Simplifying filter bed level

measurement with the


SITRANS Probe LU240

siemens.com/sitransProbeLU240
A wastewater treatment plant is a the aggressive nature of such media. flexible cables as the sensing elements.
busy place with effluent flowing The molecular makeup of ammonia
The trouble with buildup
through every day, treated with a tends to degrade some materials at a
precise mix of chemicals and physical rapid pace. Luckily, some guided wave During the washdown cycle, the water
separation processes. radar transmitters feature special seals level is near the bottom of the basin and
that are well suited for ammonia level the water surface is quite turbulent.
In this demanding environment,
applications. In such applications, this Operators were concerned that non-
operators don’t have time for devices
technology is the right choice. contacting technology would struggle
that require constant maintenance and
in sending its signal through free space
attention—there’s enough to do in a But guided wave radar in a filter bed?
as it attempted to detect the level past
day without tending to temperamental
With that groundwork of level technolo- the exposed troughs.
instruments. At each stage of opera-
gies in place, we turn to a large water
tions, the plant depends on reliable and As well, considering the narrow area
treatment plant in North Carolina and
accurate level measurement. available for level measurement in this
its use of guided wave radar on a num-
application, guided wave radar technology
Walking through a treatment facility, ber of filter beds.
seemed to be the right choice.
level instrumentation is at work every-
Among the level applications previously
where: In the control room, the historical trend
mentioned, monitoring the water level
graphs showed that, for the most part,
• In chemical storage tanks, ensuring in a filter bed is quite easy—and rarely
these devices tracked the level steadily
process chemicals don’t run out or sees guided wave radar used. Most filter
during normal operation and backwash
spill over the tanks that contain them beds have excellent accessibility to
cycles. However, the graphs also
install level instruments and their rect-
• At the headworks, taking level measure- showed periods of intermittent high-
angular-shaped basins are usually free
ments from a flume or weir to calculate level indication—some of the spikes
of obstructions that otherwise would
volumes of effluent first entering the lasting a short time and others lasting
interfere with an instrument’s signal
plant several minutes.
reaching down to the lowest point.
• In primary clarifiers, secondary clarifiers, At the filter beds, organic material was
A couple of years ago, this wastewater
sludge wells, filter beds, chemical accumulating on most of the guided
treatment plant underwent a nearly 20
tanks—you get the picture—controlling wave radar transmitters’ cables. This
75.7 million-liter expansion to meet the
and monitoring levels material was not uniformly spread out
demands of residential and commercial
along the cable and the amount of this
Most of these level measurements are growth in the area that it serves. The
organic buildup also varied.
usually carried out using ultrasonic level expansion included the design of fast
controllers and transmitters. Occasionally sand filter beds using wash water Although newer versions of guided
a plant might use radar transmitters due troughs and compressed air. wave radar transmitters can automati-
to the process connection limitations of a cally suppress buildup, filter beds in an
The large diameter wash water troughs
tank, chemical compatibility of the open environment are exposed to
about a meter apart. However, the
media, or if the measurement range changing weather, insects, and any-
influent trough pipe located above and
requires it. thing else floating on the water surface
between the wash water troughs leaves
or through the air.
However, contacting level technology only a 0.61-meter gap in between them.
such as guided wave radar is seldom This narrow gap between the large pipe Once debris begins to build up on
used—and when it is, finds itself mostly and troughs prompted the use of guid- cables or rods, moisture can more easily
in ammonia level applications due to ed wave radar level transmitters with accumulate, and buildup will continue

Save time and maintenance costs with SITRANS Probe LU240’s Ultrasonics are ideal for environmental applications: our exclusive echo processing
transparent lid. For manual observations, you no longer need to algorithms ensure reliable level readings every time. Accurate, proven features like
remove the device’s lid, but instead can observe the values you auto-false echo suppression provide advanced capabilities you can depend on at a
need with ease. low cost of ownership.

siemens.com/sitransProbeLU240
to grow. The greater the moisture generated by the piezoelectric crystals This maintenance-free solution and consis-
content on the buildup, the more used to generate the echo pulse means tent performance proved that ultrasonic
conductive this buildup becomes. that ultrasonic devices have self-clean- level technology is the right choice for this
ing faces, literally shaking themselves and many level applications found in the
To the transmitter, this accumulated
clean of dirt, condensation and buildup wastewater treatment process.
material begins to appear as a real
in the application. This minimizes the
target, which eventually leads to incon- Benefits to your operation
negative effects of condensation that
sistent level measurements. Automatic
otherwise would degrade the transmit- The SITRANS Probe LU240 has a local
suppression of this buildup is not
ted and received echo signals. display with push buttons that makes it
enough to overcome this challenge—
easy to set up by simply following the
not only because of the dynamics of the With ultrasonic level technology’s
built-in wizard.
buildup, but the end of the transmitter’s proven history in water applications, it
cable must be completely unsubmerged was clear that by using a SITRANS Probe With just a handful of parameter
for its automatic activation. LU240 transmitter, with its large signal entries, the instrument is operational
power and capabilities to mask unwanted in minutes. The compact signal beam
A temporary solution… and then a
reflections, a consistent level measure- angle and high signal strength make it
better one
ment might finally be possible. possible to install the device in level
Operators didn’t immediately make the applications that at first seem to call
Easy installation + excellent
correlation between the intermittent for more specialized technology.
performance
high-level spikes and material sticking
Not only is the SITRANS Probe LU240
on the cables. They would occasionally Operators removed the existing guided
more economical pricewise, but it is
spray the cables with high-pressure wave radar device and installed the
also a maintenance-free device. Its
water jets during the periodic wash- SITRANS Probe LU240 without trouble,
consistent performance gives you
downs to keep the basin and surround- even considering the narrow space
dependable control over the critical
ing area clean. restrictions between pipes.
cycles necessary for your bed filter
After washdown and once residual Once the device was set up, the water operations.
water was cleared off the cables, the level was lowered to expose the troughs.
About the SITRANS Probe LU240
operation of the guided wave radar Operators activated the backwash cycle,
devices improved—that is, until buildup which created a turbulent surface due to SITRANS Probe LU240 is a compact,
started to return, thereby causing the air flow that is part of the process. rugged, and high-performance ultra-
inference again. During this critical time and subsequent sonic transmitter that is engineered to
cycles, the ultrasonic level transmitter last. With the unparalleled control and
Operators needed a more permanent
tracked the level quite well. access now possible with Industry 4.0,
fix
this digital age still requires accurate
The echo signals captured using SIMATIC
As mentioned above, filter beds are an and rugged process instrumentation.
PDM diagnostics software utility showed
easy level measurement for transmitters The SITRANS Probe LU240 is a cost-
that at the lowest level, the transmitter
using non-contacting ultrasonic technol- effective, intelligent level solution ready
could see the pipes, but they didn’t cause
ogy. As the name implies, to obtain a for digitalization with Hart 7, providing
interference with the level measurement.
level measurement with this technology, value far beyond its initial cost.
In fact, the echo signal reflecting from
the sensor does not contact the liquid or
the water surface was so strong that
solid’s surface. Instead, the measure-
operators didn’t need to apply the instru-
ment is derived using the time of flight
ment’s Auto False Echo Suppression
principle: the echo signal generated by
capabilities to negate the reflections
the instrument is transmitted and re-
caused by the pipes and troughs.
ceived by the transducer and the corre-
sponding distance or level can be Back in the control room, operators com-
viewed on the device’s local display. pared the performance of the SITRANS
Probe LU240 to the remaining guided
Most commonly, the 4-20 mA output
wave radar transmitters in the other filter
signal is sent to the control room where
beds. The transducer section remained
it is relayed to an HMI (human machine
clean and the historical trend graph
interface). These days, with the environ-
showed consistent level measurement. Published by
mental industry’s ever-increasing digita-
lization efforts, level information can be Based on these results, operators removed Siemens 2018
interconnected with Siemens Mind- another (and more troublesome!) guided Process Industries and Drives
Sphere for data analysis, better efficiency, wave radar transmitter on a nearby filter Östliche Rheinbrückenstr. 50
and process management. bed. Both SITRANS Probe LU240 transmit- 76187 Karlsruhe
Germany
ters have been operating flawlessly under
With non-contacting technology, the © Siemens 2018
the same conditions as the guided wave
issue with buildup developing on the
radar transmitters.
area of transmission is virtually nonexistent.