(C) F0032-00016 - Aa Instrument Drawings Data Sheet Catalog For CCW PUMP
(C) F0032-00016 - Aa Instrument Drawings Data Sheet Catalog For CCW PUMP
Status: Approved
For Review
EPC CONTRACTORS
I HI –TESSC–CTCI –DHI CONSORTI UM
SUPPLI ER
DOCUMENT TI TLE
I nstrument Drawi ngs & Data Sheet & Catal og for CCW PUMP
ELEMENT FEATURES
1 Use Temperature Measuring For Bearing
2 Type Pt 1 00 Ohm at 0 ℃
3 Connection Dual
4 Number of Wire 6 Wire
5 Protecting Tube Stainless Steel
6 Element insulator Ceramic Tube
7 Operating Temperature 0~200℃
8 Accuracy Class B
9 Mouting method Movable Thread
1 0 Codes & Standard IEC 60751
1 1 Manufacturer WISE
12 Motor Bearing Housing_Drive Side / 1 EA
Installation / Q'ty
13 Motor Bearing Housing_Non Drive Side / 1 EA
14
15
16
17
* HYOSUNG DOC. No. ELI6200046
* HYOSUNG ITEM No. -
NOTE : 1 . Others Not mentioned in the specification shall be in accordance with HYOSUNG standard.
2. Shape may differ from the actual.
Extension lead wire thermocouple and
resistance temperature detector
Model : R300 series
Service intended
This type of detector does not use terminal head, rather it
directly connects to an indicator or a transmitter. It is very
useful where the distance between measuring parts and
the location of its head is too far. The measuring parts and
its head can be connected by using an extension wire.
Extension wire can be selected according to its
installation site condition, its protection shape of armored
tube, and its wire covering material.
Standard features
■ R.T.D.
Class A : ± (0.15 + 0.002 l t l)
Basic outline drawing Class B : ± (0.3 + 0.005 l t l)
■ R.T.D.
3.2, 4.8, 6.4 and 8.0 mm
671
Main order Ordering information
3. Element
8. Connection type
K K (0.75) 3 T (0.4)
Refer to mounting table (12th and 13th character)
XX
J J (0.75) 4 E (0.4)
5 347SS
6 321SS
7 316L SS
9 Other
D9 3.2 (Sheath)
E9 4.8 (Sheath)
F9 6.4 (Sheath)
G9 8.0 (Sheath)
H9 9.5 (Sheath / TC only)
F8 6.4 (Tube)
G8 8.0 (Tube)
J0 10.0 (Tube)
K9 12.0 (Tube)
M9 15.0 (Tube)
1 2 3 4 5 6 7 8 9 10
Sample
R311 P K 1 F9 9 X XX X 1A ordering code
672
Mounting, connection type and insert length table - 11th thru 14th characters
Fixed thread
lag length
Nipple length
673
2. WINDING TEMPERATURE
SENSORS FOR MOTOR
REV DATE Description of Revision
SPECIFICATIONS 0 8-Sep-20 Original Issued
OF 1
WINDING TEMPERATURE DETECTOR 2
3
ELEMENT FEATURES
1 Use Temperature Measuring For Stator Coil
2 Type Pt 1 00 Ohm at 0 ℃
3 Connection Dual
4 Number of Wire 6 Wire
5 Body Material Epoxy Molding
6 Rated Current 5mA
7 Insulation Class Class F = 1 55℃ (31 1 ℉)
8 Accuracy Class B
9 Dielectric Strength 1 .5kV at 60Hz
1 0 Insulation Class JIS C 4003F
1 1 Codes & Standard JIS C 1 604, Other Are Based on JEM 1 252
1 2 Manufacturer SMG
1 3 Model No. TX40B PT1 00B 3M6
1 4 Installation / Q'ty Inside of Coil Slot (Hottest spot) / 2 EA per Phase
15
16
* HYOSUNG DOC. No. ELI61 00071
* HYOSUNG ITEM No. DMB1 000669
NOTE : 1 . Others Not mentioned in the specification shall be in accordance with HYOSUNG standard.
2. Shape may differ from the actual.
04
3. TEMPERATURE SENSORS
TRANSMITTER
Data Sheet Rail mounted Temperature Transmitter
DS/TTR200-EN
TTR200
HART,
Pt1 00 (RTD), thermocouples,
Electrical isolation
Input
- Resistance thermometers
- Thermocouples
- Resistance-type transmitter (0 ... 5000 )
- Voltages, mV transmitter (-1 25 ... 1 1 00 mV
Output
- 2-wire technique
- 4 ... 20 mA temperature linear
- HART signal
Measurement error
- 0.1 K
Continuous sensor and self-monitoring
- 2-function LEDs
- Supply voltage monitoring
- Wire break and corrosion monitoring (NE 89)
Unit software acc. to NE 53
Approvals for explosion protection
- Intrinsic Safety: ATEX EEx ia (Zone 0)
- non-incendive: ATEX EEx n A
Configuration
- FDT/DTM
- SMART VISION DSV401
- EDD
2-function LEDs
Sensor matching
Hardware write protection
Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN
HART, Pt1 00 (RTD), thermocouples, Electrical isolation
Contents
1 Technical data......................................................................................................................................................3
1 .1 Input................................................................................................................................................................3
1 .2 Output.............................................................................................................................................................3
1 .3 Power supply (polarity safe)......................................................................................................................... 4
2 General information ............................................................................................................................................4
2.1 Ambient conditions .........................................................................................................................................4
2.2 Electromagnetic compatibility.........................................................................................................................4
2.3 EMI/RFI shielding ...........................................................................................................................................4
2.4 Measuring accuracy .......................................................................................................................... 5
2.5 Operating conditions ......................................................................................................................................7
2.6 Mechanical design.................................................................................................................... 8
3 Communication ...................................................................................................................................................8
4 Explosion-protection relevant information.......................................................................................................8
4.1 TTR200-E1 (intrinsically safe) ....................................................................................................................8
4.2 TTR200-E2 (non-incendive) .......................................................................................................................9
5 Approvals .............................................................................................................................. 9
6 Terminal connection diagrams ........................................................................................................................1 0
7 Dimensional drawings ......................................................................................................................................1 0
8 Ordering information.........................................................................................................................................1 1
9 Order form configuration............................................................................................................................... 1 2
2
Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN
HART, Pt1 00 (RTD), thermocouples, Electrical isolation
1 Technical data
1 .1 Input 1 .2 Output
Transmission characteristics
1 .1 .1 Resistance temperature linear
RTD resistance thermometer resistance linear
Pt1 00 in acc. with DIN IEC 60751 , JIS, MIL, Ni in acc. with voltage linear
DIN 43760, Cu
Output signal
(for additional information, see the section "Measuring accuracy")
Configurable 4 ... 20 mA (standard)
Resistance measurement
Configurable 20 ... 4 mA
0 500
(NE43 dynamic range: 3.8 ... 20.5 mA)
0 5000
Simulation mode
Sensor connections
3.5 ... 23.6 mA
2-, 3-, 4-wire circuit
Induced current consumption
Connecting cables
< 3.5 mA
2-, 3-, 4-wire max. sensor line resistance (RW) for each wire 50
Maximum output current
in acc. with NE 89 (March 2003);
23.6 mA
(3-wire balanced, 2-wire circuit compensation up to 1 00 sensor
Configurable error current signal
total line resistance)
override 22 mA (20.0 23.6 mA)
Measurement current
underdrive 3.6 mA (3.5 4.0 mA)
< 300 µA
Sensor short-circuit
< 5 (for RTD)
Sensor wire break (temperature resistance measurement 2-, 3-,
4-wire)
Measuring range 0 ... 500 > 0.6 ... 1 0 k
Measuring range 0 ... 5 k > 5.3 ... 1 0 k
Corrosion detection in accordance with NAMUR NE 89
3-wire resistance reading > 50
4-wire resistance reading > 50
1 .1 .2 Thermocouples/Voltages
Types
B, E, J, K, L, N, R, S, T, U, C, D
Voltages
-1 25 ... 1 25 mV
-1 25 ... 1 1 00 mV
Connecting cables
Max. sensor line resistance (RW) for each line 1 .5 k , total 3 k
Sensor wire break monitoring in accordance with Namur NE 89
pulsed with 1 µA outside the measurement interval
Thermocouple measurement 5.3 ... 1 0 k
Voltage measurement 5.3 ... 1 0 k
Input resistance
> 10 M
Internal reference junction
Pt1 000, DIN IEC 60751 Cl. B
(no jumpers necessary)
Sensor matching
via single point (offset adjustment)
via two point adjustment
Sensor fault signaling
RTD sensor: Short circuit and wire break
Linear resistance measurement: Wire break
Thermocouple: Wire break
Linear voltage measurement: Wire break
3
Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN
HART, Pt1 00 (RTD), thermocouples, Electrical isolation
2 General information
Electrical isolation 3.5 kV DC (approx. 2.5 KV AC) 60 s
(input/output)
MTBF time 28 years at 60 °C ambient
temperature
Input filter 50 / 60 Hz
Switch-on delay < 1 0 s (I a 3.6 mA during starting
cycle)
Warm-up time 5 min.
Ramp-up time t90 400 1 000 ms
Readingupdated1 ) 1 0/sec
Output filter Digital filter 1 st order: 0 ... 1 00 s
1) depending on sensor type and sensor circuit
4
Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN
HART, Pt1 00 (RTD), thermocouples, Electrical isolation
Total accuracy = digital measuring accuracy [°C] + (D/A measuring accuracy [%] x I conf. measuring span [°C] I /1 00% )
(refer to the block diagram on next page)
Example 1 :
Pt1 00 (IEC 60751 ), conf. measuring range 0 ... 1 00 °C, conf. measuring span = measurement end measurement start = 1 00 °C
Digital measuring accuracy: ± 0,08 °C
D/A measuring accuracy ± 0.05% x (1 00 °C/1 00%) = ± 0,05 °C
Total accuracy: Digital accuracy + D/A accuracy; ± 0,08 °C + (± 0,05 °C) = ± 0,1 3 °C
Example 2:
Thermocouple type K, conf. measuring range 0 ... 1 000 °C, conf. measuring span = measurement end measurement start = 1 000 °C
Digital measuring accuracy: ± 0,35 °C
D/A measuring accuracy ± 0.05% x (1 000 °C/1 00%) = ± 0,50 °C
4)
Total accuracy : Digital accuracy + D/A accuracy; ± 0,35 °C + (± 0,50 °C) = ± 0,85 °C
Long-term drift
1)
± 0.05 °C or ± 0.05% per year, the larger value applies.
5
Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN
HART, Pt1 00 (RTD), thermocouples, Electrical isolation
ó ë ó
ß Ü
î
ç ß
Ü ß
õ õ
íôë µÊ ÜÝ
ï ø¢îôë µÊ ßÝ êð÷ í
ê é
è
ßððîðî
Fig. 2
1 24-bit A/D converter 6 Digital measuring accuracy
2 Microcontroller 7 D/A measuring accuracy
3 1 6-bit D/A converter 8 Overall measuring accuracy
4 HART signal 9 Terminal 1 1 , measurement of 4 20 mA output current without
5 Load (observe voltage drop, refer to the section "Terminal opening / interrupting the current loop (internal resistance
connection diagrams") ammeter < 1 5 )
6
Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN
HART, Pt1 00 (RTD), thermocouples, Electrical isolation
Supply voltage influence/load influence: within the specified limits for the voltage/load the total influence is less than 0.001 % per volt
Common-mode interference no influence up to 1 00 V Veff (50 Hz) or 50 VDC
Ambient temperature influence: based on 23 °C / 73.4 °F (ambient temperature range: -40 ... 85 °C / -40 °F ... 1 85 °F)
1)
Sensor Ambient temperature influence Ambient temperature influence
For 1 °C / 1 .8 °F dev. to 23 °C / 73,4 °F For 1 °C / 1 .8 °F dev. to 23 °C / 73,4 °F
for digital readings for D/A converter
Voltage measurement
-1 25 ... 1 25 mV ± 1 .5 µV ± 0.003 %
-1 25 ... 1 1 00 mV ± 1 5 µV ± 0.003 %
1)
percentages refer to the configured measuring span
ME - Measuring end, MS - Measuring span
Example 1
Pt1 00 configured measuring range 0 ... 1 00 °C, (measuring span 1 00 °C), ambient temperature 33 °C
Dev. from standard temperature: 33 ... 23 °C (reference) = 1 0 °C
Affect of ambient temperature on digital measurement: 1 0 °C x ± 0.004 °C / °C = ± 0.04 °C
Affect of ambient temperature on D/A converter: 1 0 °C x (± 0.003 % / °C) x (1 00 °C / 1 00 %) = ± 0.03 °C
Example 2
TC type K, conf. measuring range 0 ... 1 000 °C, (measuring span 1 000 °C), ambient temperature 33 °C
Measuring start 0 °C corresponds to 0.0 mV; measuring end = 1 000 °C corresponds to 41 .6 mV; measuring span = 1 000 °C or 41 .6 mV
Dev. from standard temperature: 33 ... 23 °C (reference) = 1 0 °C
Affect of ambient temperature on digital measurement: 1 0 °C x [(± 0.001 % x 41 .6 mV / 41 .6 mV) + (1 00% x ± 0.009 °C / 1 000°C)] x
(1 000°C / 1 00%)] / °C = ± 0.1 9 °C
Affect of ambient temperature on D/A converter: 1 0 °C x [± 0.003 % x 1 000 °C / 1 00 %] / °C = ± 0.3 °C
7
Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN
HART, Pt1 00 (RTD), thermocouples, Electrical isolation
3 Communication
HART protocol version 5 Diagnostic signaling
The system is registered with the HART Communication Foundation. Optical via LEDs, red/green
(red LED: sensor & unit fault signaling
ξ ã îëð Ѹ³ö
green LED: supply voltage display)
í Over/underdrive acc. to NE43
HART diagnostic
ÌÌÎîðð
ÚÍÕ
Ó±¼»³ Diagnostic information (NE1 07)
ØßÎÌ
Sensor error (wire break or short circuit)
Device error
ï
î ßððîï î
Over/under measuring range
Simulation activated
* if necessary
Fig. 3
1 Hand-held terminal 3 Ground connection
2 FDT/DTM technology (optional) 4 Explosion-protection relevant information
4 Power supply (process
interface) 4.1 TTR200-E1 (intrinsically safe)
Operating modes Approved for use in zone 0.
Point-to-point communication mode: standard (general address
0) Designation:
Multidrop mode (addressing 1 ... 1 5) II 1 G EEx ia IIC T6 (Zone 0)
II 2 (1 ) G EEx [ia] ib IIC T6 (zone 1 [0])
Configuration options and tools
II 2 G (1 D) Ex [iaD] ib IIC T6 (zone 1 [20])
FDT/DTM technology via TTX200 DTM driver
DSV401 (SMART VISION)
Important
EDD - via TTX200 EDD driver
The Ex or ignition-proof designation is provided on the name
Configuration parameters plate.
Measurement type
Sensor type, connection type EC prototype test certificate: Refer to PTB 05 ATEX201 7 X.
Fault signaling
Flow range
Temperature table
General information, e.g., TAG number Temperature Permissible ambient temperature range
class Device category 1 Device category 2 use
Damping
Signal simulation of output use
See "Order form configuration" T6 -40 44 °C -40 56 °C
T5 -40 56 °C -40 71 °C
Write Protection T4, T3, T2, T1 -40 60°C -40 85 °C
Hardware write protection via DIP switch
8
Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN
HART, Pt1 00 (RTD), thermocouples, Electrical isolation
Safety specifications
Intrinsically safe EEx ia IIC explosion protection
Supply circuit Measurement current Measurement current
circuit / passive circuit / active
transducer (RTD) transducer (RTD)
Max. voltage U i = 30 V U o = 6,5 V U o = 1 ,2 V
Short-circuit current I i = 1 30 mA I o = 25 mA I o = 50 mA
Max. power Pi = 0,8 W Po = 38 mW Po = 60 mW
Internal inductance Li = 0,5 mH Li = 0 mH Li = 0 mH
Internal capacitance Ci = 5 nF Ci = 49 nF Ci = 49 nF
Maximum permissible Lo= 5 mH Lo = 5 mH
external inductance
Maximum permissible Co= 1 ,55 µF Co= 1 ,05 µF
external capacitance
Designation:
II 3 G EEx n A II T6
Important
The Ex or ignition-proof designation is provided on the name
plate.
T6 -40 56 °C
T5 -40 71 °C
T4 -40 85 °C
5 Approvals
CE mark:
The TTR200 meets all requirements for the CE mark in accordance
with IEC 61 326 (2006).
Ignition protection:
The TTR200 complies with the requirements of ATEX directive 94/9
EC. For additional information, refer to the section "Explosion-
protection relevant information").
9
Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN
HART, Pt1 00 (RTD), thermocouples, Electrical isolation
Note
Terminal 1 1 : Measurement of 4 20 mA output current without opening / interrupting the current loop (see chapter 2.4.1 Block diagram).
7 Dimensional drawings
10
Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN
HART, Pt1 00 (RTD), thermocouples, Electrical isolation
8 Ordering information
Rail mounted Temperature Transmitter Variant digit No. 1 -7 8 9 10 Code
TTR200 Catalog No. TTR200-
Standard configuration:
Pt1 00 3-wire circuit, 0 ... 1 00 °C, Damping off, rising characteristic
Override for sensor or device errors (>= 22 mA)
Explosion protection
No ignition protection Y 0
Communication protocol
HART H
11
Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN
HART, Pt1 00 (RTD), thermocouples, Electrical isolation
Configuration Selection
DIN IEC 60 751 RTD Pt1 0 Pt50 Pt1 00 (standard)
Cu Cu1 0 Cu1 00
Linear resistance 0 500
measurement 0 5000
IEC 584 Thermocouple Type K Type J Type N Type R Type S Type T
Type E Type B
12
4. VIBRATION SENSORS FOR
PUMP & MOTOR
330400 and 330425 Accelerometer Acceleration
Transducers
Bently Nevada* Asset Condition Monitoring
Description
These accelerometers are intended for critical machinery applications where
casing acceleration measurements are required, such as gear mesh monitoring.
The 330400 is designed to address the requirements of American Petroleum
Institute Standard 670 for accelerometers. It provides an amplitude range of 50
g peak and a sensitivity of 100 mV/g. The 330425 is identical except it provides a
larger amplitude range (75 g peak) and a sensitivity of 25 mV/g.
Caution
If housing measurements are being made for overall protection of the machine,
thought should be given to the usefulness of the measurement for each
application. Most common machine malfunctions (imbalance, misalignment,
etc.) originate at the rotor and cause an increase (or at least a change) in rotor
vibration. In order for any housing measurement alone to be effective for overall
machine protection, a significant amount of rotor vibration must be faithfully
transmitted to the bearing housing or machine casing, or more specifically, to
the mounting location of the transducer.
Page 1 of 8
Specifications
Broadband
Parameters are specified from +20 to +30 °C (+68 to Noise Floor (10
+86 °F) and 100 Hz unless otherwise indicated. Hz to 15 kHz):
Note: Operation outside the specified limits may result in false 0.098 m/s2 (0.01 g) rms.
readings or loss of machine monitoring.
Both Units
Electrical Frequency
330400 Response:
Sensitivity: 10 Hz to 15 kHz
10.2 mV/m/s2 (100 mV/g) ±5%. (600 cpm to 900,000 cpm) ±3dB;
Acceleration 30 Hz to 10 kHz
range:
(1800 cpm to 600,000 cpm) ±10%
490 m/s2 (50 g) peak overall
acceleration within the 10 Hz to Temperature
15 kHz frequency span. Vibration Sensitivity:
at frequencies above 15 kHz, -11% to +3% typical over the
especially at the transducers operating temperature range.
resonance will significantly
decrease this range. Transverse
Sensitivity:
Amplitude
Linearity: Less than 5% of axial.
Page 2 of 8
For serial numbers Ex nL IIC T4
AEx nA IIC T4
NOT preceded by the
Class I, Div 2 Groups A, B, C & D
letter “G” (shipped prior
When installed per dwg 167538
to April 2004):
T4 @ -40°C ≤ Ta ≤ 100°C
980 mm/s2/µstrain (0.100
g/µstrain) without Mounting Base
(API adapter);
4.9 mm/s2/µstrain (0.0005 European/ATEX
g/µstrain) with Mounting Base
(API adapter) supplied with the
accelerometer. II 1 G
Ex ia IIC T4 Ga
Note: Bently Nevada recommends
T4 @ -55°C ≤ Ta ≤ 121°C
installing with the Mounting base to
minimize base strain sensitivity for serial
numbers NOT preceded by the letter “G”.
II 3 G
Maximum cable Ex nA IIC T4 Gc
length: T4 @ -55°C ≤ Ta ≤ 121°C
305 metres (1000 ft) with no
degradation of signal.
IECEx
Power requirements:
Ex ia IIC T4 Ga
Input Voltage Ex nA IIC T4 Gc
-24 ± 0.5 Vdc. T4 @ -55°C ≤ Ta ≤ 121°C
Bias Current: BRAZIL
2 mA nominal. Ex ia IIC T4 Ga
Output Bias T4 @ -40°C ≤ Ta ≤ 100°C
Voltage:
-8.5 ± 0.5 Vdc. Country specific approvals may be available.
Please consult your local Customer Care
Grounding:
Representative for more information.
Case isolated.
Hazardous Area Approvals
For further certification and approvals information please visit the
Multiple approvals for hazardous following website:
areas certified by Canadian www.ge-mcs.com/bently
Standards Association (CSA) in
North America and by LCIE in
Europe.
North America
Ex ia IIC T4
AEx ia IIC T4
Class I, Div 1 Groups A, B, C & D
Class II, Groups E, F, and G
Class III
When installed per dwg 167538
T4 @ -40°C ≤ Ta ≤ 100°C
Page 3 of 8
Compliance and Certification Physical
EMC Weight (no cable):
Standards: 99 g (3.5 oz), typical
EN 61326-2-1 Test configurations,
Diameter:
operational conditions and
performance criteria for sensitive 23 mm (0.93 in).
test and measurement equipment
for EMC unprotected applications Height:
Page 4 of 8
Interconnect Cables
Part Number-AA 16710
Accessories
The following are standard lengths
Feet Metres (approx.) 127088-01
6 1.8 330400 and 330425
8 2.4 Accelerometer Operations
10 3.0 Manual.
12 3.6
15 4.5
00531080
17 5.0
20 6.0 Mating connector for 330400 and
25 7.6 330425 Accelerometers.
30 9.0 37439-01
33 10.0
50 15.2 For use with serial numbers NOT
99 30.0 preceded with the letter “G”.
NOTE: Non-standard/custom lengths Mounting Base, ¼-28 to ¼-28.
can also be ordered at additional cost Reduces base strain sensitivity.
37439-02
For use with serial numbers NOT
preceded with the letter “G”.
130539 Mounting Base, M8X1 to M8X1.
3-conductor shielded 18 AWG (1.0 Reduces base strain sensitivity.
mm 2) cable with 3-socket plug 43217
and fluorosilicone elastomer boot
at one end, terminal lugs at the Accelerometer Mounting Kit used
other end. Minimum length of 2.0 with extension part number
ft (0.6 m), maximum length of 99 108576-01 and O-ring part
ft (30 m). A manual is available to number 04290422 to allow room
assist with installation of this for the 330400 or 330425
cable (part number 133080-01). accelerometer.
16925 (See separate datasheet, p/n
141630-01.)
3-conductor shielded 22 AWG (0.5
mm 2) cable with 3-socket plug at
one end, terminal lugs at the
other end. Minimum length of 2.0
ft (0.6 m), maximum length of 99
ft (30 m).
Page 5 of 8
Graphs and Figures
Page 6 of 8
25
20
dB referenced to 100 Hz
15
10
-5
10 100 1000 10000 100000
Frequency (Hz)
0.5
dB referenced to 100 Hz
-0.5
-1
-1.5
-2
10 100 1000 10000
Frequency (Hz)
Page 7 of 8
5. PRESSURE GAUGE
FOR PUMP
Sheet : 1 of 1
■ SEPARATED ASSEMBLY □ R.T.D ONLY 18. THERMOCOUPLE ISA TYPE Pt 100 ohm at 0℃
9. INPUT SIGNAL □ T/C ( E ) TYPE ■ RTD ( Pt 100 ohm ) 27. OPTION ■ A : NIPPLE & UNION
14. COVER ■ SCREWED CAP & CHAIN □ 30. MATERIAL □ SS304 □ SS316 □
15. ENCLOSURE ■ WEATHER PROOF □ EXPLOSION PROOF 31. MOUNTING SIZE
■ ACCURACY A
LATER 4 LATER N/A N/A - - 95 100 0 ~ 150 Pump Bearing Housing Temperature Measurement A,B,C
B : SPRING LOAD
C : OILSEALING
Liquid Filled Pressure Gauge
Pressure Gauge
Summary
This gauge is proper for measuring the
pressure in place where mechanical
Differential
its interior devices are precipitated in
Switch
silicon liquid and by doing this, it is able
to suppress vibration which is used by the
viscosity resistance of liquid. This pressure
gauge guarantees its performance and the
life span as it has relatively better durability
than other general pressure gauges
Pressure Gauge
Accessories of
because it prevents abrasion of the interior
devices using lubricative fluid.
SS-3071 SS-3074
Safety Management Production Specification
Thermometer Switch
▶ Range
Thermometer &
- Do not give impact during the ▶ Diameter
transportation, installation and usage · 60,75,100,150mm -0.1~2MPa
60mm
- Be sure to install pressure gauge to be ▶ Accuracy -0.1~0MPa
horizontal and vertical. · 60,75mm:±1.5%ofFullScale 75mm
· 100,150mm:±1.0%ofFullScale 0~35MPa
Thermocouple
· Fluctuatingpressure:60%ofFullScale 150mm
& R.T.D
0~200MPa
- Various plants such as petrochemistry, ▶ Working Temperature
· Ambient:-20~65℃
etc.
· Fluid:-20~80℃
- Oil pressure press, etc. where a lot of
vibration and pulsation exist ▶ Degree of protection
· IP67
- Where a lot of temperature changes exist
Thermowell
- For shipbuilding and power plant
- For industrial use, special fluid line, etc.
Product Specification
· B-Type(Surfacetype)
· D-Type(Flushmountingtype)
+ Cover + Element
· BD-Type(Panelattachmenttype)
· STS304 · STS304,STS316
· Slip-on-Fit · Ctypebourdontube,helicaltypebourdontube
+ Pointer
· Aluminum
+ Connection + Movement
Indicator etc.
· Blackcoating
· STS316 · STS304
· PF,PT↔1/4,3/8
· UNF7/16 + Dial + Option
· Aluminum
· Bracket
· Whitecolorcoating
+ Window · Throttles
· Black(MPa),red(bar)gradationsandcharacters
· Temperedsafetyglass, · Accessories
Technical data
Laminatedsafetyglass
www.mykins.co.kr 73
Liquid Filled Pressure Gauge
Pressure Gauge
Model No. Conn'n (d) ØD ØD1 ØD2 b n t L2 h ØC(OB) ØH
UNF7/16
SS-3071&SS-3072 NPT&PT,PF1/8 72 64 84 12 - (39) 12 (48) 4.5 72
NPT&PT,PF1/4
60mm
UNF7/16
SS-3073&SS-3074 NPT&PT,PF1/8 72 64 90 - 18 (39) 12 (20) 4.5 81
Switch
UNF7/16
SS-3071&SS-3072 NPT&PT,PF1/4 87 77 100 14 - (40) 14 (54) 4.5 88
NPT&PT,PF3/8
75mm
UNF7/16
SS-3073&SS-3074 NPT&PT,PF1/4 87 77 107 - 22 (40) 14 (17) 4.5 97
Pressure Gauge
Accessories of
NPT&PT,PF3/8
UNF7/16
NPT&PT,PF1/4
SS-3071&SS-3072 114 100 128 17 - (46) 17 (76) 5.5 115
NPT&PT,PF3/8
NPT&PT,PF1/2
Thermometer Switch
100mm
UNF7/16
Thermometer &
NPT&PT,PF1/4
SS-3073&SS-3074 114 100 135 - 33 (46) 17 (26) 5.5 120
NPT&PT,PF3/8
NPT&PT,PF1/2
UNF7/16
NPT&PT,PF1/4
SS-3071&SS-3072 168 152 188 17 - (50) 17 (100) 5.5 174
NPT&PT,PF3/8
Thermocouple
NPT&PT,PF1/2
& R.T.D
150mm
UNF7/16
NPT&PT,PF1/4
SS-3073&SS-3074 168 152 188 - 33 (50) 17 (26) 5.5 174
NPT&PT,PF3/8
NPT&PT,PF1/2
*()Themeasurementintheblanketisapproximate.
Thermowell
Transmitter
Indicator etc.
Technical data
www.mykins.co.kr 75
6. BEARING TEMPERATURE
SENSORS AND
TRANSMITTER FOR PUMP
Sheet : 1 of 1
□ MATERIAL □
4. CASE □ CAST IRON □ ALUMINUM □ PHENOLIC 15. CONNECTION □ 1/4" ■ 1/2" □ 3/8"
PROTECTION □ MATERIAL
Standard
symbols of
Indicator etc.
sheath resistance
temperature
detectors
Technical data
'LYLVLRQV
Switch
Pressure Gauge
Accessories of
Thermometer Switch
Thermometer &
Response Time of Sheath Resistance Bulb
Thermocouple
Thee "t" Constants (63.2%) when RESIMIC is immersed into lOO℃ (boiling water) Form O℃(ice bath)
& R.T.D
Ø3.2 less then 2 sec.
Ø4.8 less then 4 see
Ø6.4 less then 6 sec.
Ø8.0 less then 11
Thermowell
Temperature (℃)
100
Transmitter
63.2
Ø8.0
Ø6.4
Indicator etc.
Ø4.8
Ø3.2
Technical data
0 5 10 15 20 25 30 35 40 45 50 55 60
Time (Sec)
www.mykins.co.kr 283
Ordering
Information
Model No.
SS-5040 Series
6HH7DEOH
'RXEOH
Sheath Resistance Temperature Detectors
PP
PP
PP
PP
www.mykins.co.kr
285
Accessories of Differential
Technical data Indicator etc. Transmitter Thermowell Thermocouple Thermometer & Pressure Gauge Pressure Gauge & Pressure Gauge
& R.T.D Thermometer Switch
Switch
Sheath Resistance Temperature Detectors
Model No. | SS-5041 W Model No. | SS-5042W Model No. | SS-5042W-1 Model No. | SS-5042W-2
( Sheath ) ( Sheath ) ( Sheath ) ( Sheath )
Pressure Gauge &
Differential
Switch
Pressure Gauge
Accessories of
Thermometer Switch
Thermometer &
Model No. | SS-5042W-3 Model No. | SS-5042W-4 Model No. | SS-5043W Model No. | SS-5043W-1
( Sheath ) ( Sheath ) ( Sheath ) ( Sheath )
Thermocouple
& R.T.D
Thermowell
Transmitter
Model No. | SS-5044W-1 Model No. | SS-5044W-1 -1 Model No. | SS-5044W-2 Model No. | SS-5044W-2-1
( Sheath ) ( Sheath Spring Load ) ( Sheath ) ( Sheath Spring Load )
Indicator etc.
Technical data
Applications
■ ■ Process■industry
■ ■ Machine■building■and■plant■construction
Special features
■ ■ TÜV■certified■SIL■version■for■protective■equipment■
developed■per■IEC■61 508■(option)
■ ■ Configurable■with■almost■all■soft-■and■hardware■tools
■ ■ Universal■for■the■connection■of■1 ■or■2■sensors
-■Resistance■thermometer■/■resistance■sensor
-■Thermocouple■/■mV■sensor
-■Potentiometer
■ ■ Signalling■in■accordance■with■NAMUR■NE43,■sensor-
break■detection■in■accordance■with■NE89,■EMC■in■
accordance■with■NE21 Fig. left: Digital temperature transmitter model T32.1 S
■ ■ Isolation■voltage■AC■1 200■V■between■sensor/current■loop Fig. right: Digital temperature transmitter model T32.3S
Description
These■temperature■transmitters■are■designed■for■universal■ The■T32■transmitter■also■has■additional■sophisticated■
use■in■the■process■industry.■They■offer■high■accuracy,■ supervisory■functionality■such■as■monitoring■of■the■sensor■
galvanic■isolation■and■excellent■protection■against■ wire■resistance■and■sensor-break■detection■in■accordance■
electromagnetic■influences■(EMI).■Via■HART®■protocol,■the■ with■NAMUR■NE89■as■well■as■monitoring■of■the■measuring■
T32■temperature■transmitters■are■configurable■(interoperable)■ range.■Moreover,■this■transmitter■has■comprehensive■cyclic■
with■a■variety■of■open■configuration■tools.■In■addition■to■the■ self-monitoring■functionality.
different■sensor■types,■e.g.■sensors■in■accordance■with■DIN■
EN■60751 ,■JIS■C1 606,■DIN■43760,■IEC■60584■or■DIN■4371 0,■ The■dimensions■of■the■head-mounted■transmitter■match■
customer-specific■sensor■characteristics■can■also■be■defined,■ the■Form-B■DIN■connecting■heads■with■extended■mounting■
through■the■input■of■value■pairs■(user-defined■linearisation). space,■e.g.■WIKA■model■BSS.
Through■the■configuration■of■a■sensor■with■redundancy■(dual■ The■rail-mounted■transmitters■can■be■used■for■all■standard■
sensor),■on■a■sensor■failure■it■will■automatically■change■over■ rack■systems■in■accordance■with■IEC■6071 5.
to■the■working■sensor.
The■transmitters■are■delivered■with■a■basic■configuration■or■
Furthermore■there■is■the■possibility■to■activate■Sensor■ configured■according■to■customer■specifications.
Drift■Detection.■With■this,■an■error■signal■occurs■when■the■
magnitude■of■the■temperature■difference■between■sensor■1 ■
and■sensor■2■exceeds■a■user-selectable■value.
1 )■ Other■units■e.■g.■°F■and■K■possible 1 0) Based■on■a■potentiometer■value■of■50■%
2)■ Measuring■deviation■(input■+■output)■at■ambient■temperature■23■°C■±3■K,■without■ 1 1 )■ Based■on■400■°C■MV■with■cold■junction■compensation■error
influence■of■lead■resistance;■example■calculation■see■page■4 1 2)■ Based■on■1 000■°C■MV■with■cold■junction■compensation■error
3) Temperature■coefficient■(input■+■output)■per■°C 1 3)■ Based■on■measuring■range■0■...■1 ■V,■400■mV■MV
4)■ x■configurable■between■1 0■…■1 000 1 4) The■transmitter■can■be■configured■below■these■limits■but■not■recommended■due■to■loss■
5)■ Based■on■3-wire■Pt1 00,■Ni1 00,■1 50■°C■MV of■accuracy.
6)■ Based■on■1 50■°C■MV 1 5) Specification■valid■only■for■measuring■range■between■450■...■1 820■°C
7) In■ambient■temperature■range■-40■…■+85■°C
bold: basic configuration
8)■ Based■on■a■sensor■with■max.■5■kΩ
italic: This sensors are not allowed at option SIL (T32.xS.xxx-S)
9)■ Rtotal:■1 0■...■1 00■kΩ
MV■=■Measuring■value■(temperature■measuring■values■in■°C)
Note:
The■transmitter■can■be■configured■below■these■limits■but■not■
recommended■due■to■loss■of■accuracy.
Input Measuring deviation Average temperature coefficient (TC) Connection lead Long-term
per DIN EN 60770, 23 °C ± 3 K for each 1 0 K ambient temperature effects stability 1
change in the range -40 ... +85 °C 1 ) year
Resistance■ -200■°C■≤■■MW■≤■200■°C:■±0.1 0■K ±(0.06■K■+■0.01 5■%■MW)
thermometer■ MW■>■200■°C:■±(0.1 ■K■+■0.01 ■%■| MW-200■K| )■ 4-wire:■no■effect
Pt1 00/JPt1 00/ 3) ■■■■■■■■■(0■to■50■Ω■each■wire) ±60■mΩ■or■
Ni1 00■2)■ 3-wire:■±0.02■Ω■/■1 0■Ω 0.05■%■of■MV, ■
Resistance■ ≤■890■Ω:■ 0.053■Ω■6)■or■0.01 5■%■MV■7) ±(0.01 ■Ω■+■0.01 ■%■MV) ■■■■■■■■■(0■to■50■Ω■each■wire) whichever■is■
sensor■5) ≤■21 40■Ω:■ 0.1 28■Ω■6)■or■0.01 5■%■MV■7) 2-wire:■resistor■of■the■ greater
≤■4390■Ω:■ 0.263■Ω■6)■or■0.01 5■%■MV■7) connection■leads■4)
≤■8380■Ω:■ 0.503■Ω■6)■or■0.01 5■%■MV■7)
Potentiometer■5) Rpart/Rtotal■is■max.■±0.5■% ±(0.1 ■%■MV)
Thermocouples -1 50■°C■<■MV■<■0■°C:■±(0.3■K■+■0.2■%■| MV| ) Type■E:■MV■>■-1 50■°C:■±(0.1 ■K■+■0.01 5■%■| MV| )
■ Type■E,■J MV■>■0■°C:■±(0.3■K■+■0.03■%■MV) Type■J:■MV■>■-1 50■°C:■±(0.07■K■+■0.02■%■| MV| )
■ Type■T,■U -1 50■°C■<■MV■<■0■°C:■±(0.4■K■+■0.2■%■| MV| ) -1 50■°C■<■MV■<■0■°C:■±(0.07■K■+■0.04■%■MV)
MV■>■0■°C:■±(0.4■K■+■0.01 ■%■MV) MV■>■0■°C:■±(0.07■K■+■0.01 ■%■MV)■
Example calculation
Pt1 00 / 4-wire / measuring range 0 ... 1 50 °C / ambient Thermocouple type K / measuring range 0 ... 400 °C / internal
temperature 33 °C compensation (cold junction) / ambient temperature 23 °C
Input■Pt1 00,■MV■<■200■°C■ ±0.1 00■K Input■type■K,■0■°C■<■MV■<■1 300■°C ±0.56■K
Input■±(0.03■%■of■1 50■K)■ ±0.045■K ±(0.4■K■+■0.04■%■of■400■K)
TC■1 0■K■-■input■■■±(0.06■K■+■0.01 5■%■of■1 50■K) ±0.083■K Cold■junction■±0.8■K ±0.80■K
TC■1 0■K■-■output■■±(0.03■%■of■1 50■K) ±0.045■K Output■±(0.03■%■of■400■K)■ ±0.1 2■K
Measuring deviation - typical ±0.1 45 K Measuring deviation - typical ±0.98 K
(√input²+output²+TCinput²+TCoutput²) (√input²+cold■junction²+output²■)
Measuring deviation - maximum ±0.273 K Measuring deviation - maximum ±1 .48 K
(input+output+TCinput+TCoutput)■ (input+cold■junction+output)■
Dust,■category■2
IIB■iaD:
■■■Co■=■570■µF■3)
■■■Lo■=■1 644■mH
■■■Lo/Ro■=■5.75■µH/Ω
T32.1 S.0IS/ CSA■approval■09.2095056 {-50}■-40■... ■+80■°C■(T4) Vmax■=■DC■30■V 1 0.5■...■30■V
T32.3S.0IS {-50}■-40■... ■+75■°C■(T5) I max■=■1 30■mA
Intrinsically■safe■installation■per■drawing■ {-50}■-40■... ■+60■°C■(T6) Pi■=■800■mW
1 1 396220 Ci■=■7.8■nF
Class■I,■Zone■0,■Ex■ia■IIC Li■=■1 00■µH
Class■I,■Zone■0,■AEx■ia■IIC
Non-incendive■field■wiring■per■drawing■ DC■30■V
1 1 396220
Class■I,■division■2,■groups■A,■B,■C,■D
T32.1 S.0IS/ FM■approval■3034620 {-50}■-40■... ■+85■°C■(T4) Voc■=■6.5■V Vmax■=■30■V 1 0.5■...■30■V
T32.3S.0IS {-50}■-40■... ■+75■°C■(T5) I sc■=■9.3■mA I max■=■1 30■mA
Intrinsically■safe■installation■per■drawing■ {-50}■-40■... ■+60■°C■(T6) Pmax■=■1 5.2■mW Pi■=■800■mW
1 1 396220 Ca■=■24■µF Ci■=■7.8■nF
Class■I,■Zone■0,■AEx■ia■IIC La■=■365■µH Li■=■1 00■µH
Class■I,■division■1 ,■groups■A,■B,■C,■D
FM■approval■AEx■ia■only
Non-incendive■field■wiring■per■drawing■
1 1 396220
Class■I,■division■2,■groups■A,■B,■C,■D
Class■I,■Division■2,■IIC
T32.1 S.0NI/ II■3G■Ex■nL■IIC■T4/T5/T6 {-50}■-40■... ■+85■°C■(T4) U o■=■DC■3.1 ■V Ui■=■40■V 1 0.5■...■40■V
T32.3S.0NI II■3G■Ex■nA■IIC■T4/T5/T6 {-50}■-40■... ■+75■°C■(T5) I o■=■0.26■mA I i■=■23■mA■*)
II■3G■Ex■ic■IIC■T4/T5/T6 {-50}■-40■... ■+60■°C■(T6) Ci■=■208■nF Pi■=■1 ■W
Li■=■negligible Ci■=■7.8■nF
Co■≤■1 000■µF Li■=■1 00■µH
Lo■≤■1 000■mH
ratio■Lo/Ro■(for■ignition■protection■
type■ic)
Lo/Ro■≤■9■mH/Ω■(for■IIC)
Lo/Ro■≤■39■mH/Ω■(for■IIB)
Lo/Ro■≤■78■mH/Ω■(for■IIA)
2)■ Power■supply■input■protected■against■reverse■polarity;■Load■RA■≤■(U B■-■1 0.5■V)■/■0.023■A■with■RA■in■Ω■and■U B■in■V■(without■HART®)
On■switching■on,■an■increase■in■the■power■supply■of■2■V/s■is■needed;■otherwise■the■temperature■transmitter■will■remain■in■a■safe■condition■at■3.5■mA.
3)■ Ci■already■considered
{■} Items■in■curved■brackets■are■options■for■additional■price,■not■for■rail■mounting■version■T32.3S
*) The■maximum■operating■current■is■limited■by■the■T32.■The■maximum■output■current■of■the■associated■energy-limited■apparatus■does■not■have■to■be■≤■23■mA.
Case
Transmitter■model Material Weight Ingress■protection■1 ) Terminal■connections
(screws■captive)
T32.1 S■head■mounting■ Plastic■PBT,■glass■ 0.07■kg IP■00■ Cross-section■head■and■rail■min.■0.1 4■mm2
version fibre■reinforced Electronics■completely■potted Wire■cross-section■max.■1 .5■mm2
T32.3S■rail■mounting■ Plastic 0.2■kg IP■20 Wire■cross-section■max.■2.5■mm2
version
1 )■Ingress■protection■per■IEC■529■/■DIN■EN■60529
Options
Models T32.1 R, T32.3R
Higher■measuring■rate Measured■value■update■approx.■1 0/s
Limited■accuracy multiply■the■accuracy■limit■values■given■for■the■T32.xS■model■by■factor■2
Limited■sensor■diagnostics Limited■self-monitoring■function
Sensor■input exclusively■for■thermocouples
SIL■certification without
External■cold■junction without
Dual■sensor■function without
Attention:
For■direct■communication■via■the■serial■interface■of■a■PC/notebook,■a■HART®■modem■is■needed■(see■"Accessories").
As■a■general■rule,■parameters■which■are■defined■in■the■scope■of■the■universal■HART®■commands■(e.g.■the■measuring■range)■
can,■in■principle,■be■edited■with■all■HART®■configuration■tools.
1 1 2891 30.02
Load■RA■in■Ω
Load■RA■≤■(UB■-■1 0.5■V)■/■0.023■A■with■RA■in■Ω■and■U B■in■V
(without■HART®)
Ex■ia Ex■nA/nL/ic
Voltage■U B■in■V
1 1 234547.0X
Sensor■2 Sensor■2
Identical■dual■sensors■are■supported■
for■all■sensor■models,■i.■e.■dual■sensor■
Analogue output
combinations■as■for■example■Pt1 00/
Pt1 00■or■thermocouple■type■K/■type■K■
are■possible.
4■...■20■mA■-■loop A■further■rule■is■that■both■sensor■val-
ues■have■the■same■unit■and■the■same■
sensor■range.
For■head■mounting■and■rail■mounting■case,■connection■clamps■for■the■HART®■modem■are■available.
Dimensions in mm
Head mounting version Rail mounting version
1 1 234377.01
CT01 29.01
Terminal■1 -4:
Transmitter■ sensor,■see■
power■supply designation■
24■V of■terminal■
connections
RL■=■Resistance■for■the■HART®■ Transmitter
communication
RL■min.■250■Ω,■max.■1 1 00■Ω
If■RL■is■<250■Ω■in■the■respective■electrical■
circuit,■RL■must■be■increased■to■at■least■
1 1 2421 75.02
250■Ω■by■connecting■external■resistances.
USB■HART®■
modem Bluetooth HART®
Ex■ia communicator■
RS■232-C
RL■=■Resistance■for■the■HART®■ Transmitter
communication
RL■min.■250■Ω,■max.■1 1 00■Ω
If■RL■is■<250■Ω■in■the■respective■electrical■
circuit,■RL■must■be■increased■to■at■least■
250■Ω■by■connecting■external■resistances.
1 1 242299.02
HART®
communicator■
US
B FSK■
modem
HART® modem
Model Description Order No.
Model■01 0031 USB-interface,■specifically■designed■for■use■with■modern■notebooks 1 1 0251 66
HART® communicator
Model Description Order No.
FC475HP1 EKLUGMT HART®■protocol,■Li-Ion■battery,■power■supply■AC■90■...■240■V, on■request
without■EASY■UPGRADE;■ATEX,■FM■and■CSA■(intrinsically■safe)
©■2008■WIKA■Alexander■Wiegand■SE■&■Co.■KG,■all■rights■reserved.
The■specifications■given■in■this■document■represent■the■state■of■engineering■at■the■time■of■publishing.
We■reserve■the■right■to■make■modifications■to■the■specifications■and■materials.