Ring Wall 6v0201

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 5

CLIENT: AILCONSULTANT: LTTS DESIGN CALCULATION FOR TANK RING WALL FOUNDATION

TAG NO. 6V0201


SR. NO. PERTICULAR UNIT DATA

1 GENERAL
Concrete grade (fck) M 30.00
Concrete unit weight (gc) kN/m3 25.00
Soil unit weight (gs) kN/m3 18.00
Angle of repose for soil (f) 30.00
Coefficient of active pressure [(1-sinf)/(1+sinf)] 0.33
Coefficient of Friction (μ) 0.50
Net SBC of soil kN/m2 232.00
Gross SBC of soil = Net SBC + overburden of soil = kN/m2 268.00
Increase in permissible stresses due to wind and seismic % 25.00
Steel grade (fy) N/mm2 500.00
ptmin for ring wall in % (IS 456, Cl 32.5) % 0.10
Clear cover to foundation (Cv) = mm 50.00
Clear cover to wall mm 50.00
Founding level below NGL (Df) mm 2000.00
Finish Floor level from NGL (H) mm 650.00
Top of wall above FFL (Tow) mm 300.00
Slab required-Y=yes, N=No N
PCC thickness mm 75.00

2 TANK DATA
Diameter of vessel mm 3500.00
PCD of vessel mm 3620.00
Height of vessel mm 4500.00
Empty weight (For values refer Appendix-A) kN 123.65
Operating weight (For values refer Appendix-A) kN 658.25
Hydrotest weight (For values refer Appendix-A) kN 668.60

3 WIND LOAD
Wind Base Shear (Vw) (For values refer Appendix-A) kN 57.29
BM due to wind at tank bottom (Mwt) (For values refer Appendix-A) kNm 210.50
BM due to wind at founding level (Mwf)= Mwt + Vw*(Df+Tow) = kNm 379.51

4 SEISMIC LOAD
Shear force due to seismic load (Vs) (For values refer Appendix-A) kN 119.80
BM due to seismic at tank bottom (Mst) (For values refer Appendix-A) kNm 504.75
BM due to seismic at founding level (Msf)= Mst + Vs*(Df+Tow) = kNm 858.16

DVJ Page 1 01/03/2024


CLIENT: AILCONSULTANT: LTTS DESIGN CALCULATION FOR TANK RING WALL FOUNDATION

SR. NO. PERTICULAR UNIT DATA


5 RING WALL AND FOUNDATION DATA
Distance of bolt centre (pcd) to outer face of ring wall mm 125.00
Distance of bolt centre (pcd) to inner face of ring wall mm 125.00
Width of ring wall (Tw) mm 250.00
Raft projection from inside face of ring wall mm 350.00
Raft projection from outside face of ring wall mm 350.00
Total width of wall foundation = wall thk + raft projection on each side = mm 950.00
Provide full raft or individual foundation below ring beam-FR-full raft IR
Diameter of foundation-outside = D = PCD + wall thk + raft projection = mm 4570.00
Diameter of foundation-inside = d = PCD - wall thk - raft projection = mm 2670.00
Foundation thickness at edge mm 300.00
Foundation thickness at face of wall (Tf) mm 300.00
Area of the foundation Af = [p * (D2-d2)] / 4 m2 10.80
Moment of Inertia (MI) of foundation If= [p * (D4-d4)] / 64 m4 18.92
Section modulus of foundation Zf = [p * (D -d )] / (32*D)
4 4 m3 8.28
Weight of the foundation (Wf)= (Af x Tf x gc) = kN 81.03
Weight of ring wall (Wr)= (p * PCD * Tw * Hw * gc) = kN 188.36
Weight of soil above Foundation (Ws)= (Af * Hw *gs) -Wr = kN 275.13
Self weight of foundation (W) =Wf+Wr+Ws kN 544.52

6 STABILITY CHECK FOR FOUNDATION

6.1 OP weight + OM (seismic)


OM due to seismic at founding level (Ms) kNm 858.16
Operating weight kN 658.25
Self weight of foundation kN 544.52
Total vertical load (P) = Self weight of foundation + Operating weight = kN 1202.77
Direct stress on the soil = P/Af = kN/m2 111.33
Bending stress on the soil = Ms/Zf = kN/m2 103.66
Total stress on the soil-maximum = (P/Af) + (Ms/Zf) = kN/m 2
214.99
Total stress on the soil-minimum = (P/Af) - (Ms/Zf) = kN/m2 7.66
Permissible SBC = (Net SBC * Permisssble increase due to seismic + kN/m2 326.00
overburden of soil) =
Check for foundation stresses Ok

6.2 Empty weight of tank + OM (wind)


OM due to wind at founding level (Mw) kNm 379.51
Empty weight kN 123.65
Self weight of foundation kN 544.52
Total vertical load (P) = Self weight of foundation + Empty weight = kN 668.17
Direct stress on the soil = P/Af = kN/m2 61.84
Bending stress on the soil = Mw/Zf = kN/m2 45.84
Total stress on the soil-maximum = (P/Af) + (Mw/Zf) = kN/m 2
107.69
Total stress on the soil-minimum = (P/Af) - (Mw/Zf) = kN/m 2
16.00
Permissible SBC = (Net SBC * Permisssble increase due to seismic + kN/m 2
326.00
overburden of soil) =
Check for foundation stresses Ok

DVJ Page 2 01/03/2024


CLIENT: AILCONSULTANT: LTTS DESIGN CALCULATION FOR TANK RING WALL FOUNDATION

SR. NO. PERTICULAR UNIT DATA


6.3 Operating weight of tank+ OM (wind)
OM due to wind at founding level (Mw) kNm 379.51
Operating weight kN 658.25
Self weight of foundation kN 544.52
Total vertical load (P) = Self weight of foundation + Operating weight = kN 1202.77
Direct stress on the soil = P/Af = kN/m2 111.33
Bending stress on the soil = Mw/Zf = kN/m2 45.84
Total stress on the soil-maximum = (P/Af) + (Mw/Zf) = kN/m 2
157.17
Total stress on the soil-minimum = (P/Af) - (Mw/Zf) = kN/m 2
65.48
Permissible SBC = (Net SBC * Permisssble increase due to seismic + kN/m 2
326.00
overburden of soil) =
Check for foundation stresses Ok

6.4 Check hydrotest weight


Hydrotest weight kN 668.60
Self weight of foundation kN 544.52
Total vertical load (P) = Self weight of foundation + Hydrotest weight = kN 1213.12
Direct stress on the soil = P/Af = kN/m2 111.33
Gross SBC kN/m2 268.00
Check for foundation stresses Ok

6.5 Sliding Check


Foactor of safety against slinding = μ * 0.9 *P / Vs > 1.5 4.52

6.6 Uplift Check


Self weight of foundation kN 544.52
Uplift due to water table at 1m = Dessity of water * height * footing area = kN 108.04
Foactor of safety against uplift = weight of structure / uplift force > 1.5 5.04

6.7 Overturning Check


overturning moment (OM) kNm 858.16
stabilizing moment (SM) = [(Operating weight+selfweight of kNm 1959.31
foundation)*0.9]*(PCD/2)
Foactor of safety against overturning = OM / SM > 1.5 2.28

7 REINFORCEMENT FOR FOUNDATION

7.1 BOTTOM REINFORCEMENT


Maximum stress on soil kN/m2 214.99
BM at the face of ring wall (M) = wl /2 =
2
kNm 13.17
Effective depth of foundation = d = Tf-Cv -db/2= mm 245.00
Area of main steel reqduired = (0.5*fck*b*d/fy)*[1-√1-(4.6*1.5*M/fck*b*d )] =
2
mm /m
2
187.83
Minimum area of main steel = 0.12*Tf/100 = mm /m
2
360.00
Area of main steel provided = Ast.prov mm2/m 360.00
Diameter of main steel provided (db) mm 10.00
Area of each bar mm 2
78.54
Spacing of main steel required mm 218.00
Spacing of main steel provided mm 200.00
Shear kN 22.57
Shear Stress τv N/mm2 0.08
τc N/mm2 0.29

DVJ Page 3 01/03/2024


CLIENT: AILCONSULTANT: LTTS DESIGN CALCULATION FOR TANK RING WALL FOUNDATION

SR. NO. PERTICULAR UNIT DATA


7.2 DISTRIBUTION REINFORCEMENT
Minimum percentage of distribution steel % 0.12
Area of distribution steel required = 0.12*Tf/100 = mm2 360.00
Diameter of distribution steel provided mm 10.00
Area of each bar mm2 78.54
Spacing of distribution steel required mm 218.00
Spacing of distribution steel provided mm 200.00

8 REINFORCEMENT FOR RING WALL

Design Axial Stregth of wall Puw = 0.3(t-1.2e-2ea)fck = kN/m 2114.92


Stress N/mm2 7.05
Max factored stress from finite element analysis N/mm 2
0.23
Minimum area of distribution
steel required = 0.1*Tw/100 = mm2 250.00
Diameter of distribution steel mm 10.00
Area of each bar mm2 78.54
Spacing of distribution steel required mm 314.16
Spacing of distribution steel provided mm 200.00

8.1 HOOP REINFORCEMENT


Max factored stress from finite element analysis N/mm2 0.21
Hoop tension in ring wall = Stress*wall thk = kN 52.50
Area of steel required = Ast.reqd mm2 60.34
Diameter of hoop steel provided mm 10.00
Area of each bar mm2 78.54
Spacing of hoop steel required mm 1302.00
Spacing of hoop steel provided mm 150.00

DVJ Page 4 01/03/2024


(1-sinf)/(1+sinf)

You might also like