CUT E 350-600 Mark I High Pressure Pump Frequency Converter (FC1) Parameters Check (For Model J1000x.x)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

13/08/2021 CUT E 350-600 Mark I

High pressure pump frequency converter (FC1) parameters check (for model J1000x.x)

The frequency converter of J1000:

1) Power on the inverter (open the QM8), and display

2) Confirm the light of this button


off (Remote control mode).

3) Press 8 times until display parameter setting mode , Press ,


enter the parameter setting, displays A1-01, character “A” flicker.

4) Set parameter:b1-01=01. Press

to let "A" switch to "b", then press till “01” flicker. Press , set value to 01, and press ,
again to save the value, “End” will displayed at this moment.

5) Set the rest of parameters:


b1-01=01 b1-02=01 b1-03=00 b1-04=01
C1-01=2 C1-02=2 C6-02=07
E1-01=380 E1-04=60 E1-05=380
E1-06=60 E1-07=1.5 E1-08=24
E2-01=5.5 o2-02=0

6) Finally, press several times till displayed.

Select value Frequency value Select value Frequency value


1.0 8.5Hz 10 36.4Hz
1.2 9.7Hz 11 38.1Hz
1.5 12.1Hz 12 39.6Hz
2.0 14.5Hz 13 41.3Hz
2.5 16.9Hz 14 42.5Hz
3 18.6Hz 15 43.94Hz
4 21.8Hz 16 45.74Hz
5 24.9Hz 17 46.89Hz
6 27.4Hz 18 47.87Hz
7 30.3Hz 19 50.55Hz
8 32Hz 20 52.2Hz
9 34Hz

(Error: ±0.1Hz)