DDM METHOD
DESIGN PROCEDURE – FLAT SLAB
➢ Calculate the slab thickness using table 9.5 (c) of
ACI Code. Assume α > 0.80 if edge beam is present.
5 @ 20′= 100′
R S
P Q
14″×24″ beam
b
5 @ 25′ = 125′
LINE PLAN
SOLUTION
1.Slab thickness. According to ACI code table 9.5 (c)
slab thickness for exterior and interior panel with edge
beam and for grade 40 steel (assuming α ≥ 0.80) is
given by
h = ln /40
For 18’’ circular column equivalent square column
= √(π/4 d2 ) = √( π/4 (18)2 = 16’’
ln = 25 -16/12 = 23.667 ft
7’’
24’’
b. Ib = k bw h3/12 14’’
Drop panel
7’
5 @ 20′= 100′
R S
P Q
14″×24″ beam
5 @ 25′ = 125′
LINE PLAN
a. Shear at Exterior column face 20.5’’
20’
16’
25’’
’
b. At interior column
bo = 4 x 25 =100 inch 16’’
Assumed loaded area for shear is shown in figure.
Vu =[20 x 25 – 25x25/144] x 0.344 = 170.5 k
ɸVc= ɸ4√f’cbod =0.75 x 4√3000 x100X 9 = 147.9 kips
ɸVc < Vu UNSAFE
Increase thickness of the drop panel to 11’’.
d = 10’’ bo= 4(16+10) =104’’
Vu = [20 x 25 – 26 x 26 /144] x 0.344 = 170.39 kips
ɸVc = 0.75x 4 x √3000 x 104 x 10 = 170.88 kips
Vu< Vc SAFE
Check for punching shear beyond the drop ( where
thickness of slab changes to 7’’) would be ok.
25’
c+d
20’
c+d
Drop panel
7’
5 @ 20′= 100′
R S
P Q
14″×24″ beam
5 @ 25′ = 125′
LINE PLAN
c. βt
Refer to effective beam size in para 2a above
C = Ʃ( 1- 0.63 X / Y ) X3Y/3
X = shorter dimension of rectangular part Y =
longer “ “ “ “
C1 = (1- 0.63x 14/24) 143 x 24 /3 +
(1- 0.63x 7/17)73x17/3 = 15324 in4
C2 = (1- 0.63x 14/17) 143 x 17 /3+
(1- 0.63x 7/31)73x31/3 = 10522 in4
C = 15324 inch4
Is = 20x12(7)3/12 = 6860 in4
βt = C / 2 Is = 15324 / (2x6860) = 1.12
c. Percentage Moment in C.S. ACI Code 13.6.4
l2/l1 =20/25 = 0.8
α1 l2/l1 =0
% of int –ve moment in C.S.= 75%
% of +ve moment in C.S. = 60%
% of ext –ve moment in C.S.
for l2/l1= 0.8
βt = 0 100
α1l2/l1 = 0 βt =1.12 88.8
βt = 2.5 75
% in C.S. = 100 -1.12 /2.5 (100 - 75) = 88.8%
Distribution of negative and positive
moment
Distribution of negative and positive moment
d. Distribution of moment
Drop panel
7’
5 @ 20′= 100′
R S
P Q
14″×24″ beam
5 @ 25′ = 125′
LINE PLAN
Distribution of moment
E-W dir Ext –ve 16.19 10 6 1.62 0.00233 1.68 9#5 Use ρmin
N-S Dir -ve 13.0 3.75 9.5 3.47 0.0023 1.18 4 #6 Use ρmin
½ C.S +ve 7.0 4.5 5.5 1.56 0.00284 0.84 4 #6 Spacing
limit
N-S Dir -ve 41.68 7.5 5.5 5.56 0.00543 2.69 9#5
½ M.S +ve 22.44 7.5 5.5 3.0 0.00293 1.45 7# 5 ,,
For calculation of steel reinforcement we use flexural
formula,
Mu = ɸρbd2 fy(1- 0.59 ρfy/f’c)
For example for a moment of 36.14 kft, As is worked
out as under:
36.14x12 =0.9 x ρx12(10)2x40(1- 0.59ρ40/3)
7.87ρ2 - ρ + 0.0100 = 0
ρ = 0.01099
As= ρbd = 0.01099x12x10x10= 13.18 in2
use 30#6 bars
Note 1. For C.S -ve moment in both directions, b for
calculation of steel area has been taken as 10 ft.
2. #6 bars have been used in C.S. and #5 in M.S.
SLAB REINFORCE MENT – PANEL (R)
DESIGN EXAMPLE
Design the panel (S) of the above floor system
Solution
1. Total factored static moment in E-W direction and its
distribution
a. Mo = wul2 ln2/8 = 0.344x20(23.67)2/8 = 481.83 kft
ln = 25-16/12= 23.67 ft
l2 =20 ft 0.65 0.65
b. D.F.
0.35
-ve moment = 0.65 Mo= 0.65x481.83 = 313.19 k
+ve moment = 0.35Mo= 0.35x481.83 = 168.64 kft
c % Moment in C.S l2/l1 = 0.8 α1l2/l1= 0
-ve moment = 75%
+ve moment = 60%
8..5′
Drop panel
7’
5 @ 20′= 100′
R
s
16″ sq col 18″ dia col
P Q
14″×24″ beam
5 @ 25′ = 125′
LINE PLAN
d. Distribution ofmoment
Location Total Moment C.S Moment M.S. Moment
kft kft kft
E-W Dir 313.19 234.89 78.30
–ve
moment
E-W Dir 168.64 101.18 67.46
+ ve
moment
2. Total factored static moment in N-W Direction and
its distribution
Same as para 8 a of previous example
3 Design of slab reinforcement – panel (s)