER】Key, Primary screen flashing, and revise
data through【∧ 】 、【∨ 】 、【<】、 【>】
Push【ENTER】Key, parameters setting successfully
Status display mode for Inverter statis monitor、Alarm display、Output frequency setting and run/ stop
Inverter and so on.
U0100
Stop Communication
Reverse
DC braking
表Speed
5-4 display
转速显示内容 content
Motor control mode Operation Stop
V/f control mode Motor synchronized speed Set speed
Sensorless vector control Mode Motor estimated speed Set speed
During Inverter status monitor display, press【<】key or 【>】key one times, switching the display content
on the primary screen at one times, the display content on primary screen can also be switched by the function
code. As for the details, pls. referring the function code: F2303.
When the alrarm is stopped, alarm type will be shown on the primary screen.
※ During alarm display, even press【<】Key or 【>】Key, it can’t be switched the display on primary screen.
※ It can be switched to the function code display mode through press【PROG】key during alarm display.
-21-
During status monitor display, frequency setting as the below method whatever is on operation or at stop
※ 1 While no needing the frequency setting,press【PR/CL】key return to status monitor display Mode.
Basic operation
Function code setting
Normal operation used for the changing the value of function code.
For example: set F1414=10
Operation Display Description
Status monitor display(frequency display)
-22-
Press【∧】key, changing number to 14, second display
parameters number 14 flashing, may be revised again.
【∧ 】*4
※ 1 When no
needing to set the new value, return to parameter number setting interface through
【PROG】Key.Parameter numble in the second monitor flashing.
Confirmation
Some function codes need to re-confirm for the prevent of wrong operation which could be caused
of data re-written.
For example:set F1001=10
-23-
Primary monitor parameter value 1 flashing, that is
meaning to be revised the current value.
【ENTER】
※1 ready flashing, press 【PROG/ CLEAR】key return to function code selection interface while
found out some wrong on operation, and interrupt the action of input.
※2 Press【PROG/ CLEAR】key could also return to status monitor display mode interface.
-24-
For example: Display the disfference with the factory preset
Operation Display Description
Select function code F1602
(Changed code display function)
【∧ 】/【∨ 】 Or
-25-
Alarm status confirmation
Alarm status confirmation is the function shown the Inverter status in case of a Alarm.
It could be confirmed for alarm status during the latest 5 times through function code F1806~F1810
New alarm happened, the easliest alarm will be deleted. That is latest alarm in F1806, and the earliest
one in F1810.
For example: While the latest alarm occurs, the confirmation for Inverter’s status.
Or
【ENTER】 Or
【PR/CL】 Or
Function code F1805=9 is set. all alarm record will be deleted. At this moment, the data records in
F1806 t~ F1810 will be erased.
-26-
※ 1:Display name as below:
Display Content Unit
Alarm Name -
Output Frequency Hz
Output current A
Output Voltage V
Dc Voltage V
Output Power kW
Radiator Temperature ℃
※2 The value displayed is the status before the occurrence of an alarm. Therefore, if an alarm is caused by transient over-current, over
voltage he stored value is the different from the current value、voltage value on the alarm.
During search of the function code, of which user data is discrepant from
the default settings, the display is on flashing status.
The display is flashing during the trasfer of host function code data to the
operation panel.
During the trasfer of the operation panel function code to host, it is displayed flashing.
It is displayed flashing, while the desired data can’t be found through the function code
search and alarm history record.
-27-
Function Code
-28-
Function Code List
Basic Operation Function F10xx~F13xx
50~460V
1006 Base Frequency 0.1~600Hz 0.01Hz ※1
-29-
Setting Factory
Code Function Name Data Content
resolution preset
-30-
Setting Factory
Code Function Name Data Content
resolution preset
-31-
Setting Factory
Code Function Name Data Content
resolution preset
-32-
Setting Factory
Code Function Name Data Content
resolution preset
-33-
Setting Factory
Code Function Name Data Content
resolution preset
-34-
Code Function Name Data Content Setting Factory
resolution preset
1309 Operation direction 0: Start from the direction opposite to current 1 0
Switching in v/f control directiorn after a stop
mode 1: Continuous Operation
1315 Shotest operation time 0~99.99 sec. 0.01 sec. 0
function
1316 2nd upper frequency 5~600Hz [Hz] 0.01 [Hz] 60
1317 3rd upper frequency 5~600Hz [Hz] 0.01 [Hz] 60
1318 Cooling fan ON/OFF 0:0N/OFF control 1 0
control 1:Normally ON
-35-
Function Code List-Input/Output Functions F14xx~F16xx
Input/Output Functions F14xx~F16xx
Setting Factory
Code Function Name Data Content
resolution preset
-36-
Setting Factory
Code Function Name Data Content
resolution preset
1414 Input terminal DI1 0:Unused 1:FR, 1 1
1415 Definition 2:RR, 3:2DF,
1416 Input terminal DI2 4:3DF 5:MBS,
1417 Definition 6:ES, 7:RST,
1418 Input terminal DI3 8:AD2, 9:AD3
Definition 10:JOG, 11:5DF,
Input terminal DI4 12:9DF, 13:FR+JOG,
Definition 14:RR+JOG, 15:FR+AD2,
Input terminal DI5 16:RR+AD2, 17:FR+AD3,
18:RR+AD3, 19:FR+2DF,
Definition
20:RR+2DF, 21:FR+3DF,
22:RR+3DF, 23:FR+2DF+3DF,
24:RR+2DF+3DF, 25:FR+AD2+2DF,
26:RR+AD2+2DF, 27:FR+AD2+3DF,
28:RR+AD2+3DF, 32:RR+AD3+2DF,
29:FR+AD2+2DF+3DF, 34:RR+AD3+3DF,
30:RR+AD2+2DF+3DF, 39:FR+5DF,
31:FR+AD3+2DF, 47:PC,
33:FR+AD3+3DF, 58:FR+CCL,
35:FR+AD3+2DF+3DF, 64:FR+MBS,
36:RR+AD3+2DF+3DF, 67:2DF+AD2,
37:PTR, 69:3DF+AD2,
40:HD, 74:2MAX,
46:CCL, 76:VFPID,
57:P0, 83:For factory
59:FR+RCCL, Adjustment
65:RR+MBS, 85:PIDL,
68:2DF+AD3, 87:RPID1,
70:3DF+AD3, 89:PID2EX,
75:3MAX, 92:ICLEAR
77:PIDLCK, 114:1DFA,
79:Terminal selection for 116 :
continuous DC braking 1DFA+1DFB,
84: S2, 118: RCOM,
86: PIDH, 120: 1DFA+ROPE,
88: PID1EX, 122: 1DFA+1DFB
91: IHOLD, +ROPE+RCOM,
109: RCCL,
115: 1DFB,
117: ROPE,
119: ROPE+RCOM,
121: 1DFB+RCOM,
130:RUN
131:STOP
135:FR/RR
136:R3W
137: ROPE+RCOM+R3W
138: Valid for high speed pulse
train
253~255: for factory
adjustment
-37-
Setting Factory
Code Function Name Data Content
resolution preset
1422 Reference frequency 1000~60000 1Hz 1000
for pulse input
-38-
Setting Factory
Code Function Name Data Content
resolution preset
1504 Internal analog output 0:No function 1 0
Function 2 1:Set frequency [Hz]
2:Output frequency [Hz]
3:PID1 feedback value [Hz]
4:PID2 feedback value [Hz]
5:Output current [A]
6:Output voltage [V]
7:DC voltage [V]
8:Radiator temperature [℃]
9: Load factor [%] (accumulated vale of electric
thermistor)
10: Load factor [%](Ratio to rated current)
11:VRF analog input value [V]
12:V/I analog input value [V]
14:Speed [rpm]
15:Active power [kW]
16:Apparent power [kVA]
17:PID1 command value [Hz]
18:PID1 input deviation value [Hz]
19:PID2 command value [Hz]
20:PID2 input deviation value [Hz]
24:External PID1 output value [Hz]
25:External PID2 output value [Hz]
35:Command frequency [Hz]
36:Command torque [%]
-39-
Setting Factory
Code Function Name Data Content
resolution preset
-40-
Setting Factory
Code Function Name Data Content
resolution preset
-41-
Function Code List – System-Related Functions F16xx~F18xx
System-related Functions F16xx~F18xx
Setting Factory
Code Function Name Data content
resolution preset
-42-
Setting Factory
Code Function name Data content
resolution preset
1707 Missing phase detection 0:No input phase loss, No output phase loss 1 3
Function 1:Input phase loss, No output phase loss
2:No input phase loss, output phase loss
3:Input phase loss, output phase loss
-43-
Setting Factory
Code Function Name Data content
resolution preset
mode selected)
-44-
Special Functions F19xx~F20xx
2002 V·f separation command 0:No function (command given by VRF) 0.01V 0
voltage 0.01~10.23V
-45-
Graph operation function F21xx~Fxx
-46-
Setting Factory
Code Function Name Data Content
resolution preset
-47-
Setting Factory
Code Function Name Data Content
resolution preset
-48-
Display Function F23xx
-49-
Setting Factory
Code Function Name Data Content
resolution preset
-50-
PID Function F30xx~F33xx
3006 PID1control integral separation 5~100%(upper frequency limit reference) 0.1% 100
judgement value
-51-
Setting Factory
Code Function Name Data Content
resolution preset
3016 PID1 control integral time 0.01~100 sec. 0.01 sec. 0.1
(negative :F3012=2)
-52-
Setting Factory
Code Function Name Data Content
resolution preset
-53-
Setting Factory
Code Function Name Data Content resolution preset
3103 PID2 control proportional 0~100 0.01 0.1
gain
-54-
Setting Factory
Code Function Name Data Content
resolution preset
3125 PID end setting value 1~100%(upper frequency limit standard) 0.1% 20
3127 PID feedback signal 0:Only warning 0.01 sec. 2
abnormal detection time 0.01~119.99 sec.
120:No abnormal detection
3201 PID control action selection 0:Open loop control 1 0
1:PID1 control
2:PID2 control
4:External terminal switching PID control
5:Timing switch PID control
-55-
Setting Factory
Code Function Name Data Content
resolution preset
-56-
Water Supply Function F34xx
Pressure command
3405 Pref 0~9.999MPa 0.001MPa 0
3406 Analog feedback upper 0~±9.999MPa 0.001MPa 0
pressure limit
-57-
Communication Functions F40xx~F41xx
2:Even
-58-
Motor Parameters F5xxx
capacity X:Poles
Y:Rated Voltage
Z:Motor Capacity
2:Type E
3:Type B
4:Type F
5:Type H
5006 Motor’s rated voltage 0:The voltage selected by F5001 1V 0
during auto tuning of
parameters 100~460V
-59-
75kW or above 0.01 ~ 0.01mH
600mH
5012 Motor rotator inductance 55kW or below 0.1 ~ 0.1mH
6000mH
75kW or above 0.01 ~ 0.01mH
600mH
5013 Motor’s mutual inductance 55kW or below 0.1 ~ 0.1mH
6000mH
75kW or above 0.01 ~ 0.01mH
600mH
5014 Motor excitation current 0.01~650A 0.01A ※1
Motor’s moment of
5015 inerita 0~65kgm2 0.001kgm2 ※1
-60-
Vector Control F60xx
6005 Multiple for starting 0.1~2 times(for applicable motor) 0.01 times 1
excitation current
Proportional gain
6011 Speed control ASR 0~20 sec. 0.001 sec. ※1
Integral time
-61-
Setting Factory
Code Function Name Data Content resolution preset
6014 Motor virbration 0:No Function 1 0
reduction rate 1:75%
2:50%
3:25%
Lower frequency limit
6015 0~240Hz 0.01Hz 0
for motor vibration
reduction function
Upper frequency limit
6016 0~240Hz 0.01Hz 0
For motor vibration
reduction
6019 Variable 2nd gain for 0:No variable gain function 0.01% 15
Speed control
0.01~150%
6020 Frequency top of 0~240Hz 0.01Hz 10
variable gain for speed
control
6021 Frequency bottom of 0~240Hz 0.01Hz 30
variable gain for speed
control
-62-
■ Water supply function code description
F3401
pump
Judgement equation:
K·F*≥Ff...... (1)
F* is frequency comman,Ff is frequency feedback value, k(≦1) is auxiliary pump switch ratio.
While using pressure command, frquency command turns into pressure command, and frequency
feedback value turned into pressure feedback value. The larger K, the slower swithcing to Inverter pump. By the way, that
function code also used for main pump sleep wake up, the same method as the above.
F3405 is used for set pressure command value through operation panel, While F3405≠0 , even setting F3001=2、3、4、5、9,
it is invalid for analog reference pressure value. Action as the pressure command setted by F3405.
While F3405=0 , If set code F3001=2、3、4、5、9,which is analog reference. Pressure command
decided by analog value.
-63-
F3406 is valid code under the control mode of pressure command given
While F3002=1、3、5 : Set pressure value at 5V
While F3002=2、4、6 : Set pressure value at 10V
While F3002=7、8、9 : Set pressure value at 20mA
-64-
Energy-saving Function
Energy-saving Function
These codes are for the selection of energy saving mode、parameters setting for the operation of energy saving.
Simple energy-saving
F1902 0~50% 1% 0
rate
Simple energy-saving
F1903 0~65000 Sec. 1 Sec. 10
time
After selecting this mode,No need to set the others parameters, Inverter can enter into the auto saving operation.
It performes obviously on the stable output, especially for the loading of fan and pump. The energy saving still enabled,
This code used for setting the recommend rate of voltage droped under energy-saving mode.
For example:Rated output voltage: 300V, and F1902=20%, The output voltage will decrease to 300*(1-20%)=240V,
Simple energy saving function can be adjusted by hand, making the related Voltage/Frequency in compliant with the load
charactertistics and torque charactertistics in order to get the best peformance of energy-saving.
-65-
■ F1903=0~65000
This code is used for setting the delay time of running energy-saving while the conditions are ready.
While Inverter finished acclerating and running stable, is satisified to simple energy saving, set the value
of F1903 in order to find the suitable time into the operation of simple energy-saving mode.
Operation command
F1902
Output voltage
◆While inverter were on the conditions of energy-saving, output voltage satisified with voltage decrease
rate to execute V/F control, even under frequency command changing. But, while Inverter stop
command given, the original output voltage slowly increased till to completely recovery, and then
turned into deceleration procedure.
◆Turned into simple energy-saving action, the voltage decreased slowly in avoid of drastically changing
for the torque of loading, should be kept the slope around 10 sec. for Max. output voltage value.
For example: Inverter Max. output voltage is 440V,Normally run at 22.7Hz, and output voltage is 200V,
Simple energy-saving rate is 50%,so, approximately it could take around 2.3 sec. to drop the voltage to 100V.
◆ Disabled simple energy-saving condition through using stop command, needs the fast recovery of voltage
in avoid of not enough torque for loading, and causing the decline for control capacity. It should make
slope of 1 sec. for Max. output voltage.
-66-
For example:Inverter max. output voltage is 440V run at 22.7Hz output voltage 200V, and simple
energy-saving rate is 50%, it is needing 0.23 sec. from 100V up to 200V when exited from the simple
energy-saving action, and then do the action of deceleration while the voltage was recovered.
◆Simple energy-saving function decreased the output voltage of Inverter. Therefore, the voltage dropped
caused the decreased rotation speed due to the different conditions of loading. If some equipments are not
permitted to reduce the rotation speed, it is needing the complimentary of energy-saving and rotation in
accordance with auto energy-saving mode (Speed Control) and the combination of PID control.
◆Do not use this method, if the performance of energy-saving is not good even through decreasing the
voltage.
◆Re-judge the condition and start the simple energy-saving, while starting through flying、Alarm auto
recovery、Momentary stop and re-start.
◆The stop action during the simple energy-saving is the output voltage returned to the original value, and
then into the action of deceleration, so, the stop time could be slightly changed. The recovery time is
needed under the occasion of existing the sequency control.
◆This function could automatically calculate voltage value in higher efficiency, and play a role of
stability and energy-saving functions.
◆Even auto energy-saving mode is set, it also work at normal control method during the action of
acceleration/deceleration.
◆Stop action in Auto energy saving, which is different with that of simple energy-saving. Stop command
and action of deceleration is at the same time, therefore, stop time is also the same as the normal action.
But, while reclaimed energy can’t be completely absourbed, and torque limiter needed in some
occassions, the pronlong deceleration time as referrring the protective function.
-67-
◆Auto saving control is effective during constant torque operation. When rated speed has been exceeded
during constant power operation, a weak magnectic control will be adpted as normal modes.
◆On the occasion of energy-saving、Motor speed control、the others feedback control using at the same
time, enginer-saving function could be executed with PID control functio if the system was installed
sensor.
◆The better performace for the square torque loading, such as fan、pump and the others light load, but it
◆Re-set auto energy-saving function under re-start through Flying function、Alarm auto-recovery
◆Action of energy-saving is effective during constant speed operation of stable loading torque(frequency
matching condition). Therefore, on the occasions of frequency setting throught analog frequency input,
Energy-saving is effective for slowly change of freuency setting through increasing frequency
◆ On the occasions of F1001=2、3 (Speed Control Mode), the speed should be compensated during
energy saving.
-68-
Alarm list
7-segment Alarm
Check points Actions
monitor description
display
AL1 Memory Turn off the power, while CHARGE Contact the supplier
AL3 Abnormality Are the signal and power lines Keep the signal line far away from the
separated far enough? power line
AL4 System Abrupt capacitor discharge? turn Reconfirm the modified code data. Turn the
Abnormality off the power, so, the CHARGE power on/off several times, if the alarm is still
lfamp turn off, turn the power on, pls. reset the system, using F1604=1, and
on again and check the alarm. then turn power on and off again, All the
AL5 System Excessive external noise? Install the noise collector and filter.
AL9 Abnormality Are the signal and power lines Keep the signal line far away from the
separated far enough? power line
-69-
AL10 System Turn off the power, while CHARGE Contact the local supplier
lamp turns of, turn the power on
Abnormality
again and check the alarm again.
oCPn Momentary overload Abrupt change in load? Eliminate the abrupt change(Increase)
during constant speed. (Increase) Decrease the setting value.
Setting for current limiting
function (F1701)too high?
-70-
7- segment Alarm Actions
monitor Check points
descripation
display
oCPd Momentary overload Excessive deceleration rate with Extend the deceleration time.
during deceleration GD2? Decrease the setting value.
setting for current limiting
function (F1701) too high?
Overvoltage during
ouA Whether start-up occur during Change to flying start mode.
acceleration
idle run.
Overvoltage during
oun Whether motor is turned by Redesign the system so that the motor is not
constant speed driven by external force.
Other force?
Overvoltage during Use a brake resistor with a larger capacity.
oud Excessive deceleration Extened the deceleration time.
deceleration (so that GD2 of the load is met)
-71-
7- segment Alarm
Check points Actions
monitor
description
display
Over-shoot or under-shoot
GAL 2 Overspeed
happened?
Confirm speed command value or
oPn o Missing output phase Missing an output phase? Connect the output cables securely.
oPn 1 Misssing input phase Missing an in input phase? Check and improve the input current..
Gnd F Check grounding Short-circuited when grounding? Confirm output cable and motor insulation
short-circuit current performance.
FAn L Cooling fan Cooling fan is working? Check the fan performance
abnormality
rYoFF Main relay Turn of power and wait untill Contact the supplier.
CHARGE lamp turns off, turn the
abnormality
power on again and check the
alarm?
-72-
Fault Analysis
Problem Check points
Voltage at input termianls R、S、T are normal?
Main circuit
Whether is the motor wired correctly?
Load fluctuating?
Frequency setting (analog) signal fluctuating?
Rotation is not stability
Whether is correct setting for the capacity of Inverter ; number of poles
and capacity of motor under senslorless speed control mode?
-73-