Professional Documents
Culture Documents
Lab 3 Three Phase Motor Rev For 10102023 014430pm
Lab 3 Three Phase Motor Rev For 10102023 014430pm
LAB EXPERIMENT # 3
OBJECTIVES:
Install and operate the forward and reverse of three phase induction motor circuit by
using magnetic contactors.
Understand the methods to reverse the rotation of motor.
Understand the effect of mechanical interlocking failure of magnetic contactors.
EQUIPMENT:
Electrical Circuit Fault Trainer.
Power Cable and Set of Test Leads.
Three Phase Induction Motor.
Multimeter.
THEORY:
The direction of rotation RI any three-phase motor can be reversed by changing any two-line
power supply of motor. Because the motor is connected to the power line regardless of which
direction is operated, a separate contactor is needed for each direction. As only one motor is in
operation, then only one overload relay is needed to protect the motor.
12
Lab No. 3
Figure 3.1 shown three pole magnetic contactor with two auxiliary contact and 220VAC coil.
Terminal 1-2, 3-4, 5-6 are main contact. Terminal 13-14, 53-54 are NO contact usually used to
latch the push button in control wiring and 21-22, 61-62 are NC contact witch usually used to
non-active other component when the system is run. A1-A2 is are coil of magnetic contactor. To
active the magnetic contactor the coil must be energized by 220 VAC.
Interlocking:
Interlocking prevents some action from taking place until some other action performed. In the
case of reversing starter, interlocking is used to prevent both contactors from being energized at
WKH same times. This would result in two of three-line V being shorted together. Interlocking
force V one contactor to be de-energized before the other one can be energized. Electrical
interlocking is accomplished by connecting the Normally Closed auxiliary contact on one
contactor in series with the coil of other contactor.
Figure 3.2 shows a Forward and Reverse of three phase motor by using Magnetic Contactor,
assumed that the “forward” push button is pressed. A current will release into magnetic
contactor coil KM1 through Normally Close KM2 and magnetic contactor KM1 will be
energized by an electromagnetic flux to change the contact position. The main contact of KM1
will close and connecting line voltage to the motor through the thermal overload. Auxiliary
contact NO of KM1 will be closed and latch the “forward” button after it is pressed.
At this time the “Reverse” button will not be active, due to the electrical and mechanical
interlocking systems used in this type of control circuit. If you will change the direction of
rotation, press” stop” button and let the motor stops running.
Reverse Operation:
When the “Reverse” push button is pressed, a current released into the Normally Close KM1 to
magnetic contactor coil KM2 and magnetic contactor KM2 will be energized by an
electromagnetic flux to change the contact position. The main contact of KM2 will close and
connecting line voltage to the motor through the thermal overload. Because of connections of
the L1 and L2 are reversed, the motor rotation will reverse. It is impossible for the reverse
contacts opened until “stop” button is pressed, due to the electrical and mechanical interlocking
systems used in this type of control circuit.
Toggle switches are installed to simulate the fault condition. The magnetic contactor may has
fault/ broken with coil, NO or NC or main contact. Magnetic contactor which broken may cause
of over current through the magnetic contactor.
13
Lab No. 3
Figure 3.2. Forward and Reverse of Three Phase Induction Motor Circuit by Using Magnetic
Contactor
Explanation:
14
Lab No. 3
5. Switch ON the ELCB, three phase MCB and observe the power lamp indicator.
Does the power lamp indicator light? Yes / No
Control circuit
1 L to N V
voltage input
2 A1 to A2 V
Coil KM1
A1 to A2 Ohm
16
Lab No. 3
16. Select the fault simulator switch F5 to “Faulty” position and observe the motor and
control lamp indicator.
By using multimeter check voltage of supply and coil of KM1 and write the data in the Table
3.2 column “Faulty”.
18. Switch OFF the single phase MCB.
19. By using multimeter check the coil resistance of KM1 and write the data in the Table 3.2
column “Faulty”. Analyze the data to find trouble shoot.
20. Switch F5 to “normal” position.
21. By using multimeter check the coil resistance and auxiliary contacts NO, NC continuity of
KM1. Write the data in the Table 3.3 column “Normal”.
22. Switch ON the single phase MCB. Press push button “A” to run the motor at forward rotation.
23. By using multimeter check voltage of Control Circuit Input supply, coil and auxiliary contact
of KM1 and write the data in the Table 3.3 column “Normal”.
24. Select the fault simulator switch F6 to “Faulty” position.
25. Press push button “A” to start the motor and hold the button.
27. By using multimeter check voltage of supply, coil, auxiliary contacts NO, NC of KM1 and
write the data in the Table 3.3 column “Faulty”.
28. Switch OFF the single phase MCB.
17
Lab No. 3
Table 3.3. Magnetic Contactor KM1 Measurement at Normal and Faulty Condition (NO Faulty)
29. By using multimeter check the coil resistance and auxiliary contacts NO, NC continuity of
KM1 and write the data in the Table 3.3 column “Faulty”. Analyze the data to find trouble
shoot.
30. Switch F6 to “normal” position.
31. By using multimeter check the coil resistance and auxiliary contacts NO, NC continuity of
KM1. Write the data in the Table 3.4 column “Normal”.
32. Switch ON the single phase MCB, Press push button “A” to run the motor at forward
rotation.
33. By using multimeter check voltage of supply, coil, auxiliary contact NO, NC of KM1 and
write the data in the Table 3.4 column “Normal”.
Table 3.4. Magnetic Contactor KM1 Measurement at Normal and Faulty Condition (NC Faulty)
18
Lab No. 3
40. After finishing this experiment, turn off the three phase MCB, ELCB and unplug the
power cable.
41. Remove all cable connections and return equipment to the respective place
CONCLUSION:
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
19