Download as txt, pdf, or txt
Download as txt, pdf, or txt
You are on page 1of 11

Network Management Card AOS v6.5.

0
Smart-UPS & Matrix-UPS APP v6.5.0
NMC Serial Number: 5A1808T33121

Model: Smart-UPS SRT 5000


UPS Serial Number: AS1808171254
Firmware Revision: UPS 04.7 (ID1013)

Date Time Name Contact Location System IP


09/06/2023 08:44:50 AFC-SSM-PGUPS-01 Unknown AFC-SSM-PGUPS-01
10.60.7.144

Date Time User Event Code


09/06/2023 08:43:26 apc Web user 'apc' logged in from 10.60.250.137. 0x0015
09/06/2023 06:57:21 System Web user 'apc' logged out from 10.60.7.21.
0x001F
09/06/2023 06:54:14 apc Web user 'apc' logged in from 10.60.7.21. 0x0015
09/06/2023 05:35:40 System Web user 'apc' logged out from 10.60.250.137.
0x001F
09/06/2023 05:32:40 apc Web user 'apc' logged in from 10.60.250.137. 0x0015
09/06/2023 05:31:56 System Web user 'apc' logged out from 10.60.250.137.
0x001F
09/06/2023 05:30:05 Device UPS: In bypass in response to the UPS front-
panel or a user-initiated software command, typically for maintenance. 0x011C
09/06/2023 05:28:07 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
09/06/2023 05:27:33 Device UPS: The battery power is too low to support
the load; if power fails, the UPS will be shut down immediately. 0x0107
09/06/2023 05:27:33 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
09/06/2023 05:27:33 Device UPS: Restored the local network management
interface-to-UPS communication. 0x0101
09/06/2023 05:27:25 apc Web user 'apc' logged in from 10.60.250.137. 0x0015
09/06/2023 05:27:09 System Network service started. IPv6 address
FE80::2A29:86FF:FE04:AC8B assigned by link-local autoconfiguration. 0x0007
09/06/2023 05:27:07 System Network service started. System IP is
10.60.7.144 from manually configured settings. 0x0007
09/06/2023 05:27:03 System Network Interface coldstarted. 0x0001
09/06/2023 05:26:30 Device UPS: A battery charger fault exists. 0x012A
09/06/2023 05:26:24 Device UPS: A battery charger fault no longer exists.
0x012B
09/06/2023 05:25:47 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
09/06/2023 05:25:13 Device UPS: The output power is turned off. 0x0114
09/06/2023 05:25:13 Device UPS: The graceful shutdown period has ended.
0x014F
09/06/2023 05:25:13 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is off. 0x0186
09/06/2023 05:25:13 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is off. 0x0186
09/06/2023 05:25:13 Device UPS: The battery power is too low to support
the load; if power fails, the UPS will be shut down immediately. 0x0107
09/06/2023 05:25:13 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
09/06/2023 05:25:13 Device UPS: A battery charger fault exists. 0x012A
09/06/2023 05:25:13 Device UPS: Restored the local network management
interface-to-UPS communication. 0x0101
09/06/2023 05:24:49 System Network service started. IPv6 address
FE80::2A29:86FF:FE04:AC8B assigned by link-local autoconfiguration. 0x0007
09/06/2023 05:24:48 System Network service started. System IP is
10.60.7.144 from manually configured settings. 0x0007
09/06/2023 05:24:43 System Network Interface coldstarted. 0x0001
09/06/2023 05:18:34 apc Web user 'apc' logged in from 10.60.250.137. 0x0015
09/06/2023 05:18:27 Device UPS: The output power is turned off. 0x0114
09/06/2023 05:18:27 Device UPS: The graceful shutdown period has ended.
0x014F
09/06/2023 05:18:27 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is off. 0x0186
09/06/2023 05:18:27 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is off. 0x0186
09/06/2023 05:18:27 Device UPS: The battery power is too low to support
the load; if power fails, the UPS will be shut down immediately. 0x0107
09/06/2023 05:18:27 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
09/06/2023 05:18:27 Device UPS: A battery charger fault exists. 0x012A
09/06/2023 05:18:26 Device UPS: Restored the local network management
interface-to-UPS communication. 0x0101
09/06/2023 05:18:03 System Network service started. IPv6 address
FE80::2A29:86FF:FE04:AC8B assigned by link-local autoconfiguration. 0x0007
09/06/2023 05:18:01 System Network service started. System IP is
10.60.7.144 from manually configured settings. 0x0007
09/06/2023 05:17:57 System Network Interface coldstarted. 0x0001
09/06/2023 05:16:42 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
09/06/2023 05:16:10 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
09/06/2023 05:16:10 Device UPS: Battery life exceeded cleared. 0x018D
09/06/2023 05:15:51 Device UPS: A battery charger fault exists. 0x012A
09/06/2023 05:15:48 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
09/06/2023 05:15:45 Device UPS: A battery charger fault no longer exists.
0x012B
09/06/2023 04:57:12 apc Web user 'apc' logged in from 10.60.250.137. 0x0015
09/06/2023 04:21:42 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
09/06/2023 04:21:37 Device UPS: Internal pack disconnected cleared. 0x01A1
09/06/2023 04:21:09 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
09/06/2023 04:21:08 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is now turned off. 0x0135
09/06/2023 04:21:08 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is now turned off. 0x0135
09/06/2023 04:21:08 Device UPS: A battery charger fault exists. 0x012A
09/06/2023 04:21:07 Device UPS: The output power is turned off. 0x0114
09/06/2023 04:21:07 Device UPS: The graceful shutdown period has ended.
0x014F
09/06/2023 04:20:53 Device UPS: Internal pack disconnected. 0x01A0
09/05/2023 21:06:43 System NTP update successful. 0x004A
09/04/2023 23:17:11 Device UPS: Self-Test passed. 0x01D2
09/04/2023 23:16:50 Device UPS: Self-Test started by automatic timer.
0x0137
09/01/2023 23:10:20 Device UPS: Battery life exceeded cleared. 0x018D
09/01/2023 01:06:26 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
09/01/2023 01:05:48 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
09/01/2023 01:05:42 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
09/01/2023 01:05:42 Device UPS: Battery life exceeded cleared. 0x018D
08/31/2023 22:49:59 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
08/31/2023 21:11:48 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/31/2023 21:10:56 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
08/31/2023 21:10:56 Device UPS: Battery life exceeded cleared. 0x018D
08/31/2023 21:09:00 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
08/31/2023 20:51:49 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/31/2023 20:51:14 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
08/31/2023 20:51:14 Device UPS: Battery life exceeded cleared. 0x018D
08/31/2023 20:42:13 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
08/31/2023 20:38:49 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/31/2023 20:37:55 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
08/31/2023 20:37:55 Device UPS: Battery life exceeded cleared. 0x018D
08/31/2023 18:11:55 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
08/31/2023 18:11:49 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/31/2023 18:11:11 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
08/31/2023 18:11:11 Device UPS: Battery life exceeded cleared. 0x018D
08/31/2023 17:57:49 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
08/31/2023 17:57:49 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/31/2023 17:57:30 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
08/31/2023 17:57:30 Device UPS: Battery life exceeded cleared. 0x018D
08/30/2023 04:03:07 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
08/30/2023 04:02:50 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/30/2023 04:02:29 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
08/30/2023 04:02:29 Device UPS: Battery life exceeded cleared. 0x018D
08/30/2023 03:59:33 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
08/30/2023 03:58:50 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/30/2023 03:58:49 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
08/28/2023 01:11:04 Device UPS: No longer on battery power. 0x010A
08/28/2023 01:11:04 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
08/28/2023 00:52:56 Device UPS: Bypass not in range ; distorted waveform.
0x020F
08/28/2023 00:52:55 Device UPS: On battery power in response to low input
voltage. 0x0109
08/27/2023 02:34:15 Device UPS: No longer on battery power. 0x010A
08/27/2023 02:34:14 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
08/27/2023 02:32:46 Device UPS: Bypass not in range ; distorted waveform.
0x020F
08/27/2023 02:32:46 Device UPS: On battery power in response to distorted
input. 0x0109
08/27/2023 02:19:38 Device UPS: No longer on battery power. 0x010A
08/27/2023 02:19:37 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
08/27/2023 02:18:48 Device UPS: Bypass not in range ; distorted waveform.
0x020F
08/27/2023 02:18:48 Device UPS: On battery power in response to rapid
change of input. 0x0109
08/22/2023 21:06:33 System NTP update successful. 0x004A
08/21/2023 23:17:36 Device UPS: Self-Test passed. 0x01D2
08/21/2023 23:17:15 Device UPS: Self-Test started by automatic timer.
0x0137
08/20/2023 22:45:04 Device UPS: Battery life exceeded cleared. 0x018D
08/08/2023 21:06:36 System NTP update successful. 0x004A
08/07/2023 23:18:14 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/07/2023 23:18:01 Device UPS: Self-Test passed. 0x01D2
08/07/2023 23:17:40 Device UPS: Self-Test started by automatic timer.
0x0137
07/25/2023 21:06:27 System NTP update successful. 0x004A
07/24/2023 23:19:02 Device UPS: Self-Test passed. 0x01D2
07/24/2023 23:18:41 Device UPS: Self-Test started by front panel. 0x0137
07/24/2023 23:18:40 Device UPS: Battery life exceeded cleared. 0x018D
07/20/2023 02:16:34 Device UPS: No longer on battery power. 0x010A
07/20/2023 02:16:33 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
07/20/2023 00:46:11 Device UPS: On battery power in response to distorted
input. 0x0109
07/20/2023 00:46:11 Device UPS: Bypass not in range ; distorted waveform.
0x020F
07/15/2023 07:37:03 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
07/11/2023 23:24:40 Device UPS: Self-Test passed. 0x01D2
07/11/2023 23:24:19 Device UPS: Self-Test started by front panel. 0x0137
07/11/2023 21:06:00 System NTP update successful. 0x004A
07/01/2023 07:37:28 Device UPS: Battery life exceeded cleared. 0x018D
07/01/2023 03:35:20 Device UPS: No longer on battery power. 0x010A
07/01/2023 03:35:19 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
07/01/2023 03:32:04 Device UPS: On battery power in response to distorted
input. 0x0109
07/01/2023 03:32:04 Device UPS: Bypass not in range ; distorted waveform.
0x020F
07/01/2023 00:56:52 Device UPS: No longer on battery power. 0x010A
07/01/2023 00:56:52 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
07/01/2023 00:54:20 Device UPS: On battery power in response to distorted
input. 0x0109
07/01/2023 00:54:20 Device UPS: Bypass not in range ; distorted waveform.
0x020F
06/29/2023 23:56:03 Device UPS: Self-Test passed. 0x01D2
06/29/2023 23:55:43 Device UPS: Self-Test started by automatic timer.
0x0137
06/29/2023 23:54:54 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
06/27/2023 21:05:55 System NTP update successful. 0x004A
06/15/2023 23:56:25 Device UPS: Self-Test passed. 0x01D2
06/15/2023 23:56:04 Device UPS: Self-Test started by front panel. 0x0137
06/15/2023 23:55:40 Device UPS: Self-Test passed. 0x01D2
06/15/2023 23:55:19 Device UPS: Self-Test started by front panel. 0x0137
06/15/2023 23:55:15 Device UPS: Battery life exceeded cleared. 0x018D
06/14/2023 03:37:04 Device UPS: No longer on battery power. 0x010A
06/14/2023 03:37:04 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
06/14/2023 03:35:01 Device UPS: Bypass not in range ; distorted waveform.
0x020F
06/14/2023 03:35:01 Device UPS: On battery power in response to distorted
input. 0x0109
06/14/2023 01:11:18 Device UPS: No longer on battery power. 0x010A
06/14/2023 01:11:18 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
06/14/2023 01:09:08 Device UPS: Bypass not in range ; distorted waveform.
0x020F
06/14/2023 01:09:08 Device UPS: On battery power in response to distorted
input. 0x0109
06/13/2023 21:05:56 System NTP update successful. 0x004A
06/06/2023 22:38:49 Device UPS: Self-Test passed. 0x01D2
06/06/2023 22:38:28 Device UPS: Self-Test started by automatic timer.
0x0137
05/30/2023 21:05:27 System NTP update successful. 0x004A
05/25/2023 03:25:52 Device UPS: No longer on battery power. 0x010A
05/25/2023 03:25:51 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/25/2023 03:25:00 Device UPS: On battery power in response to distorted
input. 0x0109
05/25/2023 03:25:00 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/25/2023 02:17:45 Device UPS: No longer on battery power. 0x010A
05/25/2023 02:17:43 Device UPS: On battery power in response to distorted
input. 0x0109
05/25/2023 01:29:53 Device UPS: No longer on battery power. 0x010A
05/25/2023 01:29:52 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/25/2023 01:29:13 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/25/2023 01:29:12 Device UPS: On battery power in response to low input
voltage. 0x0109
05/23/2023 22:39:14 Device UPS: Self-Test passed. 0x01D2
05/23/2023 22:38:54 Device UPS: Self-Test started by automatic timer.
0x0137
05/21/2023 21:44:42 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
05/16/2023 21:05:18 System NTP update successful. 0x004A
05/09/2023 22:39:39 Device UPS: Self-Test passed. 0x01D2
05/09/2023 22:39:18 Device UPS: Self-Test started by automatic timer.
0x0137
05/07/2023 21:45:05 Device UPS: Battery life exceeded cleared. 0x018D
05/02/2023 21:05:20 System NTP update successful. 0x004A
04/25/2023 22:40:03 Device UPS: Self-Test passed. 0x01D2
04/25/2023 22:39:42 Device UPS: Self-Test started by automatic timer.
0x0137
04/23/2023 07:19:08 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
04/18/2023 21:04:31 System NTP update successful. 0x004A
04/11/2023 22:40:26 Device UPS: Self-Test passed. 0x01D2
04/11/2023 22:40:05 Device UPS: Self-Test started by front panel. 0x0137
04/09/2023 07:20:29 Device UPS: Self-Test passed. 0x01D2
04/09/2023 07:20:08 Device UPS: Self-Test started by front panel. 0x0137
04/09/2023 07:19:57 Device UPS: Self-Test passed. 0x01D2
04/09/2023 07:19:37 Device UPS: Self-Test started by front panel. 0x0137
04/09/2023 07:19:33 Device UPS: Battery life exceeded cleared. 0x018D
04/04/2023 21:03:51 System NTP update successful. 0x004A
04/02/2023 18:05:49 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
03/29/2023 22:38:14 Device UPS: Self-Test passed. 0x01D2
03/29/2023 22:37:53 Device UPS: Self-Test started by front panel. 0x0137
03/29/2023 22:37:20 Device UPS: Self-Test passed. 0x01D2
03/29/2023 22:36:59 Device UPS: Self-Test started by front panel. 0x0137
03/21/2023 21:03:57 System NTP update successful. 0x004A
03/20/2023 21:22:12 Device UPS: Self-Test passed. 0x01D2
03/20/2023 21:21:52 Device UPS: Self-Test started by automatic timer.
0x0137
03/19/2023 18:06:13 Device UPS: Battery life exceeded cleared. 0x018D
03/18/2023 02:16:28 Device UPS: No longer on battery power. 0x010A
03/18/2023 02:16:27 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
03/18/2023 02:10:18 Device UPS: Bypass not in range ; distorted waveform.
0x020F
03/18/2023 02:10:18 Device UPS: On battery power in response to distorted
input. 0x0109
03/18/2023 01:23:15 Device UPS: No longer on battery power. 0x010A
03/18/2023 01:23:14 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
03/18/2023 01:00:17 Device UPS: Bypass not in range ; distorted waveform.
0x020F
03/18/2023 01:00:16 Device UPS: On battery power in response to distorted
input. 0x0109
03/17/2023 22:59:47 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
03/07/2023 21:03:50 System NTP update successful. 0x004A
03/06/2023 21:22:38 Device UPS: Self-Test passed. 0x01D2
03/06/2023 21:22:17 Device UPS: Self-Test started by automatic timer.
0x0137
03/03/2023 23:00:11 Device UPS: Battery life exceeded cleared. 0x018D
02/21/2023 21:03:51 System NTP update successful. 0x004A
02/20/2023 21:23:02 Device UPS: Self-Test passed. 0x01D2
02/20/2023 21:22:42 Device UPS: Self-Test started by automatic timer.
0x0137
02/10/2023 15:57:48 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
02/07/2023 21:03:57 System NTP update successful. 0x004A
02/06/2023 21:23:28 Device UPS: Self-Test passed. 0x01D2
02/06/2023 21:23:07 Device UPS: Self-Test started by automatic timer.
0x0137
02/05/2023 22:16:22 Device UPS: Battery near end of life cleared. 0x018B
01/25/2023 16:37:33 Device UPS: Battery near end of life. Order
replacement battery, APCRBC140, for the internal pack, cartridge 1. 0x018A
01/24/2023 21:03:45 System NTP update successful. 0x004A
01/23/2023 21:24:24 Device UPS: Self-Test passed. 0x01D2
01/23/2023 21:24:02 Device UPS: Self-Test started by front panel. 0x0137
01/15/2023 14:19:14 System Web user 'apc' logged out from 10.60.250.21.
0x001F
01/15/2023 14:16:14 apc Web user 'apc' logged in from 10.60.250.21. 0x0015
01/11/2023 21:22:05 Device UPS: Self-Test passed. 0x01D2
01/11/2023 21:21:44 Device UPS: Self-Test started by automatic timer.
0x0137
01/11/2023 16:37:54 Device UPS: Battery near end of life cleared. 0x018B
01/10/2023 21:03:31 System NTP update successful. 0x004A
12/28/2022 21:22:30 Device UPS: Self-Test passed. 0x01D2
12/28/2022 21:22:09 Device UPS: Self-Test started by automatic timer.
0x0137
12/27/2022 21:03:22 System NTP update successful. 0x004A
12/14/2022 21:22:55 Device UPS: Self-Test passed. 0x01D2
12/14/2022 21:22:34 Device UPS: Self-Test started by front panel. 0x0137
12/13/2022 21:03:10 System NTP update successful. 0x004A
12/08/2022 16:55:55 Device UPS: Battery near end of life. Order
replacement battery, APCRBC140, for the internal pack, cartridge 1. 0x018A
12/05/2022 01:36:17 Device UPS: No longer on battery power. 0x010A
12/05/2022 01:36:16 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
12/05/2022 01:36:02 Device UPS: Bypass not in range ; distorted waveform.
0x020F
12/05/2022 01:36:01 Device UPS: On battery power in response to rapid
change of input. 0x0109
12/05/2022 01:15:41 Device UPS: No longer on battery power. 0x010A
12/05/2022 01:15:41 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
12/05/2022 01:15:29 Device UPS: Bypass not in range ; distorted waveform.
0x020F
12/05/2022 01:15:29 Device UPS: On battery power in response to rapid
change of input. 0x0109
12/03/2022 21:45:17 Device UPS: Self-Test passed. 0x01D2
12/03/2022 21:44:56 Device UPS: Self-Test started by automatic timer.
0x0137
11/29/2022 21:02:21 System NTP update successful. 0x004A
11/24/2022 16:56:19 Device UPS: Battery near end of life cleared. 0x018B
11/19/2022 21:45:42 Device UPS: Self-Test passed. 0x01D2
11/19/2022 21:45:21 Device UPS: Self-Test started by automatic timer.
0x0137
11/19/2022 21:13:40 Device UPS: Battery near end of life. Order
replacement battery, APCRBC140, for the internal pack, cartridge 1. 0x018A
11/15/2022 21:01:49 System NTP update successful. 0x004A
11/05/2022 21:46:23 Device UPS: Self-Test passed. 0x01D2
11/05/2022 21:46:02 Device UPS: Self-Test started by front panel. 0x0137
11/05/2022 21:14:26 Device UPS: Self-Test passed. 0x01D2
11/05/2022 21:14:05 Device UPS: Self-Test started by front panel. 0x0137
11/05/2022 21:14:03 Device UPS: Battery near end of life cleared. 0x018B
11/01/2022 21:01:56 System NTP update successful. 0x004A
10/27/2022 20:16:26 Device UPS: Self-Test passed. 0x01D2
10/27/2022 20:16:05 Device UPS: Self-Test started by automatic timer.
0x0137
10/18/2022 21:02:00 System NTP update successful. 0x004A
10/13/2022 20:16:51 Device UPS: Self-Test passed. 0x01D2
10/13/2022 20:16:30 Device UPS: Self-Test started by automatic timer.
0x0137
10/11/2022 20:09:35 Device UPS: Battery near end of life. Order
replacement battery, APCRBC140, for the internal pack, cartridge 1. 0x018A
10/04/2022 21:02:02 System NTP update successful. 0x004A
09/29/2022 20:17:15 Device UPS: Self-Test passed. 0x01D2
09/29/2022 20:16:55 Device UPS: Self-Test started by automatic timer.
0x0137
09/27/2022 20:10:00 Device UPS: Battery near end of life cleared. 0x018B
09/20/2022 21:01:31 System NTP update successful. 0x004A
09/15/2022 20:17:41 Device UPS: Self-Test passed. 0x01D2
09/15/2022 20:17:20 Device UPS: Self-Test started by automatic timer.
0x0137
09/15/2022 20:17:20 Device UPS: Battery near end of life. Order
replacement battery, APCRBC140, for the internal pack, cartridge 1. 0x018A
09/06/2022 21:01:02 System NTP update successful. 0x004A
09/01/2022 20:18:09 Device UPS: Self-Test passed. 0x01D2
09/01/2022 20:17:48 Device UPS: Self-Test started by front panel. 0x0137
09/01/2022 20:17:46 Device UPS: Battery near end of life cleared. 0x018B
08/25/2022 14:41:18 apc Web user 'apc' logged out from 10.60.250.147. 0x001F
08/25/2022 14:40:47 apc Web user 'apc' logged in from 10.60.250.147. 0x0015
08/25/2022 14:40:40 apc Web user 'apc' logged out from 10.60.250.147. 0x001F
08/25/2022 14:40:16 apc Web user 'apc' logged in from 10.60.250.147. 0x0015
08/23/2022 21:00:33 System NTP update successful. 0x004A
08/21/2022 21:30:30 Device UPS: Self-Test passed. 0x01D2
08/21/2022 21:30:09 Device UPS: Self-Test started by automatic timer.
0x0137
08/21/2022 18:00:20 Device UPS: Battery near end of life. Order
replacement battery, APCRBC140, for the internal pack, cartridge 1. 0x018A
08/09/2022 20:59:46 System NTP update successful. 0x004A
08/07/2022 21:30:54 Device UPS: Self-Test passed. 0x01D2
08/07/2022 21:30:33 Device UPS: Self-Test started by automatic timer.
0x0137
07/26/2022 20:58:56 System NTP update successful. 0x004A
07/24/2022 21:31:47 Device UPS: Self-Test passed. 0x01D2
07/24/2022 21:31:26 Device UPS: Self-Test started by front panel. 0x0137
07/13/2022 03:42:32 Device UPS: Self-Test passed. 0x01D2
07/13/2022 03:42:11 Device UPS: Self-Test started by automatic timer.
0x0137
07/12/2022 20:59:02 System NTP update successful. 0x004A
07/09/2022 00:29:02 Device UPS: No longer on battery power. 0x010A
07/09/2022 00:29:02 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
07/08/2022 23:23:20 Device UPS: On battery power in response to low input
voltage. 0x0109
07/08/2022 23:23:20 Device UPS: Bypass not in range ; distorted waveform.
0x020F
06/29/2022 03:42:56 Device UPS: Self-Test passed. 0x01D2
06/29/2022 03:42:35 Device UPS: Self-Test started by automatic timer.
0x0137
06/28/2022 20:59:08 System NTP update successful. 0x004A
06/15/2022 03:43:21 Device UPS: Self-Test passed. 0x01D2
06/15/2022 03:43:01 Device UPS: Self-Test started by automatic timer.
0x0137
06/14/2022 20:59:18 System NTP update successful. 0x004A
06/10/2022 00:50:42 Device UPS: No longer on battery power. 0x010A
06/10/2022 00:50:42 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
06/10/2022 00:50:22 Device UPS: On battery power in response to distorted
input. 0x0109
06/10/2022 00:50:22 Device UPS: Bypass not in range ; distorted waveform.
0x020F
06/09/2022 23:49:40 Device UPS: No longer on battery power. 0x010A
06/09/2022 23:49:39 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
06/09/2022 23:49:17 Device UPS: Bypass not in range ; distorted waveform.
0x020F
06/09/2022 23:49:16 Device UPS: On battery power in response to low input
voltage. 0x0109
06/01/2022 03:44:08 Device UPS: Self-Test passed. 0x01D2
06/01/2022 03:43:48 Device UPS: Self-Test started by automatic timer.
0x0137
06/01/2022 03:43:46 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is now turned on. 0x0134
06/01/2022 03:43:46 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is now turned on. 0x0134
06/01/2022 03:43:46 Device UPS: The output power is now turned on. 0x0113
06/01/2022 03:43:46 Device UPS: Switched outlet group 2, Outlet Group 2,
has been commanded to turn on, sequenced. 0x0174
06/01/2022 03:43:46 Device UPS: Switched outlet group 1, Outlet Group 1,
has been commanded to turn on, sequenced. 0x0174
05/31/2022 23:10:57 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is now turned off. 0x0135
05/31/2022 23:10:57 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is now turned off. 0x0135
05/31/2022 23:10:57 Device UPS: Switched outlet group 2, Outlet Group 2,
has been commanded to turn off, sequenced. 0x0174
05/31/2022 23:10:57 Device UPS: Switched outlet group 1, Outlet Group 1,
has been commanded to turn off, sequenced. 0x0174
05/31/2022 23:10:57 Device UPS: The output power is turned off. 0x0114
05/31/2022 23:10:57 Device UPS: The graceful shutdown period has ended.
0x014F
05/31/2022 20:59:26 System NTP update successful. 0x004A
05/23/2022 00:02:32 Device UPS: No longer on battery power. 0x010A
05/23/2022 00:02:31 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/23/2022 00:02:13 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/23/2022 00:02:13 Device UPS: On battery power in response to distorted
input. 0x0109
05/22/2022 23:38:38 Device UPS: No longer on battery power. 0x010A
05/22/2022 23:38:38 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/22/2022 23:38:21 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/22/2022 23:38:21 Device UPS: On battery power in response to distorted
input. 0x0109
05/22/2022 07:32:56 Device UPS: Self-Test passed. 0x01D2
05/22/2022 07:32:35 Device UPS: Self-Test started by front panel. 0x0137
05/22/2022 05:03:04 Device UPS: No longer on battery power. 0x010A
05/22/2022 05:03:03 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/22/2022 05:02:59 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/22/2022 05:02:59 Device UPS: On battery power in response to rapid
change of input. 0x0109
05/21/2022 23:29:02 Device UPS: No longer on battery power. 0x010A
05/21/2022 23:29:02 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/21/2022 23:28:56 Device UPS: On battery power in response to distorted
input. 0x0109
05/21/2022 23:28:56 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/20/2022 20:39:08 Device UPS: Self-Test passed. 0x01D2
05/20/2022 20:38:47 Device UPS: Self-Test started by front panel. 0x0137
05/17/2022 20:59:34 System NTP update successful. 0x004A
05/15/2022 03:13:15 Device UPS: No longer on battery power. 0x010A
05/15/2022 03:13:15 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/15/2022 03:13:09 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/15/2022 03:13:09 Device UPS: On battery power in response to distorted
input. 0x0109
05/15/2022 01:08:10 Device UPS: No longer on battery power. 0x010A
05/15/2022 01:08:09 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/15/2022 01:08:02 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/15/2022 01:08:02 Device UPS: On battery power in response to distorted
input. 0x0109
05/08/2022 21:32:31 Device UPS: Self-Test passed. 0x01D2
05/08/2022 21:32:10 Device UPS: Self-Test started by automatic timer.
0x0137
05/03/2022 20:59:42 System NTP update successful. 0x004A
04/24/2022 21:32:51 Device UPS: Self-Test passed. 0x01D2
04/24/2022 21:32:30 Device UPS: Self-Test started by front panel. 0x0137
04/22/2022 02:13:11 Device UPS: No longer on battery power. 0x010A
04/22/2022 02:13:10 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
04/22/2022 02:12:34 Device UPS: Bypass not in range ; distorted waveform.
0x020F
04/22/2022 02:12:34 Device UPS: On battery power in response to distorted
input. 0x0109
04/21/2022 23:09:42 Device UPS: No longer on battery power. 0x010A
04/21/2022 23:09:41 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
04/21/2022 23:09:29 Device UPS: Bypass not in range ; distorted waveform.
0x020F
04/21/2022 23:09:29 Device UPS: On battery power in response to distorted
input. 0x0109
04/21/2022 04:13:25 Device UPS: No longer on battery power. 0x010A
04/21/2022 04:13:25 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
04/21/2022 04:13:11 Device UPS: On battery power in response to distorted
input. 0x0109
04/21/2022 04:13:11 Device UPS: Bypass not in range ; distorted waveform.
0x020F
04/20/2022 23:16:33 Device UPS: No longer on battery power. 0x010A
04/20/2022 23:16:33 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
04/20/2022 23:16:22 Device UPS: Bypass not in range ; distorted waveform.
0x020F
04/20/2022 23:16:22 Device UPS: On battery power in response to distorted
input. 0x0109
04/19/2022 20:59:51 System NTP update successful. 0x004A
04/15/2022 00:50:59 Device UPS: Self-Test passed. 0x01D2
04/15/2022 00:50:38 Device UPS: Self-Test started by automatic timer.
0x0137
04/15/2022 00:50:37 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is now turned on. 0x0134
04/15/2022 00:50:37 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is now turned on. 0x0134
04/15/2022 00:50:37 Device UPS: The output power is now turned on. 0x0113
04/15/2022 00:50:36 Device UPS: Switched outlet group 2, Outlet Group 2,
has been commanded to turn on, sequenced. 0x0174
04/15/2022 00:50:36 Device UPS: Switched outlet group 1, Outlet Group 1,
has been commanded to turn on, sequenced. 0x0174
04/14/2022 23:01:28 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is now turned off. 0x0135
04/14/2022 23:01:28 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is now turned off. 0x0135
04/14/2022 23:01:28 Device UPS: The output power is turned off. 0x0114
04/14/2022 23:01:28 Device UPS: The graceful shutdown period has ended.
0x014F
04/14/2022 23:01:27 Device UPS: Switched outlet group 2, Outlet Group 2,
has been commanded to turn off, sequenced. 0x0174
04/14/2022 23:01:27 Device UPS: Switched outlet group 1, Outlet Group 1,
has been commanded to turn off, sequenced. 0x0174
04/14/2022 04:01:18 Device UPS: Self-Test passed. 0x01D2
04/14/2022 04:00:58 Device UPS: Self-Test started by automatic timer.
0x0137
04/14/2022 04:00:57 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is now turned on. 0x0134
04/14/2022 04:00:57 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is now turned on. 0x0134
04/14/2022 04:00:56 Device UPS: The output power is now turned on. 0x0113
04/14/2022 04:00:56 Device UPS: Switched outlet group 2, Outlet Group 2,
has been commanded to turn on, sequenced. 0x0174
04/14/2022 04:00:56 Device UPS: Switched outlet group 1, Outlet Group 1,
has been commanded to turn on, sequenced. 0x0174
04/14/2022 01:46:00 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is now turned off. 0x0135
04/14/2022 01:46:00 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is now turned off. 0x0135
04/14/2022 01:46:00 Device UPS: Switched outlet group 2, Outlet Group 2,
has been commanded to turn off, sequenced. 0x0174
04/14/2022 01:46:00 Device UPS: Switched outlet group 1, Outlet Group 1,
has been commanded to turn off, sequenced. 0x0174
04/14/2022 01:46:00 Device UPS: The output power is turned off. 0x0114
04/14/2022 01:46:00 Device UPS: The graceful shutdown period has ended.
0x014F
04/11/2022 20:15:41 Device UPS: Self-Test passed. 0x01D2
04/11/2022 20:15:20 Device UPS: Self-Test started by front panel. 0x0137
04/07/2022 00:06:21 Device UPS: Self-Test passed. 0x01D2

You might also like