Notes:
1. Field Push button outside the dyke required for closing of the valve
2. Based on closing time requirement, bidder shall provide flow control
valve in actuator vent and with suitable locking arrangement applied
after proper setting.
3. These ROSOVs are part of SIS and used as Emergency Shut Down
Valves for tank overfill protection. Complete actuated valve assembly
shall be SIL3 capable as per IEC 61508, certified by third party
agencies like Exida/TUV. To calculate PFD (AVG) , the ESDV PFD and
SFF is required. Bidder shall submit the same with the technical offer
along with third party certifications and Functional Safety Manual.
4. All accessories like SOV shall also be SIL3 capable. Individual SIL
certification shall be submitted.
5. The actuator shall incorporate a safety feature such as a spring
cartridge to prevent the accidental release of spring tension during
servicing. The actuator spring shall be fully enclosed in a metal housing
and permanently treated to resist atmospheric corrosion. The type of
JOINT WORKING GROUP (IOCL/BPCL/HPCL)
a. Operating 230 V AC / 50 Hz
Voltage-
Energisation
b. Drop Out BTS
Voltage
c. Power
Consumption BTS
19 Coil
c. Insulation Standard
class
d. Cable Entry Class F or better as per IEC60085/IS1271
e. Cable Gland
f. Terminals ½” NPT(F)+Plug
g. Other
wetted SS 304, double compression
parts
h. Leakage Internal for 2.5sqmm conductors
Vendor‟s design
Zero Leakage
SPEC. ACC.
20 Mounting Solenoid valves with mounting brackets
21 Name Plate SS 304
22 Documents- Installation/ Operation instructions to be
Catalogue/Manual supplied
23 Certification CCOE/CMRI type approvals to be submitted
24 SS tubing As required
26 Cable Shall be supplied suitable for haz. area
glands/Reducers/Plug classification
s/Shrouds
27 Approved makes for ASCO/ Herion (Norgren)
SOV
Notes:
10. Flameproof Nickel plated brass, double compression cable glands shall be
provided. Cable glands shall be covered with shroud. Extra cable entry
shall be plugged with suitable E Exd Plug.