‫ﻣﺷﺭﻭﻉ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻣﻧﻅﻭﻣﺔ ﻁﺎﻗﺔ ﻛﻬﺭﻭﺿﻭﺋﻳﺔ ﻟﺯﻭﻡ‬

‫‪ ‬ﻣﺟﻣﻊ ﺍﻟﻬﻼﻝ ﺍﻷﺣﻣﺭ ﺍﻟﻁﺑﻲ ﻓﻲ ﻣﻧﻁﻘﺔ ﺍﻟﺻﺎﺧﻭﺭ ﻓﻲ ﻣﺣﺎﻓﻅﺔ ﺣﻠﺏ‬


‫‪ ‬ﻣﺷﻔﻰ ﺍﻷﻁﻔﺎﻝ ﻟﻠﻬﻼﻝ ﺍﻷﺣﻣﺭ ﺍﻟﻌﺭﺑﻲ ﺍﻟﺳﻭﺭﻱ ﻓﻲ ﻣﺣﺎﻓﻅﺔ ﺣﻠﺏ‬
‫‪ ‬ﺍﻟﻣﺟﻣﻊ ﺍﻟﻁﺑﻲ ﻟﻠﻬﻼﻝ ﺍﻷﺣﻣﺭ ﺍﻟﻌﺭﺑﻲ ﺍﻟﺳﻭﺭﻱ ﻓﻲ ﺟﺭﻣﺎﻧﺎ ﻓﻲ ﻣﺣﺎﻓﻅﺔ ﺭﻳﻑ‬
‫ﺩﻣﺷﻖ‬

‫ﺩﻓﺗﺭ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‬

‫ﺁﺫﺍﺭ ‪٢٠٢٣‬‬
‫ﺍﻟﻬﺩﻑ ﻣﻥ ﺍﻟﻣﺷﺭﻭﻉ ‪:‬‬
‫ﺗﻘ ﺪﻳﻢ ﻭﺗﺮﻛﻴ ﺐ ﻭﺗﻮﺻ ﻴﻞ ﻣﻨﻈﻮﻣ ﺎﺕ ﻁﺎﻗ ﺔ ﻛﻬﺮﻭﺿ ﻮﺋﻴﺔ ﻟﻜ ﻞ ﻣ ﻦ ﻣﺠﻤ ﻊ ﺍﻟﻬ ﻼﻝ ﺍﻷﺣﻤ ﺮ ﺍﻟﻄﺒ ﻲ ﻓ ﻲ ﻣﻨﻄﻘ ﺔ ﺍﻟﺼ ﺎﺧﻮﺭ ﻓ ﻲ‬
‫ﻣﺤﺎﻓﻈ ﺔ ﺣﻠ ﺐ ﻭ ﺍﻟﻠ ﺬﻱ ﻳﺘﻜ ﻮﻥ ﻣ ﻦ ﻛﺘﻠﺘ ﻴﻦ ) ‪١‬ﻭ‪ ( ٢‬ﺣﻴ ﺚ ﻛﺘﻠ ﺔ ﺍﻟﺒﻨ ﺎء ﺍﻻﻭﻝ ﻳﺘﻜ ﻮﻥ ﻣ ﻦ ﺛ ﻼﺙ ﻁﻮﺍﺑ ﻖ )ﺍﻟﻘﺒ ﻮ‪-‬ﺍﻷﺭﺿ ﻲ ‪-‬‬
‫ﺍﻟﻄ ﺎﺑﻖ ﺍﻷﻭﻝ ( ﻭ ﻛﺘﻠ ﺔ ﺍﻟﺒﻨ ﺎء ﺍﻟﺜ ﺎﻧﻲ ﻣ ﻦ ﺃﺭﺑ ﻊ ﻁﻮﺍﺑﻖ)ﺍﻟﻘﺒ ﻮ‪-‬ﺍﻷﺭﺿ ﻲ ‪-‬ﺍﻟﻄ ﺎﺑﻖ ﺍﻷﻭﻝ ‪-‬ﺍﻟﻄ ﺎﺑﻖ ﺍﻟﺜ ﺎﻧﻲ(‪ ,‬ﻭ ﻣﺸ ﻔﻰ ﺍﻷﻁﻔ ﺎﻝ‬
‫ﻟﻠﻬ ﻼﻝ ﺍﻷﺣﻤ ﺮ ﺍﻟﻌﺮﺑ ﻲ ﺍﻟﺴ ﻮﺭﻱ ﻓ ﻲ ﻣﺤﺎﻓﻈ ﺔ ﺣﻠ ﺐ ﻭﺍﻟ ﺬﻱ ﻳﺘﻜ ﻮﻥ ﻣ ﻦ ﺳ ﺒﻊ ﻁﻮﺍﺑ ﻖ )ﺍﻟﻘﺒ ﻮ ‪-‬ﺍﻷﺭﺿ ﻲ ‪-‬ﺍﻟﻄ ﺎﺑﻖ ﺍﻷﻭﻝ ‪-‬ﺍﻟﻄ ﺎﺑﻖ‬
‫ﺍﻟﺜ ﺎﻧﻲ ‪-‬ﺍﻟﻄ ﺎﺑﻖ ﺍﻟﺜﺎﻟ ﺚ – ﺍﻟﻄ ﺎﺑﻖ ﺍﻟﺮﺍﺑ ﻊ ‪ -‬ﺍﻟﻄ ﺎﺑﻖ ﺍﻟﺨ ﺎﻣﺲ – ﺍﻟﻄ ﺎﺑﻖ ﺍﻟﺴ ﺎﺩﺱ – ﺍﻟﻄ ﺎﺑﻖ ﺍﻟﺴ ﺎﺑﻊ ( ﻭﻫ ﻮ ﻣﺠﻬ ﺰ ﺑ ﺜﻼﺙ ﻣﺼ ﺎﻋﺪ‬
‫ﺑﺎﺳ ﺘﻄﺎﻋﺎﺕ ﻣﺨﺘﻠﻔ ﺔ ﺳ ﻮﻑ ﻳ ﺘﻢ ﺭﺑ ﻂ ﻣﺼ ﻌﺪ ﻭﺍﺣ ﺪ ﻓﻘ ﻂ ﻋﻠ ﻰ ﻣﻨﻈﻮﻣ ﺎﺕ ﺍﻟﻄﺎﻗ ﺔ ﺍﻟﻜﻬﺮﻭﺿ ﻮﺋﻴﺔ ﻭﺍﻟﻤﺠﻤ ﻊ ﺍﻟﻄﺒ ﻲ ﻟﻠﻬ ﻼﻝ‬
‫ﺍﻷﺣﻤ ﺮ ﺍﻟﻌﺮﺑ ﻲ ﺍﻟﺴ ﻮﺭﻱ ﺑﻤﺪﻳﻨ ﺔ ﺟﺮﻣﺎﻧ ﺎ ﻓ ﻲ ﻣﺤﺎﻓﻈ ﺔ ﺭﻳ ﻒ ﺩﻣﺸ ﻖ ﻭﺍﻟ ﺬﻱ ﻳﺘﻜ ﻮﻥ ﻣ ﻦ ﺛ ﻼﺙ ﻁﻮﺍﺑ ﻖ )ﺍﻷﺭﺿ ﻲ ‪-‬ﺍﻟﻄ ﺎﺑﻖ ﺍﻷﻭﻝ‬
‫‪-‬ﺍﻟﻄ ﺎﺑﻖ ﺍﻟﺜ ﺎﻧﻲ (ﻣ ﻊ ﻗﺴ ﻢ ﺍﻻﺳ ﻌﺎﻑ‪ .‬ﻟ ﺰﻭﻡ ﺗ ﺄﻣﻴﻦ ﺍﻟﻄﺎﻗ ﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴ ﺔ ﺩﻭﻥ ﺍﻧﻘﻄ ﺎﻉ ﻋ ﻦ ﺍﻟﺘﺠﻬﻴ ﺰﺍﺕ ﺍﻟﻄﺒﻴ ﺔ ﻭﺍﻟﻜﻬﺮﺑﺎﺋﻴ ﺔ‬
‫ﺍﻟﻀ ﺮﻭﺭﻳﺔ ﺑﺎﻟﺘﻨ ﺎﻭﺏ ﻣ ﻊ ﺍﻟﻤﺨ ﺮﺝ ﺍﻟﻤﺸ ﺘﺮﻙ )ﺷ ﺒﻜﺔ ‪ -‬ﻣﺠﻤﻮﻋ ﺔ ( ﺣﻴ ﺚ ﺍﻷﻓﻀ ﻠﻴﺔ ﻟﻠﻄﺎﻗ ﺔ ﺍﻟﻜﻬﺮﻭﺿ ﻮﺋﻴﺔ ﻭﺫﻟ ﻚ ﻟﻤ ﺪﺓ ﺛ ﻼﺙ‬
‫ﺳﺎﻋﺎﺕ ﺻﺒﺎﺣﻴﺔ ﺧﻼﻝ ﻓﺘﺮﺓ ﺍﻟﺪﻭﺍﻡ ﺍﻟﺮﺳﻤﻲ ﻟﻠﻤﺴﺘﻮﺻﻒ ﻭﺗﺸﻤﻞ ﺍﻷﻋﻤﺎﻝ ﻣﺎﻳﻠﻲ‪:‬‬

‫ﺁ‪-‬ﺍﻷﻋﻣﺎﻝ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻟﻺﻧﺎﺭﺓ ﻭﺍﻟﻣﺂﺧﺫ ﻭﺍﻟﺧﺩﻣﺎﺕ ‪:‬‬


‫ﺗﺷﻣﻝ ﺍﻷﻋﻣﺎﻝ ﻣﺎﻳﻠﻲ ‪:‬‬
‫‪ -١‬ﺗﻘ ﺩﻳﻡ ﻭﺗﻣﺩﻳ ﺩ ﻭﺗﻭﺻ ﻳﻝ ﻛ ﺎﺑﻼﺕ ﺍﻟﺗﻐﺫﻳ ﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳ ﺔ ﺍﻟﺭﺋﻳﺳ ﻳﺔ ﺑ ﻳﻥ ﻣﺻ ﺎﺩﺭ ﺍﻟﺗﻐﺫﻳ ﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳ ﺔ‬
‫)ﺍﻟﻣﺧ ﺭﺝ ﺍﻟﻣﺷﺗﺭﻙ))ﺷ ﺑﻛﺔ‪-‬ﻣﺟﻣﻭﻋ ﺔ(( – ﻛﻬﺭﻭﺿ ﻭﺋﻳﺔ ( ﻭﺍﻟﻠﻭﺣ ﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳ ﺔ ﺍﻟﺛﺎﻧﻭﻳ ﺔ ﺍﻟﺟﺩﻳ ﺩﺓ‬
‫ﺑﻣﻘﺎﻁﻌﻬﺎ ﺍﻟﻣﺧﺗﻠﻔﺔ )‪ (AC‬ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ﻭﻓﻖ ﻛﻣﻳﺎﺕ ﺍﻟﻛﺷﻑ ﺍﻟﺗﻘﺩﻳﺭﻱ‪/:‬ﻡ‪.‬ﻁ‪/‬‬
‫‪ ‬ﻣﻭﻗﻊ ﺍﻟﺻﺎﺧﻭﺭ‪:‬‬
‫‪ – ١-١‬ﻟﺯﻭﻡ ﻛﺗﻠﺔ ﺍﻟﺑﻧﺎء ‪: ١‬‬
‫‪٢‬‬
‫(‬ ‫‪ -١-١-١‬ﺑﻣﻘﻁﻊ) ‪ ٢٤٠×٤‬ﻣﻠﻡ‬
‫‪٢‬‬
‫(‬ ‫‪ -١-١-٢‬ﺑﻤﻘﻄﻊ) ‪ ٧٠×٢‬ﻣﻠﻢ‬
‫‪٢‬‬
‫(‬ ‫‪ -١-١-٣‬ﺑﻣﻘﻁﻊ) ‪ ٢٫٥×٢‬ﻣﻠﻡ‬
‫‪٢‬‬
‫(‬ ‫‪ -١-١-٤‬ﺑﻤﻘﻄﻊ) ‪ ١٠×٢‬ﻣﻠﻢ‬
‫‪ -١-١-٥‬ﺑﻤﻘﻄﻊ ) ‪ ١٦×٢‬ﻣﻠﻢ ‪( ٢‬‬
‫‪ –١-٢‬ﻟﺰﻭﻡ ﻛﺘﻠﺔ ﺍﻟﺒﻨﺎء ‪: ٢‬‬
‫‪-١-٢-١‬ﺑﻤﻘﻄﻊ) ‪ ٢٤٠×٤‬ﻣﻠﻢ ‪( ٢‬‬
‫‪ -١-٢-٢‬ﺑﻤﻘﻄﻊ) ‪ ١٦×٢‬ﻣﻠﻢ ‪( ٢‬‬
‫‪-١-٢-٣‬ﺑﻤﻘﻄﻊ) ‪ ٢٫٥×٢‬ﻣﻠﻢ ‪( ٢‬‬
‫‪ -١-٢-٤‬ﺑﻤﻘﻄﻊ) ‪ ٤×٢‬ﻣﻠﻢ ‪( ٢‬‬
‫ﻣﻭﻗﻊ ﻣﺷﻔﻰ ﺍﻷﻁﻔﺎﻝ‪:‬‬ ‫‪‬‬
‫‪٢‬‬
‫‪ -١‬ﺑﻣﻘﻁﻊ )‪ ١٦×٢‬ﻣﻠﻡ (‬
‫‪ -٢‬ﺑﻤﻘﻄﻊ) ‪ ١٦×٤‬ﻣﻠﻢ ‪( ٢‬‬
‫ﻣﻭﻗﻊ ﺟﺭﻣﺎﻧﺎ‪:‬‬ ‫‪‬‬
‫‪٢‬‬
‫(‬ ‫‪ -١‬ﺑﻣﻘﻁﻊ )‪ ١٦×٢‬ﻣﻠﻡ‬

‫‪ -٢‬ﺗﻘﺩﻳﻡ ﻭﺗﻣﺩﻳﺩ ﻭﺗﻭﺻﻳﻝ ﻛﺎﺑﻼﺕ ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺭﺋﻳﺳﻳﺔ ﺑﻳﻥ ﻧﻬﺎﻳﺔ ﺍﻷﻟﻭﺍﺡ ﻭﺍﻻﻧﻔﻳﺭﺗﺭ ﺑﻣﻘﻁﻊ )‪ ١٦×٢‬ﻣﻡ‪DC) (٢‬‬
‫(ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ﻟﻛﺎﻓﺔ ﺍﻟﻣﺷﺎﺭﻳﻊ ﺍﻟﺛﻼﺙ ﻭﻓﻖ ﻛﻣﻳﺎﺕ ﺍﻟﻛﺷﻑ ﺍﻟﺗﻘﺩﻳﺭﻱ‪ /:‬ﻡ‪.‬ﻁ‪/‬‬
‫‪ -٣‬ﺗﻘ ﺩﻳﻡ ﻭﺗﻣﺩﻳ ﺩ ﻭﺗﺭﻛﻳ ﺏ ﻭﺗﻭﺻ ﻳﻝ ﻧﻘﻁ ﺔ ﺿ ﻭﺋﻳﺔ ﻅ ﺎﻫﺭﺓ ﺟﺩﻳ ﺩﺓ ﻟﻛ ﻝ ﻣ ﻥ ﻣﺷ ﺭﻭﻋﻲ ﺍﻟﺻ ﺎﺧﻭﺭ ﻭﻣﺷ ﻔﻰ ﺍﻷﻁﻔ ﺎﻝ‬
‫ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ﻭﻓﻖ ﻛﻣﻳﺎﺕ ﺍﻟﻛﺷﻑ ﺍﻟﺗﻘﺩﻳﺭﻱ‪/:‬ﻋﺩﺩ‪/‬‬
‫‪ -٤‬ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻣﺄﺧﺫ ﻛﻬﺭﺑﺎﺋﻲ ﻋﺎﺩﻱ ﻣﺅﺭﺽ ﻋﻳﺎﺭ ‪ ١٦‬ﺃﻣﺑﻳﺭ ﻟﻛﺎﻓﺔ ﺍﻟﻣﺷﺎﺭﻳﻊ ﺍﻟﺛﻼﺙ ﻭﻓﻖ ﻛﻣﻳﺎﺕ ﺍﻟﻛﺷﻑ‬
‫ﺍﻟﺗﻘﺩﻳﺭﻱ ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ‪/:‬ﻋﺩﺩ‪/‬‬
‫‪ -٥‬ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻣﺄﺧﺫ ﻛﻬﺭﺑﺎﺋﻲ ﻣﻥ ﻧﻭﻉ ﺷﻭﻛﻭ ﻣﺅﺭﺽ ﻋﻳﺎﺭ ‪ ١٦‬ﺃﻣﺑﻳﺭ ﻟﻛﺎﻓﺔ ﺍﻟﻣﺷﺎﺭﻳﻊ ﺍﻟﺛﻼﺙ ﻭﻓﻖ ﻛﻣﻳﺎﺕ ﺍﻟﻛﺷﻑ‬
‫ﺍﻟﺗﻘﺩﻳﺭﻱ ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ‪/:‬ﻋﺩﺩ‪/‬‬
‫‪ -٦‬ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻟﻭﺣﺎﺕ ﺗﻐﺫﻳﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺟﺩﻳﺩﺓ ﻟﺯﻭﻡ ﺍﻹﻧﺎﺭﺓ ﻭﺍﻟﻣﺂﺧﺫ ﻭﺍﻟﺧﺩﻣﺎﺕ ﻭﻓﻖ ﻛﻣﻳﺎﺕ ﺍﻟﻛﺷﻑ ﺍﻟﺗﻘﺩﻳﺭﻱ ﻣﻊ ﻛﻝ ﻣﺎﻳﻠﺯﻡ‬
‫‪/:‬ﻋﺩﺩ‪/‬‬
‫ﻣﻭﻗﻊ ﺍﻟﺻﺎﺧﻭﺭ‪:‬‬ ‫‪‬‬
‫ﺭﻗﻡ ‪٢‬‬ ‫)‪ (B’2,B’1,B’0‬ﻟﻁﻭﺍﺑﻖ ﻛﺗﻠﺔ ﺍﻟﺑﻧﺎء ﺭﻗﻡ ‪ ١‬ﻭ)‪ (B”3,B”2,B”1 ,B”0‬ﻟﻁﻭﺍﺑﻖ ﻛﺗﻠﺔ ﺍﻟﺑﻧﺎء‬
‫ﻣﻭﻗﻊ ﻣﺷﻔﻰ ﺍﻷﻁﻔﺎﻝ‪:‬‬ ‫‪‬‬
‫ﻟﻛﺎﻓﺔ ﻁﻭﺍﺑﻖ ﻭ ﻣﺻﻌﺩ ﻭﺍﺣﺩ ﻓﻲ ﺍﻟﻣﺷﺭﻭﻉ‪.‬‬ ‫)‪(B`8,B`7,B`6,B`5,B`4,B`3,B`2,B`1,B`0, B’-1‬‬
‫ﻣﻭﻗﻊ ﺟﺭﻣﺎﻧﺎ‪:‬‬ ‫‪‬‬
‫)‪ (B2,B1,B0, B’0‬ﻟﻁﻭﺍﺑﻖ ﻭ ﻗﺳﻡ ﺍﻻﺳﻌﺎﻑ ﻓﻲ ﺍﻟﻣﺷﺭﻭﻉ‪.‬‬

‫‪ -٧‬ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻟﻭﺣﺔ ﺗﻐﺫﻳﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺭﺋﻳﺳﻳﺔ ‪ ) ATS‬ﺷﺑﻛﺔ – ﻛﻬﺭﻭﺿﻭﺋﻳﺔ ( ) `‪ ( k‬ﻟﻛﻝ ﻣﻥ ﻛﺗﻠﺗﻲ ﺍﻟﺑﻧﺎء ‪١‬ﻭ‬
‫‪ ٢‬ﻓﻲ ﻣﺷﺭﻭﻉ ﺍﻟﺻﺎﺧﻭﺭ ﻭﻓﻖ ﻛﻣﻳﺎﺕ ﺍﻟﻛﺷﻑ ﺍﻟﺗﻘﺩﻳﺭﻱ ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ‪/:‬ﻋﺩﺩ‪/‬‬

‫ﻭﺫﻟﻙ ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﺫﻛﻭﺭﺓ ﺃﺩﻧﺎﻩ‬

‫ﺏ‪ -‬ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ ‪/ :‬ﻣﻘﻁﻭﻉ‪/‬‬
‫ﺗﺷﻣﻝ ﺃﻋﻣﺎﻝ ﻫﺫﺍ ﺍﻟﺑﻧﺩ ﻣﺎ ﻳﻠﻲ ‪:‬‬

‫ﻣﻭﻗﻊ ﺍﻟﺻﺎﺧﻭﺭ‪:‬‬ ‫‪‬‬


‫ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬ ‫‪-١‬‬
‫) ﺍﻷﻟﻭﺍﺡ ﻣﻊ ﻗﻭﺍﻋﺩﻫﺎ ﻭﺇﻛﺳﺳﻭﺍﺭﺍﺗﻬﺎ ‪ -‬ﺍﻟﻣﻌﺭﺟﺎﺕ ‪ -‬ﺍﻟﻣﺩﺧﺭﺍﺕ ( ﻟﺯﻭﻡ ﻛﺗﻠﺔ ﺍﻟﺑﻧﺎء ﺭﻗﻡ ‪ ١‬ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‪/ :‬ﻣﻘﻁﻭﻉ‪/‬‬
‫ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬ ‫‪-٢‬‬
‫) ﺍﻷﻟﻭﺍﺡ ﻣﻊ ﻗﻭﺍﻋﺩﻫﺎ ﻭﺇﻛﺳﺳﻭﺍﺭﺍﺗﻬﺎ ‪ -‬ﺍﻟﻣﻌﺭﺟﺎﺕ ‪ -‬ﺍﻟﻣﺩﺧﺭﺍﺕ ( ﻟﺯﻭﻡ ﻛﺗﻠﺔ ﺍﻟﺑﻧﺎء ﺭﻗﻡ ‪ ٢‬ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‪/:‬ﻣﻘﻁﻭﻉ‪/‬‬
‫‪-‬ﺗﻘﺩﻳﻡ ﻭﺗﻧﻔﻳﺫ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺷﺑﻛﺔ ﺗﺄﺭﻳﺽ ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ﻣﻥ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﺃﻣﺭﺍﺱ ﻭﻛﺎﺑﻼﺕ ﻭﺃﻭﺗﺎﺩ‬ ‫‪-٣‬‬
‫ﻭﻓﻘﺎ ً ﻟﻠﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻭﺍﻟﻣﺧﻁﻁﺎﺕ ﻟﺯﻭﻡ ﺃﻋﻣﺎﻝ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‪/:‬ﻣﻘﻁﻭﻉ‪/‬‬
‫ﺗﻘﺩﻳﻡ ﻭﺗﻧﻔﻳﺫ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺷﺑﻛﺔ ﻣﺎﻧﻌﺎﺕ ﺍﻟﺻﻭﺍﻋﻖ ﻣﻊ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﺃﻣﺭﺍﺱ ﻭﻛﺎﺑﻼﺕ ﻭﺃﻭﺗﺎﺩ ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ‬ ‫‪-٤‬‬
‫ﻭﻓﻘﺎ ً ﻟﻠﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻭﺍﻟﻣﺧﻁﻁﺎﺕ‪/ :‬ﻣﻘﻁﻭﻉ‪/‬‬

‫‪ ‬ﻣﻭﻗﻊ ﻣﺷﻔﻰ ﺍﻷﻁﻔﺎﻝ‪:‬‬


‫‪ .١‬ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬
‫) ﺍﻷﻟﻭﺍﺡ ﻣﻊ ﻗﻭﺍﻋﺩﻫﺎ ﻭﺇﻛﺳﺳﻭﺍﺭﺍﺗﻬﺎ ‪ -‬ﺍﻟﻣﻌﺭﺟﺎﺕ ‪ -‬ﺍﻟﻣﺩﺧﺭﺍﺕ ( ﻟﺯﻭﻡ ﺍﻟﻘﺑﻭ ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ‪/‬ﻣﻘﻁﻭﻉ‬
‫‪ .٢‬ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬
‫) ﺍﻷﻟﻭﺍﺡ ﻣﻊ ﻗﻭﺍﻋﺩﻫﺎ ﻭﺇﻛﺳﺳﻭﺍﺭﺍﺗﻬﺎ ‪ -‬ﺍﻟﻣﻌﺭﺟﺎﺕ ‪ -‬ﺍﻟﻣﺩﺧﺭﺍﺕ ( ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ ﺍﻷﺭﺿﻲ ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ‪/‬ﻣﻘﻁﻭﻉ‬
‫‪ .٣‬ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬
‫) ﺍﻷﻟﻭﺍﺡ ﻣﻊ ﻗﻭﺍﻋﺩﻫﺎ ﻭﺇﻛﺳﺳﻭﺍﺭﺍﺗﻬﺎ ‪ -‬ﺍﻟﻣﻌﺭﺟﺎﺕ ‪ -‬ﺍﻟﻣﺩﺧﺭﺍﺕ ( ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ ﺍﻷﻭﻝ ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‪/‬ﻣﻘﻁﻭﻉ‬

‫‪ .٤‬ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬
‫) ﺍﻷﻟﻭﺍﺡ ﻣﻊ ﻗﻭﺍﻋﺩﻫﺎ ﻭﺇﻛﺳﺳﻭﺍﺭﺍﺗﻬﺎ ‪ -‬ﺍﻟﻣﻌﺭﺟﺎﺕ ‪ -‬ﺍﻟﻣﺩﺧﺭﺍﺕ ( ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺛﺎﻧﻲ ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‪/‬ﻣﻘﻁﻭﻉ‬
‫‪ .٥‬ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬
‫) ﺍﻷﻟﻭﺍﺡ ﻣﻊ ﻗﻭﺍﻋﺩﻫﺎ ﻭﺇﻛﺳﺳﻭﺍﺭﺍﺗﻬﺎ ‪ -‬ﺍﻟﻣﻌﺭﺟﺎﺕ ‪ -‬ﺍﻟﻣﺩﺧﺭﺍﺕ ( ﻟﺯﻭﻡ ﻛﻝ ﻣﻥ ﺍﻟﻁﻭﺍﺑﻖ ﺍﻟﻣﺗﻛﺭﺭﺓ ) ﺍﻟﺛﺎﻟﺙ ﻭﺍﻟﺭﺍﺑﻊ ﻭﺍﻟﺧﺎﻣﺱ ﻭﺍﻟﺳﺎﺩﺱ‬
‫( ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‪/‬ﻣﻘﻁﻭﻉ‬
‫ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬ ‫‪.٦‬‬
‫) ﺍﻷﻟﻭﺍﺡ ﻣﻊ ﻗﻭﺍﻋﺩﻫﺎ ﻭﺇﻛﺳﺳﻭﺍﺭﺍﺗﻬﺎ ‪ -‬ﺍﻟﻣﻌﺭﺟﺎﺕ ‪ -‬ﺍﻟﻣﺩﺧﺭﺍﺕ ( ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺳﺎﺑﻊ ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ‪/‬ﻣﻘﻁﻭﻉ‬
‫ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬ ‫‪.٧‬‬
‫) ﺍﻷﻟﻭﺍﺡ ﻣﻊ ﻗﻭﺍﻋﺩﻫﺎ ﻭﺇﻛﺳﺳﻭﺍﺭﺍﺗﻬﺎ ‪ -‬ﺍﻟﻣﻌﺭﺟﺎﺕ ‪ -‬ﺍﻟﻣﺩﺧﺭﺍﺕ ( ﻟﺯﻭﻡ ﻣﺻﻌﺩ ﻭﺍﺣﺩ ﻓﻘﻁ ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ‪/‬ﻣﻘﻁﻭﻉ‬
‫ﺗﻘﺩﻳﻡ ﻭﺗﻧﻔﻳﺫ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺷﺑﻛﺔ ﺗﺄﺭﻳﺽ ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ﻣﻥ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﺃﻣﺭﺍﺱ ﻭﻛﺎﺑﻼﺕ ﻭﺃﻭﺗﺎﺩ‬ ‫‪.٨‬‬
‫ﻭﻓﻘﺎ ً ﻟﻠﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻭﺍﻟﻣﺧﻁﻁﺎﺕ ﻟﺯﻭﻡ ﺃﻋﻣﺎﻝ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‪/‬ﻣﻘﻁﻭﻉ‬
‫ﺗﻘﺪﻳﻢ ﻭﺗﺮﻛﻴﺐ ﻭﺗﻮﺻﻴﻞ ﺷﺒﻜﺔ ﻣﺎﻧﻌﺎﺕ ﺍﻟﺼﻮﺍﻋﻖ ﻣﻊ ﺗﻘﺪﻳﻢ ﻭﺗﺮﻛﻴﺐ ﺃﻣﺮﺍﺱ ﻭﻛﺎﺑﻼﺕ ﻭﺃﻭﺗﺎﺩ ﻣﻊ ﻛﻞ ﻣﺎﻳﻠﺰﻡ‪/ :‬ﻣﻘﻄﻮﻉ‪/‬‬ ‫‪.٩‬‬

‫‪ ‬ﻣﻭﻗﻊ ﺟﺭﻣﺎﻧﺎ‪:‬‬
‫‪ .١‬ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬
‫) ﺍﻷﻟﻭﺍﺡ ﻣﻊ ﻗﻭﺍﻋﺩﻫﺎ ﻭﺇﻛﺳﺳﻭﺍﺭﺍﺗﻬﺎ ‪ -‬ﺍﻟﻣﻌﺭﺟﺎﺕ ‪ -‬ﺍﻟﻣﺩﺧﺭﺍﺕ ( ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ ﺍﻷﺭﺿﻲ ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‬
‫‪/‬ﻣﻘﻁﻭﻉ‬
‫‪ .٢‬ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬
‫) ﺍﻷﻟﻭﺍﺡ ﻣﻊ ﻗﻭﺍﻋﺩﻫﺎ ﻭﺇﻛﺳﺳﻭﺍﺭﺍﺗﻬﺎ ‪ -‬ﺍﻟﻣﻌﺭﺟﺎﺕ ‪ -‬ﺍﻟﻣﺩﺧﺭﺍﺕ ( ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ ﺍﻷﻭﻝ ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‪/‬ﻣﻘﻁﻭﻉ‬
‫‪ .٣‬ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬
‫) ﺍﻷﻟﻭﺍﺡ ﻣﻊ ﻗﻭﺍﻋﺩﻫﺎ ﻭﺇﻛﺳﺳﻭﺍﺭﺍﺗﻬﺎ ‪ -‬ﺍﻟﻣﻌﺭﺟﺎﺕ ‪ -‬ﺍﻟﻣﺩﺧﺭﺍﺕ ( ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺛﺎﻧﻲ ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ‬
‫ﺍﻟﻔﻧﻳﺔ‪/‬ﻣﻘﻁﻭﻉ‬
‫‪ .٤‬ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬
‫) ﺍﻷﻟﻭﺍﺡ ﻣﻊ ﻗﻭﺍﻋﺩﻫﺎ ﻭﺇﻛﺳﺳﻭﺍﺭﺍﺗﻬﺎ ‪ -‬ﺍﻟﻣﻌﺭﺟﺎﺕ ‪ -‬ﺍﻟﻣﺩﺧﺭﺍﺕ ( ﻟﺯﻭﻡ ﻗﺳﻡ ﺍﻹﺳﻌﺎﻑ ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ‬
‫ﺍﻟﻔﻧﻳﺔ‪/‬ﻣﻘﻁﻭﻉ‬
‫‪ .٥‬ﺗﻘﺩﻳﻡ ﻭﺗﻧﻔﻳﺫ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺷﺑﻛﺔ ﺗﺄﺭﻳﺽ ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ﻣﻥ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﺃﻣﺭﺍﺱ ﻭﻛﺎﺑﻼﺕ ﻭﺃﻭﺗﺎﺩ‬
‫ﻭﻓﻘﺎ ً ﻟﻠﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻭﺍﻟﻣﺧﻁﻁﺎﺕ ﻟﺯﻭﻡ ﺃﻋﻣﺎﻝ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‪/‬ﻣﻘﻁﻭﻉ‬
‫‪ .٦‬ﺗﻘﺪﻳﻢ ﻭﺗﺮﻛﻴﺐ ﻭﺗﻮﺻ ﻴﻞ ﺷ ﺒﻜﺔ ﻣﺎﻧﻌﺎﺕ ﺍﻟﺼ ﻮﺍﻋﻖ ﻣﻊ ﺗﻘﺪﻳﻢ ﻭﺗﺮﻛﻴﺐ ﺃﻣﺮﺍﺱ ﻭﻛﺎﺑﻼﺕ ﻭﺃﻭﺗﺎﺩ ﻣﻊ ﻛﻞ ﻣﺎﻳﻠﺰﻡ‪:‬‬
‫‪/‬ﻣﻘﻄﻮﻉ‪/‬‬

‫أ‪.‬اﳌﻮاﺻﻔﺎت اﻟﻔﻨﻴﺔ ﻟﻸﻋﻤﺎل اﻟﻜﻬﺮ ﺋﻴﺔ ﻟﺰوم اﻹ رة واﳌﺂﺧﺬ واﳋﺪﻣﺎت‪:‬‬


‫‪ ‬ﺷﺭﻭﻁ ﻋﺎﻣﺔ‪:‬‬
‫ﺟﻣﻳﻊ ﺗﻣﺩﻳﺩﺍﺕ ﺍﻹﻧﺎﺭﺓ ﻭﺍﻟﻣﺂﺧﺫ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﻅﺎﻫﺭ‪.‬‬ ‫‪-‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺍﻟﻘﻳﻡ ﺍﻹﺳﻣﻳﺔ ﻟﻠﻣﻔﺎﺗﻳﺢ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﻣﻘﺩﻣﺔ )‪٢٥٠‬ﻓﻭﻟﺕ‪٥٠,‬ﻫﺭﺗﺯ‪١٠,‬ﺃﻣﺑﻳﺭ(‪.‬‬ ‫‪-‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺍﻟﻘﻳﻡ ﺍﻹﺳﻣﻳﺔ ﻟﻠﻣﺂﺧﺫ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﻣﻘﺩﻣﺔ )‪٢٥٠‬ﻓﻭﻟﺕ‪٥٠,‬ﻫﺭﺗﺯ‪١٦,‬ﺃﻣﺑﻳﺭ(‪.‬‬ ‫‪-‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﻣﻘﺎﻁﻊ ﺍﻷﺳﻼﻙ ﻟﺯﻭﻡ ﺗﻣﺩﻳﺩﺍﺕ ﺍﻟﻧﻘﻁﺔ ﺍﻟﺿﻭﺋﻳﺔ ) ﺍﻹﻧﺎﺭﺓ ( ﻻﺗﻘﻝ ﻋﻥ )‪١٬٥‬ﻣﻡ‪.( ٢‬‬ ‫‪-‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﻣﻘﺎﻁﻊ ﺍﻷﺳﻼﻙ ﻟﺯﻭﻡ ﺗﻣﺩﻳﺩﺍﺕ ) ﺍﻟﻣﺂﺧﺫ ( ﻻﺗﻘﻝ ﻋﻥ )‪٢٬٥‬ﻣﻡ‪.( ٢‬‬ ‫‪-‬‬
‫ﻳﺗﻡ ﺗﺭﻛﻳﺏ ﺍﻟﻣﻔﺎﺗﻳﺢ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻋﻠﻰ ﺇﺭﺗﻔﺎﻉ )‪١٢٠‬ﺳ ﻡ( ﻋﻥ ﺳ ﻁﺢ ﺍﻟﺑﻼﻁ ﻭﻋﻠﻰ ﺑﻌﺩ )‪٢٠‬ﺳ ﻡ( ﻣﻥ ﺣﺎﺟﺏ ﺍﻟﺑﺎﺏ‬ ‫‪-‬‬
‫ﻓﻲ ﺍﻟﺟﻬﺔ ﺍﻟﻣﻔﺗﻭﺣﺔ ﻣﻧﻪ ﺣﺳﺏ ﺗﻭﺟﻳﻬﺎﺕ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ‪.‬‬
‫ﻳﺗﻡ ﺗﺭﻛﻳﺏ ﺍﻟﻣﺂﺧﺫ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻋﻠﻰ ﺇﺭﺗﻔﺎﻉ )‪٤٠‬ﺳﻡ( ﻋﻥ ﺳﻁﺢ ﺍﻟﺑﻼﻁ ﺣﺳﺏ ﺗﻭﺟﻳﻬﺎﺕ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ‬ ‫‪-‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﻛﺎﻓﺔ ﺍﻟﻛﺎﺑﻼﺕ ﻭﺍﻷﺳ ﻼﻙ ﺍﻟﻣﻘﺩﻣﺔ ﺑﻣﻘﺎﻁﻌﻬﺎ ﺍﻟﻣﺧﺗﻠﻔﺔ ﻣﻥ ﻧﻭﻉ )ﻣﺑﺭﻭﻡ ‪ NYY‬ﺷ ﻌﺭﻱ( ﺑﺗﻭﺗﺭ ﻋﺯﻝ‬ ‫‪-‬‬
‫)‪١٠٠٠/٦٠٠‬ﻭﺍﻁ( ﺑﺄﻟﻭﺍﻥ ﻣﺧﺗﻠﻔﺔ ﻭﺃﻥ ﺗﺗﺣﻣﻝ ﺩﺭﺟﺔ ﺣﺭﺍﺭﺓ ﻋﻣﻝ ﻋﻅﻣﻰ )‪٧٠‬ﺩﺭﺟﺔ ﻣﺋﻭﻳﺔ ( ﻭﺃﻥ ﺗﻛﻭﻥ ﺧﺎﺿﻌﺔ ﻟﺗﻭﺗﺭ‬
‫ﺇﺧﺗﺑﺎﺭ )‪٤‬ﻛﻳﻠﻭ ﻓﻭﻟﺕ( ﻭﺃﻥ ﻳﻛﻭﻥ ﻗﺎﺑﻝ ﻟﻼﺳﺗﺧﺩﺍﻡ ﻓﻲ ﺷﺑﻛﺎﺕ ﺍﻟﺗﻭﺯﻳﻊ ﺫﺍﺕ ﺍﻟﺗﻭﺗﺭ ﺍﻟﻣﻧﺧﻔﺽ ‪.‬‬

‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺗﻣﺩﻳﺩﺍﺕ ﺍﻟﻣﺂﺧﺫ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻣﻧﻔﺻﻠﺔ ﻋﻥ ﺗﻣﺩﻳﺩﺍﺕ ﺍﻹﻧﺎﺭﺓ ﺑﻘﺳﺎﻁﻝ ﻭﺃﺳﻼﻙ ﻣﺳﺗﻘﻠﺔ ﺧﺎﺻﺔ ﺑﻛﻝ ﻣﻧﻬﺎ‪.‬‬ ‫‪-‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﻋﻠﺏ ﺍﻟﺗﻭﺯﻳﻊ ﻭﺍﻟﺗﻳﺏ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﺑﻼﺳﺗﻳﻛﻲ ﻏﻳﺭﻗﺎﺑﻝ ﻟﻠﻛﺳﺭ ﻭﻣﻥ ﺃﺟﻭﺩ ﺍﻷﻧﻭﺍﻉ ﺍﻟﻣﺗﻭﻓﺭﺓ ﻓﻲ ﺍﻟﺳﻭﻕ‬ ‫‪-‬‬
‫ﺍﻟﻣﺣﻠﻳﺔ‪.‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺟﻣﻳﻊ ﺍﻟﻣﺂﺧﺫ ﻭﺍﻟﻣﻔﺎﺗﻳﺢ ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﻗﺑﻝ ﺍﻟﻌﺎﺭﺽ ﻫﻲ ﻣﻥ ﺃﺟﻭﺩ ﺍﻟﻣﺎﺭﻛﺎﺕ ﺍﻟﻣﺗﻭﻓﺭﺓ ﻓﻲ ﺍﻟﺳﻭﻕ ﺍﻟﻣﺣﻠﻳﺔ‬ ‫‪-‬‬
‫ﻳﺗﻡ ﺗﻘﺩﻳﻡ ﻧﻣﺎﺫﺝ ﻣﻧﻬﺎ ﻟﻠﻣﺻﺎﺩﻗﺔ ﻋﻠﻳﻬﺎ ﻣﻥ ﻗﺑﻝ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﺃﺻﻭﻻً ﻗﺑﻝ ﺍﻟﺗﺭﻛﻳﺏ‪.‬‬

‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺍﻟﻛﺎﺑﻼﺕ ﻭﺍﻷﺳﻼﻙ ﺑﻣﻘﺎﻁﻌﻬﺎ ﺍﻟﻣﺧﺗﻠﻔﺔ ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﻗﺑﻝ ﺍﻟﻌﺎﺭﺽ ﺻﻧﺎﻋﺔ )ﺍﻟﺷﺭﻛﺔ ﺍﻟﻌﺎﻣﺔ ﻟﻠﻛﺎﺑﻼﺕ‬ ‫‪-‬‬
‫) ﺣﻭﺵ ﺑﻼﺱ( ﺃﻭ ﺍﻟﺷﺭﻛﺔ ﺍﻟﺳﻭﺭﻳﺔ ﻟﻠﻛﺎﺑﻼﺕ‪....‬ﺃﻭ ﻣﺎﻳﻌﺎﺩﻟﻬﺎ(‪.‬‬
‫ﻳﺟ ﺏ ﺃﻥ ﺗﻛﻭﻥ ﻛ ﺎﻓ ﺔ ﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻠﻭﺣ ﺎﺕ ﺍﻟﻛﻬﺭﺑ ﺎﺋﻳ ﺔ ﺍﻟﺟ ﺩﻳ ﺩﺓ ) ﺍﻹﻧ ﺎﺭﺓ ﻭﺍﻟﻣ ﺂﺧ ﺫ ﻭﺍﻟﺧ ﺩﻣ ﺎﺕ ( ) ﺍﻟﻘﻭﺍﻁﻊ (‬ ‫‪-‬‬
‫ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﻗﺑﻝ ﺍﻟﻌﺎﺭﺽ ﺻ ﻧﺎﻋﺔ ﺇﺣﺩﻯ ﺍﻟﺷ ﺭﻛﺎﺕ ) ﺍﻳﺗﻭﻥ ‪-‬ﺷ ﻧﺎﻳﺩﺭ‪ ABB -‬ﺃﻭ ﻣﺎﻳﻌﺎﺩﻟﻬﺎ ( ﺿ ﻣﻥ ﺍﻟﻣﻭﺍﺻ ﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﺩﺭﺟﺔ‬
‫ﺃﺩﻧﺎﻩ ﺃﻣﺎ ﺑﺎﻗﻲ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ)ﻟﻣﺑﺎﺕ ﺍﻹﺷﺎﺭﺓ( ﻣﻥ ﻧﻔﺱ ﺍﻟﺷﺭﻛﺎﺕ ﺍﻟﻣﺻﻧﻌﺔ ﻟﻠﻘﻭﺍﻁﻊ ﻳﺗﻡ ﺗﻘﺩﻳﻡ ﻧﻣﺎﺫﺝ ﻣﻧﻬﺎ ﻟﻠﻣﺻﺎﺩﻗﺔ ﻋﻠﻳﻬﺎ‬
‫ﻣﻥ ﻗﺑﻝ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﺃﺻﻭﻻً‪.‬‬
‫‪ .١‬ﺗﻘ ﺩﻳﻡ ﻭﺗﻣﺩﻳ ﺩ ﻭﺗﻭﺻ ﻳﻝ ﻛ ﺎﺑﻼﺕ ﺍﻟﺗﻐﺫﻳ ﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳ ﺔ ﺍﻟﺭﺋﻳﺳ ﻳﺔ ﺑ ﻳﻥ ﻣﺻ ﺎﺩﺭ ﺍﻟﺗﻐﺫﻳ ﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳ ﺔ‬
‫)ﺍﻟﻣﺧ ﺭﺝ ﺍﻟﻣﺷﺗﺭﻙ))ﺷ ﺑﻛﺔ‪-‬ﻣﺟﻣﻭﻋ ﺔ(( – ﻛﻬﺭﻭﺿ ﻭﺋﻳﺔ ( ﻭﺍﻟﻠﻭﺣ ﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳ ﺔ ﺍﻟﺛﺎﻧﻭﻳ ﺔ ﺍﻟﺟﺩﻳ ﺩﺓ‬
‫ﺑﻣﻘﺎﻁﻌﻬﺎ ﺍﻟﻣﺧﺗﻠﻔﺔ ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ‪/‬ﻡ‪.‬ﻁ‪/‬‬
‫ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣ ﻝ ﺗﻘ ﺩﻳﻡ ﻛ ﺎﺑﻼﺕ ﺗﻐﺫﻳ ﺔ ﻛﻬﺭﺑﺎﺋﻳ ﺔ ﻣﺑﺭﻭﻣ ﺔ‪ NYY‬ﺷ ﻌﺭﻱ)‪ (AC‬ﺑﻣﻘﺎﻁﻌﻬ ﺎ ﺍﻟﻣﺧﺗﻠﻔ ﺔ ﺍﻟﻣﺷ ﺎﺭ ﺇﻟﻳﻬ ﺎ ﻓ ﻲ ﻣﻘﺩﻣ ﺔ ﺍﻹﺿ ﺑﺎﺭﺓ‬
‫ﺍﻟﻔﻧﻳ ﺔ ﻭﺑﺎﻟﻣﻭﺍﺻ ﻔﺎﺕ ﺍﻟﻔﻧﻳ ﺔ ﺍﻟﻣﺷ ﺎﺭ ﺇﻟﻳﻬ ﺎ ﻓ ﻲ ﺍﻟﺷ ﺭﻭﻁ ﺍﻟﻌﺎﻣ ﺔ ﻟ ﺯﻭﻡ ﺗﻐﺫﻳ ﺔ ﺍﻟﻠﻭﺣ ﺎﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳ ﺔ ﺍﻟﺛﺎﻧﻭﻳ ﺔ ﺍﻟﺟﺩﻳ ﺩﺓ ﻣ ﻥ‬
‫ﻣﺻ ﺎﺩﺭ ﺍﻟﺗﻐﺫﻳ ﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳ ﺔ )ﻣﺧ ﺭﺝ ﻣﺷ ﺗﺭﻙ "ﺷ ﺑﻛﺔ‪-‬ﻣﺟﻣﻭﻋ ﺔ" ‪ -‬ﻛﻬﺭﻭﺿ ﻭﺋﻳﺔ( ﻭﻧﻘﻠﻬ ﺎ ﺇﻟ ﻰ ﻣﻭﻗ ﻊ ﺍﻟﻌﻣ ﻝ ﺣﻳ ﺙ‬
‫ﻳ ﺗﻡ ﻧﻘﻠﻬ ﺎ ﻋﻠ ﻰ ﺣﺳ ﺎﺏ ﺍﻟﻣﺗﻌﻬ ﺩ ﺑﺷ ﻛﻝ ﻓﻧ ﻲ ﻭﺳ ﻠﻳﻡ ‪ ,‬ﻭﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣ ﻝ ﻋﻣﻠﻳ ﺎﺕ ﺍﻟﺗﺳ ﺣﻳﺏ ﻭﺍﻟﺗﻣﺩﻳ ﺩ ﺿ ﻣﻥ ﻗﺳ ﺎﻁﻝ ﺍﻟ ـ‬
‫‪ PVC‬ﺃﻭﻣﺟ ﺎﺭﻱ ﺑﻼﺳ ﺗﻳﻛﻳﺔ ﺃﻭﻣﻌﺩﻧﻳ ﺔ ﺗﺛﺑ ﺕ ﺟ ﺩﺍﺭﻳﺎ" ﺑﺷ ﻛﻝ ﻓﻧ ﻲ ﻭﺫﻟ ﻙ ﺑﻣﻘ ﺎﻁﻊ ﻣﺗﻧﺎﺳ ﺑﺔ ﻣ ﻊ ﻣﻘ ﺎﻁﻊ ﺍﻟﻛ ﺎﺑﻼﺕ‬
‫ﻭﺫﻟﻙ ﻭﻓﻖ ﺍﻟﻣﺧﻁﻁﺎﺕ ﺍﻟﺻﻧﺩﻭﻗﻳﺔ ﺍﻟﺗﺻﻣﻳﻣﻳﺔ ﻟﻁﺭﻳﻘﺔ ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻓﻲ ﻛﻝ ﻣﺷﺭﻭﻉ ﻭﺍﻟﻣﺭﻓﻘﺔ ﺑﺎﻹﺿﺑﺎﺭﺓ ﺍﻟﻔﻧﻳﺔ‪.‬‬
‫ﻭﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣ ﻝ ﺍﻟﺗﺄﻛ ﺩ ﻣ ﻥ ﺟﺎﻫﺯﻳ ﺔ ﻗﺳ ﺎﻁﻝ ﺍﻟﺗﻣﺩﻳ ﺩ ﻭﻓ ﻲ ﺣ ﺎﻝ ﻅﻬ ﻭﺭ ﻗﺳ ﺎﻁﻝ ﻏﻳ ﺭ ﺳ ﺎﻟﻛﺔ ﻳﺗﺭﺗ ﺏ ﻋﻠ ﻰ ﺍﻟﻣﺗﻌﻬ ﺩ‬
‫ﺍﻟﻘﻳ ﺎﻡ ﺑﻌﻣﻠﻳ ﺎﺕ ﺍﻟﺣﻔ ﺭ ﻭﺗﻘ ﺩﻳﻡ ﻭﺗﺭﻛﻳ ﺏ ﻗﺳ ﻁﻝ ﺟﺩﻳ ﺩ ﻭﺇﻋ ﺎﺩﺓ ﺗﺳ ﻭﻳﺔ ﺍﻟﺳ ﻁﻭﺡ ﻛﻣ ﺎ ﻛﺎﻧ ﺕ ﻋﻠﻳ ﻪ ﻭﻛ ﻝ ﻣ ﺎ ﻳﻠ ﺯﻡ ﻟﻠﻣﺳ ﺎﻓﺔ‬
‫ﺍﻟﺗ ﻲ ﻗ ﺩ ﺗﻅﻬ ﺭ ﻣﻐﻠﻘ ﺔ ﻟﺗ ﺄﻣﻳﻥ ﺟﺎﻫﺯﻳ ﺔ ﺍﻟﻌﻣ ﻝ ﺑﺷ ﻛﻝ ﻓﻧ ﻲ‪ ،‬ﻣ ﻊ ﺗﻘ ﺩﻳﻡ ﻛﺎﻓ ﺔ ﻣﺳ ﺗﻠﺯﻣﺎﺕ ﺍﻟﺗﻣﺩﻳ ﺩ ﻭﺍﻟﺗﺛﺑﻳ ﺕ ﻭﺍﻟﺗﻭﺻ ﻳﻝ‬
‫ﺣﺳﺏ ﻭﺍﻗﻊ ﺍﻟﻌﻣﻝ ﻭﺗﻌﻠﻳﻣﺎﺕ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﺑﺣﻳﺙ ﻳﻛﻭﻥ ﺍﻟﻌﻣﻝ ﻭﻓﻖ ﺃﻓﺿﻝ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﻭﺍﻟﺟﻭﺩﺓ ﺍﻟﻔﻧﻳﺔ ‪.‬‬

‫ﻳﺗﻡ ﺗﻘﺩﻳﻡ ﺍﻟﻛﺎﺑﻼﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻣﻥ ﺍﺣﺩﻯ ﺍﻟﺷﺭﻛﺎﺕ ﺍﻟﻣﺻﻧﻌﺔ ﻟﻠﻛﺎﺑﻼﺕ )ﺣﻭﺵ ﺑﻼﺱ ﺃﻭ ﺍﻟﺳﻭﺭﻳﺔ ﻟﻠﻛﺎﺑﻼﺕ ‪ .......‬ﺃﻭﻣﺎﻳﻌﺎﺩﻟﻬﺎ(‬
‫ﺣﺳﺏ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺳﻭﺭﻳﺔ) ‪ (IEC‬ﺃﻭ ﺣﺳﺏ ﺍﻟﻣﻭﺍﺻﻔﺔ ﺍﻷﻟﻣﺎﻧﻳﺔ ) ‪. (VDE‬‬
‫ﻛﻣﺎ ﻳﻘﻊ ﻋﻠﻰ ﻋﺎﺗﻖ ﺍﻟﻣﺗﻌﻬﺩ ﺗﻭﺻ ﻳﻝ ﺑﺩﺍﻳﺎﺕ ﻭﻧﻬﺎﻳﺎﺕ ﺍﻟﻛﺎﺑﻼﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺣﻳﺙ ﺗﻛﻭﻥ ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻟﻠﻭﺣﺔ ﺟﺎﻫﺯﺓ‬
‫ﻟﻠﻌﻣﻝ ﺑﺎﻟﺷﻛﻝ ﺍﻷﻣﺛﻝ ﻭﻓﻘﺎ" ﻟﺗﻌﻠﻳﻣﺎﺕ ﺍﻹﺩﺍﺭﺓ‪.‬‬
‫ﻳﻘﺩﺭ ﺍﻟﻌﻣﻝ ﺑﺎﻟﻣﺗﺭ ﺍﻟﻁﻭﻟﻲ‪.‬‬
‫‪ .٢‬ﺗﻘ ﺪﻳﻢ ﻭﺗﻤﺪﻳ ﺪ ﻭﺗﻮﺻ ﻴﻞ ﻛ ﺎﺑﻼﺕ ﺍﻟﺘﻐﺬﻳ ﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴ ﺔ ﺍﻟﺮﺋﻴﺴ ﻴﺔ ﺑ ﻴﻦ ﻧﻬﺎﻳ ﺔ ﺍﻷﻟ ﻮﺍﺡ ﻭﺍﻻﻧﻔﻴﺮﺗ ﺮ‬
‫ﺑﻤﻘﻄﻊ )‪ ١٦×٢‬ﻣﻢ‪( DC) (٢‬ﻣﻊ ﻛﻞ ﻣﺎ ﻳﻠﺰﻡ‪ /‬ﻡ‪.‬ﻁ‬

‫ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣ ﻝ ﺗﻘ ﺩﻳﻡ ﻛ ﺎﺑﻼﺕ ﺗﻐﺫﻳ ﺔ ﻛﻬﺭﺑﺎﺋﻳ ﺔ ﺛﻧﺎﺋﻳ ﺔ ﻣﺑﺭﻭﻣ ﺔ‪ NYY‬ﺷ ﻌﺭﻱ ﺑﻣﻘﻁ ﻊ )‪١٦×٢‬ﻣ ﻡ‪ DC ( ٢‬ﻟ ﺯﻭﻡ ﺗﻐﺫﻳ ﺔ ﺍﻻﻧﻔﻳﺭﺗ ﺭ‬
‫ﻣ ﻥ ﺍﻷﻟ ﻭﺍﺡ ﺑ ﺎﻟﻣﻘﻁﻊ ﺍﻟﻣﺷ ﺎﺭ ﺇﻟﻳ ﻪ ﻟﻛﺎﻓ ﺔ ﺍﻟﻣﺷ ﺎﺭﻳﻊ ﺍﻟﻣ ﺫﻛﻭﺭﺓ ﻭﻧﻘﻠﻬ ﺎ ﺇﻟ ﻰ ﻣﻭﻗ ﻊ ﺍﻟﻌﻣ ﻝ ﺣﻳ ﺙ ﻳ ﺗﻡ ﻧﻘﻠﻬ ﺎ ﻋﻠ ﻰ ﺣﺳ ﺎﺏ‬
‫ﺍﻟﻣﺗﻌﻬ ﺩ ﺑﺷ ﻛﻝ ﻓﻧ ﻲ ﻭﺳ ﻠﻳﻡ ‪ ,‬ﻭﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣ ﻝ ﻋﻣﻠﻳ ﺎﺕ ﺍﻟﺗﺳ ﺣﻳﺏ ﻭﺍﻟﺗﻣﺩﻳ ﺩ ﺿ ﻣﻥ ﻗﺳ ﺎﻁﻝ ﺍﻟ ـ ‪ PVC‬ﺃﻭﻣﺟ ﺎﺭﻱ‬
‫ﺑﻼﺳ ﺗﻳﻛﻳﺔ ﺃﻭﻣﻌﺩﻧﻳ ﺔ ﺗﺛﺑ ﺕ ﺟ ﺩﺍﺭﻳﺎ" ﺑﺷ ﻛﻝ ﻓﻧ ﻲ ﻭﺫﻟ ﻙ ﺑﻣﻘ ﺎﻁﻊ ﻣﺗﻧﺎﺳ ﺑﺔ ﻣ ﻊ ﻣﻘ ﺎﻁﻊ ﺍﻟﻛ ﺎﺑﻼﺕ‬
‫ﻭﺫﻟ ﻙ ﻭﻓ ﻖ ﺍﻟﻣﺧﻁﻁ ﺎﺕ ﺍﻟﺻ ﻧﺩﻭﻗﻳﺔ ﺍﻟﺗﺻ ﻣﻳﻣﻳﺔ ﻟﻁﺭﻳﻘ ﺔ ﺍﻟﺗﻐﺫﻳ ﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳ ﺔ ﻓ ﻲ ﻛ ﻝ ﻣﺷ ﺭﻭﻉ ﻭﺍﻟﻣﺭﻓﻘ ﺔ ﺑﺎﻹﺿ ﺑﺎﺭﺓ‬
‫ﺍﻟﻔﻧﻳﺔ‪.‬‬
‫ﻭﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣ ﻝ ﺍﻟﺗﺄﻛ ﺩ ﻣ ﻥ ﺟﺎﻫﺯﻳ ﺔ ﻗﺳ ﺎﻁﻝ ﺍﻟﺗﻣﺩﻳ ﺩ ﻭﻓ ﻲ ﺣ ﺎﻝ ﻅﻬ ﻭﺭ ﻗﺳ ﺎﻁﻝ ﻏﻳ ﺭ ﺳ ﺎﻟﻛﺔ ﻳﺗﺭﺗ ﺏ ﻋﻠ ﻰ ﺍﻟﻣﺗﻌﻬ ﺩ‬
‫ﺍﻟﻘﻳ ﺎﻡ ﺑﻌﻣﻠﻳ ﺎﺕ ﺍﻟﺣﻔ ﺭ ﻭﺗﻘ ﺩﻳﻡ ﻭﺗﺭﻛﻳ ﺏ ﻗﺳ ﻁﻝ ﺟﺩﻳ ﺩ ﻭﺇﻋ ﺎﺩﺓ ﺗﺳ ﻭﻳﺔ ﺍﻟﺳ ﻁﻭﺡ ﻛﻣ ﺎ ﻛﺎﻧ ﺕ ﻋﻠﻳ ﻪ ﻭﻛ ﻝ ﻣ ﺎ ﻳﻠ ﺯﻡ ﻟﻠﻣﺳ ﺎﻓﺔ‬
‫ﺍﻟﺗ ﻲ ﻗ ﺩ ﺗﻅﻬ ﺭ ﻣﻐﻠﻘ ﺔ ﻟﺗ ﺄﻣﻳﻥ ﺟﺎﻫﺯﻳ ﺔ ﺍﻟﻌﻣ ﻝ ﺑﺷ ﻛﻝ ﻓﻧ ﻲ‪ ،‬ﻣ ﻊ ﺗﻘ ﺩﻳﻡ ﻛﺎﻓ ﺔ ﻣﺳ ﺗﻠﺯﻣﺎﺕ ﺍﻟﺗﻣﺩﻳ ﺩ ﻭﺍﻟﺗﺛﺑﻳ ﺕ ﻭﺍﻟﺗﻭﺻ ﻳﻝ‬
‫ﺣﺳﺏ ﻭﺍﻗﻊ ﺍﻟﻌﻣﻝ ﻭﺗﻌﻠﻳﻣﺎﺕ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﺑﺣﻳﺙ ﻳﻛﻭﻥ ﺍﻟﻌﻣﻝ ﻭﻓﻖ ﺃﻓﺿﻝ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﻭﺍﻟﺟﻭﺩﺓ ﺍﻟﻔﻧﻳﺔ ‪.‬‬
‫ﻳﺗﻡ ﺗﻘﺩﻳﻡ ﺍﻟﻛﺎﺑﻼﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻣﻥ ﺍﺣﺩﻯ ﺍﻟﺷﺭﻛﺎﺕ ﺍﻟﻣﺻﻧﻌﺔ ﻟﻠﻛﺎﺑﻼﺕ )ﺣﻭﺵ ﺑﻼﺱ ﺃﻭ ﺍﻟﺳﻭﺭﻳﺔ ﻟﻠﻛﺎﺑﻼﺕ ﺃﻭ ﺍﻻﺗﺣﺎﺩ‬
‫‪....‬ﺃﻭﻣﺎﻳﻌﺎﺩﻟﻬﺎ( ﺣﺳﺏ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺳﻭﺭﻳﺔ) ‪ (IEC‬ﺃﻭ ﺣﺳﺏ ﺍﻟﻣﻭﺍﺻﻔﺔ ﺍﻷﻟﻣﺎﻧﻳﺔ ) ‪. (VDE‬‬
‫ﻛﻣﺎ ﻳﻘﻊ ﻋﻠﻰ ﻋﺎﺗﻖ ﺍﻟﻣﺗﻌﻬﺩ ﺗﻭﺻ ﻳﻝ ﺑﺩﺍﻳﺎﺕ ﻭﻧﻬﺎﻳﺎﺕ ﺍﻟﻛﺎﺑﻼﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺣﻳﺙ ﺗﻛﻭﻥ ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻟﻠﻭﺣﺔ ﺟﺎﻫﺯﺓ‬
‫ﻟﻠﻌﻣﻝ ﺑﺎﻟﺷﻛﻝ ﺍﻷﻣﺛﻝ ﻭﻓﻘﺎ" ﻟﺗﻌﻠﻳﻣﺎﺕ ﺍﻹﺩﺍﺭﺓ‪.‬‬
‫ﻳﻘﺩﺭ ﺍﻟﻌﻣﻝ ﺑﺎﻟﻣﺗﺭ ﺍﻟﻁﻭﻟﻲ‪.‬‬

‫‪ .٣‬ﺗﻘﺪﻳﻢ ﻭﺗﻤﺪﻳﺪ ﻭﺗﺮﻛﻴﺐ ﻭﺗﻮﺻﻴﻞ ﻧﻘﻄﺔ ﺿﻮﺋﻴﺔ ﻅﺎﻫﺮﺓ ﺟﺪﻳﺪﺓ ﻣﻊ ﻛﻞ ﻣﺎ ﻳﻠﺰﻡ‪/:‬ﻋﺪﺩ‪.‬‬


‫ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻧﻘﻁﺔ ﺿ ﻭﺋﻳﺔ ﻅﺎﻫﺭﺓ ﻓﻲ ﻣﻭﻗﻊ ﺍﻟﻌﻣﻝ ﺣﺳ ﺏ ﺍﻟﻣﺧﻁﻁﺎﺕ ﺍﻟﺗﺻ ﻣﻳﻣﻳﺔ ﻭﺗﻌﻠﻳﻣﺎﺕ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ‬
‫ﻟﺯﻭﻡ ﻣﺷﺭﻭﻋﻲ ﺍﻟﺻﺎﺧﻭﺭ ﻭﻣﺷﻔﻰ ﺍﻷﻁﻔﺎﻝ ﻓﻘﻁ ﺣﻳﺙ )‪ ٥٨‬ﻧﻘﻁﺔ ﻟﻠﺻﺎﺧﻭﺭ ﻭ ‪ ٧٦‬ﻧﻘﻁﺔ ﻟﻣﺷﻔﻰ ﺍﻷﻁﻔﺎﻝ( ﻣﻊ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ‬
‫ﻭﺗﺳ ﺣﻳﺏ ﺍﻷﺳ ﻼﻙ ﻭﺍﻟﻛﺎﺑﻼﺕ ﻭﺍﻟﻣﺟﺎﺭﻱ ﻭﺍﻟﻌﻠﺏ ﺍﻟﺑﻼﺳ ﺗﻳﻛﻳﺔ )ﻟﻠﻣﻔﺎﺗﻳﺢ ﻭﻧﻘﻁ ﺍﻟﺗﻭﺯﻳﻊ( ﻭﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ﻟﺗﻣﺩﻳﺩﺍﺕ ﺍﻟﻧﻘﻁﺔ‬
‫ﺍﻟﺿ ﻭﺋﻳﺔ ﻣﻊ ﻣﺳ ﺗﻠﺯﻣﺎﺕ ﺗﺛﺑﻳﺕ ﺍﻟﻣﺟﺎﺭﻱ‪ ،‬ﺣﻳﺙ ﺗﻌﺗﺑﺭ ﻛﻝ ﻧﻘﻁﺔ ﺗﻐﺫﻳﺔ ﻟﺟﻬﺎﺯ ﺇﻧﺎﺭﺓ ﻣﺳ ﻁﺢ ﺑﻠﻳﺩﺍﺕ ﺃﻭﺟﻬﺎﺯ ﺇﻧﺎﺭﺓ ﻣﻳﺗﺎﻝ‬
‫ﺟﺩﺍﺭﻱ ﻫﻲ ﻧﻘﻁﺔ ﺿ ﻭﺋﻳﺔ ﺃﻱ ﻋﺩﺩ ﺍﻟﻧﻘﺎﻁ ﺑﻌﺩﺩ ﺃﺟﻬﺯﺓ ﺍﻹﻧﺎﺭﺓ ﻭﻳﻘﻊ ﻋﻠﻰ ﻋﺎﺗﻖ ﺍﻟﻣﺗﻌﻬﺩ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻣﻔﺗﺎﺡ ﻋﻳﺎﺭ ‪ ١٠/‬ﺃﻣﺑﻳﺭ‪/‬‬
‫ﻭﻓﻖ ﺍﻟﻣﺧﻁﻁﺎﺕ ﺍﻟﺗﺻﻣﻳﻣﻳﺔ ﺍﻟﻣﺭﻓﻘﺔ ﺣﻳﺙ ﺳﻌﺭﻫﺎ ﻣﺣﻣﻠﺔ ﻋﻠﻰ ﺍﻟﺳﻌﺭ ﺍﻻﺟﻣﺎﻟﻲ ﻟﻠﻧﻘﺎﻁ ﺍﻟﺿﻭﺋﻳﺔ ﺍﻟﻣﻘﺩﻣﺔ ﺑﺣﻳﺙ ﻻﻳﺯﻳﺩ ﻋﺩﺩ ﺍﻟﻧﻘﺎﻁ‬
‫ﺍﻟﺿﻭﺋﻳﺔ ﻓﻲ ﻛﻝ ﻏﺭﻓﺔ ﻋﻥ ﻧﻘﻁﺔ ﺿﻭﺋﻳﺔ ﻭﺍﺣﺩﺓ‪.‬‬
‫ﻳﺷﻣﻝ ﺍﻟﻌﻣﻝ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ﻟﺗﻘﺩﻳﻡ ﺍﻟﻌﻣﻝ ﺑﺎﻟﺷﻛﻝ ﺍﻷﻣﺛﻝ ﻭﻓﻘﺎ" ﻟﺗﻭﺟﻳﻬﺎﺕ ﺍﻹﺩﺍﺭﺓ ﻭﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ‪.‬‬
‫ﺗﻘﺩﺭ ﺍﻷﻋﻣﺎﻝ ﺑﺎﻟﻌﺩﺩ‪.‬‬

‫‪ .٤‬ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻣﺄﺧﺫ ﻛﻬﺭﺑﺎﺋﻲ ﻋﺎﺩﻱ ﻣﺅﺭﺽ ﺃﺣﺎﺩﻱ ﻋﻳﺎﺭ ‪ ١٦‬ﺃﻣﺑﻳﺭ ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ‪/:‬ﻋﺩﺩ‪/‬‬
‫ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ﻟﺗﻣﺩﻳﺩﺍﺕ ﺍﻟﻣﺂﺧﺫ ﻣﻥ ﺃﺳ ﻼﻙ ﻭﻗﺳ ﺎﻁﻝ ﻭﻋﻠﺏ ﺑﻼﺳ ﺗﻳﻛﻳﺔ )ﺍﻟﻣﺄﺧﺫ ﻭﻧﻘﻁ ﺍﻟﺗﻭﺯﻳﻊ(‬
‫ﻣﻊ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻ ﻳﻝ ﻣﺄﺧﺫ ﻛﻬﺭﺑﺎﺋﻲ ﻋﺎﺩﻱ ﺃﺣﺎﺩﻱ ﻋﻳﺎﺭ ‪ ١٦‬ﺃﻣﺑﻳﺭ ﻟﺯﻭﻡ ﺍﻟﺧﺩﻣﺎﺕ ﻭﺫﻟﻙ ﻭﻓﻖ ﺃﻓﺿ ﻝ ﺍﻟﻣﻭﺍﺻ ﻔﺎﺕ‬
‫ﻭﺑﺟﻭﺩﺓ ﻓﻧﻳﺔ ﻋﺎﻟﻳﺔ ﻭ ﺫﻟﻙ ﺣﺳ ﺏ ﺗﻌﻠﻳﻣﺎﺕ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﻟﺯﻭﻡ ﺍﻟﻣﺷ ﺎﺭﻳﻊ ﺍﻟﺛﻼﺙ ﺍﻟﻣﺫﻛﻭﺭﺓ )ﺍﻟﺻ ﺎﺧﻭﺭ ‪ ٤٦‬ﻣﺄﺧﺫ ‪ ,‬ﻣﺷ ﻔﻰ‬
‫ﺍﻷﻁﻔﺎﻝ ‪ ٤٨‬ﻣﺄﺧﺫ ‪ ,‬ﺟﺭﻣﺎﻧﺎ ‪(١٣‬ﺣﻳﺙ ﻳﻘﺩﻡ ﻣﻧﻪ ﻧﻣﻭﺫﺝ ﻳﺗﻡ ﺍﻟﻣﻭﺍﻓﻘﺔ ﻋﻠﻳﻪ ﻣﻥ ﻗﺑﻝ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﻗﺑﻝ ﺍﻟﺗﺭﻛﻳﺏ‪.‬‬
‫ﻭﻛﻝ ﻣﺎﻳﻠﺯﻡ ﻟﺗﺳﻠﻳﻡ ﺍﻟﻌﻣﻝ ﺟﺎﻫﺯﺍ" ﻟﺗﻘﺩﻳﻡ ﺍﻟﻌﻣﻝ ﺑﺎﻟﺷﻛﻝ ﺍﻷﻣﺛﻝ ﻭﻓﻘﺎ" ﻟﺗﻌﻠﻳﻣﺎﺕ ﺍﻹﺩﺍﺭﺓ‪.‬‬
‫ﻳﻘﺩﺭ ﺍﻟﻌﻣﻝ ﺑﺎﻟﻌﺩﺩ‪.‬‬

‫‪ .٥‬ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻣﺄﺧﺫ ﻛﻬﺭﺑﺎﺋﻲ ﻣﻥ ﻧﻭﻉ ﺷﻭﻛﻭ ﻣﺅﺭﺽ ﺃﺣﺎﺩﻱ ﻋﻳﺎﺭ ‪ ١٦‬ﺃﻣﺑﻳﺭ ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ‪/:‬ﻋﺩﺩ‪/‬‬
‫ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ﻟﺗﻣﺩﻳﺩﺍﺕ ﺍﻟﻣﺂﺧﺫ ﻣﻥ ﺃﺳ ﻼﻙ ﻭﻗﺳ ﺎﻁﻝ ﻭﻋﻠﺏ ﺑﻼﺳ ﺗﻳﻛﻳﺔ )ﺍﻟﻣﺄﺧﺫ ﻭﻧﻘﻁ ﺍﻟﺗﻭﺯﻳﻊ(‬
‫ﻣﻊ ﺗﻘ ﺩﻳﻡ ﻭﺗﺭﻛﻳ ﺏ ﻭﺗﻭﺻ ﻳ ﻝ ﻣ ﺄﺧ ﺫ ﻛﻬﺭﺑ ﺎﺋﻲ ﻣﻥ ﻧﻭﻉ ﺷ ﻭﻛﻭ ﺃﺣ ﺎﺩﻱ ﻋﻳ ﺎﺭ ‪ ١٦‬ﺃﻣﺑﻳﺭ ﻟﺯﻭﻡ ﺍﻟﺧ ﺩﻣ ﺎﺕ‬
‫ﻭﺫﻟﻙ ﻭﻓﻖ ﺃﻓﺿ ﻝ ﺍﻟﻣﻭﺍﺻ ﻔﺎﺕ ﻭﺑﺟﻭﺩﺓ ﻓﻧﻳﺔ ﻋﺎﻟﻳﺔ ﻭ ﺫﻟﻙ ﺣﺳ ﺏ ﺗﻌﻠﻳﻣﺎﺕ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﻟﺯﻭﻡ ﺍﻟﻣﺷ ﺎﺭﻳﻊ ﺍﻟﺛﻼﺙ ﺍﻟﻣﺫﻛﻭﺭﺓ‬
‫)ﺍﻟﺻ ﺎﺧﻭﺭ‪ ١٢‬ﻣﺄﺧﺫ ‪ ,‬ﻣﺷ ﻔﻰ ﺍﻷﻁﻔﺎﻝ ‪ ٢٧‬ﻣﺄﺧﺫ ‪ ,‬ﺟﺭﻣﺎﻧﺎ ‪(٢٢‬ﺣﻳﺙ ﻳﻘﺩﻡ ﻣﻧﻪ ﻧﻣﻭﺫﺝ ﻳﺗﻡ ﺍﻟﻣﻭﺍﻓﻘﺔ ﻋﻠﻳﻪ ﻣﻥ ﻗﺑﻝ ﻓﺭﻳﻖ‬
‫ﺍﻟﻣﺭﺍﻗﺑﺔ ﻗﺑﻝ ﺍﻟﺗﺭﻛﻳﺏ‪.‬‬
‫ﻭﻛﻝ ﻣﺎﻳﻠﺯﻡ ﻟﺗﻘﺩﻳﻡ ﺍﻟﻌﻣﻝ ﺑﺎﻟﺷﻛﻝ ﺍﻷﻣﺛﻝ ﻭﻓﻘﺎ ً ﻟﺗﻌﻠﻳﻣﺎﺕ ﺍﻹﺩﺍﺭﺓ‪.‬‬
‫ﻳﻘﺩﺭ ﺍﻟﻌﻣﻝ ﺑﺎﻟﻌﺩﺩ‪.‬‬
‫‪ .٦‬ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻟﻭﺣﺎﺕ ﺗﻐﺫﻳﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺟﺩﻳﺩﺓ ﻟﺯﻭﻡ ﺍﻹﻧﺎﺭﺓ ﻭﺍﻟﻣﺂﺧﺫ ﻭﺍﻟﺧﺩﻣﺎﺕ ﻣﻊ ﻛﻝ ﻣﺎﻳﻠﺯﻡ‪/:‬ﻋﺩﺩ‬
‫ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣ ﻝ ﺗﻘ ﺩﻳﻡ ﻭﺗﺭﻛﻳ ﺏ ﻭﺗﻭﺻ ﻳﻝ ﻟﻭﺣ ﺎﺕ ﺗﻐﺫﻳ ﺔ ﻛﻬﺭﺑﺎﺋﻳ ﺔ ﺟﺩﻳ ﺩﺓ ﻟ ﺯﻭﻡ ﺍﻹﻧ ﺎﺭﺓ ﻭﺍﻟﻣﺂﺧ ﺫ ﻭﺍﻟﺧ ﺩﻣﺎﺕ‬
‫ﻣ ﻥ ﺍﻟﻧ ﻭﻉ ﺍﻟﻅ ﺎﻫﺭ )ﺳ ﺑﻌﺔ ﻟ ﺯﻭﻡ ﻛﺗﻠﺗ ﻲ ﻣﺷ ﺭﻭﻉ ﺍﻟﺻ ﺎﺧﻭﺭ‪,‬ﺗﺳ ﻌﺔ ﻟ ﺯﻭﻡ ﻁﻭﺍﺑ ﻖ ﻭ ﻣﺻ ﺎﻋﺩ ﻣﺷ ﺭﻭﻉ ﻣﺷ ﻔﻰ ﺍﻷﻁﻔ ﺎﻝ‪,‬‬
‫ﺃﺭﺑﻌ ﺔ ﻟ ﺯﻭﻡ ﻁﻭﺍﺑ ﻖ ﻭ ﻗﺳ ﻡ ﺍﻻﺳ ﻌﺎﻑ ﻓ ﻲ ﻣﺷ ﺭﻭﻉ ﺟﺭﻣﺎﻧ ﺎ( ﻛﻣ ﺎ ﻫ ﻲ ﻣﻭﺿ ﺣﺔ ﻓ ﻲ ﺍﻟﻣﺧﻁﻁ ﺎﺕ‬
‫ﺍﻟﺗﺻ ﻣﻳﻣﻳﺔ ﺍﻟﻣﺭﻓﻘ ﺔ ﺑﺎﻹﺿ ﺑﺎﺭﺓ ﺍﻟﻔﻧﻳ ﺔ‪ ,‬ﻋﻠ ﻰ ﺃﻥ ﺗﻛ ﻭﻥ ﺍﻟﻠﻭﺣ ﺔ ﻣ ﻥ ﻧ ﻭﻉ ﻣﺎﺭﻛ ﺔ ﻣﻌﺭﻭﻓ ﺔ ﺍﻟﺟ ﻭﺩﺓ ﻭﺗﻛ ﻭﻥ ﺍﻟﻠﻭﺣ ﺔ‬
‫ﻣﺟﻬ ﺯﺓ ﺑﺑ ﺎﺏ ﺗﻅﻬ ﺭ ﻣﻧ ﻪ ﺃﺫﺭﻉ ﺍﻟﻘﻭﺍﻁ ﻊ ﻭﺑ ﺎﺏ ﺷ ﻔﺎﻑ ﻳﻐﻁ ﻲ ﺗﻠ ﻙ ﺍﻟﻘﻭﺍﻁ ﻊ ﻭﺗﺣ ﻭﻱ ﺍﻟﻠﻭﺣ ﺔ ﺑ ﺩﺍﺧﻠﻬﺎ ﺑ ﺎﺭ‬
‫ﻧﺗﺭ ﻭﺑﺎﺭ ﺃﺭﺿﻲ ﻟﺗﻭﺻﻳﻝ ﺷﺑﻛﺔ ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ‪.‬‬
‫ﻳﻛ ﻭﻥ ﺟﺳ ﻡ ﺍﻟﻠﻭﺣ ﺔ ﻣ ﻥ ﺍﻟ ـ‪ P.V.C‬ﺍﻟﻌ ﺎﺯﻝ ﻭﻳﺣ ﻭﻱ ﺳ ﻛﺔ ﻟﺗﺭﻛﻳ ﺏ ﺍﻟﻘﻭﺍﻁ ﻊ ﻋﻠ ﻰ ﺃﻥ ﺗﻛ ﻭﻥ ﺍﻟﻠﻭﺣ ﺔ ﻣ ﻥ ﺍﻟﻧ ﻭﻉ ﺍﻟﻛﺗ ﻳﻡ ﺍﻟﻣ ﺎﻧﻊ‬
‫ﻟﻠﺭﻁﻭﺑﺔ‪.‬‬
‫ﻛﻣﺎ ﻳﺗﺿﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻗﻭﺍﻁﻊ ﺍﻟﺣﻣﺎﻳﺔ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﺣﺭﺍﺭﻱ ﺍﻟﻣﻐﻧﺎﻁﻳﺳﻲ ﻭ ﻗﺎﻁﻊ ﺍﻟﺗﺑﺩﻳﻝ ﺍﻟﻳﺩﻭﻱ ﺳﻭﺍء ﺃﻛﺎﻥ ﺃﺣﺎﺩﻱ ﺃﻭ ﺭﺑﺎﻋﻲ‬
‫ﻭﻓﻖ ﺍﻟﻣﺧﻁﻁﺎﺕ ﺍﻟﺗﺻ ﻣﻳﻣﻳﺔ ﺍﻟﻣﺭﻓﻘﺔ ﻭﺑﺗﻳﺎﺭﺍﺕ ﺍﺳ ﻣﻳﺔ ﻛﻣﺎ ﻫﻲ ﻣﻭﺿ ﺣﺔ ﻋﻠﻰ ﺍﻟﻣﺧﻁﻁﺎﺕ ﺍﻟﺗﺻ ﻣﻳﻣﻳﺔ ﺍﻟﻣﺭﻓﻘﺔ ﻭﺳ ﻌﺔ ﺍﻟﻘﻁﻊ‬
‫ﻟﻘﻭﺍﻁﻊ ﺍﻟﺣﻣﺎﻳﺔ ﻻﺗﻘﻝ ﻋﻥ ‪/٦/‬ﻙ‪.‬ﺃ ﻣﻥ ﻣﺎﺭﻛﺔ )ﺍﻳﺗﻭﻥ‪ -‬ﺷ ﻧﺎﻳﺩﺭ‪......ABB -‬ﺃﻭ ﻣﺎ ﻳﻌﺎﺩﻟﻬﺎ( ﻭﺗﻛﻭﻥ ﻣﺯﻭﺩﺓ ﻛﻝ ﻣﻧﻬﺎ ﺑﻠﻣﺑﺎﺕ‬
‫ﺇﺷﺎﺭﺓ ﺑﺎﻟﻌﺩﺩ ﺍﻟﻣﺷﺎﺭ ﺇﻟﻳﻪ ﻓﻲ ﺍﻟﻠﻭﺣﺎﺕ ﺍﻟﻣﻁﻠﻭﺑﺔ ﻭﻓﻖ ﺍﻟﻣﺧﻁﻁﺎﺕ ﺍﻟﺗﺻﻣﻳﻣﻳﺔ ﺍﻟﻣﺫﻛﻭﺭﺓ‪.‬‬

‫ﻳﺟﺏ ﻋﻠﻰ ﺍﻟﻣﺗﻌﻬﺩ ﺃﻥ ﻳﻘﺩﻡ ﻣﻧﻬﺎ ﻧﻣﺎﺫﺝ ﻟﻠﻣﺻﺎﺩﻗﺔ ﻋﻠﻳﻬﺎ ﻣﻥ ﻗﺑﻝ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﻗﺑﻝ ﺍﻟﺗﺭﻛﻳﺏ‪.‬‬
‫ﻛﻣﺎ ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ﻣﻥ ﻣﺳ ﺗﻠﺯﻣﺎﺕ ﺍﻟﺗﺛﺑﻳﺕ ﻭﺍﻟﺗﻭﺻ ﻳﻝ ﺑﺣﻳﺙ ﻳﺗﻡ ﺍﻟﺗﺭﻛﻳﺏ ﻭﻓﻖ ﺃﻓﺿ ﻝ ﺍﻟﻣﻭﺍﺻ ﻔﺎﺕ‬
‫ﻭﺑﺟﻭﺩﺓ ﻓﻧﻳﺔ ﻋﺎﻟﻳﺔ‪.‬‬
‫ﺣﻳﺙ ﻳﺗﻡ ﺗﻐﺫﻳﺔ ﺍﻟﻠﻭﺣﺎﺕ ﺍﻟﻣﺫﻛﻭﺭﺓ ﻟﻛﻝ ﻁﺎﺑﻖ ﻭ ﻗﺳ ﻡ ﻣﻥ ﻣﺻ ﺎﺩﺭ ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ) ﻣﺧﺭﺝ ﻣﺷ ﺗﺭﻙ "ﺷ ﺑﻛﺔ‪-‬ﻣﺟﻣﻭﻋﺔ" –‬
‫ﻛﻬﺭﻭﺿﻭﺋﻳﺔ(‪.‬‬

‫ﻭﻛﻝ ﻣﺎ ﻳﻠﺯﻡ ﻟﺗﻘﺩﻳﻡ ﺍﻟﻌﻣﻝ ﺑﺎﻟﺷﻛﻝ ﺍﻷﻣﺛﻝ ﻭﻓﻘﺎ ً ﻟﺗﻌﻠﻳﻣﺎﺕ ﺍﻹﺩﺍﺭﺓ‪.‬‬


‫ﻳﻘﺩﺭ ﺍﻟﻌﻣﻝ ﺑﺎﻟﻌﺩﺩ‪.‬‬

‫‪ .٧‬ﻣﻭﺍﺻﻔﺎﺕ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻟﻭﺣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺭﺋﻳﺳﻳﺔ ‪ ) ATS‬ﺷﺑﻛﺔ – ﻛﻬﺭﻭﺿﻭﺋﻳﺔ ( ‪/ :‬ﻋﺩﺩ‪/‬‬
‫ﺷﺮﻭﻁ ﺍﻟﺘﻌﻬﺪ‪:‬‬
‫ﻳﺨﻀﻊ ﺍﻟﺘﻌﻬﺪ ﺑﺎﻹﺿﺎﻓﺔ ﺇﻟﻰ ﺩﻓﺘﺮ ﺍﻟﺸﺮﻭﻁ ﺍﻟﻔﻨﻴﺔ ﺍﻟﺨﺎﺻﺔ ﻭﺍﻟﺸﺮﻭﻁ ﺍﻟﺤﻘﻮﻗﻴﺔ ﻭﺍﻟﻤﺎﻟﻴﺔ ﺇﻟﻰ ﺍﻟﻌﺮﺽ ﺍﻟﻔﻨﻲ ﻭﺍﻟﻜﺘﺎﻟﻮﻛﺎﺕ ﻭﻛﺎﻓﺔ ﺍﻟﻨﺸﺮﺍﺕ ﺍﻟﻔﻨﻴﺔ‬
‫ﻭﺍﻟﻮﺛﺎﺋﻖ ﺍﻟﻤﻘﺪﻣﺔ ﻣﻊ ﺍﻟﻌﺮﺽ ﻣﻮﺿﻮﻉ ﺍﻟﺘﻌﻬﺪ ﻭﻳﺘﻢ ﺗﻘﺪﻳﻢ ﺍﻟﻌﺮﺽ ﺍﻟﻔﻨﻲ ﻣﻊ ﺑﻴﺎﻥ ﺍﻟﻤﻌﻠﻮﻣﺎﺕ ﻭﻓﻖ ﻣﺎ ﻳﻠﻲ ‪:‬‬
‫ﻳﺟﺏ ﺗﻘﺩﻳﻡ ﺍﻟﻧﺷﺭﺍﺕ ﺍﻟﻔﻧﻳﺔ ﻭﺍﻟﻛﺎﺗﻠﻭﻛﺎﺕ ﻭﺍﻟﻭﺛﺎﺋﻖ ﻭﺍﻟﺷﻬﺎﺩﺍﺕ ﻣﺑﻳﻧﺎ ً ﻋﻠﻳﻬﺎ ﺑﺷﻛﻝ ﻭﺍﺿﺢ ﻛﺎﻓﺔ ﺍﻟﻣﻌﻠﻭﻣﺎﺕ ﺍﻟﻔﻧﻳﺔ‬ ‫‪-‬‬
‫ﺣﺳﺏ ﻣﺎ ﻫﻭ ﻭﺍﺭﺩ ﺑﺩﻓﺗﺭ ﺍﻟﺷﺭﻭﻁ ﺍﻟﻔﻧﻳﺔ ﻟﻛﺎﻓﺔ ﺍﻟﻣﻛﻭﻧﺎﺕ ﺍﻷﺳﺎﺳﻳﺔ ﻟﻠﻭﺣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ‪ ،‬ﻭﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺍﻟﻣﻌﻠﻭﻣﺎﺕ‬
‫ﻭﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻭﺍﺭﺩﺓ ﺿﻣﻥ ﺍﻟﻌﺭﺽ ﺍﻟﻔﻧﻲ ﻟﻠﻌﺎﺭﺽ ﻣﻁﺎﺑﻘﺔ ﻟﻠﻣﻌﻠﻭﻣﺎﺕ ﻭﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻭﺍﺭﺩﺓ ﺑﺎﻟﻧﺷﺭﺍﺕ ﺍﻟﻔﻧﻳﺔ‬
‫ﺍﻷﺳﺎﺳﻳﺔ ﻭﺍﻟﺗﻔﺻﻳﻠﻳﺔ ‪.‬‬
‫ﻳﺗﻌﻬﺩ ﺍﻟﻌﺎﺭﺽ ﺧﻁﻳﺎ ً ﻓﻲ ﻋﺭﺿﻪ ﺑﺗﻘﺩﻳﻡ ﻧﺷﺭﺍﺕ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺻﻳﺎﻧﺔ ﻭﺍﻻﺳﺗﺛﻣﺎﺭ ﻋﻧﺩ ﺍﻟﺗﺭﺳﻳﺔ ﺃﻭ ﺍﻟﺗﻭﺭﻳﺩ ‪.‬‬ ‫‪-‬‬
‫ﻛﻣﺎ ﻳﺅﺧﺫ ﺑﻌﻳﻥ ﺍﻻﻋﺗﺑﺎﺭ ﺣﻳﻥ ﺍﻟﺗﻘﻳﻳﻡ ﺍﻟﻔﻧﻲ ﺳﻣﻌﺔ ﺍﻟﻌﺎﺭﺽ ﻭﻣﺷﺎﺭﻳﻌﻪ ﺍﻟﺳﺎﺑﻘﺔ ﻭﺃﻧﻪ ﻗﺩ ﻗﺎﻡ ﺑﺄﻋﻣﺎﻝ ﻣﻣﺎﺛﻠﺔ ﻧﺎﺟﺣﺔ‬ ‫‪-‬‬
‫ﻭﻗﺎﻡ ﺑﺗﻭﺭﻳﺩ ﻟﻭﺣﺎﺕ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺃﺛﺑﺗﺕ ﺟﺩﺍﺭﺗﻬﺎ ﻭﻭﺛﻭﻗﻳﺗﻬﺎ ﺧﻼﻝ ﺍﺳﺗﺛﻣﺎﺭﻫﺎ ﻭﻟﺩﻳﻪ ﺍﻟﺧﺑﺭﺓ ﺍﻟﻛﺎﻓﻳﺔ ﻭﺍﻟﻭﺭﺷﺔ ﺍﻟﻣﺧﺗﺻﺔ ﻓﻲ‬
‫ﻣﺟﺎﻝ ﺗﻘﺩﻳﻡ ﻭﺗﺟﻣﻳﻊ ﺍﻟﻠﻭﺣﺎﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺭﺋﻳﺳﻳﺔ ﻭﺍﻟﺛﺎﻧﻭﻳﺔ ‪.‬‬
‫ﺍﻟﺗﺯﺍﻡ ﺍﻟﻌﺎﺭﺽ ﺑﺗﻘﺩﻳﻡ ﺧﺩﻣﺔ ﻣﺎﺑﻌﺩ ﺍﻟﺑﻳﻊ ﻋﻧﺩ ﺍﻟﺿﺭﻭﺭﺓ ‪.‬‬ ‫‪-‬‬
‫)ﻫﺎﻡ ﺟﺪﺍً(‪ :‬ﻳﺠﺐ ﺃﻥ ﺗﻜﻮﻥ ﺍﻟﻠﻮﺣﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﻭﻛﺎﻓﺔ ﺍﻟﺘﺠﻬﻴﺰﺍﺕ ﺍﻟﻤﻠﺤﻘﺔ ﺑﻬﺎ ﻣﻦ ﺍﻟﻨﻮﻉ ﺫﻭ ﺍﻟﺠﻮﺩﺓ ﺍﻷﻋﻠﻰ ﻭﺍﻟﺪﺭﺟﺔ ﺍﻷﻭﻟﻰ ﻓﻨﻴﺎ ً‬
‫ﻭﺍﻟﻌﻤﺮ ﺍﻟﻔﻨﻲ ﺍﻷﻁﻮﻝ ‪High Durability &high quality specifications and first technical Class‬‬
‫ﻣﻥ ﺃﺟﻝ ﺍﻟﺣﻔﺎﻅ ﻋﻠﻰ ﻧﻅﺎﻡ ﺗﺷﻐﻳﻝ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻣﺿﻣﻭﻥ ﺍﻟﻣﺷﺭﻭﻉ ﺍﻟﻣﺫﻛﻭﺭ ﺑﺻﻭﺭﺓ ﺧﺎﻟﻳﺔ ﻣﻥ ﺍﻷﻋﻁﺎﻝ‪.‬‬ ‫‪-‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﻛﺎﻓﺔ ﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻠﻭﺣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺟﺩﻳﺩﺓ ﻭﻏﻳﺭ ﻣﺟﺩﺩﺓ ‪ ,‬ﻣﻊ ﺑﻳﺎﻥ ﺳﻧﺔ ﺍﻟﺻﻧﻊ ﺑﺷﻛﻝ ﻭﺍﺿﺢ ‪.‬‬ ‫‪-‬‬
‫ﻳﻔﺿﻝ ﺃﻥ ﺗﻛﻭﻥ ﺍﻟﻠﻭﺣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻭﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺭﺋﻳﺳﻳﺔ ﻣﻥ ﻧﻔﺱ ﺍﻟﻣﺎﺭﻛﺔ ﻭﺍﻟﻣﻧﺷﺄ ﻟﻛﺎﻓﺔ ﺍﻟﺑﻧﻭﺩ‪.‬‬ ‫‪-‬‬
‫‪ ‬ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‪:‬‬
‫ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺗﻘﺪﻳﻢ ﺍﻟﻠﻮﺣﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﺍﻟﺮﺋﻴﺴﻴﺔ ﺑﺤﻴﺚ ﺗﻜﻮﻥ ﻗﺎﺑﻠﺔ ﻟﻠﺘﺮﻛﻴﺐ ﻋﻠﻰ ﻗﺎﻋﺪﺓ ﺑﻴﺘﻮﻧﻴﺔ ﻟﺘﺄﻣﻴﻦ ﺍﻟﺘﻐﺬﻳﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﻟﻠﻮﺣﺎﺕ‬
‫ﺍﻟﺜﺎﻧﻮﻳﺔ ﻋﻦ ﻁﺮﻳﻖ ﻛﺎﺑﻼﺕ ﻛﻬﺮﺑﺎﺋﻴﺔ ﺗﻮﺻﻞ ﺑﺎﻟﻤﺨﺎﺭﺝ ﺍﻟﺨﺎﺻﺔ ﺑﺎﻟﻠﻮﺣﺔ ﺍﻟﺮﺋﻴﺴﻴﺔ ﻭﻣﻨﻬﺎ ﺇﻟﻰ ﺍﻟﻠﻮﺣﺎﺕ ﺍﻟﺜﺎﻧﻮﻳﺔ ﺍﻟﺠﺪﺍﺭﻳﺔ‬
‫ﻭﻟﻮﺣﺎﺕ )ﺍﻹﻧﺎﺭﺓ ﻭﺍﻟﻤﺂﺧﺬ ﻭﺍﻟﺨﺪﻣﺎﺕ( ﻭﻋﻠﻰ ﺍﻟﻌـــﺎﺭﺽ ﺑﻴـــﺎﻥ ﻣﺎﺭﻛﺔ ﻭﺑﻠﺪ ﺍﻟﺼﻨﻊ ﻭﺍﻟﺘﺠﻤﻴﻊ ﻟﻠﻮﺣـــﺔ ﻭﻛﺬﻟﻚ ﻣﺎﺭﻛﺔ ﻭﺑﻠﺪ ﺍﻟﻤﻨﺸﺄ‬
‫ﻟﻠﻘﻮﺍﻁﻊ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﻭﺍﻟﺘﺠﻬﻴﺰﺍﺕ ﺍﻷﺳﺎﺳﻴﺔ ﺍﻟﻤﻜﻮﻧﺔ ﻟﻠﻮﺣﺔ ﻭﺑﻴﺎﻥ ﻛﺎﻓﺔ ﺍﻟﻤﻮﺍﺻﻔﺎﺕ ﺍﻟﻔﻨﻴﺔ ﻟﻠﻠﻮﺣﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﺣﺴﺐ ﻣﺎ ﻳﻠﻲ‪:‬‬
‫‪ -"١‬ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﺗﺻﻣﻳﻣﻳﺔ ﺍﻟﻌﺎﻣﺔ ﻭﺍﻷﺳﺎﺳﻳﺔ ﻟﻠﻭﺣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺭﺋﻳﺳﻳﺔ ﺍﻟﺟﺩﺍﺭﻳﺔ‪:‬‬
‫ﺗﺻﻣﻡ ﺍﻟﻠﻭﺣﺔ ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﻭﺍﻟﻧﻅﻡ ﺍﻟﻌﺎﻟﻣﻳﺔ ﻭﺗﺻﻧﻊ ﺍﻟﻠﻭﺣﺔ ﻣﻥ ﺻﻔﺎﺋﺢ ﺍﻟﻔﻭﻻﺫ ﺑﺎﻟﺳﻣﺎﻛﺔ ﺍﻟﻣﻧﺎﺳﺑﺔ ﺑﺣﺩﻭﺩ )‪٢‬ﻣﻡ( ‪,‬‬ ‫‪-‬‬
‫ﻭﻣﺩﻋﻣﺔ ﺑﺑﺭﻭﻓﻳﻝ ﻣﻧﺎﺳﺏ ﻭﻫﻲ ﻣﻐﻠﻘﺔ ﻣﻥ ﺍﻟﺟﻭﺍﻧﺏ ﻭﺍﻟﺧﻠﻑ ‪،‬ﻭﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺟﺩﺍﺭﻳﺔ ﻭﺗﻛﻭﻥ ﻣﻔﺗﻭﺣﺔ ﻣﻥ ﺍﻷﺳﻔﻝ ﻟﺩﺧﻭﻝ‬
‫ﺍﻟﻛﺎﺑﻼﺕ ﻭﻳﻔﺿﻝ ﺃﻥ ﺗﻛﻭﻥ ﻣﻐﻠﻘﺔ ﺑﻐﻁﺎء ﺳﻔﻠﻲ ﻣﺯﻭﺩ ﺑﻔﺗﺣﺎﺕ ﻣﻧﺎﺳﺑﺔ ﺃﻭ ﺣﻠﻘﺎﺕ ﺇﺣﻛﺎﻡ ﻟﺩﺧﻭﻝ ﺍﻟﻛﺎﺑﻼﺕ ﻭﻣﻧﻊ ﺩﺧﻭﻝ ﺍﻷﺟﺳﺎﻡ‬
‫ﺍﻟﻐﺭﻳﺑﺔ ﻭﺗﻛﻭﻥ ﺍﻟﻠﻭﺣﺔ ﻣﺩﻫﻭﻧﺔ ﺑﺎﻟﺩﻫﺎﻥ ﺍﻹﻟﻛﺗﺭﻭﺳﺗﺎﺗﻳﻙ ﺑﻁﺭﻳﻘﺔ ﺍﻟﺑﺦ ﻭﺍﻟﺷﻭﻱ ﺣﻳﺙ ﻳﺻﺑﺢ ﺍﻟﺩﻫﺎﻥ ﻣﺗﻣﺎﺳﻙ ﻣﻊ ﻣﻌﺩﻥ ﺍﻟﻠﻭﺣﺔ‬
‫ﻭﻏﻳﺭ ﻗﺎﺑﻝ ﻟﻠﺗﻘﺷﺭ)ﻭﻳﻔﺿﻝ ﺗﻘﺩﻳﻡ ﻣﺧﻁﻁ ﺑﺄﺑﻌﺎﺩ ﻭﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻠﻭﺣﺔ ﺿﻣﻥ ﺍﻟﻌﺭﺽ ﺍﻟﻔﻧﻲ(‬
‫ﻳﺟﻬﺯ ﺑﺎﺏ ﺍﻟﻠﻭﺣﺔ ﺑﺟﻭﺍﻧﺎﺕ ﻟﻣﻧﻊ ﺩﺧﻭﻝ ﺍﻟﻐﺑﺎﺭ ﻭﻗﺑﺿﺎﺕ ﻣﻌﺩﻧﻳﺔ ﻭﻗﻔﻝ ﻟﻔﺗﺢ ﺍﻟﺑﺎﺏ‪,‬ﻛﻣﺎ ﺗﺟﻬﺯ ﺑﺣﻠﻘﺎﺕ ﻣﻌﺩﻧﻳﺔ ﺑﺄﻋﻠﻰ ﺍﻟﻠﻭﺣﺔ‬
‫ﺑﻣﻘﻁﻊ ﻣﻧﺎﺳﺏ ﻟﺣﻣﻝ ﺍﻟﻠﻭﺣﺔ ‪.‬‬
‫ﻭﻳﺟﺏ ﺃﻥ ﺗﺗﺣﻣﻝ ﺟﻣﻳﻊ ﻅﺭﻭﻑ ﺍﻟﻧﻘﻝ ﻭﺍﻟﺗﺣﻣﻳﻝ ﻭﺍﻟﺗﻧﺯﻳﻝ ﻭﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺗﻭﺻﻳﻝ ﻭﺍﻟﺗﺷﻐﻳﻝ ﺩﻭﻥ ﺣﺩﻭﺙ ﺍﻟﺗﻭﺍءﺍﺕ ﺃﻭ ﺗﺷﻭﻫﺎﺕ ﺃﻭﺻﺩﺃ ‪.‬‬ ‫‪-‬‬
‫ﺗﻭﺯﻉ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻅﺎﻫﺭﺓ ﻋﻠﻰ ﻭﺍﺟﻬﺔ ﺍﻟﻠﻭﺣﺔ ﻭﺗﺭﻛﺏ ﺣﺳﺏ ﺍﻟﺷﺭﻭﻁ ﻭﺍﻹﺻﻭﻝ ﺍﻟﻔﻧﻳﺔ ﺑﺣﻳﺙ ﺗﻅﻬﺭ ﻣﻥ ﻭﺍﺟﻬﺔ ﺍﻟﻠﻭﺣﺔ‬ ‫‪-‬‬
‫ﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻣﺭﺍﻗﺑﺔ ﻭﺍﻟﺗﺣﻛﻡ ﻟﻠﻭﺣﺔ )ﻟﻣﺑﺎﺕ ﺍﻻﺷﺎﺭﺓ _ﺍﻟﻣﻔﺎﺗﻳﺢ ﻭﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻘﻳﺎﺱ ﺍﻟﻣﺧﺗﻠﻔﺔ( ‪ ،‬ﻭﺗﻛﻭﻥ ﻭﺍﺿﺣﺔ ﻟﻠﻣﺭﺍﻗﺑﺔ ﻭﺍﻟﺗﺷﻐﻳﻝ ‪,‬‬
‫ﺗﻭﺯﻉ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﺗﺭﻛﺏ ﺩﺍﺧﻝ ﺍﻟﻠﻭﺣﺔ ﻋﻠﻰ ﻫﻳﺋﺔ ﺻﻔﻭﻑ ﺃﻭ ﺃﻋﻣﺩﺓ ﻣﺗﻭﺍﺯﻳﺔ ﻭﺗﺛﺑﺕ ﻋﻠﻰ ﺳﻛﻙ ﻣﺑﺎﺷﺭﺓ ﺃﻭ ﺑﻭﺍﺳﻁﺔ ﻗﺎﻋﺩﺓ ﺧﺎﺻﺔ‬ ‫‪-‬‬
‫ﺣﺳﺏ ﺍﻟﻠﺯﻭﻡ ‪ ,‬ﻭﻳﺗﻡ ﺗﺭﻛﻳﺏ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﺩﺍﺧﻝ ﺍﻟﻠﻭﺣﺔ ﺑﺗﺑﺎﻋﺩ ﻛﺎﻑ ﻭﺑﺷﻛﻝ ﻣﺭﻳﺢ ﻳﺳﻣﺢ ﺑﺎﻟﺻﻳﺎﻧﺔ ﻭﺍﻟﺗﻭﺳﻊ ﺍﻟﻣﺳﺗﻘﺑﻠﻲ‪.‬‬
‫ﺗﻛﻭﻥ ﺃﺑﻌﺎﺩ ﺍﻟﻠﻭﺣﺔ ﺑﻣﺎ ﻳﻧﺎﺳﺏ ﺗﻭﻓﺭ ﻓﺭﺍﻏﺎﺕ ﻣﻧﺎﺳﺑﺔ ﺩﺍﺧﻝ ﺍﻟﻠﻭﺣﺔ ﻻﺗﻘﻝ ﻋﻥ ‪ %٢٠‬ﻭﺣﺳﺏ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻘﻳﺎﺳﻳﺔ‪.‬‬ ‫‪-‬‬
‫ﺗﻣﺩﺩ ﺍﻟﺗﻭﺻﻳﻼﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺍﻟﺧﺎﺻﺔ ﺑﺩﺍﺭﺓ ﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻘﻳﺎﺱ ﻭﺍﻟﻣﺭﺍﻗﺑﺔ ﻭﺍﻟﺗﺣﻛﻡ ﻟﻠﻭﺣﺔ ﺿﻣﻥ ﻣﺟﺎﺭﻱ ﺑﻼﺳﺗﻳﻛﻳﺔ ﻧﻅﺎﻣﻳﺔ‬ ‫‪-‬‬
‫ﻭﺗﻛﻭﻥ ﺍﻷﺳﻼﻙ ﻣﻣﺩﺓ ﺑﺷﻛﻝ ﻣﺗﻭﺍﺯﻱ ﻋﻠﻰ ﻁﻭﻝ ﺍﻟﻣﺟﺭﻯ ﻭﺧﺎﺭﺝ ﺍﻟﻣﺟﺭﻯ ﻭﻣﺣﺯﻣﺔ ﺑﺣﺯﺍﻣﺎﺕ ﺑﻼﺳﺗﻳﻛﻳﺔ ﺑﺷﻛﻝ ﻓﻧﻲ‪.‬‬
‫ﺗﺟﻬﺯ ﺍﻟﻠﻭﺣﺔ ﺑﻔﺗﺣﺎﺕ ﻧﻅﺎﻣﻳﺔ ﻭﻣﻧﺎﺳﺑﺔ ﻟﺩﺧﻭﻝ ﻛﺎﺑﻼﺕ ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻟﻠﻭﺣﺔ ﻭﺧﺭﻭﺝ ﺍﻟﻛﺎﺑﻼﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ‪.‬‬ ‫‪-‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﻛﺎﺑﻼﺕ ﻭﺃﺳﻼﻙ ﺍﻟﺗﻭﺻﻳﻝ ﺍﻟﺩﺍﺧﻠﻲ ﻧﺣﺎﺳﻳﺔ ﻣﻌﺯﻭﻟﺔ ﻭﺑﻣﻘﺎﻁﻊ ﻣﻧﺎﺳﺑﺔ‪ .‬ﻭﺍﺳﺗﺧﺩﺍﻡ ﻋﺩﺓ ﺃﻟﻭﺍﻥ ﻣﻭﺣﺩﺓ‬ ‫‪-‬‬
‫ﻣﻥ ﺍﻷﺳﻼﻙ ‪.‬‬
‫ﻛﺎﻓﺔ ﺃﻁﺭﺍﻑ ﺃﺳﻼﻙ ﻭﻛﺎﺑﻼﺕ ﺍﻟﺗﺣﻛﻡ )ﺑﺷﻛﻝ ﺩﺑﻭﺱ ﺃﻭﺷﻭﻛﺔ( ﺗﺟﻬﺯ ﺑﺟﻧﻛﺳﻳﻭﻧﺎﺕ ﻭﺻﻝ ﻧﻅﺎﻣﻳﺔ ‪Cable Terminal‬‬ ‫‪-‬‬
‫‪ /Extensions/‬ﻟﻠﻭﺻﻝ ﻣﻊ ﻛﺎﺑﻼﺕ ﺍﻟﺗﺣﻛﻡ ﺍﻟﺧﺎﺭﺟﻳﺔ ﻭﺗﺭ ّﻣﺯ ﻭﺗﺭﻗّﻡ ﺑﺎﻟﺗﻭﺍﻓﻖ ﻭﺍﻟﺗﻁﺎﺑﻖ ﻣﻊ ﺍﻟﻣﺧﻁﻁ ﺍﻟﺗﺻﻣﻳﻣﻲ ﻭﺍﻟﺗﻧﻔﻳﺫﻱ‬
‫ﻟﺩﺍﺭﺓ ﺍﻟﺗﺣﻛﻡ‪.‬‬
‫ﺗﺟﻬﺯ ﺍﻟﻠﻭﺣﺔ ﺑﻠﻭﺣﺎﺕ ﺇﺳﻣﻳﺔ ﻟﻠﺗﺟﻬﻳﺯﺍﺕ ﺧﺎﺭﺝ ﻭﺩﺍﺧﻝ ﺍﻟﻠﻭﺣﺔ ﻭﻳﻠﺻﻖ ﺍﻟﻣﺧﻁﻁ ﺍﻟﺗﺻﻣﻳﻣﻲ ﻭﺍﻟﺗﻧﻔﻳﺫﻱ ﻟﺩﺍﺭﺓ ﺍﻟﺗﺣﻛﻡ‬ ‫‪-‬‬
‫ﺩﺍﺧﻝ ﺍﻟﻠﻭﺣﺔ ﺑﻁﺭﻳﻘﺔ ﻓﻧﻳﺔ ﻏﻳﺭ ﻗﺎﺑﻠﺔ ﻟﻠﺗﻠﻑ‪.‬‬
‫ﻳﻔﺿﻝ ﺃﻥ ﺗﺟﻬﺯ ﺍﻟﻠﻭﺣﺔ ﺑﺑﺎﺭﺍﺕ ﻣﺩﺧﻝ ﻟﻭﺻﻝ ﻛﺎﺑﻼﺕ ﺍﻟﺗﻐﺫﻳﺔ ﻣﻥ ﺍﻟﺷﺑﻛﺔ ﺍﻟﻌﺎﻣﺔ ﻭﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬ ‫‪-‬‬
‫ﻭﻁﻘﻡ ﺑﺎﺭﺍﺕ ﻣﺧﺭﺝ ﻟﻭﺻﻝ ﻗﻭﺍﻁﻊ ﺍﻟﻣﺧﺎﺭﺝ ﻟﻠﻭﺣﺔ ﺣﻳﺙ ﻳﻠﺯﻡ ﺍﻟﻌﻣﻝ ﺍﻟﻔﻧﻲ ‪ ,‬ﻭﻛﺫﻟﻙ ﻳﺟﺏ ﺃﻥ ﺗﺟﻬﺯ ﺍﻟﻠﻠﻭﺣﺔ ﺑﻣﺂﺧﺫ‬

‫ﺃﻭ ﺟﻧﻛﺳﻳﻭﻧﺎﺕ ﻭﺻﻝ ﺑﻌﺩﺩ ﻗﻭﺍﻁﻊ ﺍﻟﻣﺧﺎﺭﺝ ﻟﻭﺻﻝ ﻛﺎﺑﻼﺕ ﺗﻐﺫﻳﺔ ﺍﻟﻠﻭﺣﺎﺕ ﺍﻟﺛﺎﻧﻭﻳﺔ ‪ ,‬ﻭﺗﻛﻭﻥ ﺑﺎﺭﺍﺕ ﺍﻟﻣﺩﺍﺧﻝ ﻭﺍﻟﻣﺧﺎﺭﺝ ﻧﺣﺎﺳﻳﺔ‬
‫ﻭﻣﻁﺎﺑﻘﺔ ﻟﻠﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻘﻳﺎﺳﻳﺔ ﻭﻧﻭﻋﻳﺔ ﺍﻟﻧﺣﺎﺱ ﺃﻭﺭﺑﻲ ﺇﻟﻛﺗﺭﻭﻟﻳﺗﻲ ‪ ,‬ﻭﻳﻔﺿﻝ ﺃﻥ ﻳﻛﻭﻥ ﻣﻘﻁﻊ ﺍﻟﺑﺎﺭﺍﺕ ﻳﺣﻘﻖ ﻛﺛﺎﻓﺔ ﺗﻳﺎﺭ ﻻ‬
‫ﺗﺯﻳﺩ ﻋﻥ )‪ ١٫٥‬ﺃﻣﺑﻳﺭ‪/‬ﻣﻠﻡ‪ (٢‬ﻣﻊ ﺗﺣﺩﻳﺩ ﺃﺑﻌﺎﺩ ﻣﻘﺎﻁﻊ ﺍﻟﺑﺎﺭﺍﺕ ﺣﺳﺏ ﺍﺳﺗﻁﺎﻋﺔ ﺍﻟﻠﻭﺣﺔ ‪ ,‬ﻭﺗﺟﻬﺯ ﺍﻟﻠﻭﺣﺔ ﺑﺑﺎﺭ ﺍﻟﻧﺗﺭ ﻭﺑﺎﺭ ﺗﺄﺭﻳﺽ‬
‫ﻧﺣﺎﺳﻲ ﺑﺷﻛﻝ ﻣﻧﻔﺻﻝ ﻭﺑﻣﻘﻁﻊ ﻣﺳﺎﻭﻱ ﻟﺑﺎﺭ ﺍﻟﻧﺗﺭ ﻭﻻ ﻳﻘﻝ ﻋﻥ ﻧﺻﻑ ﻣﻘﻁﻊ ﺑﺎﺭ ﺍﻟﻔﺎﺯ ﻭﻳﺛﺑﺕ ﺍﻟﻧﺗﺭ ﻋﻠﻰ ﻋﻭﺍﺯﻝ ﻭﺗﺟﻬﺯ ﻛﺎﻓﺔ‬
‫ﺍﻟﺑﺎﺭﺍﺕ ﺑﻣﺭﺍﺑﻁ ﻣﻥ ﺃﺟﻝ ﺍﻟﺗﻭﺻﻳﻝ ﻋﻠﻳﻬﺎ‪ ,‬ﻭﻳﺗﻡ ﺗﻌﻠﻳﻡ ﺃﻭ ﺗﻐﻠﻳﻑ ﺍﻟﺑﺎﺭﺍﺕ ﻭﺭﺅﻭﺱ ﺍﻟﻛﺎﺑﻼﺕ ﺑﻼﺻﻖ ﺣﺭﺍﺭﻱ ﻣﻠﻭﻥ ﺣﺳﺏ‬
‫ﺗﺳﻠﺳﻝ ﺍﻟﺳﺗﺎﻧﺩﺭ ﺍﻟﻌﺎﻟﻣﻲ‪ ,‬ﻣﻊ ﻭﺟﻭﺩ ﺃﻣﺎﻛﻥ ﺗﺛﺑﻳﺕ ﻭﺗﻌﻠﻳﻖ ﺿﻣﻥ ﺍﻟﻠﻭﺣﺎﺕ ﻟﻠﻛﺎﺑﻼﺕ ﺗﺿﻣﻥ ﻋﺩﻡ ﺗﺣﻣﻳﻝ ﻭﺯﻥ ﺍﻟﻛﺎﺑﻝ ﻋﻠﻰ‬
‫ﺍﻟﺑﺎﺭﺍﺕ ‪.‬‬

‫‪ -"٢‬ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻟﻠﻭﺣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺭﺋﻳﺳﻳﺔ‪ /‬ﺷﺑﻛﺔ ‪ -‬ﻛﻬﺭﻭﺿﻭﺋﻳﺔ ‪) /‬ﻟﻭﺣﺔ ‪:(ATS‬‬


‫ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺗﻘﺩﻳﻡ ﻟﻭﺣﺔ ﺗﻐﺫﻳﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺭﺋﻳﺳﻳﺔ ﻭﺍﺣﺩﺓ )ﺷﺑﻛﺔ – ﻛﻬﺭﻭﺿﻭﺋﻳﺔ( ﻗﺎﺑﻠﺔ ﻟﻠﺗﺭﻛﻳﺏ ﻋﻠﻰ ﻗﺎﻋﺩﺓ ﺑﻳﺗﻭﻧﻳﺔ‬
‫ﻟﻠﺗﺑﺩﻳﻝ ﻳﺩﻭﻱ ‪ /‬ﺁﻟﻲ )‪ (ATS‬ﻟﺟﻬﺔ ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﻳﻥ ﺍﻟﺷﺑﻛﺔ ﺍﻟﻌﺎﻣﺔ ﻭﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ ﻣﺯﻭﺩﺓ ﺑﻛﻭﻧﺗﺎﻛﺗﻭﺭﻳﻥ‬
‫ﺛﻼﺛﻲ ﺍﻟﻁﻭﺭ ﺍﻟﺗﻳﺎﺭ ﺍﻻﺳﻣﻲ ﻟﻛﻝ ﻣﻧﻬﺎ )‪ ٤٠٠‬ﺃﻣﺑﻳﺭ ( ﻭﻣﺯﻭﺩﺓ ﺑﻣﺧﺭﺟﻳﻥ ﻋﺑﺎﺭﺓ ﻋﻥ ﻗﻭﺍﻁﻊ ﺣﺭﺍﺭﻳﺔ ﻣﻐﻧﺎﻁﻳﺳﻳﺔ ﺃﺣﺎﺩﻳﺔ ﺍﻟﻁﻭﺭ ﻭﻗﻭﺍﻁﻊ‬
‫ﺧﺩﻣﺔ ﻭﻣﺣﻠﻝ ﺷﺑﻛﺔ ﻭﻟﻣﺑﺎﺕ ﺇﺷﺎﺭﺓ‪.....‬ﺍﻟﺦ ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﺩﺭﺟﺔ ﺃﺩﻧﺎﻩ ﻟﺯﻭﻡ ﺗﻐﺫﻳﺔ ﺍﻟﻠﻭﺣﺎﺕ ﺍﻟﺛﺎﻧﻭﻳﺔ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻟﻣﺷﺭﻭﻉ ‪.‬‬
‫‪ ١-"٢‬ﻣﻜﻮﻧﺎﺕ ﻟﻮﺣﺔ ﺍﻟﺘﻐﺬﻳﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﺍﻟﺮﺋﻴﺴﻴﺔ ﺍﻟﺠﺪﺍﺭﻳﺔ ﻟﻮﺣﺔ )‪ (ATS‬ﻟﺰﻭﻡ ﺗﻐﺬﻳﺔ ﺍﻟﻠﻮﺣﺎﺕ ﺍﻟﺜﺎﻧﻮﻳﺔ ‪:‬‬
‫ﺗﺤﺘﻮﻱ ﺍﻟﻠﻮﺣﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﺍﻟﺮﺋﻴﺴﻴﺔ ﻋﻠﻰ ﻛﻮﻧﺘﺎﻛﺘﻮﺭ ﻟﻜﻞ ﻣﻦ ﺍﻟﺸﺒﻜﺔ ﻭﻣﻨﻈﻮﻣﺔ ﺍﻟﻄﺎﻗﺔ ﺍﻟﻜﻬﺮﻭﺿﻮﺋﻴﺔ ﻣﺘﻨﺎﺳﺒﺔ ﻣﻊ ﺍﺳﺘﻄﺎﻋﺔ‬
‫ﻣﺼﺎﺩﺭ ﺍﻟﺘﻐﺬﻳﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﻭﺍﻟﺤﻤﻮﻻﺕ ﺍﻟﻤﻐﺬﺍﺓ‪ ،‬ﻛﻤﺎ ﺗﺤﺘﻮﻱ ﺍﻟﻠﻮﺣﺔ ﻟﻠﺘﺒﺪﻳﻞ ﺍﻵﻟﻲ ﻟﺠﻬﺔ ﺍﻟﺘﻐﺬﻳﺔ ﺑﻴﻦ ﺍﻟﺸﺒﻜﺔ ﺍﻟﻌﺎﻣﺔ ﻭﺍﻟﻤﺨﺮﺝ‬
‫ﻣﻦ ﻣﻨﻈﻮﻣﺔ ﺍﻟﻄﺎﻗﺔ ﺍﻟﻜﻬﺮﻭﺿﻮﺋﻴﺔ ﻋﻠﻰ ﻗﺎﻁﻊ ﺗﺒﺎﺩﻟﻲ ﻗﻼﺏ ﻋﻦ ﻁﺮﻳﻖ ﻛﻮﻧﺘﻜﺘﻮﺭﺍﺕ ﻣﺠﻬﺰﺓ ﺑﻘﻔﻞ ﻛﻬﺮﺑﺎﺋﻲ )‪ (ATS‬ﻋﺪﺩ ‪١‬‬
‫ﺗﻌﻤﻞ ﺑﺸﻜﻞ ﺁﻟﻲ‪/‬ﻳﺪﻭﻱ ﻭﻫﻲ ﻣﻦ ﺻﻨﺎﻋﺔ ﺇﺣﺪﻯ ﺍﻟﺸﺮﻛﺎﺕ ﺍﻟﻌﺎﻟﻤﻴﺔ ﺍﻟﻤﺘﺨﺼﺼﺔ ﺑﻬﺬﺍ ﺍﻟﻤﺠﺎﻝ ﻭﺍﻟﺤﺎﺻﻠﺔ ﻋﻠﻰ ﺷﻬﺎﺩﺓ ﺿﻤﺎﻥ ﺍﻟﺠﻮﺩﺓ‬
‫‪ ISO 9001‬ﺻﺎﺩﺭﺓ ﻋﻦ ﺟﻬﺔ ﻋﺎﻟﻤﻴﺔ ﻣﻌﺘﻤﺪﺓ‪ ،‬ﻭﻳﺠﺐ ﺗﻘﺪﻳﻢ ﻧﺴﺨﺔ ﻋﻦ ﻫﺬﻩ ﺍﻟﺸﻬﺎﺩﺓ ﺳﺎﺭﻳﺔ ﺍﻟﺼﻼﺣﻴﺔ ﺑﺘﺎﺭﻳﺦ ﺗﻘﺪﻳﻢ ﺍﻟﻌﺮﺽ‪،‬‬
‫ﻭﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺑﻴﺎﻥ ﺍﻟﻤﺎﺭﻛﺔ ﻭﺑﻠﺪ ﺍﻟﻤﻨﺸﺄ ﻟﺘﺠﻬﻴﺰﺍﺕ ﺍﻟﺘﺒﺪﻳﻞ ﺍﻵﻟﻲ‪ ,‬ﻭﻳﺠﺐ ﺃﻥ ﻳﻜﻮﻥ ﻣﻦ ﺇﺣﺪﻯ ﺍﻟﻤﺎﺭﻛﺎﺕ ﺍﻟﻌﺎﻟﻤﻴﺔ ‪ABB,EATON, Schnider‬‬
‫‪ -‬ﻛﻭﻧﺗﺎﻛﺗﻭﺭﺍﺕ ﺍﻟﺗﺑﺩﻳﻝ ﺍﻵﻟﻲ ﺑﻳﻥ ﺍﻟﺷﺑﻛﺔ ﻭ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ ﺛﻼﺛﻳﺔ ﺍﻟﻁﻭﺭ )ﺛﻼﺛﻳﺔ ﺍﻷﻗﻁﺎﺏ(‬
‫ﻳﺗﻳﺎﺭ ﺍﺳﻣﻲ ﻻﻳﻘﻝ ﻋﻥ )‪ ١٦٠‬ﺃﻣﺑﻳﺭ(‪ ،‬ﺗﻌﻣﻝ ﻋﻠﻰ ﺗﻭﺗﺭ )‪ ٤٠٠/٣٨٠‬ﻓﻭﻟﺕ( ﻭﻋﻧﺩ ﺩﺭﺟﺔ ﺣﺭﺍﺭﺓ ﻻﺗﻘﻝ ﻋﻥ )‪ْ ٥٠‬ﻡ(‪.‬‬
‫ﻣﻥ ﺃﺟﻭﺩ ﺍﻷﻧﻭﺍﻉ ) ‪ ABB,EATON,Schnider‬ﺃﻭ ﻣﺎ ﻳﻌﺎﺩﻟﻬﺎ( ﻟﺯﻭﻡ ﺍﻟﺗﺑﺩﻳﻝ ﺁﻟﻲ ‪/‬ﻳﺩﻭﻱ ﺑﺣﻳﺙ ﻳﻛﻭﻥ ﻟﻬﺎ‬
‫ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺗﺎﻟﻳﺔ‪:‬‬
‫*ﻧﻭﻋﻳﺔ ﻭﺍﺳﺗﻁﺎﻋﺔ ﻗﻁﻊ ﻣﻧﺎﺳﺏ ﻟﻺﻗﻼﻋﺎﺕ ﺍﻟﻣﺗﻛﺭﺭﺓ ﺍﻟﺛﻘﻳﻠﺔ‪.‬‬
‫* ﺗﻭﺗﺭ ﺍﻟﻌﺯﻝ ﻻ ﻳﻘﻝ ﻋﻥ )‪ ٦٩٠‬ﻓﻭﻟﺕ(‪.‬‬
‫* ﺗﻭﺗﺭ ﻋﻣﻝ ﺍﻟﻭﺷﻳﻌﺔ )‪ ٢٤٠÷٢٠٠‬ﻓﻭﻟﺕ(‪.‬‬
‫* ﺍﻟﻛﻭﻧﺗﻛﻭﺭﺍﺕ ﺗﺗﺣﻣﻝ ﻻ ﻳﻘﻝ ﻋﻥ )‪ ٥‬ﻣﻠﻳﻭﻥ ﺇﻗﻼﻉ(‪.‬‬
‫*ﺍﻟﻛﻭﻧﺗﻛﻭﺭﺍﺕ ﺗﺗﺣﻣﻝ ﻻﻳﻘﻝ ﻋﻥ )‪ ١٥‬ﺇﻗﻼﻉ ﻓﻲ ﺍﻟﺳﺎﻋﺔ(‪.‬‬
‫‪ -‬ﻗﻭﺍﻁﻊ ﺍﻟﻣﺧﺎﺭﺝ ﺛﻧﺎﺋﻳﺔ ﺍﻟﻁﻭﺭ ﻣﻥ ﻧﻭﻉ ‪ MCB‬ﺑﺗﻳﺎﺭﺍﺕ ﺇﺳﻣﻳﺔ )‪ ٦‬ﺍﻣﺑﻳﺭ ﻋﺩﺩ ‪ ٣٢ , /١/‬ﺃﻣﺑﻳﺭ ﻋﺩﺩ ‪/١/‬‬
‫‪ ٥٠ ,‬ﺃﻣﺑﻳﺭ ﻋﺩﺩ ‪ (/١/‬ﺑﺎﻟﻧﺳﺑﺔ ﻟﻠﻭﺣﺔ ﺍﻟﺧﺎﺻﺔ ﺑﻛﺗﻠﺔ ﺍﻟﺑﻧﺎء ﺭﻗﻡ ‪ ١‬ﻭ ﺑﺗﻳﺎﺭﺍﺕ ﺇﺳﻣﻳﺔ )‪ ٦‬ﺍﻣﺑﻳﺭ ﻋﺩﺩ ‪ ١٠ , /٢/‬ﺃﻣﺑﻳﺭ ﻋﺩﺩ‬
‫‪ ١٦ ,/١/‬ﺃﻣﺑﻳﺭ ﻋﺩﺩ ‪ (/١/‬ﺑﺎﻟﻧﺳﺑﺔ ﻟﻠﻭﺣﺔ ﺍﻟﺧﺎﺻﺔ ﺑﻛﺗﻠﺔ ﺍﻟﺑﻧﺎء ﺭﻗﻡ ‪ ٢‬ﻭﻫﻲ ﺣﺭﺍﺭﻳﺔ ﻣﻐﻧﺎﻁﻳﺳﻳﺔ ‪ ،‬ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺑﻳﺎﻥ ﻣﺎ‬
‫ﻳﻠﻲ‪:‬‬
‫‪ ‬ﺍﻟﺗﻳﺎﺭ ﺍﻹﺳﻣﻲ ﻟﻠﻘﺎﻁﻊ‪ In‬ﻋﻧﺩ ﺗﻭﺗﺭ )‪ ٤٠٠/٣٨٠‬ﻓﻭﻟﺕ( ﻭﻋﻧﺩ ﺩﺭﺟﺔ ﺣﺭﺍﺭﺓ ﻻﺗﻘﻝ ﻋﻥ )‪ْ ٥٠‬ﻡ(‪.‬‬
‫‪ ‬ﺗﻭﺗﺭ ﺍﻟﻌﺯﻝ ﻟﻠﻘﺎﻁﻊ )‪ (Ui‬ﻭﺗﻭﺗﺭ ﺍﻟﻌﻣﻝ ﻟﻠﻘﺎﻁﻊ )‪.( Ue‬‬
‫‪ ‬ﺷﺩﺓﺍﻟﻘﻁﻊ )‪ Interrupting Rating‬ﺃﻭ ‪ (Breaking CapacityIcu‬ﻭﻳﻔﺿﻝ ﺃﻥ ﻻ ﺗﻘﻝ ﻋﻥ ]‪.18[KA‬‬

‫ﻗﻭﺍﻁﻊ ﺍﻟﺧﺩﻣﺔ ﻣﻥ ﻧﻭﻉ ‪ MCB‬ﺣﺭﺍﺭﻳﺔ ﻣﻐﻧﺎﻁﻳﺳﻳﺔ ﺑﺗﻳﺎﺭﺍﺕ ﺃﺳﻣﻳﺔ )ﺃﺣﺎﺩﻳﺔ ﺍﻟﻁﻭﺭ ‪ ١٦‬ﺍﻣﺑﻳﺭ ﻭ ‪ ٢٥‬ﺃﻣﺑﻳﺭ( ‪.‬‬ ‫‪-‬‬
‫ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺑﻳﺎﻥ ﻣﺎ ﻳﻠﻲ‪:‬‬
‫ﺍﻟﺗﻳﺎﺭ ﺍﻹﺳﻣﻲ ﻟﻠﻘﺎﻁﻊ‪ In‬ﻋﻧﺩ ﺗﻭﺗﺭ )‪ ٤٠٠/٣٨٠‬ﻓﻭﻟﺕ( ﻭ )‪ ٢٥٠/٢٣٠‬ﻓﻭﻟﺕ( ﻋﻧﺩ ﺩﺭﺟﺔ ﺣﺭﺍﺭﺓ ﻻﺗﻘﻝ ﻋﻥ )‪ْ ٥٠‬ﻡ(‪.‬‬ ‫‪‬‬
‫ﺗﻭﺗﺭ ﺍﻟﻌﺯﻝ ﻟﻠﻘﺎﻁﻊ )‪ (Ui‬ﻭﺗﻭﺗﺭ ﺍﻟﻌﻣﻝ ﻟﻠﻘﺎﻁﻊ )‪(Ue‬‬ ‫‪‬‬
‫ﺷﺩﺓ ﺍﻟﻘﻁﻊ)‪ Interrupting Rating‬ﺃﻭ ‪ (Breaking CapacityIcu‬ﻭﻳﻔﺿﻝ ﺃﻥ ﻻ ﺗﻘﻝ ﻋﻥ ]‪.10[KA‬‬ ‫‪‬‬
‫ﻳﺟﺏ ﺃﻥ ﻳﺯﻭﺩ ﺍﻟﻘﺎﻁﻊ ﺍﻟﺗﺑﺎﺩﻟﻲ ﺑﻘﻔﻝ ﻣﻳﻛﺎﻧﻳﻛﻲ ﻭﻗﻔﻝ ﻛﻬﺭﺑﺎﺋﻲ ﻳﻣﻧﻊ ﺍﻟﺗﻌﺷﻳﻖ ﺍﻟﻣﺷﺗﺭﻙ ﻟﻛﻝ ﻣﻥ ﺍﻟﻛﻭﻧﺗﺎﻛﺗﻭﺭﻳﻥ ﻣﻥ ﻧﻔﺱ ﺍﻟﺷﺭﻛﺔ‬ ‫‪‬‬
‫ﺍﻟﺻﺎﻧﻌﺔ ﻟﻠﻛﻭﻧﺗﺎﻛﺗﻭﺭﺍﺕ ﻭﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺗﻭﺻﻳﻑ ﻭﺑﻳﺎﻥ ﻣﺧﻁﻁ ﻋﻣﻝ ﺩﺍﺭﺓ ﺍﻟﻘﻔﻝ ﺍﻟﻛﻬﺭﺑﺎﺋﻲ‪.‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺍﻟﻛﻭﻧﺗﺎﻛﺗﻭﺭﺍﺕ ﻣﺯﻭﺩ ﺑﺗﻣﺎﺳﺎﺕ ﻣﺳﺎﻋﺩﺓ ﻗﻼﺑﺔ ﻋﺩﺩ ‪ /٢/‬ﻟﻠﻭﺻﻝ ﻣﻊ ﺁﻟﻳﺔ ﻋﻣﻝ ﺍﻟﻘﻔﻝ ﺍﻟﻛﻬﺭﺑﺎﺋﻲ ﻭﻟﻣﺑﺎﺕ‬ ‫‪‬‬
‫ﺍﻹﺷﺎﺭﺓ‪.‬‬
‫ﻳﻔﺿﻝ ﺃﻥ ﺗﻛﻭﻥ ﺩﺍﺭﺓ ﺍﻟﻘﻔﻝ ﺍﻟﻛﻬﺭﺑﺎﺋﻲ ﻋﻥ ﻁﺭﻳﻖ ﻭﺷﻳﻌﺗﻲ ﻓﺻﻝ ﻭﻭﺻﻝ ﺗﻭﺻﻝ ﻋﻥ ﻁﺭﻳﻖ ﺗﻣﺎﺳﺎﺕ ﻋﻛﺳﻳﺔ ﻓﻲ‬ ‫‪‬‬
‫ﻟﻣﻧﻊ ﺗﺩﺍﺧﻠﻬﻣﺎ ﻣﻌﺎ ً ﺗﺣﺕ ﺃﻱ ﻅﺭﻑ‪.‬‬ ‫ﺍﻟﻛﻭﻧﺗﺎﻛﺗﻭﺭﻳﻥ‬
‫ﻳﻔﺿﻝ ﺃﻥ ﻳﺯﻭﺩ ﻛﻝ ﻛﻭﻧﺗﺎﻛﺗﻭﺭ ﺑﺗﻣﺎﺳﺎﺕ ﻣﺳﺎﻋﺩﺓ ﺇﺿﺎﻓﻳﺔ ﻟﻧﻘﻝ ﺇﺷﺎﺭﺍﺕ ﺍﻟﻔﺻﻝ ﺇﻟﻰ ﻧﻅﺎﻡ ﺍﻟﺗﺣﻛﻡ ﺍﻵﻟﻲ‪.‬‬ ‫‪‬‬

‫ﺗﺣﺩﻳﺩ ﻁﺭﻳﻘﺔ ﺗﻭﺿﻊ ﺍﻟﻛﻭﻧﺗﺎﻛﺗﻭﺭﻳﻥ ﺑﺎﻟﻠﻭﺣﺔ ﺑﺷﻛﻝ ﻣﺗﺟﺎﻭﺭ ﺃﻓﻘﻲ ﺃﻭ ﻋﻣﻭﺩﻱ ﺣﻳﺙ ﻳﻔﺿﻝ ﺫﺍﺕ ﺍﻟﺗﻭﺿﻊ ﺍﻷﻓﻘﻲ‪.‬‬ ‫‪‬‬

‫‪ _-٢-"٢‬ﺍﻟﻤﻮﺍﺻﻔﺎﺕ ﺍﻟﻔﻨﻴﺔ ﻟﺪﺍﺭﺓ ﺍﻟﻤﺮﺍﻗﺒﺔ ﻭﺍﻟﺘﺤﻜﻢ ﺑﻌﻤﻞ ﻗﺎﻁﻊ ﺍﻟﺘﺒﺪﻳﻞ ﺍﻵﻟﻲ‪:‬‬


‫ﻭﻫﻲ ﺍﻟﺪﺍﺭﺓ ﺍﻟﺘﻲ ﺗﺆﻣﻦ ﻓﻲ ﺣﺪﻫﺎ ﺍﻷﺩﻧﻰ ﻣﺮﺍﻗﺒﺔ ﺍﻟﺒﺎﺭﺍﻣﺘﺮﺍﺕ ﺍﻷﺳﺎﺳﻴﺔ ﻟﻠﻮﺣﺔ ﺗﺒﺪﻳﻞ ﺟﻬﺔ ﺍﻟﺘﻐﺬﻳﺔ‬
‫)ﺷﺒﻜﺔ – ﻣﻨﻈﻮﻣﺔ ﻛﻬﺮﻭﺿﻮﺋﻴﺔ(‪.‬‬
‫ﻭﺗﻘﻮﻡ ﺑﺎﻟﺘﺤﻜﻢ ﺑﻨﻈﺎﻡ ﻋﻤﻞ ﺍﻟﻜﻮﻧﺘﺎﻛﺘﻮﺭﺍﺕ ﺁﻟﻲ ‪ /‬ﻳﺪﻭﻱ ﻭﻳﺠﺐ ﺃﻥ ﺗﺤﺘﻮﻱ ﻫﺬﻩ ﺍﻟﺪﺍﺭﺓ ﻓﻲ ﺣﺪﻫﺎ ﺍﻷﺩﻧﻰ ﻣﺎ ﻳﻠﻲ‪:‬‬
‫‪ -‬ﻗﺎﻁﻊ ﺣﻤﺎﻳﺔ ﺃﻭ ﻗﺎﻁﻊ ﺑﻔﻴﻮﺯ ﻟﺤﻤﺎﻳﺔ ﻭﺷﺎﺋﻊ ﻟﻜﻞ ﻣﺼﺪﺭ ﻣﻦ ﻣﺼﺎﺩﺭ ﺍﻟﺘﻐﺬﻳﺔ‪.‬‬
‫‪ -‬ﺣﻤﺎﻳﺔ ﻗﻄﻊ ﻓﺎﺯ ﻟﻜﻞ ﻣﺼﺪﺭ ﻣﻦ ﻣﺼﺎﺩﺭ ﺍﻟﺘﻐﺬﻳﺔ‪.‬‬
‫‪ -‬ﻗﺎﻁﻊ ﺣﻤﺎﻳﺔ ﺛﻼﺛﻲ ﺃﻭ)ﻗﺎﻁﻊ ﺛﻼﺛﻲ ﺑﻔﻴﻮﺯﺍﺕ ﻣﻊ ﻓﻴﻮﺯﺍﺕ ﺇﺣﺘﻴﺎﻁ( ﺑﺘﻴﺎﺭﺇﺳﻤﻲ ﻣﻨﺎﺳﺐ ﻭﺣﻤﺎﻳﺔ ﻣﻨﺎﺳﺒﺔ‪,‬ﻟﺤﻤﺎﻳﺔ ﻋﻨﺎﺻﺮ ﺩﺍﺭﺓ‬
‫ﺍﻟﺘﺤﻜﻢ ﺑﻜﻼ ﻭﺿﻌﻴﺘﻲ ﺍﻟﻘﻮﺍﻁﻊ ‪ ،‬ﻛﻤﺎ ﻳﺘﻢ ﺍﺧﺘﺒﺎﺭ ﻋﻤﻞ ﻣﻨﻈﻮﻣﺔ ﺍﻟﻠﻮﺣﺔ ﻣﻦ ﺧﻼﻝ ﺗﻠﻚ ﺍﻟﻘﻮﺍﻁﻊ‪.‬‬
‫‪ -‬ﺃﺟﻬﺰﺓ ﻗﻴﺎﺱ ﺍﻟﺒﺎﺭﺍﻣﺘﺮﺍﺕ ﺍﻷﺳﺎﺳﻴﺔ ﻟﻠﻮﺣﺔ ﺍﻟﺘﺒﺪﻳﻞ ﺟﻬﺔ ﺍﻟﺘﻐﺬﻳﺔ )ﺷﺒﻜﺔ – ﻣﻨﻈﻮﻣﺔ ﻛﻬﺮﻭﺿﻮﺋﻴﺔ( ﻭﺗﺘﻜﻮﻥ ﻣﻦ‪:‬‬
‫ﺟﻬﺎﺯ ﻣﺤﻠﻞ ﺍﻟﺸﺒﻜﺔ ﻣﻊ ﻛﺎﻓﺔ ﻣﻠﺤﻘﺎﺗﻪ ﻣﻦ ﻣﺤﻮﻻﺕ ﺍﻟﺸﺪﺓ ﻟﺒﻴﺎﻥ ﺍﻟﺒﺎﺭﺍﻣﺘﺮﺍﺕ ﺍﻷﺳﺎﺳﻴﺔ ﻟﻜﻞ ﻣﻦ ﺗﻴﺎﺭ ﻭﺗﻮﺗﺮ ﻭﺗﺮﺩﺩ ﺍﻟﺸﺒﻜﺔ‬
‫ﻭﻣﻨﻈﻮﻣﺔ ﺍﻟﻄﺎﻗﺔ ﺍﻟﻜﻬﺮﻭﺿﻮﺋﻴﺔ )ﻋﺪﺩ ‪ (/٢/‬ﻭﻳﻜﻮﻥ ﺫﻭ ﻧﻮﻋﻴﺔ ﻣﻤﺘﺎﺯﺓ ﻭﻣﻦ ﻣﺎﺭﻛﺔ ﻋﺎﻟﻤﻴﺔ ﻣﺘﺨﺼﺼﺔ ﺑﻬﺬﺍ ﺍﻟﻤﺠﺎﻝ ﻭﻳﻈﻬﺮ‬
‫ﺑﺎﺭﺍﻣﺘﺮﺍﺕ ﺍﻻﺳﺘﻄﺎﻋﺔ )‪( Power metering: KW, KVA, KVAr, Power factor, KWhr‬ﻭﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺑﻴﺎﻥ ﻣﻮﺍﺻﻔﺎﺕ‬
‫ﺍﻟﺠﻬﺎﺯ ﺍﻟﻔﻨﻴﺔ ﺍﻷﺳﺎﺳﻴﺔ )ﻣﺠﺎﻝ ﺍﻟﻌﻤﻞ ‪ ،OperatingRange‬ﺩﻗﺔ ﺍﻟﻘﻴﺎﺱ ‪ ،Accuracy‬ﻣﺠﺎﻝ‬
‫ﺩﺭﺟﺔ ﺍﻟﺤﻤﺎﻳﺔ ‪ ،IP‬ﻭﺩﺭﺟﺔ ﺣﺮﺍﺭﺓ ﺍﻟﻌﻤﻞ ﺑﺎﻟﺤﺪ ﺍﻷﺩﻧﻰ )‪-٥-‬‬ ‫ﺍﻟﻘﻴﺎﺱ‪،Measurement Ranges‬‬
‫‪ْ ٥٥+‬ﻡ((‪.‬‬
‫‪ ‬ﻣﺑﺩﻟﺔ ﻟﺗﺣﺩﻳﺩ ﻧﻅﺎﻡ ﻋﻣﻝ ﺍﻟﻛﻭﻧﺗﺎﻛﺗﻭﺭﺍﺕ)ﺷﺑﻛﺔ ﻓﻘﻁ ‪ /Manual‬ﻓﺻﻝ ‪/‬ﺁﻟﻲ ‪.( Auto‬‬
‫‪ -‬ﻳﺠﺐ ﺃﻥ ﺗﺆﻣﻦ ﺩﺍﺭﺓ ﺍﻟﻤﺮﺍﻗﺒﺔ ﻭﺍﻟﺘﺤﻜﻢ ﻓﻲ ﺍﻟﺤﺪ ﺍﻷﺩﻧﻰ ﺇﻅﻬﺎﺭ ﺍﻹﺷﺎﺭﺍﺕ ﺍﻟﺘﺎﻟﻴﺔ ﻋﻠﻰ ﻭﺍﺟﻬﺔ ﺍﻟﻠﻮﺣﺔ ﻣﻦ ﺧﻼﻝ ﺇﺷﺎﺭﺍﺕ‬
‫‪ Indicators‬ﺃﻭ ﻟﻤﺒﺎﺕ ﺇﺷﺎﺭﺓ ﻟﻴﺰﺭﻳﺔ ﻣﻠﻮﻧﺔ ﺑﺎﻟﻠﻮﻥ ﺍﻟﻤﻨﺎﺳﺐ ﺃﻭ ﻣﻦ ﺧﻼﻝ ﻟﻤﺒﺎﺕ ﺇﺷﺎﺭﺓ ﻋﺎﺩﻳﺔ ﺻﻨﺎﻋﻴﺔ ﺑﻨﻮﻋﻴﺔ ﺟﻴﺪﺓ‪،‬‬
‫ﻭﺍﻹﺷﺎﺭﺍﺕ ﻫﻲ‪:‬‬
‫‪ .١‬ﺇﺷﺎﺭﺓ ﺗﻴﺎﺭ ﺍﻟﺸﺒﻜﺔ ﺟﺎﻫﺰﺓ )ﻛﻮﻧﺘﺎﻛﺘﻮﺭ ﺍﻟﺸﺒﻜﺔ ﻣﻮﺻﻮﻝ(‪.Mains Power‬‬
‫‪ .٢‬ﺇﺷﺎﺭﺓ ﺗﻴﺎﺭ ﻟﻤﻨﻈﻮﻣﺔ ﺍﻟﻜﻬﺮﻭﺿﻮﺋﻴﺔ ﺟﺎﻫﺰﺓ )ﻛﻮﻧﺘﺎﻛﺘﻮﺭ ﺍﻟﻤﻨﻈﻮﻣﺔ ﺍﻟﻜﻬﺮﻭﺿﻮﺋﻴﺔ ﻣﻮﺻﻮﻝ( ‪Solar Power‬‬
‫‪ ‬ﻳﺟﺏ ﺃﻥ ﺗﺅﻣﻥ ﺩﺍﺭﺓ ﺍﻟﻣﺭﺍﻗﺑﺔ ﻭﺍﻟﺗﺣﻛﻡ ﺇﻋﺩﺍﺩﺍﺕ ﻧﻅﺎﻡ ﺍﻟﺗﺷﻐﻳﻝ ﻭﺍﻟﻌﻣﻝ ﺍﻵﻟﻲ ﻟﻠﻘﺎﻁﻊ ﺍﻟﺗﺑﺎﺩﻟﻲ ﻭﻫﻲ ﺑﺎﻟﺣﺩ ﺍﻷﺩﻧﻰ ﻛﻣﺎ ﻳﻠﻲ‪:‬‬
‫‪ ‬ﺍﻷﻓﺿﻠﻳﺔ ﺗﻛﻭﻥ ﻟﻭﺻﻝ ﻛﻭﻧﺗﺎﻛﺗﻭﺭﺍﻟﻣﻧﻅﻭﻣﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ ﻋﻧﺩ ﻭﺟﻭﺩ ﺍﻟﺗﻳﺎﺭ ﻋﻠﻰ ﻛﻝ ﻣﻥ ﻗﺎﻁﻊ ﺍﻟﺷﺑﻛﺔ‬
‫ﻭﻗﺎﻁﻊ ﺍﻟﻣﻧﻅﻭﻣﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‪.‬‬
‫‪ ‬ﻓﺻﻝ ﻛﻭﻧﺗﺎﻛﺗﻭﺭ ﺍﻟﺷﺑﻛﺔ ﻋﻧﺩ ﺍﻧﻘﻁﺎﻉ ﺗﻳﺎﺭ ﺍﻟﺷﺑﻛﺔ ﺃﻭ ﺣﺩﻭﺙ ﺧﻠﻝ ﻓﻲ ﺗﻳﺎﺭ ﺍﻟﺷﺑﻛﺔ‪.‬‬
‫‪ ‬ﻋﻠﻰ ﺍﻟﻣﺗﻌﻬﺩ ﺃﻥ ﻳﻘﺩﻡ ﺍﻟﻣﺧﻁﻁﺎﺕ ﺍﻟﺗﺻﻣﻳﻣﻳﺔ ﺍﻟﺗﻧﻔﻳﺫﻳﺔ ﺍﻟﻧﻬﺎﺋﻳﺔ ﻟﺩﺍﺭﺓ ﺍﻟﻣﺭﺍﻗﺑﺔ ﻭﺍﻟﺗﺣﻛﻡ ﺑﻌﻣﻝ ﻗﺎﻁﻊ ﺍﻟﺗﺑﺩﻳﻝ ﻋﻧﺩ ﺍﻻﺳﺗﻼﻡ‪،‬‬
‫ﻭﻛﺫﻟﻙ ﻭﺿﻊ ﺍﻟﻣﺧﻁﻁ ﺍﻟﺗﻧﻔﻳﺫﻱ ﻟﺩﺍﺭﺓ ﺍﻟﺗﺣﻛﻡ ﺿﻣﻥ ﺍﻟﻠﻭﺣﺔ ﻭﻛﺫﻟﻙ ﻁﻘﻡ ﻓﻳﻭﺯﺍﺕ ﺇﺣﺗﻳﺎﻁ‪.‬‬
‫ﻳﺗﺿﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻘﻁﺔ ﻛﺑﺎﺳﺔ ﺟﺭﺱ ﻣﻊ ﺟﺭﺱ ﻣﻌﺩﻧﻲ ﻣﻥ ﺃﺟﻭﺩﺍﻟﻣﺎﺭﻛﺎﺕ ﺍﻟﻌﺎﻟﻣﻳﺔ ﻧﻔﺱ ﻣﺎﻭﺭﺩ ﻓﻲ ﺑﻧﺩ‬
‫ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻘﻁﺔ ﺿﻭﺋﻳﺔ ﻭﻟﻛﻥ ﻳﺳﺗﺑﺩﻝ ﺍﻟﻣﻔﺗﺎﺡ ﺑﻛﺑﺎﺳﺔ ﺟﺭﺱ ﻭﺫﻟﻙ ﻭﻓﻖ ﺃﻓﺿﻝ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﻭﺑﺟﻭﺩﺓ ﺗﻧﻔﻳﺫ‬
‫ﻋﺎﻟﻳﺔ ﺣﺳﺏ ﺍﻟﻣﺧﻁﻁﺎﺕ ﺍﻟﺗﺻﻣﻳﻣﻳﺔ ﻭﺗﻭﺟﻳﻬﺎﺕ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﺣﻳﺙ ﻳﻘﺩﻡ ﻧﻣﻭﺫﺝ ﻣﻧﻪ ﻟﻠﻣﻭﺍﻓﻘﺔ ﻋﻠﻳﻪ ﻣﻥ ﻗﺑﻝ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﻗﺑﻝ‬
‫ﺍﻟﺗﺭﻛﻳﺏ‪.‬‬
‫ً‬
‫ﻛﻣﺎ ﻳﺗﺿﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻛﺎﻓﺔ ﻣﺳﺗﻠﺯﻣﺎﺕ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺗﺛﺑﻳﺕ ﻭﺍﻟﺗﻭﺻﻳﻝ ﺑﺣﻳﺙ ﻳﻛﻭﻥ ﺟﺎﻫﺯﺍ ﻟﻠﻌﻣﻝ‪.‬‬
‫ﻭﻛﻝ ﻣﺎﻳﻠﺯﻡ ﻟﺗﺳﻠﻳﻡ ﺍﻟﻌﻣﻝ ﺟﺎﻫﺯﺍ" ﻟﻼﺳﺗﺛﻣﺎﺭ ﺑﺎﻟﺷﻛﻝ ﺍﻷﻣﺛﻝ ﻭﻓﻘﺎ" ﻟﻠﺷﺭﻭﻁ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺧﺎﺻﺔ ﻭﻟﺗﻌﻠﻳﻣﺎﺕ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ‪.‬‬
‫ﻳﻘﺩﺭ ﺍﻟﻌﻣﻝ ﺑﺎﻟﻌﺩﺩ‪.‬‬
‫ﺏ‪ -‬ﺃﻋﻣﺎﻝ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻧﻅﺎﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻛﻬﺭﺿﻭﺋﻳﺔ ﻣﻊ ﻛﺎﻓﺔ ﻣﻠﺣﻘﺎﺗﻬﺎ‬
‫‪/:‬ﻣﻘﻁﻭﻉ‪/‬‬
‫‪ -١‬ﺍﻟﻐﺎﻳﺔ ﻣﻥ ﺍﻟﻌﻣﻝ‪:‬‬
‫ﺍﻟﻐﺎﻳﺔ ﻣﻥ ﺍﻟﻌﻣﻝ ﻫﻭ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻣﻥ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﻟﺯﻭﻡ ﺗﺄﻣﻳﻥ ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻟﺗﺷﻐﻳﻝ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻣﻳﻛﺎﻧﻳﻛﻳﺔ‬
‫ﻭﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻭﺍﻟﻁﺑﻳﺔ ﺍﻟﺿﺭﻭﺭﻳﺔ ﻛﺑﺩﻳﻝ ﻋﻥ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻻﺣﺗﻳﺎﻁﻳﺔ )ﺷﺑﻛﺔ ‪ -‬ﻣﺟﻣﻭﻋﺔ( ﻓﻲ ﺣﺎﻝ ﺗﻭﻓﺭ ﺍﻟﺳﻁﻭﻉ ﺍﻟﺷﻣﺳﻲ‬
‫ﺍﻟﻛﺎﻓﻲ ﻟﺗﻐﻁﻳﺔ ﺣﻣﻭﻻﺕ ﺃﻋﻅﻣﻳﺔ ﻭﺫﻟﻚ ﻟﻤﺪﺓ ﺧﻤﺲ ﺳﺎﻋﺎﺕ ﺻﺒﺎﺣﻴﺔ ﺧﻼﻝ ﻓﺘﺮﺓ ﺍﻟﺴﻄﻮﻉ ﺍﻟﺸﻤﺴﻲ ﻭﺛﻼﺙ ﺳﺎﻋﺎﺕ ﺧﻼﻝ ﻓﺘﺮﺓ‬
‫ﻏﻴﺎﺏ ﺍﻟﺴﻄﻮﻉ ﺍﻟﺸﻤﺴﻲ ﻟﺘﻐﻄﻴﺔ ﻓﺘﺮﺓ ﺍﻟﺪﻭﺍﻡ ﺍﻟﺮﺳﻤﻲ ﻟﻠﻤﺠﻤﻌﺎﺕ ﺍﻟﻄﺒﻴﺔ ﺍﻟﻤﺬﻛﻮﺭﺓ ﻭ ﺍﻟﺘﻲ ﻻ ﺗﺘﺠﺎﻭﺯ ﺛﻤﺎﻧﻴﺔ ﺳﺎﻋﺎﺕ ﻓﻌﻠﻴﺔ‪.‬‬
‫‪ ‬ﻣﻭﻗﻊ ﺍﻟﺻﺎﺧﻭﺭ‪:‬‬
‫ﻓﻲ ﻛﺘﻠﺔ ﺍﻟﺒﻨﺎء ﺭﻗﻢ ‪، (17 KW ) ١‬ﻭﻓﻲ ﻛﺘﻠﺔ ﺍﻟﺒﻨﺎء ﺭﻗﻢ ‪ ٢‬ﺍﻷﺫﻳﺔ ﺍﻟﺪﻣﺎﻏﻴﺔ ) ‪.( 6.6 KW‬‬
‫ﻣﺷﺭﻭﻉ ﻣﺷﻔﻰ ﺍﻷﻁﻔﺎﻝ‪:‬‬ ‫‪‬‬
‫)‪ (3.5KW‬ﻓﻲ ﺍﻟﻘﺑﻭ‪ ( 4KW) ,‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻷﺭﺿﻲ‪ ( 2.5KW) ,‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻷﻭﻝ‪ ( 5KW) ,‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺛﺎﻧﻲ‪,‬‬
‫)‪ ( 2KW‬ﻓﻲ ﻛﻝ ﻁﺎﺑﻖ ﻣﻥ ﺍﻟﻁﻭﺍﺑﻖ ﺍﻟﻣﺗﻛﺭﺭﺓ » ﻟﺚ وراﺑﻊ وﺧﺎﻣﺲ وﺳﺎدس«‬
‫‪ ( 5KW) ،‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺳﺎﺑﻊ ‪ ( 10KW)،‬ﻟﻣﺻﻌﺩ ﻭﺍﺣﺩ‪.‬‬

‫‪ ‬ﻣﻭﻗﻊ ﺟﺭﻣﺎﻧﺎ‪:‬‬
‫)‪(5.5 KW‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻷﺭﺿﻲ‪ ( 6.75KW) ,‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻷﻭﻝ‪ ( 7KW) ,‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺛﺎﻧﻲ‪ ( 2. 5KW) ,‬ﻓﻲ ﻗﺳﻡ ﺍﻹﺳﻌﺎﻑ‬

‫‪ -٢‬ﺍﻷﻋﻣﺎﻝ ﺍﻟﺗﺣﺿﻳﺭﻳﺔ‪:‬‬
‫ﺗﻌﺗﺑﺭ ﺍﻟﺷﺭﻭﻁ ﻭﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﻭﺿﻭﻋﺔ ﻣﻥ ﻗﺑﻝ ﺇﺩﺍﺭﺓ ﺍﻟﻣﻧﻅﻣﺔ ﻫﻲ ﺍﻷﺳﺎﺱ ﻟﻘﻳﺎﻡ ﺍﻟﻣﺗﻌﻬﺩ ﺑﺗﺄﻣﻳﻥ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﻭﺍﻟﺗﺣﺿﻳﺭ‬
‫ﻟﻠﻣﺧﻁﻁﺎﺕ ﺍﻟﺗﻔﺻﻳﻠﻳﺔ )‪ (Shop Drawings‬ﻟﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﺑﻣﺎﻳﺗﻧﺎﺳﺏ ﻣﻊ ﻁﺑﻳﻌﺔ ﺍﻟﻣﻭﺍﻗﻊ ﺍﻟﻌﺎﺋﺩ ﻟﻠﻣﺷﺭﻭﻉ‬
‫ﻭﺍﻟﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﻓﻲ ﻣﻘﺩﻣﺔ ﺍﻹﺿﺑﺎﺭﺓ ﺍﻟﻔﻧﻳﺔ‪.‬‬

‫‪ -٣‬ﺍﻟﺷﺭﻭﻁ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻟﺗﻭﺭﻳﺩ‪:‬‬


‫‪ -‬ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺍﻷﺟﻬﺯﺓ ﺍﻟﻣﻘﺩﻣﺔ ﻣﺻﻧﻌﺔ ﻣﻥ ﻗﺑﻝ ﺇﺣﺩﻯ ﺍﻟﺷﺭﻛﺎﺕ ﺍﻟﻣﺧﺗﺻﺔ ﺑﺗﻁﺑﻳﻖ ﺃﺣﺩﺙ ﺍﻟﺗﻘﻧﻳﺎﺕ ﻓﻲ ﻣﺟﺎﻝ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ‬
‫ﻣﻥ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﻭﺃﻥ ﺗﻛﻭﻥ ﺟﻣﻳﻊ ﺃﺟﺯﺍء ﺍﻟﻣﻧﻅﻭﻣﺔ ﻣﻊ ﻛﺎﻓﺔ ﻣﻠﺣﻘﺎﺗﻬﺎ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﻌﺎﻟﻲ ﺍﻟﺟﻭﺩﺓ ﻭﺍﻟﻣﺻﻧﻌﺔ ﻭﻓﻖ ﺃﺣﺩﺙ ﺍﻟﻣﻌﺎﻳﻳﺭ‬
‫ﺍﻟﻌﺎﻟﻣﻳﺔ‪،‬‬
‫ﻭﺗﻘﺩﻳﻡ ﺍﻟﻛﺗﺎﻟﻭﻛﺎﺕ ﻭﺍﻟﻧﺷﺭﺍﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺧﺎﺻﺔ ﺑﺗﻠﻙ ﺍﻷﺟﻬﺯﺓ ﻣﻭﺿﺢ ﻋﻠﻳﻬﺎ ﺍﻻﺳﺗﻁﺎﻋﺎﺕ ﺍﻟﻣﻁﻠﻭﺑﺔ ﻭﺍﻟﻧﻣﺎﺫﺝ ﺍﻟﻣﺧﺗﺎﺭﺓ ﻟﺗﻠﻙ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ‪،‬‬
‫ﻭﻳﻠﺗﺯﻡ ﺍﻟﻌﺎﺭﺽ ﺑﺗﺄﻣﻳﻥ ﻛﺎﺩﺭ ﻓﻧﻲ ﺫﻭ ﺧﺑﺭﺓ ﺟﻳﺩﺓ ﻟﺗﻧﻔﻳﺫ ﺃﻋﻣﺎﻝ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺗﺷﻐﻳﻝ‪.‬‬
‫‪ -‬ﻳﺧﺿﻊ ﺍﻟﻣﺗﻌﻬﺩ ﺇﻟﻰ ﺩﻓﺗﺭ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻫﺫﺍ ﻭﻳﺗﻭﺟﺏ ﻋﻠﻳﻪ ﻭﻋﻠﻰ ﻣﺳﺅﻭﻟﻳﺗﻪ ﺩﺭﺍﺳﺔ ﻭﺇﺧﺗﻳﺎﺭ ﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ‬
‫ﻭﺗﺣﺩﻳﺩ ﻛﻣﻳﺎﺗﻬﺎ ﺍﻟﻧﻬﺎﺋﻳﺔ ﺣﻳﺙ ﺗﻌﺗﺑﺭﺍﻟﻛﻣﻳﺎﺕ ﺍﻟﻭﺍﺭﺩﺓ ﻓﻲ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺧﺎﺻﺔ ﺑﺄﻋﻣﺎﻝ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﻫﻲ ﻛﻣﻳﺎﺕ‬
‫ﺗﻘﺩﻳﺭﻳﺔ ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺃﻥ ﻳﺣﺩﺩﻫﺎ ﻓﻲ ﻋﺭﺿﻪ ﺍﻟﻔﻧﻲ ﺑﻧﺗﻳﺟﺔ ﺩﺭﺍﺳﺗﻪ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺗﻲ ﻳﺟﺏ ﺃﻥ ﻳﻘﺩﻣﻬﺎ ﻣﻊ ﻋﺭﺿﻪ ﺍﻟﻔﻧﻲ ﻭﺍﻟﻣﺗﻭﺍﻓﻘﺔ ﻣﻊ‬
‫ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻷﻋﻅﻣﻳﺔ ﺍﻟﻣﻁﻠﻭﺏ ﺗﺄﻣﻳﻥ ﺗﻐﺫﻳﺗﻬﺎ ﺑﺎﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ ﺍﻟﺧﺎﺻﺔ ﺑﻣﻭﻗﻊ ﺍﻟﻣﺷﺭﻭﻉ ﻭﺍﻟﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﺃﻋﻼﻩ ﻟﻛﻝ ﻁﺎﺑﻖ ﻭ ﻗﺳﻡ‬
‫ﻭﺍﻟﺗﻲ ﺳﻳﻘﻭﻡ ﺍﻟﻣﺗﻌﻬﺩ ﺑﺗﻭﺭﻳﺩﻫﺎ‪.‬‬
‫‪ -‬ﻭﻳﻘﻊ ﻋﻠﻰ ﻋﺎﺗﻖ ﺍﻟﻣﺗﻌﻬﺩ ﺇﻋﺩﺍﺩ ﺍﻟﺩﺭﺍﺳﺔ ﺍﻟﺗﻧﻔﻳﺫﻳﺔ ﻟﻠﺣﻭﺍﻣﻝ ﺍﻟﻣﻌﺩﻧﻳﺔ ﻟﻧﻅﺎﻡ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﻭﻛﺫﻟﻙ ﺗﺻﻣﻳﻡ ﺍﻟﻘﻭﺍﻋﺩ ﺍﻟﺑﻳﺗﻭﻧﻳﺔ‬
‫ﺍﻟﻼﺯﻣﺔ ﻟﺗﺛﺑﻳﺗﻪ ﺑﺣﻳﺙ ﺗﺗﺣﻣﻝ ﺳﺭﻋﺔ ﻫﺑﺔ ﺭﻳﺎﺡ ﻻ ﺗﻘﻝ ﻋﻥ )‪. (120Km/h‬‬
‫‪ -‬ﻳﺟﺏ ﺗﻭﺭﻳﺩ ﺗﺟﻬﻳﺯﺍﺕ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﺑﺷﻛﻝ ﻳﺿﻣﻥ ﺳﻼﻣﺗﻬﺎ ﻭﻭﺻﻭﻟﻬﺎ ﺇﻟﻰ ﻣﻭﻗﻊ ﺍﻟﺗﺭﻛﻳﺏ ﻛﻣﺎ ﻫﻲ ﻣﻭﺭﺩﺓ ﻣﻥ ﻣﺻﺩﺭﻫﺎ‪.‬‬
‫‪ -‬ﻳﺟﺏ ﺗﻘﺩﻳﻡ ﻧﺷﺭﺍﺕ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺻﻳﺎﻧﺔ ﻭﺷﻬﺎﺩﺍﺕ ﺑﻠﺩ ﺍﻟﻣﻧﺷﺄ ﺣﻳﺙ ﻳﻠﺯﻡ ﺑﻌﺩ ﺍﻟﺗﺭﺳﻳﺔ‪.‬‬
‫ـ ﻳﻘﻊ ﻋﻠﻰ ﻋﺎﺗﻖ ﺍﻟﻌﺎﺭﺽ ﺃﻥ ﻳﻘﺩﻡ ﻓﻲ ﻋﺭﺿﻪ ﻣﺎ ﻳﺛﺑﺕ ﺍﻟﺗﺯﺍﻣﻪ ﺑﺗﻘﺩﻳﻡ ﻗﻁﻊ ﺍﻟﻐﻳﺎﺭ ﻭﺧﺩﻣﺔ ﻣﺎ ﺑﻌﺩ ﺍﻟﺑﻳﻊ‪.‬‬
‫‪ -‬ﻳﻘﻊ ﻋﻠﻰ ﻋﺎﺗﻖ ﺍﻟﻌﺎﺭﺽ ﺗﻘﺩﻳﻡ ﻣﻊ ﺍﻷﺟﻬﺯﺓ ﺍﻟﻣﻘﺩﻣﺔ ﺻﻧﺩﻭﻕ ﻋﺩﺓ ﻳﺩﻭﻳﺔ ﻟﻠﺻﻳﺎﻧﺔ ﻭﺍﻟﻘﻳﺎﺱ‪.‬‬
‫‪ - ٤‬ﺍﻟﺷﺭﻭﻁ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻟﺗﺭﻛﻳﺏ‪:‬‬
‫‪ -‬ﻳﺧﺿﻊ ﺍﻟﻣﺗﻌﻬﺩ ﺑﺎﻻﺿﺎﻓﺔ ﺇﻟﻰ ﺩﻓﺗﺭ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻰ ﻛﺎﻓﺔ ﺍﻟﻧﺷﺭﺍﺕ ﻭﺍﻟﻛﺗﺎﻟﻭﻛﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻟﺗﻌﻬﺩ ﻭﺍﻟﻣﺭﻓﻘﺔ ﺑﺎﻟﻌﺭﺽ ﺍﻟﻔﻧﻲ‬
‫ﺍﻟﺗﻲ ﻳﺟﺏ ﺃﻥ ﺗﻭﺿﺢ ﻛﺎﻓﺔ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻼﺯﻣﺔ ﻟﺗﻧﻔﻳﺫ ﺍﻟﻣﺷﺭﻭﻉ‪ .‬ﻭﻳﺗﻭﺟﺏ ﻋﻠﻳﻪ ﻭﻋﻠﻰ ﻣﺳﺅﻭﻟﻳﺗﻪ ﺇﺧﺗﻳﺎﺭ ﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻁﺎﻗﺔ‬
‫ﺍﻟﺷﻣﺳﻳﺔ ﺑﺷﻛﻝ ﻳﺗﻭﺍﻓﻖ ﻣﻊ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻟﻣﻁﻠﻭﺑﺔ ﻭ ﺍﻟﺗﻲ ﺳﻳﻘﻭﻡ ﺍﻟﻣﺗﻌﻬﺩ ﺑﺗﻭﺭﻳﺩﻫﺎ ﻟﺯﻭﻡ ﺗﺟﻬﻳﺯ ﺍﻟﻣﻧﻅﻭﻣﺔ‪.‬‬
‫‪ -‬ﻳﺟﺏ ﺗﻭﺭﻳﺩ ﺗﺟﻬﻳﺯﺍﺕ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﺑﺷﻛﻝ ﻳﺿﻣﻥ ﺳﻼﻣﺗﻬﺎ ﻭﻭﺻﻭﻟﻬﺎ ﺇﻟﻰ ﻣﻭﻗﻊ ﺍﻟﺗﺭﻛﻳﺏ ﻛﻣﺎ ﻫﻲ ﻣﻭﺭﺩﺓ ﻣﻥ ﻣﺻﺩﺭﻫﺎ‪.‬‬
‫‪ -‬ﻳﺟﺏ ﺃﻥ ﺗﻧﻔﺫ ﺍﻟﺣﻭﺍﻣﻝ ﺍﻟﻣﻌﺩﻧﻳﺔ ﺑﺣﻳﺙ ﺗﺗﺣﻣﻝ ﺟﻣﻳﻊ ﺍﻟﻘﻭﻯ ﻭﺍﻟﺣﻣﻭﻻﺕ ﺍﻟﻣﺗﻭﻗﻌﺔ‪ ,‬ﻭﺑﺎﺭﺗﻔﺎﻉ ﺑﺣﺩﻭﺩ ‪ ٢‬ﻡ ﻋﻥ ﺃﺭﺿﻳﺔ ﺍﻟﺳﻁﺢ ﻣﻭﻗﻊ ﺗﺭﻛﻳﺏ‬
‫ﺍﻷﻟﻭﺍﺡ‬
‫‪ -‬ﻳﺟﺏ ﺗﻘﺩﻳﻡ ﻧﺷﺭﺍﺕ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺻﻳﺎﻧﺔ ﻭﺷﻬﺎﺩﺍﺕ ﺑﻠﺩ ﺍﻟﻣﻧﺷﺄ ﺣﻳﺙ ﻳﻠﺯﻡ ﺑﻌﺩ ﺍﻟﺗﺭﺳﻳﺔ‪.‬‬
‫‪ -‬ﻳﻘﻊ ﻋﻠﻰ ﻋﺎﺗﻖ ﺍﻟﻣﺗﻌﻬﺩ ﻋﻧﺩ ﺍﻻﻧﺗﻬﺎء ﻣﻥ ﺗﺭﻛﻳﺏ ﺗﺟﻬﻳﺯﺍﺗﻪ ﺍﻟﻘﻳﺎﻡ ﺑﺗﺟﺭﺑﺔ ﻭﺗﺷﻐﻳﻝ ﻫﺫﻩ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﻭﺍﺧﺗﺑﺎﺭﻫﺎ ﻭﻣﻌﺎﻳﺭﺗﻬﺎ ﺗﻣﻬﻳﺩﺍً‬
‫ﻟﻼﺳﺗﻼﻡ‪.‬‬
‫‪ -٥‬ﺍﻟﺗﺯﺍﻣﺎﺕ ﺍﻟﻌﺎﺭﺽ‪:‬‬
‫‪ -١‬ﺗﻘﺩﻳﻡ ﺧﺻﺎﺋﺹ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﺗﻲ ﺳﻳﻘﻭﻡ ﺑﺗﻘﺩﻳﻣﻬﺎ ﻭﺗﻧﻔﻳﺫﻫﺎ ﻭﺗﺣﺩﻳﺩ ﺍﻧﻌﻛﺎﺳﺎﺗﻬﺎ ﻣﻥ ﺣﻳﺙ ﻛﻔﺎﺑﺗﻬﺎ ﻟﺗﻐﻁﻳﺔ ﺍﻟﺣﻣﻭﻟﺔ‬
‫ﺍﻷﻋﻅﻣﻳﺔ ﺍﻟﻣﻁﻠﻭﺑﺔ ﺧﻼﻝ ﺍﻟﻔﺗﺭﺓ ﺍﻟﺯﻣﻧﻳﺔ ﺍﻟﻣﺣﺩﺩﺓ ﺑﻭﺍﺳﻁﺔ ﺍﻟﻧﻅﺎﻡ ﺍﻟﻣﻘﺩﻡ ﻣﻥ ﻗﺑﻠﻪ ﻭﻓﻘﺎ ً ﻟﺗﻘﺩﻳﺭﻩ ﻟﺧﺻﺎﺋﺹ ﺍﻟﻭﺿﻊ ﺍﻟﺟﻐﺭﺍﻓﻲ ﻟﻣﻭﻗﻊ‬
‫ﺍﻟﻣﺷﺭﻭﻉ‪.‬‬
‫‪ - ٢‬ﻳﺗﻌﻬﺩ ﺍﻟﻌﺎﺭﺽ ﺑﺗﺩﺭﻳﺏ ﻣﻬﻧﺩﺳﻳﻥ ﻭﻓﻧﻳﻳﻥ ﻹﻏﻧﺎء ﺧﺑﺭﺍﺗﻬﻡ ﻓﻲ ﻣﺟﺎﻝ ﺍﻟﺗﺷﻐﻳﻝ ﻭﺍﻟﺻﻳﺎﻧﺔ ﻓﻲ ﻣﺟﺎﻝ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ‪.‬‬
‫‪ - ٣‬ﻳﺗﻌﻬﺩ ﺍﻟﻌﺎﺭﺽ ﺑﻌﺩ ﺍﻻﻧﺗﻬﺎء ﻣﻥ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺗﺷ ﻐﻳﻝ ﺇﺟﺭﺍء ﺍﻟﻘﻳﺎﺳ ﺎﺕ ﺍﻟﻼﺯﻣﺔ ﺧﻼﻝ ﻓﺗﺭﺍﺕ ﺍﻟﻌﻣﻝ ﺍﻟﺻ ﺑﺎﺣﻳﺔ ﻭﻟﻣﺩﺓ ﺛﻼﺛﺔ ﺃﻳﺎﻡ‬
‫ﻣﺗﻭﺍﺻﻠﺔ ﺃﻭ ﻣﻧﻔﺻﻠﺔ ﻳﻛﻭﻥ ﻓﻳﻬﺎ ﺍﻟﺳﻁﻭﻉ ﺍﻟﺷﻣﺳﻲ ﻛﺎﻓﻲ ﺣﻳﺙ ﻳﺗﻡ ﺗﻘﻳﻳﻡ ﺍﻟﻣﺷﺭﻭﻉ ﻣﻥ ﺧﻼﻟﻬﺎ )ﻓﺗﺭﺓ ﺍﻟﺗﺷﻐﻳﻝ ﺍﻟﺗﺟﺭﻳﺑﻲ(‪.‬‬
‫‪ - ٤‬ﺗﻘﺩﻡ ﻛﺎﻓﺔ ﺍﻟﻧﺷ ﺭﺍﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺧﺎﺻ ﺔ ﺑﺎﻟﻣﻌﺭﺝ ﻭﺍﻟﻠﻭﺍﻗﻁ ﺍﻟﻛﻬﺭﻭﺿ ﻭﺋﻳﺔ ﻭﺍﻟﻣﺧﻁﻁﺎﺕ ﺍﻟﺗﺻ ﻣﻳﻣﻳﺔ ﺍﻷﻭﻟﻳﺔ ﻟﻠﺣﻭﺍﻣﻝ ﺍﻟﻣﻌﺩﻧﻳﺔ‬
‫ﻭﺍﻟﻘﻭﺍﻋ ﺩ ﺍﻻﺳ ﻣﻧﺗﻳ ﺔ ﺃﻭ ﺍﻟﻣﻌ ﺩﻧﻳ ﺔ ﻋﻧ ﺩ ﺗﻘ ﺩﻳﻡ ﺍﻟﻌﺭﺽ ﻣﺑﻳﻧ ﺎ ً ﺑﺷ ﻛ ﻝ ﻭﺍﺿ ﺢ ﻛ ﺎﻓ ﺔ ﺍﻟﻣﻭﺍﺻ ﻔ ﺎﺕ ﺍﻟﻔﻧﻳ ﺔ‬
‫ﻭﻓﻘﺎ ً ﻟﻣﺎ ﻫﻭ ﻣﺑﻳﻥ ﻓﻲ ﺑﻧﻭﺩ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﺩﺭﺟﺔ ﺃﺩﻧﺎﻩ ﻭﻛﺫﻟﻙ ﺍﻟﻣﺎﺭﻛﺔ ﻭﺍﻟﻁﺭﺍﺯ ﻭﺑﻠﺩ ﺍﻟﻣﻧﺷﺄ‪.‬‬
‫‪ -٦‬ﺗﻌﻠﻳﻣﺎﺕ ﺍﻟﺗﺷﻐﻳﻝ ﻭﺍﻟﺻﻳﺎﻧﺔ‪:‬‬
‫ﻳﺟﺏ ﺗﻘﺩﻳﻡ ﺗﻌﻠﻳﻣﺎﺕ ﺍﻟﺗﺷﻐﻳﻝ ﻭﺍﻟﺻﻳﺎﻧﺔ ﻟﻛﺎﻓﺔ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﻭﺗﺳﻠﻳﻣﻬﺎ ﺇﻟﻰ ﺍﻟﻣﻬﻧﺩﺱ ﺍﻟﻣﺷﺭﻑ‪ ،‬ﻭﻋﻠﻰ ﺍﻟﺟﻬﺔ ﺍﻟﻣﻧﻔﺫﺓ ﺗﺩﺭﻳﺏ ﻋﻧﺎﺻﺭ ﺍﻟﺻﻳﺎﻧﺔ‬
‫ﻣﻥ ﺍﻹﺩﺍﺭﺓ ﻭﻟﻣﺩﺓ ﺛﻼﺛﺔ ﺃﻳﺎﻡ ﻋﻠﻰ ﺗﺷ ﻐﻳﻝ ﺗﻠﻙ ﺍﻷﺟﻬﺯﺓ ﻭﺇﻋﺩﺍﺩ ﻟﻭﺣﺔ ﺧﺎﺻ ﺔ ﺑﺗﻌﻠﻳﻣﺎﺕ ﻭﺧﻁﻭﺍﺕ ﺗﺷ ﻐﻳﻝ ﻭﻣﺭﺍﻗﺑﺔ ﺍﻟﻣﻧﻅﻭﻣﺔ‬
‫ﻭﺗﺣﺩﻳﺩ ﻗﻳﻡ ﺍﻻﺳ ﺗﻁﺎﻋﺔ ﺍﻟﻌﻅﻣﻰ ﺍﻟﻣﺳ ﻣﻭﺡ ﺑﺎﺳ ﺗﺟﺭﺍﺭﻫﺎ ﺣﺳ ﺏ ﺣﺎﻟﺔ ﺍﻟﻌﻣﻝ ﻭﺗﺛﺑﻳﺗﻬﺎ ﺟﺎﻧﺏ ﺍﻟﻣﺟﻣﻭﻋﺔ ﻭﻭﺿ ﻊ ﺍﻟﺗﺳ ﻣﻳﺎﺕ ﺍﻟﻣﻧﺎﺳ ﺑﺔ‬
‫ﻭﺍﻟﺿﺭﻭﺭﻳﺔ ﻋﻠﻰ ﻟﻭﺣﺔ ﺍﻟﺗﺷﻐﻳﻝ ﻭﺍﻟﻣﻔﺎﺗﻳﺢ ﺍﻟﺿﺭﻭﺭﻳﺔ‪.‬‬
‫‪-٧‬ﺍﺳﺗﻼﻡ ﺃﻋﻣﺎﻝ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ‪:‬‬
‫ﻋﻠﻰ ﺍﻟﻣﺗﻌﻬﺩ ﺍﺧﺗﺑﺎﺭ ﻭﺗﺷ ﻐﻳﻝ ﻧﻅﺎﻡ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷ ﻣﺳ ﻳﺔ ﻭﻓﻘﺎ ً ﻟﻣﺎ ﻫﻭ ﻣﻁﻠﻭﺏ ﻓﻲ ﺍﻟﺗﺷ ﻐﻳﻝ ﺍﻟﺗﺟﺭﻳﺑﻲ‪ .‬ﻭﺗﺗﻡ ﻋﻣﻠﻳﺔ ﺍﻻﺳ ﺗﻼﻡ ﺍﻷﻭﻟﻲ‬
‫ﻷﻋﻣﺎﻝ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﺑﻌﺩ ﺍﺟﺗﻳﺎﺯﻫﺎ ﺑﻧﺟﺎﺡ ﻣﺭﺣﻠﺔ ﺍﻟﺗﺷﻐﻳﻝ ﺍﻟﺗﺟﺭﻳﺑﻲ ﺍﻟﻣﺑﻳﻧﺔ ﺃﻋﻼﻩ‪.‬‬
‫‪ - ٨‬ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻟﻣﻛﻭﻧﺎﺕ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ‪:‬‬
‫‪ ‬ﻣﻭﺍﺻﻔﺎﺕ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻭﺗﺷﻐﻳﻝ ﻧﻅﺎﻡ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﻣﻊ ﺍﻟﻬﻳﺎﻛﻝ ﺍﻟﺣﺎﻣﻠﺔ‪:‬‬
‫ﻳﺗﺿﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻭﺗﺷﻐﻳﻝ ﻣﺟﻣﻭﻋﺔ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﻟﺯﻭﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﻼﺯﻣﺔ ﻟﺗﻐﻁﻳﺔ ﺣﻣﻭﻻﺕ‬
‫ﺃﻋﻅﻣﻳﺔ‬
‫‪ ‬ﻣﻭﻗﻊ ﺍﻟﺻﺎﺧﻭﺭ‪:‬‬
‫ﻓﻲ ﻛﺘﻠﺔ ﺍﻟﺒﻨﺎء ﺭﻗﻢ ‪، (17 KW ) ١‬ﻭﻓﻲ ﻛﺘﻠﺔ ﺍﻟﺒﻨﺎء ﺭﻗﻢ ‪ ٢‬ﺍﻷﺫﻳﺔ ﺍﻟﺪﻣﺎﻏﻴﺔ ) ‪.( 6.6 KW‬‬
‫ﻋﻠﻰ ﺃﻥ ﻳﻜﻮﻥ ﻋﺪﺩ ﺍﻷﻟﻮﺍﺡ ﺑﺎﻟﺤﺪ ﺍﻷﺩﻧﻰ ﻟﻜﺘﻠﺔ ﺍﻟﺒﻨﺎء ﺭﻗﻢ ‪ ٣٢ ) ١‬ﻟﻮﺡ ( ﻭﻛﺘﻠﺔ ﺍﻟﺒﻨﺎء ﺭﻗﻢ ‪ ٢‬ﺍﻷﺫﻳﺔ ﺍﻟﺪﻣﺎﻏﻴﺔ ) ‪ ١٤‬ﻟﻮﺡ ( ﻭﻳﻔﻀﻞ‬
‫ﺍﻷﻋﻠﻰ‪.‬‬
‫‪ ‬ﻣﺷﺭﻭﻉ ﻣﺷﻔﻰ ﺍﻷﻁﻔﺎﻝ‪:‬‬
‫)‪ (3.5KW‬ﻓﻲ ﺍﻟﻘﺑﻭ‪ ( 4KW) ,‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻷﺭﺿﻲ‪ ( 2.5KW) ,‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻷﻭﻝ‪ ( 5KW) ,‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺛﺎﻧﻲ‪,‬‬
‫)‪ ( 2KW‬ﻓﻲ ﻛﻝ ﻁﺎﺑﻖ ﻣﻥ ﺍﻟﻁﻭﺍﺑﻖ ﺍﻟﻣﺗﻛﺭﺭﺓ » ﺛﺎﻟﺙ ﻭﺭﺍﺑﻊ ﻭﺧﺎﻣﺱ ﻭﺳﺎﺩﺱ« ‪ ( 5KW) ،‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺳﺎﺑﻊ‬
‫‪ ( 10KW)،‬ﻟﻣﺻﻌﺩ ﻭﺍﺣﺩ‪ ،‬ﻋﻠﻰ ﺃﻥ ﻳﻛﻭﻥ ﻋﺩﺩ ﺍﻷﻟﻭﺍﺡ ﺑﺎﻟﺣﺩ ﺍﻷﺩﻧﻰ ) ‪ ١٠‬ﻟﻭﺡ ﻟﺯﻭﻡ ﺍﻟﻘﺑﻭ ‪ ١٢ ,‬ﻟﻭﺡ ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ‬
‫ﺍﻷﺭﺿﻲ ‪ ٨ ,‬ﻟﻭﺡ ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ ﺍﻷﻭﻝ‪ ١٤ ,‬ﻟﻭﺡ ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺛﺎﻧﻲ‪ ٦ ،‬ﻟﻭﺡ ﻟﺯﻭﻡ ﻛﻝ ﻁﺎﺑﻖ ﻣﻥ ﺍﻟﻁﻭﺍﺑﻖ ﺍﻟﻣﺗﻛﺭﺭﺓ » ﺛﺎﻟﺙ‬
‫ﻭﺭﺍﺑﻊ ﻭﺧﺎﻣﺱ ﻭﺳﺎﺩﺱ« ‪ ١٤ ،‬ﻟﻭﺡ ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺳﺎﺑﻊ ‪ ٢٨ ،‬ﻟﻭﺡ ﻟﺯﻭﻡ ﻣﺻﻌﺩ ﻭﺍﺣﺩ ( ﻭﻳﻔﺿﻝ ﺍﻷﻋﻠﻰ‪.‬‬
‫‪ ‬ﻣﻭﻗﻊ ﺟﺭﻣﺎﻧﺎ‪:‬‬
‫)‪(5.5 KW‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻷﺭﺿﻲ‪ ( 6.75KW) ,‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻷﻭﻝ‪ ( 7KW) ,‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺛﺎﻧﻲ‪ ( 2. 5KW) ,‬ﻓﻲ ﻗﺳﻡ ﺍﻹﺳﻌﺎﻑ‬
‫ﻋﻠﻰ ﺃﻥ ﻳﻛﻭﻥ ﻋﺩﺩ ﺍﻷﻟﻭﺍﺡ ﺑﺎﻟﺣﺩ ﺍﻷﺩﻧﻰ ) ‪ ١٠‬ﻟﻭﺡ ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻷﺭﺿﻲ ‪ ١٣ ,‬ﻟﻭﺡ ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻷﻭﻝ ‪ ١٣ ,‬ﻟﻭﺡ ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺛﺎﻧﻲ ‪,‬‬
‫ﻭ ‪ ٦‬ﻟﻭﺡ ﻓﻲ ﻗﺳﻡ ﺍﻹﺳﻌﺎﻑ ( ﻭﻳﻔﺿﻝ ﺍﻷﻋﻠﻰ‪.‬‬

‫ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﺗﺎﻟﻳﺔ‪:‬‬


‫‪ -‬ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﺟﺩﻳﺩﺓ ﻭﻏﻳﺭ ﻣﺟﺩﺩﺓ‪.‬‬
‫‪ -‬ﻛﺎﻓﺔ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﻧﻔﺱ ﺍﻟﻁﺭﺍﺯ ﻭﺍﻻﺳﺗﻁﺎﻋﺔ ﻭﺍﻟﺷﺭﻛﺔ ﺍﻟﻣﺻﻧﻌﺔ‪.‬‬
‫‪ -‬ﺗﺗﻛﻭﻥ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﻣﻥ ﻣﺟﻣﻭﻋﺔ ﺧﻼﻳـــــﺎ ﺳﻠﻳﻛﻭﻧﻳﺔ ﻣﻥ ﻧــــﻭﻉ ﺃﺣﺎﺩﻱ ﺃﻭ ﻣﺗﻌﺩﺩ ﺍﻟﺑﻠﻭﺭﺍﺕ ﻣﺟﻣﻌﺔ ﺿﻣﻥ ﺇﻁﺎﺭ ﻣﻥ ﺍﻷﻟﻣﻧﻳﻭﻡ‬
‫ﻭﻣﺯﻭﺩﺓ ﺑﺯﺟﺎﺝ ﻣﻐﺷﻰ ﺣﺭﺍﺭﻱ ﻣﻧﺧﻔﺽ ﺍﻟﺣﺩﻳﺩ ﻭﻳﺗﻡ ﻟﺻﻘﻪ ﺑﻭﺍﺳﻁﺔ ﻁﺑﻘﺔ ﺧﺎﺻﺔ ‪ (Ethylene-Vinyl Acetate) EVA‬ﻟﻠﺣﻣﺎﻳﺔ‬
‫ﻭﺗﺄﻣﻳﻥ ﺍﻟﻠﺻﻖ ﺍﻟﺟﻳﺩ‪ ،‬ﻭﺗﺯﻭﺩ ﺍﻟﺧﻼﻳﺎ ﺑﺧﻠﻔﻳﺔ ﻟﻠﺣﻣﺎﻳﺔ ﻣﻥ ﺍﻟﺻﺩﻣﺎﺕ ﻭﺍﻟﻅﺭﻭﻑ ﺍﻟﻣﻧﺎﺧﻳﺔ ‪(Tedlar-polyester-Tedlar)TPT‬‬
‫ﻭﺗﻛﻭﻥ ﺍﻷﻟﻭﺍﺡ ﻣﺣﻣﻳﺔ ﺑﺷﻛﻝ ﻋﺎﻡ ﻭﻛﺗﻳﻣﺔ ﻣﻥ ﺍﻟﺩﺍﺧﻝ ﻭﺗﻛﻭﻥ ﻣﻥ ﺻﻧﺎﻋﺔ ﺇﺣﺩﻯ ﺍﻟﺷﺭﻛﺎﺕ ﺍﻟﻣﻌﺭﻭﻓﺔ ﻓﻲ ﻫﺫﺍ ﺍﻟﻣﺟﺎﻝ‬
‫)‪ ....yingli-solarworld-JASOLAR‬ﺃﻭﻣﺎﻳﻌﺎﺩﻟﻬﺎ( ﺣﺎﺋﺯﺓ ﻋﻠﻰ ﺷﻬﺎﺩﺓ ﺻﺎﺩﺭﺓ ﻋﻥ ﺟﻬﺎﺕ ﻣﻌﺗﻣﺩﺓ ﻋﺎﻟﻣﻳﺎ ً ﻭﺗﺣﻘﻖ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ‬
‫ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻹﺳﻣﻳﺔ ﺍﻟﺗﺎﻟﻳﺔ‪:‬‬
‫● ﺗﻭﺗﺭ ﺍﻟﻌﻣﻝ ﺍﻻﺳﻣﻲ ﻻﻳﻘﻝ ﻋﻥ )‪ ٥٠‬ﻓﻭﻟﺕ(ﺗﻘﺭﻳﺑﺎ ً‪.‬‬
‫● ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻹﺳﻣﻳﺔ ﻻﺗﻘﻝ ﻋﻥ )‪ ٥٤٠‬ﻭﺍﻁ( ﻋﻧﺩ ﺩﺭﺟﺔ ﺣﺭﺍﺭﺓ )‪ ٢٥‬ﺩﺭﺟﺔ ﻣﺋﻭﻳﺔ(‪.‬‬
‫● ﺍﻻﺷﻌﺎﻉ ﺍﻟﺷﻣﺳﻲ )‪ ١٠٠٠‬ﻭﺍﻁ‪/‬ﻡ‪ (٢‬ﻭﻓﻘﺎ ً ﻹﺧﺗﺑﺎﺭﺍﺕ ‪ STC‬ﺑﺩﺭﺟﺔ ﺣﺭﺍﺭﺓ ‪ ٢٥‬ﻣﺋﻭﻳﺔ ﻭﺑﻁﻳﻑ ‪.AM 1.5‬‬
‫● ﻋﺩﺩ ﺍﻷﻟﻭﺍﺡ ﻛﺎﻓﻳﺔ ﻟﺗﺄﻣﻳﻥ ﺍﺳﺗﻁﺎﻋﺔ ﺇﺟﻣﺎﻟﻳﺔ ﺑﺎﻟﺣﺩ ﺍﻷﺩﻧﻰ ﻛﻣﺎ ﻫﻭ ﻣﺣﺩﺩ ﺃﻋﻼﻩ ﻓﻲ ﻅﺭﻭﻑ ﺍﻟﻣﻭﻗﻊ ﻭﻳﻔﺿﻝ ﺍﻷﻋﻠﻰ‪.‬‬
‫● ﺃﻟﻭﺍﺡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﻗﺎﺑﻠﺔ ﻟﻠﺗﻭﺻﻳﻝ ﻣﻊ ﺑﻌﺿﻬﺎ ﺍﻟﺑﻌﺽ ﺑﺷﻛﻝ )ﺗﺳﻠﺳﻠﻲ‪ -‬ﺗﻔﺭﻋﻲ( ﺑﺣﻳﺙ ﺗﺅﻣﻥ ﺍﻟﺗﻭﺗﺭ ﺍﻻﺳﻣﻲ ﺍﻟﻣﻧﺎﺳﺏ ﻟﺗﻐﺫﻳﺔ‬
‫ﺍﻟﻣﻌﺭﺝ‪.‬‬
‫‪ -‬ﻳﺟﺏ ﺃﻥ ﺗﻌﻣﻝ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺿﻣﻥ ﻣﺟﺎﻝ ﺗﻐﻳﻳﺭ ﺩﺭﺟﺔ ﺍﻟﺣﺭﺍﺭﺓ ﻣﻥ )‪ ٤٠-‬ﺩﺭﺟﺔ ﻣﺋﻭﻳﺔ( ﺇﻟﻰ )‪ ٨٥‬ﺩﺭﺟﺔ ﻣﺋﻭﻳﺔ(‪.‬‬
‫‪ -‬ﻳﺟﺏ ﺃﻥ ﻻ ﻳﻘﻝ ﺍﻟﻣﺭﺩﻭﺩ ﺍﻻﺳﻣﻲ ﻟﻠﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﻋﻥ ‪ ،%21.3‬ﻭﺃﻥ ﻻ ﻳﻧﺧﻔﺽ ﻣﺭﺩﻭﺩ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﻋﻥ ‪ %٩٠‬ﻣﻥ ﻣﺭﺩﻭﺩﻫﺎ‬
‫ﺍﻹﺳﻣﻲ ﺧﻼﻝ )‪١٠‬ﺳﻧﻭﺍﺕ( ﻭﻳﺑﻳﻥ ﺫﻟﻙ ﻓﻲ ﺍﻟﻧﺷﺭﺍﺕ ﻭﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﻗﺑﻝ ﺍﻟﻣﺗﻌﻬﺩ‪.‬‬
‫‪ -‬ﺍﻟﺗﻐﻳﺭ ﻓﻲ ﺍﺳﺗﻁﺎﻋﺔ ﺍﻟﻠﻭﺡ ﺍﻟﺷﻣﺳﻲ ﻋﻧﺩ ﺍﻟﺷﺭﻭﻁ ﺍﻟﻘﻳﺎﺳﻳﺔ ﻣﻥ)‪.%(3-0‬‬
‫‪ -‬ﻛﻣﺎ ﻳﺗﺿﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻛﺎﻓﺔ ﻣﺳﺗﻠﺯﻣﺎﺕ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺗﻭﺻﻳﻝ ﻣﻥ )ﻛﺎﺑﻼﺕ ﻭﺑﺭﺍﻏﻲ ﻭﻋﺯﻕ ﻭﻭﺻﻼﺕ ﻣﻌﺩﻧﻳﺔ ﻭﻗﻭﺍﻋﺩ ﻣﻌﺩﻧﻳﺔ ﻣﺅﺭﺿﺔ‬
‫ﻣﻐﻠﻔﻧﺔ ﻏﻳﺭ ﻗﺎﺑﻠﺔ ﻟﻠﺻﺩﺃ ﺃﻭ ﺍﻟﺗﺂﻛﻝ‪.....‬ﺍﻟﺦ(‪.‬‬
‫‪ -‬ﻋﻠﺑﺔ ﺍﻟﺗﻭﺻﻳﻝ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﺫﺍﺕ ﺩﺭﺟﺔ ﺣﻣﺎﻳﺔ ﻻﺗﻘﻝ ﻋﻥ ‪IP67‬‬
‫ـ ﺣﻳﺙ ﻳﻘﻊ ﻋﻠﻰ ﻋﺎﺗﻖ ﺍﻟﺟﻬﺔ ﺍﻟﺩﺍﺭﺳﺔ ﺗﻘﺩﻳﻡ ﻛﺎﻓﺔ ﺍﻟﻣﺧﻁﻁﺎﺕ ﺍﻟﺗﺻﻣﻳﻣﻳﺔﻭﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻟﺗﻧﻔﻳﺫ ﺍﻟﻬﻳﻛﻝ ﺍﻟﻣﻌﺩﻧﻲ ﻟﺗﺛﺑﻳﺕ ﺍﻟﻬﻳﺎﻛﻝ ﺍﻟﺣﺎﻣﻠﺔ‬
‫ﻟﻸﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﻛﻣﺎ ﻫﻲ ﻣﺑﻳﻧﺔ ﻓﻲ ﺑﻧﻭﺩ ﺍﻷﻋﻣﺎﻝ ﺍﻹﻧﺷﺎﺋﻳﺔ ﻭﺍﻟﻣﻌﺩﻧﻳﺔ ﻣﻥ ﺩﻓﺗﺭ ﺍﻟﺷﺭﻭﻁ ﺍﻟﻔﻧﻳﺔ ﻋﻠﻰ ﺃﻥ ﻳﺗﻡ ﺍﻟﺗﻧﻔﻳﺫ ﺑﺟﻭﺩﺓ ﻓﻧﻳﺔ ﻋﺎﻟﻳﺔ‬
‫ﺟﺎﻫﺯﺍً ﻟﻼﺳﺗﺛﻣﺎﺭ‪.‬‬
‫ـ ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺍﻟﺗﻭﺿﻳﺢ ﻓﻲ ﻋﺭﺿﻪ ﺍﻟﻔﻧﻲ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﻓﻲ ﺍﻟﺟﺩﻭﻝ ﺭﻗﻡ ‪) /١/‬ﺑﻣﻠﺣﻖ ﺩﻓﺗﺭ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ‬
‫ﺍﻟﻔﻧﻳﺔ( ﻭﺑﺷﻛﻝ ﻣﻧﻔﺻﻝ ﻣﺩﻋﻣﺔ ﺑﺎﻟﻧﺷﺭﺍﺕ ﺍﻟﻔﻧﻳﺔ ﻭﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﺑﻘﻠﻡ ﻋﻼﻡ ﺑﺷﻛﻝ ﻭﺍﺿﺢ‪.‬‬

‫‪ ‬ـ ﻣﻭﺍﺻﻔﺎﺕ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻭﺗﺷﻐﻳﻝ ﺍﻟﻣﻌﺭﺟﺎﺕ )ﺍﻹﻧﻔﻳﺭﺗﺭ(‪:‬‬


‫ﻳﺗﺿﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﺍﻟﻣﻌﺭﺟﺎﺕ ﺍﻟﻼﺯﻣﺔ ﻟﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗـــــﺔ ﺍﻟﺷﻣﺳﻳﺔ ﻣﻥ ﺷﺭﻛﺎﺕ ﻋﺎﻟﻣﻳﺔ ﻣﺗﺧﺻﺻﺔ‬ ‫‪-‬‬
‫‪ ........‬ﺃﻭ ﻣﺎﻳﻌﺎﺩﻟﻬﺎ(‪.‬‬ ‫)‪-GROWATT -SOLartech-ABB‬‬
‫ﺑﺣﻳﺙ ﺗﺣﻘﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺗﺎﻟﻳﺔ‪:‬‬ ‫‪-‬‬
‫ﺃﻥ ﺗﻛﻭﻥ ﺍﻟﻣﻌﺭﺟﺎﺕ ﺟﺩﻳﺩﺓ ﻭﻏﻳﺭ ﻣﺟﺩﺩﺓ ‪.‬‬ ‫‪-‬‬
‫ﺃﻥ ﻳﻛﻭﻥ ﺍﻟﻣﻌﺭﺟﺎﺕ ﺍﻟﻣﻁﻠﻭﺏ ﺗﻘﺩﻳﻣﻬﺎ‪:‬‬ ‫‪-‬‬
‫‪-‬‬
‫ﻟﺯﻭﻡ ﻣﻭﻗﻊ ﺍﻟﺻﺎﺧﻭﺭ‪:‬‬ ‫‪‬‬
‫ﺃﺣﺎﺩﻱ ﺍﻟﻁﻭﺭ ﺑﺎﺳﺗﻁﺎﻋﺔ ﻻﺗﻘﻝ ﻟﻛﺗﻠﺔ ﺍﻟﺑﻧﺎء ﺭﻗﻡ ‪ ( 25KW) ١‬ﺃﻭ ﺑﺎﻟﺣﺩ ﺍﻷﻋﻠﻰ ﺧﻣﺱ ﻣﻌﺭﺟﺎﺕ ﺃﺣﺎﺩﻳﺔ ﺍﻟﻁﻭﺭ ﻗﺎﺑﻠﺔ ﻟﻠﺗﻭﺻﻳﻝ‬
‫ﻋﻠﻰ ﺍﻟﺗﺳﻠﺳﻝ ﺑﺷﻛﻝ ﻓﻧﻲ ﺑﺣﻳﺙ ﻳﻛﻭﻥ ﺍﺳﺗﻁﺎﻋﺔ ﺍﻟﻣﻌﺭﺝ ﺍﻟﻭﺍﺣﺩ ﻻ ﻳﻘﻝ ﻋﻥ )‪ (5 kw‬ﻭﻳﻔﺿﻝ ﺍﻷﻋﻠﻰ‪،‬‬
‫ﻭﻟﻛﺗﻠﺔ ﺍﻟﺑﻧﺎء ﺭﻗﻡ ‪ ٢‬ﺍﻻﺫﻳﺔ ﺍﻟﺩﻣﺎﻏﻳﺔ ﻻﺗﻘﻝ ﻋﻥ )‪ (8KW‬ﺃﻭ ﺑﺎﻟﺤﺪ ﺍﻷﻋﻠﻰ ﻣﺠﻤﻮﻋﺔ ﻣﻌﺮﺟﺎﺕ ﻻﺗﻘﻞ ﺍﻹﺳﺘﻄﺎﻋﺔ ﺍﻹﻓﺮﺍﺩﻳﺔ ﻋﻦ‬
‫)‪.(3 kw‬‬

‫ﻟﺯﻭﻡ ﻣﺷﺭﻭﻉ ﻣﺷﻔﻰ ﺍﻷﻁﻔﺎﻝ‪:‬‬ ‫‪‬‬


‫ﺃﺣﺎﺩﻱ ﺍﻟﻁﻭﺭ ﺑﺎﺳ ﺗﻁﺎﻋﺔ ﻻﺗﻘﻝ ﻋﻥ )‪ ( 5KW‬ﻓﻲ ﺍﻟﻘﺑﻭ‪ ( 5KW) ,‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻷﺭﺿ ﻲ ‪ ( 3KW),‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻷﻭﻝ‪,‬‬
‫)‪ ( 6KW‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺛﺎﻧﻲ‪ ( 3KW) ،‬ﻓﻲ ﻛﻝ ﻁﺎﺑﻖ ﻣﻥ ﺍﻟﻁﻭﺍﺑﻖ ﺍﻟﻣﺗﻛﺭﺭﺓ » ﻟﺚ وراﺑﻊ وﺧﺎﻣﺲ وﺳﺎدس« ‪،‬‬
‫)‪ ( 6KW‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺳ ﺎﺑﻊ ﻭﺛﻼﺛﻲ ﺍﻟﻁﻭﺭ ﺑﺎﺳ ﺗﻁﺎﻋﺔ ﻻﺗﻘﻝ ﻋﻥ )‪ ( 15KW‬ﻟﻣﺻ ﻌﺩ ﻭﺍﺣﺩ ﺃﻭ ﺑﺎﻟﺣﺩ ﺍﻷﻋﻠﻰ ﺧﻣﺱ ﻣﻌﺭﺟﺎﺕ‬
‫ﺃﺣﺎﺩﻳﺔ ﺍﻟﻁﻭﺭ ﻗﺎﺑﻠﺔ ﻟﻠﺗﻭﺻ ﻳﻝ ﻋﻠﻰ ﺍﻟﺗﺳ ﻠﺳ ﻝ ﺑﺷ ﻛﻝ ﻓﻧﻲ ﺑﺣﻳﺙ ﻳﻛﻭﻥ ﺍﺳ ﺗﻁﺎﻋﺔ ﺍﻟﻣﻌﺭﺝ ﺍﻟﻭﺍﺣﺩ ﻻﻳﻘﻝ ﻋﻥ ) ‪ ( 5KW‬ﻭﻳﻔﺿ ﻝ‬
‫ﺍﻷﻋﻠﻰ‪.‬‬

‫ﻟﺯﻭﻡ ﻣﻭﻗﻊ ﺟﺭﻣﺎﻧﺎ‪:‬‬ ‫‪‬‬


‫ﺃﺣﺎﺩﻱ ﺍﻟﻁﻭﺭ ﺑﺎﺳﺗﻁﺎﻋﺔ ﻻﺗﻘﻝ ﻋﻥ)‪ ( 7.5KW‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻷﺭﺿﻲ‪ ( 8KW) ,‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ ﺍﻷﻭﻝ‪ ( 8.5KW) ,‬ﻓﻲ ﺍﻟﻁﺎﺑﻖ‬
‫ﺍﻟﺛﺎﻧﻲ‪ ( 3.5KW) ,‬ﻓﻲ ﻗﺳﻡ ﺍﻹﺳﻌﺎﻑ ﻭ ﻳﻔﺿﻝ ﺍﻷﻋﻠﻰ‪.‬‬
‫ﺃﻭ ﻣﺟﻣﻭﻋﺔ ﻣﻌﺭﺟﺎﺕ ﻟﻛﻝ ﻁﺎﺑﻖ ﻗﺎﺑﻠﺔ ﻟﻠﺗﻭﺻﻳﻝ ﻋﻠﻰ ﺍﻟﺗﺳﻠﺳﻝ ﺑﺷﻛﻝ ﻓﻧﻲ ﻻﺗﻘﻝ ﺍﺳﺗﻁﺎﻋﺔ ﺍﻵﻧﻔﺭﺗﺭ ﺍﻟﻭﺍﺣﺩ ﻋﻥ ) ‪.( 3 KW‬‬
‫ﺃﻥ ﺗﻛﻭﻥ ﺟﻣﻳﻊ ﺍﻟﻣﻌﺭﺟﺎﺕ ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﻧﻔﺱ ﺍﻟﺷﺭﻛﺔ ﺍﻟﺻﺎﻧﻌﺔ‪.‬‬ ‫‪-‬‬
‫ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻻﺟﻣﺎﻟﻳﺔ ﻟﺧﺭﺝ ﺍﻟﻣﻌﺭﺟﺎﺕ ﺗﻐﻁﻲ ﺍﻟﺣﻣﻭﻻﺕ ﺍﻟﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﺃﻋﻼﻩ‪.‬‬ ‫‪-‬‬
‫‪ -‬ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺍﻟﻣﻌﺭﺟﺎﺕ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﻘﺎﺑﻝ ﻟﻠﺑﺭﻣﺟﺔ ﻭﺍﻟﺧﺎﺻﺔ ﺑﺄﻧﻅﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ‪.‬‬
‫‪ -‬ﺍﻟﻣﻌﺭﺟﺎﺕ ﻣﺯﻭﺩﺓ ﺑﺷﺎﺷﺔ ﺇﻅﻬﺎﺭ ﺭﻗﻣﻳﺔ ﺗﻭﺿﺢ ﺣﺎﻟﺔ ﺍﻟﻌﻣﻝ ﻟﻠﻣﻧﻅﻭﻣﺔ ﻭﺍﻟﻣﺣﺩﺩﺍﺕ ﺍﻟﺭﺋﻳﺳﻳﺔ ﻟﻠﻣﻧﻅﻭﻣﺔ )ﺟﻬﺩ ﻭﺗﻳﺎﺭ ﻭﺍﺳﺗﻁﺎﻋﺔ ﺩﺧﻝ‬
‫ﺍﻟﻣﻌﺭﺝ ‪ -‬ﺟﻬﺩ ﻭﺗﺭﺩﺩ ﻭﺗﻳﺎﺭ ﺧﺭﺝ ﺍﻟﻣﻌﺭﺝ – ﺩﺭﺟﺔ ﺣﺭﺍﺭﺓ ﺍﻟﻣﻌﺭﺝ – ﺍﻟﻭﻗﺕ ﻭﺍﻟﺗﺎﺭﻳﺦ – ﺍﻟﻁﺎﻗﺔ ﺍﻟﻣﻧﺗﺟﺔ ﻓﻲ ﺍﻟﻳﻭﻡ‬
‫ﺟﻬﺩ ﻧﻘﻁﺔ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻷﻋﻅﻣﻳﺔ ﻓﻲ ﺍﻟﻳﻭﻡ – ﺗﻭﻗﻳﺕ ﺑﺩء ﻭﺍﻧﺗﻬﺎء ﻋﻣﻝ ﺍﻟﻣﻌﺭﺝ ﺑﺎﻟﻳﻭﻡ ‪-‬ﻋﺩﺩ ﺳﺎﻋﺎﺕ ﻋﻣﻝ ﺍﻟﻣﻌﺭﺝ ﺑﺎﻟﻳﻭﻡ(‪.‬‬
‫‪ -‬ﻳﺟﺏ ﺃﻥ ﻳﻛﻭﻥ ﺧﺭﺝ ﺍﻟﻣﻌﺭﺟﺎﺕ ﺍﻟﻣﻘﺩﻣﺔ ﺛﻼﺛﻳﺔ ﺍﻟﻁﻭﺭ‪ ،‬ﻭﺗﻌﻣﻝ ﺑﺗﻘﻧﻳﺔ ﻣﻼﺣﻘﺔ ﻧﻘﻁﺔ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻷﻋﻅﻣﻳﺔ )‪.(MPPT‬‬
‫‪ -‬ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺇﺷﺎﺭﺓ ﺧﺭﺝ ﺍﻟﻣﻌﺭﺟﺎﺕ ﺟﻳﺑﻳﺔ ﻭﻧﻘﻳﺔ‪.‬‬
‫‪ -‬ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺗﺣﺩﻳﺩ ﻣﺎﻳﻠﻲ‪:‬‬
‫‪ ‬ﺩﺭﺟﺔ ﺣﻣﺎﻳﺔ ﺍﻟﻣﻌﺭﺝ‪.‬‬
‫‪ ‬ﻧﻭﻉ ﺍﻟﻣﻌﺭﺝ ‪ Outdoor‬ﺃﻭ ‪ indoor‬ﺣﺳﺏ ﺍﻟﻣﻭﻗﻊ ﺍﻟﻣﺣﺩﺩ ﻟﻠﺗﺭﻛﻳﺏ‪.‬‬
‫‪ ‬ﻣﺭﺩﻭﺩ ﺍﻟﻣﻌﺭﺝ ﻻﻳﻘﻝ ﻋﻥ ‪.%95‬‬
‫‪ ‬ﻣﺟﺎﻝ ﺗﻐﻳﺭ ﺍﻟﺗﻭﺗﺭ ﻟﺩﺧﻝ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭ )‪ (Dc‬ﻣﻥ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ‪.‬‬
‫‪ ‬ﺟﻬﺩ ﺍﻟﺩﺧﻝ ﺍﻷﻋﻅﻣﻲ ﻟﻠﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭ‪.‬‬
‫‪ ‬ﻣﺟﺎﻝ ﺗﻐﻳﺭ ﺍﻟﺗﻭﺗﺭ ﻟﺧﺭﺝ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺗﻧﺎﻭﺏ )‪.(Ac‬‬
‫‪ ‬ﻣﺟﺎﻝ ﺗﻐﻳﺭ ﺍﻟﺗﺭﺩﺩ ﻟﻠﺗﻳﺎﺭ ﺍﻟﻣﺗﻧﺎﻭﺏ‪.‬‬
‫‪ ‬ﺗﺣﺩﻳﺩ ﺍﻟﻣﺟﺎﻝ ﺍﻟﺣﺭﺍﺭﻱ ﻟﻌﻣﻝ ﺍﻟﻣﻌﺭﺝ ﺣﻳﺙ ﻳﻔﺿﻝ )‪.(C 50 +  C 10-‬‬
‫‪ ‬ﺗﺣﺩﻳﺩ ﻗﻳﻣﺔ ﺗﻳﺎﺭ ﺍﻟﺧﺭﺝ ﺍﻻﺳﻣﻲ ﻟﻠﻣﻌﺭﺝ‪.‬‬
‫‪ ‬ﺗﺣﺩﻳﺩ ﺍﺳﺗﻁﺎﻋﺔ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻣﻣﻛﻥ ﺭﺑﻁﻬﺎ ﻣﻊ ﺍﻟﻣﻌﺭﺝ‪.‬‬
‫‪ ‬ﺗﺣﺩﻳﺩ ﻋﺩﺩ ﻣﺩﺍﺧﻝ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭﻟﻠﻣﻌﺭﺟﺎﺕ‪.‬‬
‫‪ ‬ﻳﺟﺏ ﺃﻥ ﻳﺣﺗﻭﻱ ﺍﻟﻣﻌﺭﺝ ﻋﻠﻰ ﻛﺎﻓﺔ ﺍﻟﺣﻣﺎﻳﺎﺕ ﺍﻟﻼﺯﻣﺔ‪:‬‬
‫)ﺣﻣﺎﻳﺔ ﻣﻥ ﺯﻳﺎﺩﺓ ﺍﻟﺣﻣﻝ – ﺣﻣﺎﻳﺔ ﻣﻥ ﺗﻳﺎﺭ ﺍﻟﻘﺻﺭ – ﺣﻣﺎﻳﺔ ﻣﻥ ﺯﻳﺎﺩﺓ ﺃﻭ ﺍﻧﺧﻔﺎﺽ ﺍﻟﺗﻭﺗﺭ ﺃﻭ ﻋﺩﻡ ﺗﺗﺎﺑﻊ ﺍﻷﻁﻭﺍﺭ‬
‫ﺣﻣﺎﻳﺔ ﻣﻥ ﺍﺭﺗﻔﺎﻉ ﺩﺭﺟﺔ ﺍﻟﺣﺭﺍﺭﺓ ‪.......-‬ﺍﻟﺦ(‪.‬‬
‫‪ ‬ﻳﺗﻭﺟﺏ ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺗﻘﺩﻳﻡ ﺷﻬﺎﺩﺍﺕ ﺍﻻﺧﺗﺑﺎﺭ ﺍﻟﻣﻌﺗﻣﺩﺓ ﻋﺎﻟﻣﻳﺎ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻟﻣﻌﺭﺟﺎﺕ ﺍﻟﻣﻘﺩﻣﺔ‪.‬‬
‫ً‬

‫ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺍﻟﺗﻭﺿﻳﺢ ﻓﻲ ﻋﺭﺿﻪ ﺍﻟﻔﻧﻲ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﻓﻲ ﺍﻟﺟﺩﻭﻝ ﺭﻗﻡ ‪) /٢/‬ﺑﻣﻠﺣﻖ ﺩﻓﺗﺭ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ‬ ‫‪‬‬
‫ﺍﻟﻔﻧﻳﺔ( ﺑﺷﻛﻝ ﻣﻧﻔﺻﻝ ﻣﺩﻋﻣﺔ ﺑﺎﻟﻧﺷﺭﺍﺕ ﺍﻟﻔﻧﻳﺔ ﻭﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﺑﻘﻠﻡ ﻋﻼﻡ ﺑﺷﻛﻝ ﻭﺍﺿﺢ‪.‬‬

‫ﻣﻭﺍﺻﻔﺎﺕ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻭﺷﺣﻥ ﻭﺗﺷﻐﻳﻝ ﺍﻟﻣﺩﺧﺭﺍﺕ‪:‬‬ ‫‪‬‬


‫ﻳﺗﺿﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭ ﺗﻭﺻﻳﻝ ﻭﺷﺣﻥ ﻭﺗﺷﻐﻳﻝ ﻣﺩﺧﺭﺍﺕ ﻛﺎﻓﻳﺔ ﻟﺗﻐﻁﻳﺔ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻷﻋﻅﻣﻳﺔ ﻟﺧﺭﺝ ﺍﻟﻣﻌﺭﺟﺎﺕ‬
‫ﻟﺯﻭﻡ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﻭﻋﺩﺩﻫﺎ ﺑﺎﻟﺣﺩ ﺑﺎﻷﺩﻧﻰ‪.‬‬
‫ﻟﺯﻭﻡ ﻣﻭﻗﻊ ﺍﻟﺻﺎﺧﻭﺭ‪:‬‬ ‫‪‬‬
‫ﻟﻜﺘﻠﺔ ﺍﻟﺒﻨﺎء ﺭﻗﻢ ‪ ٣٦ ) ١‬ﻣﺪﺧﺮﺓ ( ‪ ،‬ﻭﻟﻜﺘﻠﺔ ﺍﻟﺒﻨﺎء ﺭﻗﻢ ‪ ١٦ ) ٢‬ﻣﺪﺧﺮﺓ ( ﻭﻳﻔﻀﻞ ﺍﻷﻋﻠﻰ‪.‬‬
‫‪ ‬ﻟﺯﻭﻡ ﻣﺷﺭﻭﻉ ﻣﺷﻔﻰ ﺍﻷﻁﻔﺎﻝ‪:‬‬
‫) ‪ ٨‬ﻣﺩﺧﺭﺓ ﻟﺯﻭﻡ ﺍﻟﻘﺑﻭ ‪ ٨ ,‬ﻣﺩﺧﺭﺓ ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ ﺍﻷﺭﺿﻲ ‪ ٤ ,‬ﻣﺩﺧﺭﺓ ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ ﺍﻷﻭﻝ ‪ ١٠ ,‬ﻣﺩﺧﺭﺓ ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺛﺎﻧﻲ‪،‬‬
‫‪٤‬ﻣﺩﺧﺭﺓ ﻟﺯﻭﻡ ﻛﻝ ﻁﺎﺑﻖ ﻣﻥ ﺍﻟﻁﻭﺍﺑﻖ ﺍﻟﻣﺗﻛﺭﺭﺓ » ﺛﺎﻟﺙ ﻭﺭﺍﺑﻊ ﻭﺧﺎﻣﺱ ﻭﺳﺎﺩﺱ«‪ ١٠ ،‬ﻣﺩﺧﺭﺓ ﻟﺯﻭﻡ ﺍﻟﻁﺎﺑﻖ ﺍﻟﺳﺎﺑﻊ ‪،‬‬
‫‪٢٠‬ﻣﺩﺧﺭﺓ ﻟﺯﻭﻡ ﻣﺻﻌﺩ ﻭﺍﺣﺩ ( ﻭﻳﻔﺿﻝ ﺍﻷﻋﻠﻰ‪.‬‬
‫‪ ‬ﻟﺯﻭﻡ ﻣﻭﻗﻊ ﺟﺭﻣﺎﻧﺎ‪:‬‬
‫) ‪١٢‬ﻣﺩﺧﺭﺓ ﻟﻠﻁﺎﺑﻖ ﺍﻷﺭﺿﻲ ‪ ١٦,‬ﻣﺩﺧﺭﺓ ﻟﻠﻁﺎﺑﻖ ﺍﻷﻭﻝ ‪١٦ ,‬ﻣﺩﺧﺭﺓ ﻟﻠﻁﺎﺑﻖ ﺍﻟﺛﺎﻧﻲ ‪ ٨,‬ﻣﺩﺧﺭﺓ ﻟﻘﺳﻡ ﺍﻹﺳﻌﺎﻑ( ﻭﻳﻔﺿﻝ ﺍﻷﻋﻠﻰ‪.‬‬

‫ﻭﺗﺣﻘﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺗﺎﻟﻳﺔ‪:‬‬


‫ﻧﻭﻉ ﺍﻟﻣﺩﺧﺭﺍﺕ ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﺟﺎﻑ ‪. Gel‬‬ ‫‪-‬‬
‫ﺍﻟﻣﺩﺧﺭﺓ ﺍﻟﻭﺍﺣﺩﺓ ﻻﺗﻘﻝ ﻋﻥ ) ‪ 200A - 12 V‬ﻋﻧﺩ ‪(C10‬‬ ‫‪-‬‬
‫ﺍﻟﺳﻌﺔ ﺍﻹﺟﻣﺎﻟﻳﺔ ﻟﻠﻣﺩﺧﺭﺍﺕ ﺗﺅﻣﻥ ﺗﻐﺫﻳﺔ ﻣﺳﺗﻣﺭﺓ ﻷﺣﻣﺎﻝ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﺳﺗﻁﺎﻋﺗﻬﺎ ﺍﻷﻋﻅﻣﻳﺔ ﻛﻣﺎ ﻫﻭ ﻣﺷﺎﺭ ﺃﻋﻼﻩ‪.‬‬ ‫‪-‬‬
‫ﻋﻣﻖ ﺍﻟﺗﻔﺭﻳﻎ ﻻﻳﺯﻳﺩ ﻋﻥ ‪.%٦٠‬‬ ‫‪-‬‬
‫ﻋﺩﺩ ﺩﻭﺭﺍﺕ ﺍﻟﻌﻣﻝ ﻟﻠﻣﺩﺧﺭﺓ ﻋﻧﺩ ﻋﻣﻖ ﺍﻟﺗﻔﺭﻳﻎ ﻻﻳﻘﻝ ﻋﻥ ‪.%٥٠‬‬ ‫‪-‬‬
‫ﺗﺣﺩﻳﺩ ﺗﻳﺎﺭ ﺍﻟﺷﺣﻥ ﻟﻠﻣﺩﺧﺭﺓ‪.‬‬ ‫‪-‬‬
‫ﺗﺣﺩﻳﺩ ﺗﻳﺎﺭﺍﻟﺗﻔﺭﻳﻎ ﻟﻠﻣﺩﺧﺭﺓ‪.‬‬ ‫‪-‬‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﺟﺎﻝ ﺍﻟﺣﺭﺍﺭﻱ ﻟﻌﻣﻝ ﺍﻟﻣﺩﺧﺭﺓ‪.‬‬ ‫‪-‬‬
‫ﺗﺣﺩﻳﺩ ﻭﺯﻥ ﻭﺗﺎﺭﻳﺦ ﺇﻧﺗﺎﺝ ﺍﻟﻣﺩﺧﺭﺓ‪.‬‬ ‫‪-‬‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻌﻣﺭ ﺍﻻﻓﺗﺭﺍﺿﻲ ﻟﻠﻣﺩﺧﺭﺓ‪.‬‬ ‫‪-‬‬
‫ﺗﺣﺩﻳﺩ ﻋﻣﻖ ﺍﻟﺗﻔﺭﻳﻎ ﺍﻷﻋﻅﻣﻲ ﻟﻠﻣﺩﺧﺭﺓ‪.‬‬ ‫‪-‬‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﻘﺎﻭﻣﺔ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻟﻠﻣﺩﺧﺭﺓ‪.‬‬ ‫‪-‬‬
‫ﻳﺗﻡ ﺗﺭﻛﻳﺏ ﻭ ﺗﺛﺑﻳﺕ ﺍﻟﻣﺩﺧﺭﺍﺕ ﻋﻠﻰ ﻗﻭﺍﻋﺩ ﺃﻭ ﺧﺯﻥ ﻣﻌﺩﻧﻳﺔ ﺑﺷﻛﻝ ﻓﻧﻲ ﻣﻊ ﺗﻘﺩﻳﻡ ﻛﺎﻓﺔ ﺍﻟﻠﻭﺍﺯﻡ ﺍﻟﺗﺛﺑﻳﺕ ﻭ ﺍﻟﺗﻭﺻﻳﻝ ﺑﺣﻳﺙ ﻳﻛﻭﻥ ﺍﻟﻌﻣﻝ‬ ‫‪-‬‬
‫ﻣﻧﻔﺫ ﺑﺟﻭﺩﺓ ﻓﻧﻳﺔ ﻋﺎﻟﻳﺔ ﻭ ﺣﺳﺏ ﺗﻭﺟﻳﻬﺎﺕ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ‪.‬‬

‫ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺍﻟﺗﻭﺿﻳﺢ ﻓﻲ ﻋﺭﺿﻪ ﺍﻟﻔﻧﻲ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﻓﻲ ﺍﻟﺟﺩﻭﻝ ﺭﻗﻡ ‪) /٣/‬ﺑﻣﻠﺣﻖ ﺩﻓﺗﺭ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ(‬
‫ﺑﺷﻛﻝ ﻣﻧﻔﺻﻝ ﻣﺩﻋﻣﺔ ﺑﺎﻟﻧﺷﺭﺍﺕ ﺍﻟﻔﻧﻳﺔ ﻭﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﺑﻘﻠﻡ ﻋﻼﻡ ﺑﺷﻛﻝ ﻭﺍﺿﺢ‪.‬‬

‫‪ ‬ﻣﻭﺍﺻﻔﺎﺕ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﺍﻹﻛﺳﺳﻭﺍﺭﺍﺕ ﺍﻟﻣﻠﺣﻘﺔ ﺑﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ‪:‬‬


‫ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻛﺎﻓﺔ ﺍﻹﻛﺳ ﺳ ﻭﺍﺭﺍﺕ ﺍﻟﻼﺯﻣﺔ ﻟﻌﻣﻠﻳﺔ ﺍﻟﺗﻭﺻ ﻳﻼﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﻼﺯﻣﺔ ﻓﻲ ﺣﻘﻝ ﺍﻟﻠﻭﺍﻗﻁ ﺍﻟﻛﻬﺭﻭﺿ ﻭﺋﻳﺔ‬ ‫‪‬‬
‫ﻣﻥ )ﻋﻠﺏ ﺗﻭﺻ ﻳﻝ – ﻛﺎﺑﻼﺕ ﺗﻐﺫﻳﺔ ﻭﻧﻘﻝ ﺇﺷ ﺎﺭﺓ )‪ (DC‬ﺑﻣﻘﺎﻁﻌﻬﺎ ﺍﻟﻣﺧﺗﻠﻔﺔ ﻟﺯﻭﻡ ﺍﻷﻟﻭﺍﺡ ﻭﺍﻟﺑﻁﺎﺭﻳﺎﺕ – ﻣﺟﺎﺭﻱ ﻣﻌﺩﻧﻳﺔ‬
‫ﻣﻐﻠﻔﻧﺔ ﻟﺯﻭﻡ ﺗﻣﺩﻳﺩ ﺍﻟﻛﺎﺑﻼﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﺍﻟﺧﺎﺭﺟﻳﺔ ﻣﻥ ﺧﻼﻟﻬﺎ ‪ -‬ﻗﻭﺍﻁﻊ ﻭﺣﻣﺎﻳﺎﺕ – ﺻ ﻭﻟﻳﺎﺕ – ﺟﻧﻛﺳ ﻳﻭﻧﺎﺕ ‪ -‬ﺭﺅﻭﺱ ﺩﺑﻭﺱ‬
‫ﺣﻳﺙ ﻳﻠﺯﻡ ﺍﻟﻌﻣﻝ ﺍﻟﻔﻧﻲ( ﺑﺣﻳﺙ ﺗﻛﻭﻥ ﻛﺎﻓﺔ ﻣﺳ ﺗﻠﺯﻣﺎﺕ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺗﻭﺻ ﻳﻝ ﻭﺍﻟﺗﺛﺑﻳﺕ ﻭﺍﻟﺗﺭﻗﻳﻡ ﻟﺑﺩﺍﻳﺔ ﻭﻧﻬﺎﻳﺔ ﺍﻟﻛﺑﻝ‬ ‫‪....‬ﺍﻟﺦ‬
‫ﺑﺎﻟﻣﻘﺎﻁﻊ ﺍﻟﻣﻧﺎﺳ ﺑﺔ ﻟﻼﺳ ﺗﻁﺎﻋﺎﺕ ﻭﺃﻥ ﺗﻛﻭﻥ ﻣﻥ ﺃﺟﻭﺩ ﺍﻟﻣﻭﺍﺻ ﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻟﺗﺄﻣﻳﻥ ﺟﺎﻫﺯﻳﺔ ﺍﻟﻌﻣﻝ ﺑﺟﻭﺩﺓ ﻓﻧﻳﺔ ﻋﺎﻟﻳﺔ‬
‫ﻭﺫﻟﻙ ﻟﺯﻭﻡ ﺍﻟﻣﺷﺎﺭﻳﻊ ﺍﻟﺛﻼﺙ ﺍﻟﻣﺫﻛﻭﺭﺓ‪.‬‬
‫ﻣﻠﺤﻖ ﺩﻓﺘﺮ ﺍﻟﻤﻮﺍﺻﻔﺎﺕ ﺍﻟﻔﻨﻴﺔ‬
‫‪/‬ﻣﻨﻈﻮﻣﺔ ﺍﻟﻄﺎﻗﺔ ﺍﻟﺸﻤﺴﻴﺔ‪/‬‬

‫‪ ‬ﺍﻟﺟﺩﺍﻭﻝ ﻟﺗﺟﻬﻳﺯﺍﺕ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ‪:‬‬

‫ﻣﻭﺍﺻﻔﺎﺕ ﺗﺟﻬﻳﺯﺍﺕ ﻧﻅﺎﻡ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﻣﻊ ﺍﻟﻬﻳﺎﻛﻝ ﺍﻟﺣﺎﻣﻠﺔ ﻭﻣﻠﺣﻘﺎﺗﻬﺎ ﻭﻓﻖ ﺍﻟﺟﺩﻭﻝ ﺭﻗﻡ ‪/١/‬‬

‫ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﻗﺑﻝ ﺍﻟﻌﺎﺭﺽ‬


‫ﺑﻳﺎﻥ ﺍﻟﻣﺎﺩﺓ ﻭﻣﻭﺍﺻﻔﺎﺗﻬﺎ‬
‫ﺍﻟﻭﺣﺩﺓ‬ ‫ﺭﻗﻡ‬

‫ﺟﺭﻣﺎﻧﺎ‬ ‫ﻣﺷﻔﻰ ﺍﻷﻁﻔﺎﻝ‬ ‫ﺍﻟﺻﺎﺧﻭﺭ‬

‫‪٢‬‬ ‫ﺗﺣﺩﻳﺩ ﻣﺳﺎﺣﺔ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﻭﻁﺭﻳﻘﺔ ﺍﻟﺗﺭﻛﻳﺏ‬


‫ﻡ‬ ‫‪١‬‬
‫ﻣﻊ ﺗﻘﺩﻳﻡ ﺍﻟﻣﺧﻁﻁ ﺍﻟﻼﺯﻡ‬
‫ﺍﻻﻟﺗﺯﺍﻡ ﺑﺯﺍﻭﻳﺔ ﻣﻳﻝ ﺃﻟﻭﺍﺡ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﻣﻥ )‪٣٠-٢٠‬‬
‫‪-‬‬ ‫ﺩﺭﺟﺔ ﻣﺋﻭﻳﺔ( ﻣﻊ ﺍﻟﻣﺧﻁﻁﺎﺕ ﺍﻟﻼﺯﻣﺔ‬
‫‪٢‬‬

‫ﺗﺣﺩﻳﺩ ﺍﺳﺗﻁﺎﻋﺔ ﻧﻅﺎﻡ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ )ﺍﻷﻟﻭﺍﺡ‬


‫ﻭﺍﻁ‬ ‫‪٣‬‬
‫ﺍﻟﺷﻣﺳﻳﺔ(‬

‫ﻛﻳﻠﻭ ﻭﺍﻁ‬ ‫ﺍﺳﺗﻁﺎﻋﺔ ﺍﻟﻣﺣﻭﻟﺔ )ﺍﻹﻧﻔﺭﺗﺭ(‬ ‫‪٤‬‬

‫ﺗﺣﺩﻳﺩ ﻣﻭﺍﺻﻔﺎﺕ ﻣﻌﺩﻥ ﺍﻟﻬﻳﻛﻝ ﺍﻟﻣﻌﺩﻧﻲ )ﺣﺩﻳﺩ ﻣﻐﻠﻔﻥ‬


‫‪-‬‬ ‫‪٥‬‬
‫ﺃﻭ ﺃﻟﻣﻧﻳﻭﻡ(‬

‫‪٢‬‬
‫ﻣﻠﻡ‬ ‫ﺗﺣﺩﻳﺩ ﻣﻘﻁﻊ ﺍﻟﻬﻳﻛﻝ ﺍﻟﻣﻌﺩﻧﻲ ﻭﺷﻛﻠﻪ‬ ‫‪٦‬‬

‫ﺍﻻﻟﺗﺯﺍﻡ ﺑﺗﻘﺩﻳﻡ ﻛﺎﻓﺔ ﻣﺳﺗﻠﺯﻣﺎﺕ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺗﻭﺻﻳﻝ‬


‫‪-‬‬ ‫‪٧‬‬
‫ﻭﺍﻟﺗﺛﺑﻳﺕ ﻭﻓﻖ ﻣﻭﺍﺻﻔﺎﺕ ﺩﻓﺗﺭ ﺍﻟﺷﺭﻭﻁ ﺍﻟﻔﻧﻳﺔ‬
‫ﺗﺣﺩﻳ ﺩ ﻧ ﻭﻉ ﻭﻣﻘﻁ ﻊ ﻭﻁ ﻭﻝ ﺍﻟﻛﺑ ﻝ ﺍﻟﻣﺳ ﺗﺧﺩﻡ ﺑ ﻳﻥ‬
‫‪٢‬‬
‫ﻣﻠﻡ ‪/‬ﻡ‬ ‫ﻣﺧﺭﺝ‬ ‫‪٨‬‬
‫ﺍﻟﻠﻭﺍﻗﻁ ﺍﻟﺷﻣﺳﻳﺔ ﻭﺍﻟﻣﻌﺭﺝ )‪ NYY‬ﺷﻌﺭﻱ(‬
‫ﺗﺣﺩﻳﺩ ﻧﻭﻉ ﻭﻣﻘﻁﻊ ﻭﻁﻭﻝ ﺍﻟﻛﺑﻝ ﺍﻟﺩﺍﺧﻠﻲ ﻟﻠﻠﻭﺍﻗﻁ‬
‫ﻣﻠﻡ‪/٢‬ﻡ‬ ‫ﺍﻟﺷﻣﺳﻳﺔ‬ ‫‪٩‬‬
‫)‪ NYY‬ﺷﻌﺭﻱ(‬

‫‪-‬‬ ‫ﺫﻛﺭ ﺷﻬﺎﺩﺍﺕ ﺍﻻﺧﺗﺑﺎﺭ ﻭﺗﻘﺩﻳﻡ ﻧﺳﺧﺔ ﻋﻧﻬﺎ‬ ‫‪١٠‬‬


‫ﺟﺭﻣﺎﻧﺎ‬ ‫ﻣﺷﻔﻰ ﺍﻷﻁﻔﺎﻝ‬ ‫ﺍﻟﺻﺎﺧﻭﺭ‬ ‫ﺍﻟﺧﺻﺎﺋﺹ ﺍﻟﺗﻘﻧﻳﺔ‪:‬‬
‫‪-‬‬ ‫ﺗﺣﺩﻳﺩ ﺑﻠﺩ ﺍﻟﻣﻧﺷﺄ ﻭﺍﻟﺷﺭﻛﺔ ﺍﻟﺻﺎﻧﻌﺔ‬ ‫‪١‬‬
‫ﻡ‬ ‫ﺗﺣﺩﻳﺩ ﺃﺑﻌﺎﺩ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ‬ ‫‪٢‬‬
‫‪-‬‬ ‫ﺗﺣﺩﻳﺩ ﻧﻭﻉ ﺍﻟﺧﻠﻳﺔ ﻳﻔﺿﻝ ‪/mono/‬‬ ‫‪٣‬‬
‫ﻡ‬ ‫ﺗﺣﺩﻳﺩ ﺃﺑﻌﺎﺩ ﺍﻟﺧﻠﻳﺔ‬ ‫‪٤‬‬
‫ﺗﺣﺩﻳﺩ ﻋﺩﺩ ﺍﻟﺧﻼﻳﺎ ﺿﻣﻥ ﺍﻟﻠﻭﺡ‬
‫ﻋﺩﺩ‬ ‫‪٥‬‬
‫ﺍﻟﺷﻣﺳﻲ )‪ ٦٠‬ﺃﻭ ‪(٧٢‬‬
‫‪%‬‬ ‫ﺗﺣﺩﻳﺩ ﻋﺎﻣﻝ ﺍﻹﻣﺗﻼء )‪(FF‬‬ ‫‪٦‬‬
‫ﻛﻎ‬ ‫ﺗﺣﺩﻳﺩ ﻭﺯﻥ ﺍﻟﻠﻭﺡ‬ ‫‪٧‬‬
‫ﺗﺣﺩﻳﺩ ﻋﺩﺩ ﺧﻁﻭﻁ ﺍﻟﺗﻭﺻﻳﻝ ﺿﻣﻥ‬
‫ﻋﺩﺩ‬ ‫‪٨‬‬
‫ﺍﻟﺧﻠﻳﺔ ﻻ ﺗﻘﻝ ﻋﻥ ‪ ٥‬ﺧﻁﻭﻁ )‪(Sbb‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﻭﺻﻼﺕ ﺍﻟﺭﺑﻁ ‪/‬‬
‫‪-‬‬ ‫‪٩‬‬
‫ﻣﻁﺎﻁﻳﺔ ﻣﻘﺎﻭﻣﺔ ‪(MC4) /‬‬
‫ﺗﺣﺩﻳﺩ ﻣﻭﺍﺻﻔﺎﺕ ﻋﻠﺏ ﻭﻣﺂﺧﺫ ﺗﻭﺻﻳﻝ‬
‫‪-‬‬ ‫‪١٠‬‬
‫ﺍﻟﻠﻭﺍﻗﻁ ﻭﻋﺩﺩ ﺩﻳﻭﺩﺍﺕ ﺍﻟﺗﻣﺭﻳﺭ‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﻌﺎﻣﻝ ﺍﻟﺣﺭﺍﺭﻱ ﺍﻟﺧﺎﺹ‬
‫‪%‬‬ ‫‪١١‬‬
‫ﺑﺎﻟﺗﻭﺗﺭ‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﻌﺎﻣﻝ ﺍﻟﺣﺭﺍﺭﻱ ﺍﻟﺧﺎﺹ‬
‫‪%‬‬ ‫‪١٢‬‬
‫ﺑﺎﻟﺗﻳﺎﺭ‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﻌﺎﻣﻝ ﺍﻟﺣﺭﺍﺭﻱ ﺍﻟﺧﺎﺹ‬
‫‪%‬‬ ‫‪١٣‬‬
‫ﺑﺎﻻﺳﺗﻁﺎﻋﺔ‬
‫ﺍﻟﺧﺻﺎﺋﺹ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ‪:‬‬
‫ﺗﺣﺩﻳﺩ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻻﺳﻣﻳﺔ‬
‫ﻭﺍﻁ‬ ‫‪١‬‬
‫ﻟﻠﻭﺡ ﺑﺣﻳﺙ ﻻ ﺗﻘﻝ ﻋﻥ ‪ 540‬ﻭﺍﻁ‬
‫ﺃﻣﺑﻳﺭ‬ ‫ﺗﺣﺩﻳﺩ ﺷﺩﺓ ﺗﻳﺎﺭ ﻗﺻﺭ ﺍﻟﺩﺍﺭﺓ‬ ‫‪٢‬‬
‫ﺃﻣﺑﻳﺭ‬ ‫ﺗﺣﺩﻳﺩ ﺷﺩﺓ ﺗﻳﺎﺭ ﺍﻟﻌﻣﻝ‬ ‫‪٣‬‬
‫ﻓﻭﻟﺕ‬ ‫ﺗﺣﺩﻳﺩ ﺗﻭﺗﺭ ﻓﺻﻝ ﺍﻟﺣﻣﻭﻟﺔ‬ ‫‪٤‬‬
‫ﻓﻭﻟﺕ‬ ‫ﺗﺣﺩﻳﺩ ﺗﻭﺗﺭ ﺍﻟﻌﻣﻝ‬ ‫‪٥‬‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻘﻳﻣﺔ ﺍﻟﻌﻅﻣﻰ ﻟﻠﺗﻭﺗﺭ ﺍﻟﻛﻬﺭﺑﺎﺋﻲ‬
‫ﻓﻭﻟﺕ‬ ‫‪٦‬‬
‫ﻻ ﺗﻘﻝ ﻋﻥ ‪ ١٠٠٠‬ﻓﻭﻟﺕ‬
‫ﻋﺩﺩ‬ ‫ﺗﺣﺩﻳﺩ ﻋﺩﺩ ﺍﻟﺻﻣﺎﻣﺎﺕ ﺍﻻﻟﺗﻔﺎﻓﻳﺔ‬ ‫‪٧‬‬
‫ﺗﺣﺩﻳﺩ ﻧﺳﺑﺔ ﺗﻐﻳﺭ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ‬
‫‪%‬‬ ‫‪٨‬‬
‫ﻟﻠﻭﺡ‬
‫ﻣﻼﺣﻅﺔ‪ :‬ﺟﻣﻳﻊ ﺍﻟﻣﻧﺣﻧﻳﺎﺕ ﺍﻟﺧﺎﺻﺔ ﺑﻧﻅﺎﻡ ﺍﺳﺗﺧﺩﺍﻡ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﻳﺟﺏ‬
‫ﺃﻥ ﺗﻛﻭﻥ ﻣﺭﻓﻘﺔ ﻣﻊ ﻋﺭﺽ ﺍﻟﻣﺗﻌﻬﺩ‬
‫ﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻣﻌﺭﺟﺎﺕ )ﺍﻻﻧﻔﺭﺗﻳﺭ( ﺟﺩﻭﻝ ﺭﻗﻡ ‪/٢/‬‬

‫ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﻗﺑﻝ ﺍﻟﻌﺎﺭﺽ‬


‫ﺍﻟﻭﺣﺩﺓ‬ ‫ﺑﻳﺎﻥ ﺍﻟﻣﺎﺩﺓ ﻭﻣﻭﺍﺻﻔﺎﺗﻬﺎ‬ ‫ﺭﻗﻡ‬
‫ﺟﺭﻣﺎﻧﺎ‬ ‫ﻣﺷﻔﻰ ﺍﻷﻁﻔﺎﻝ‬ ‫ﺍﻟﺻﺎﺧﻭﺭ‬

‫‪-‬‬ ‫ﺗﺣﺩﻳﺩ ﺑﻠﺩ ﺍﻟﻣﻧﺷﺄ ﻭﺍﻟﺷﺭﻛﺔ ﺍﻟﺻﺎﻧﻌﺔ ﻭﺍﻟﻁﺭﺍﺯ‬ ‫‪١‬‬


‫ﺍﻟﻣﻌﺭﺟﺎﺕ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﻘﺎﺑﻝ ﻟﻠﺑﺭﻣﺟﺔ ﻭﺍﻟﺧﺎﺻﺔ ﺑﺄﻧﻅﻣﺔ ﺍﻟﻁﺎﻗﺔ‬
‫‪-‬‬ ‫‪٢‬‬
‫ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﻣﺩﺭﺟﺔ ﺑﻣﺿﻣﻭﻧﺎﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ‪.‬‬
‫‪-‬‬ ‫ﻧﻭﻉ ﺍﻟﻣﻌﺭﺝ ‪ outdoor‬ﺃﻡ ‪Indoor‬‬ ‫‪٣‬‬
‫ﺧﺭﺝ ﺍﻟﻣﻌﺭﺝ ﺃﺣﺎﺩﻱ ﺍﻟﻁﻭﺭ ﻟﻛﺎﻓﺔ ﺍﻟﻁﻭﺍﺑﻖ‬
‫‪-‬‬ ‫‪٤‬‬
‫ﺧﺭﺝ ﺍﻟﻣﻌﺭﺝ ﺛﻼﺛﻲ ﺍﻟﻁﻭﺭ ﻟﻠﻣﺻﺎﻋﺩ ﺍﻟﺛﻼﺙ‬
‫ﺍﻻﻟﺗﺯﺍﻡ ﺑﻣﺟﺎﻝ ﺗﻐﻳﺭ ﺗﺭﺩﺩ ﺧﺭﺝ ﺍﻟﻣﻌﺭﺝ)ﻣﻥ ‪ ٠‬ﺇﻟﻰ ‪٥٠‬‬
‫‪-‬‬ ‫‪٥‬‬
‫ﻫﺭﺗﺯ(‬
‫‪%‬‬ ‫ﻣﺭﺩﻭﺩ ﺍﻟﻣﻌﺭﺝ ﻻﻳﻘﻝ ﻋﻥ ‪%٩٥‬‬ ‫‪٦‬‬
‫ﻛﻎ‬ ‫ﺗﺣﺩﻳﺩ ﻭﺯﻥ ﺍﻟﻣﻌﺭﺝ‬ ‫‪٧‬‬
‫ﻣﻠﻡ‬ ‫ﺗﺣﺩﻳﺩ ﺃﺑﻌﺎﺩ ﺍﻟﻣﻌﺭﺝ‬ ‫‪٨‬‬
‫‪-‬‬ ‫ﺗﺣﺩﻳﺩ ﺩﺭﺟﺔ ﺍﻟﺣﻣﺎﻳﺔ ﻟﻠﻣﻌﺭﺝ‬ ‫‪٩‬‬
‫ﻙ‪.‬ﻭﺍﻁ‬ ‫ﺗﺣﺩﻳﺩ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻷﻋﻅﻣﻳﺔ ﻟﺩﺧﻝ ﺍﻟﻣﻌﺭﺝ‬ ‫‪١٠‬‬
‫ﻙ‪.‬ﻭﺍﻁ‬ ‫ﺗﺣﺩﻳﺩ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﻼﺳﻣﻳﺔ ﻟﺧﺭﺝ ﺍﻟﻣﻌﺭﺝ‬ ‫‪١١‬‬
‫ﺩﺭﺟﺔ‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﺟﺎﻝ ﺍﻟﺣﺭﺍﺭﻱ ﻟﻌﻣﻝ ﺍﻟﻣﻌﺭﺝ‬ ‫‪١٢‬‬
‫ﻣﺋﻭﻳﺔ‬
‫‪-‬‬ ‫ﺍﻻﻟﺗﺯﺍﻡ ﺑﺄﻥ ﺗﻛﻭﻥ ﺇﺷﺎﺭﺓ ﺧﺭﺝ ﺍﻟﻣﻌﺭﺟﺎﺕ ﺟﻳﺑﻳﺔ ﻭ ﻧﻘﻳﺔ‬ ‫‪١٣‬‬
‫ﻓﻭﻟﺕ‬ ‫ﺗﺣﺩﻳﺩ ﻣﺟﺎﻝ ﺗﻐﻳﺭ ﺍﻟﺗﻭﺗﺭ ﻟﺩﺧﻝ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭ)‪(DC‬‬ ‫‪١٤‬‬
‫ﻓﻭﻟﺕ‬ ‫ﺗﺣﺩﻳﺩ ﻣﺟﺎﻝ ﺗﻐﻳﺭ ﺍﻟﺗﻭﺗﺭ ﻟﺧﺭﺝ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺗﻧﺎﻭﺏ)‪(AC‬‬ ‫‪١٥‬‬
‫ﺃﻣﺑﻳﺭ‬ ‫ﺗﺣﺩﻳﺩ ﻗﻳﻣﺔ ﺗﻳﺎﺭ ﺍﻟﺧﺭﺝ ﺍﻻﺳﻣﻲ ﻟﻠﻣﻌﺭﺝ‬ ‫‪١٦‬‬
‫ﻋﺩﺩ‬ ‫ﺗﺣﺩﻳﺩ ﻋﺩﺩ ﻣﺩﺍﺧﻝ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭ ﻟﻠﻣﻌﺭﺝ‬ ‫‪١٧‬‬
‫ﻓﻭﻟﺕ‬ ‫ﺗﺣﺩﻳﺩ ﺗﻭﺗﺭ ﺍﻟﺩﺧﻝ ﺍﻷﻋﻅﻣﻲ ﻟﻠﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭ‬ ‫‪١٨‬‬
‫‪-‬‬ ‫ﺗﺣﺩﻳﺩ ﻁﺭﻳﻘﺔ ﺍﻟﺗﺑﺭﻳﺩ ﻟﻠﻣﻌﺭﺝ‬ ‫‪١٩‬‬
‫ﺗﺣﺩﻳﺩ ﺷﻬﺎﺩﺍﺕ ﺍﻻﺧﺗﺑﺎﺭ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻟﻣﻌﺭﺝ ﻭ ﺗﻘﺩﻳﻡ ﻧﺳﺧﺔ‬
‫‪-‬‬ ‫‪٢٠‬‬
‫ﻋﻧﻬﺎ‬
‫ﺍﻟﺗﺯﺍﻡ‬ ‫ﺍﻟﻣﻌﺭﺝ ﻣﺯﻭﺩ ﺑﻛﺎﻓﺔ ﺍﻟﺣﻣﺎﻳﺎﺕ ﺍﻟﻣﺫﻛﻭﺭﺓ ﺑﺎﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‬ ‫‪٢١‬‬
‫ﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻣﺩﺧﺭﺍﺕ ﻟﺯﻭﻡ ﺗﺧﺯﻳﻥ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ ﺟﺩﻭﻝ ﺭﻗﻡ ‪/٣/‬‬

‫ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﻗﺑﻝ ﺍﻟﻌﺎﺭﺽ‬


‫ﺍﻟﻭﺣﺩﺓ‬ ‫ﺑﻳﺎﻥ ﺍﻟﻣﺎﺩﺓ ﻭﻣﻭﺍﺻﻔﺎﺗﻬﺎ‬ ‫ﺭﻗﻡ‬

‫ﺟﺭﻣﺎﻧﺎ‬ ‫ﻣﺷﻔﻰ ﺍﻷﻁﻔﺎﻝ‬ ‫ﺍﻟﺻﺎﺧﻭﺭ‬

‫‪-‬‬ ‫ﺗﺣﺩﻳﺩ ﺑﻠﺩ ﺍﻟﻣﻧﺷﺄ ﻭﺍﻟﺷﺭﻛﺔ ﺍﻟﺻﺎﻧﻌﺔ‬ ‫‪١‬‬

‫ﺍﻟﻣﺩﺧﺭﺍﺕ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﺟﺎﻑ ‪Gel‬‬


‫‪-‬‬ ‫‪٢‬‬
‫ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻌﺩﺩ ﺍﻹﺟﻣﺎﻟﻲ ﻟﻠﻣﺩﺧﺭﺍﺕ ﻟﺗﺄﻣﻳﻥ ﺗﻐﺫﻳﺔ‬
‫ﻋﺩﺩ‬ ‫ﻣﺳﺗﻣﺭﺓ ﻟﺣﻣﻝ ﺃﻋﻅﻣﻲ ﺍﺳﺗﻁﺎﻋﺗﻪ ﻻ ﻳﻘﻝ ﻟﻛﻝ ﻁﺎﺑﻖ‬ ‫‪٣‬‬
‫ﻭ ﻗﺳﻡ ﻛﻣﺎ ﻫﻭ ﻣﺑﻳﻥ ﺑﺎﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‬

‫‪Ah‬‬ ‫ﺍﻟﺳﻌﺔ ﺍﻹﺟﻣﺎﻟﻳﺔ ﻟﻠﻣﺩﺧﺭﺍﺕ‬ ‫‪٤‬‬

‫‪%‬‬ ‫ﺗﺣﺩﻳﺩ ﻋﻣﻖ ﺍﻟﺗﻔﺭﻳﻎ ﺑﺣﻳﺙ ﻻﻳﺯﻳﺩ ﻋﻥ ‪%٦٠‬‬ ‫‪٥‬‬

‫ﻋﺩﺩ ﺩﻭﺭﺍﺕ ﺍﻟﻌﻣﻝ ﻟﻠﻣﺩﺧﺭﺓ ﻋﻧﺩ ﻋﻣﻖ ﺍﻟﺗﻔﺭﻳﻎ‬


‫‪%‬‬ ‫‪٦‬‬
‫ﻻﻳﻘﻝ ﻋﻥ ‪%٥٠‬‬

‫ﺃﻣﺑﻳﺭ‬ ‫ﺗﺣﺩﻳﺩ ﺗﻳﺎﺭ ﺍﻟﺷﺣﻥ ﻟﻠﻣﺩﺧﺭﺓ‬ ‫‪٧‬‬

‫ﺃﻣﺑﻳﺭ‬ ‫ﺗﺣﺩﻳﺩ ﺗﻳﺎﺭ ﺍﻟﺗﻔﺭﻳﻎ ﻟﻠﻣﺩﺧﺭﺓ‬ ‫‪٨‬‬


‫ﺩﺭﺟﺔ‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﺟﺎﻝ ﺍﻟﺣﺭﺍﺭﻱ ﻟﻌﻣﻝ ﺍﻟﻣﺩﺧﺭﺓ‬ ‫‪٩‬‬
‫ﻣﺋﻭﻳﺔ‬
‫ﻛﻎ‪/‬ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﺣﺩﻳﺩ ﻭﺯﻥ ﻭﺗﺎﺭﻳﺦ ﺇﻧﺗﺎﺝ ﺍﻟﻣﺩﺧﺭﺓ‬ ‫‪١٠‬‬
‫ﺳﻧﺔ‬ ‫ﺗﺣﺩﻳﺩ ﺍﻟﻌﻣﺭ ﺍﻹﻓﺗﺭﺍﺿﻲ ﻟﻠﻣﺩﺧﺭﺓ‬ ‫‪١١‬‬

‫‪%‬‬ ‫ﺗﺣﺩﻳﺩ ﻋﻣﻖ ﺍﻟﺗﻔﺭﻳﻎ ﺍﻷﻋﻅﻣﻲ ﻟﻠﻣﺩﺧﺭﺓ‬ ‫‪١٢‬‬

‫ﺗﺣﺩﻳﺩ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻷﻋﻅﻣﻳﺔ ﻟﺩﺧﻝ‬


‫ﻙ‪.‬ﻭﺍﻁ‬ ‫‪١٣‬‬
‫ﺍﻟﻣﻌﺭﺝ‬
‫ﺩﺭﺟﺔ‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﺟﺎﻝ ﺍﻟﺣﺭﺍﺭﻱ ﻟﻌﻣﻝ ﺍﻟﻣﻌﺭﺝ‬ ‫‪١٤‬‬
‫ﻣﺋﻭﻳﺔ‬

‫ﺃﻭﻡ‬ ‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﻘﺎﻭﻣﺔ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻟﻠﻣﺩﺧﺭﺓ‬ ‫‪١٥‬‬


‫‪ ‬ﺗﻘﺪﱘ وﺗﻨﻔﻴﺬ وﺗﻮﺻﻴﻞ ﻧﻈﺎم ﺷﺒﻜﺔ رﻳﺾ ﻣﻊ ﻛﻞ ﻣﺎﻳﻠﺰم ﻣﻦ ﺗﻘﺪﱘ وﺗﺮﻛﻴﺐ أﻣﺮاس وﻛﺎﺑﻼت وأو د ‪/‬ﻣﻘﻄﻮع‪/‬‬
‫ﻳﺗﻡ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﺷﺑﻛﺔ ﺗﺄﺭﻳﺽ ﻟﺯﻭﻡ ﺃﻋﻣﺎﻝ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ ﻓﻲ ﻛﻝ ﻣﻭﻗﻊ ﻣﻥ ﻣﻭﺍﻗﻊ ﺍﻟﻣﺷﺎﺭﻳﻊ ﺍﻟﺛﻼﺙ ﻭ ﺑﺎﻟﻛﻣﻳﺔ‬
‫ﺍﻟﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﻓﻲ ﺍﻟﻛﺷﻑ ﺍﻟﺗﻘﺩﻳﺭﻱ ﺑﺣﻳﺙ ﺗﺣﻘﻖ ﺍﻟﺷﺑﻛﺔ ﻣﻘﺎﻭﻣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﻻ ﺗﺗﺟﺎﻭﺯ ‪ /٣/‬ﺃﻭﻡ ﻭﺗﺗﻛﻭﻥ ﺷﺑﻛﺔ ﺍﻟﺗﺄﺭﻳﺽ ﻣﻥ ﺑﺋﺭ‬
‫ﺗﺄﺭﻳﺽ ﺭﺋﻳﺳﻲ ﻋﺩﺩ ‪ /١/‬ﻭﺃﻭﺗﺎﺩ ﺗﺄﺭﻳﺽ ﻣﺳﺎﻋﺩﺓ ﻋﺩﺩ ‪ /٢/‬ﺑﻣﺳﺎﻓﺔ ﺑﻳﻧﻬﺎ ﻻﺗﻘﻝ ﻋﻥ ‪٤‬ﻡ‪ ،‬ﻭﻳﻣﻛﻥ ﺯﻳﺎﺩﺓ ﻋﺩﺩ ﺍﻷﻭﺗﺎﺩ ﺍﻟﻣﺳﺎﻋﺩﺓ‬
‫ﺣﺗﻰ ﺗﺣﻘﻖ ﺍﻟﻣﻘﺎﻭﻣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﻣﻁﻠﻭﺑﺔ‪.‬‬
‫ﻭﺗﻛﻭﻥ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻟﺷﺑﻛﺔ ﺍﻟﺗﺄﺭﻳﺽ ﺑﺎﻟﺣﺩ ﺍﻷﺩﻧﻰ ﻛﻣﺎ ﻳﻠﻲ‪:‬‬
‫‪ ‬ﻳﺗﻡ ﺗﺣﺩﻳﺩ ﻣﻭﺍﻗﻊ ﺑﺋﺭ ﺍﻟﺗﺄﺭﻳﺽ ﺍﻟﺭﺋﻳﺳﻲ ﻭﺍﻷﻭﺗﺎﺩ ﺍﻟﻣﺳﺎﻋﺩﺓ ﺑﻣﻭﺍﻓﻘﺔ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﻭﺗﻔﺿﻝ ﺍﻟﻣﻭﺍﺿﻊ ﺍﻟﻘﺭﻳﺑﺔ ﻣﻥ ﻗﻧﺎﺓ‬
‫ﻭﻣﺳﺎﺭﺍﺕ ﺍﻟﻛﺎﺑﻼﺕ ﻭﻓﻲ ﺍﻟﻣﻭﺍﻗﻊ ﺍﻟﺗﺭﺍﺑﻳﺔ ﻭﻳﺗﻡ ﺗﺛﺑﻳﺕ ﺗﻠﻙ ﺍﻟﻣﻭﺍﻗﻊ ﻋﻠﻰ ﺍﻟﻣﺧﻁﻁﺎﺕ‪.‬‬
‫ﺟﻭﺭﺓ ﺗﻔﺗﻳﺵ ﺑﻳﺗﻭﻧﻳﺔ ﺑﺄﺑﻌﺎﺩ ﺩﺍﺧﻠﻳﺔ ﻻ ﺗﻘﻝ ﻋﻥ )‪٤٠×٤٠×٤٠‬ﺳﻡ( ﻭﺑﻐﻁﺎء ﺑﻳﺗﻭﻧﻲ ﺃﻭ ﻓﻭﻧﺕ ﺃﻭ ﻣﻌﺩﻧﻲ ﻣﺯﻭﺩ ﺑﻘﺑﺿﺔ ﻟﺭﻓﻌﻪ‪.‬‬ ‫‪‬‬

‫ﻭﺗﺩ ﻣﻥ ﺍﻟﻧﺣﺎﺱ ﺑﻘﻁﺭ ‪٢٥‬ﻣﻡ ﻭﻁﻭﻝ ﻻ ﻳﻘﻝ ﻋﻥ ‪٢‬ﻡ ﺑﺫﻳﻝ ﺳﻔﻠﻲ ﻣﺩﺑﺏ‪.‬‬ ‫‪‬‬
‫ﻛﻭﻟﻳﺔ ﺍﻟﺭﺑﻁ ﺑﻳﻥ ﺭﺃﺱ ﺍﻟﻭﺗﺩ ﻭﺃﻣﺭﺍﺱ ﺍﻟﺗﺄﺭﻳﺽ ﻭﻳﻔﺿﻝ ﺃﻥ ﺗﻛﻭﻥ ﻣﻥ ﺻﻔﺎﺋﺢ ﺍﻟﻧﺣﺎﺱ ﺃﻭ ﺍﻟﻘﺻﺩﻳﺭ ﻭﺫﺍﺕ ﺳﻣﺎﻛﺔ‬ ‫‪‬‬
‫ﻻ ﺗﻘﻝ ﻋﻥ ‪/٦/‬ﻣﻡ‪.‬‬
‫ﺍﻟﺗﻌﺑﺋﺔ ﺑﺎﻟﺭﻣﻝ ﺍﻟﻧﺎﻋﻡ ﻭﻳﻔﺿﻝ ﻣﻊ ﺍﻟﻣﻭﺍﺩ ﺍﻟﻼﺯﻣﺔ ﻟﺣﻔﺭﺓ ﺍﻟﺗﺄﺭﻳﺽ ﻭﺣﺩﻭﺩ ﺍﻟﺗﻌﺑﺋﺔ ﻟﻣﺳﺗﻭﻯ ﺃﺩﻧﻰ ﻣﻥ ﻣﺳﺗﻭﻯ ﻭﺻﻝ‬ ‫‪‬‬
‫ﺍﻷﻣﺭﺍﺱ‪.‬‬
‫ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﺃﻣﺭﺍﺱ ﺍﻟﺗﻭﺻﻳﻝ ﻭﻫﻲ ﺑﻳﻥ ﺭﺃﺱ ﺍﻟﻭﺗﺩ ﺍﻟﻌﻠﻭﻱ ﺑﺑﺋﺭ ﺍﻟﺗﺄﺭﻳﺽ ﺍﻟﺭﺋﻳﺳﻲ ﻭﺭﺅﻭﺱ ﺍﻷﻭﺗﺎﺩ ﺍﻟﻣﺳﺎﻋﺩﺓ‬ ‫‪‬‬
‫ﻭﻛﺫﻟﻙ ﻣﻊ ﻣﺭﺑﻁ ﺍﻟﺗﻭﺻﻳﻝ ﻋﻠﻰ ﺑﺎﺭ ﺍﻟﺗﺄﺭﻳﺽ ﺑﺎﻟﻠﻭﺣﺔ‪ ,‬ﻭﺗﻛﻭﻥ ﻫﺫﻩ ﺍﻷﻣﺭﺍﺱ ﻣﻥ ﺍﻟﻧﺣﺎﺱ ﺍﻟﻌﺎﺭﻱ ﺍﻟﻣﺟﺩﻭﻝ ﺑﻣﻘﻁﻊ‬
‫ﻣﻧﺎﺳﺏ ﻻ ﻳﻘﻝ ﻋﻥ ‪٥٠‬ﻣﻠﻡ‪٢‬‬
‫)ﻣﺭﺱ ﻧﺣﺎﺳﻲ( ﺑﻁﻭﻝ ‪٥٠‬ﻡ ﺗﻘﺭﻳﺑﺎ ً ﻣﻊ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻛﺎﻓﺔ ﻟﻭﺍﺯﻡ ﺍﻟﺗﻣﺩﻳﺩ ﻭﺍﻟﺭﺑﻁ ﻭﺍﻟﻭﺻﻝ ﻣﻥ ﺻﻭﻟﻳﺎﺕ ﻭﺑﺭﺍﻏﻲ‬
‫َ‬ ‫‪‬‬
‫ﻭﺭﻧﺩﻳﻼﺕ ﻭﻋﺯﻗﺎﺕ ﺑﻧﻭﻋﻳﺔ ﺟﻳﺩﺓ ﻣﻧﺎﺳﺑﺔ ﻟﻠﺗﺄﺭﻳﺽ‪.‬‬
‫ﻭﻳﺗﺿﻣﻥ ﺍﻟﻌﻣﻝ ﻛﻝ ﻣﺎﻳﻠﺯﻡ ﻣﻥ ﺣﻔﺭ ﻭﺗﻣﺩﻳﺩ ﻭﺍﻋﺎﺩﺓ ﺭﺩﻡ ﻭﺍﺳﺗﻌﺎﺩﺓ ﺍﻟﺳﻁﻭﺡ ﺍﻟﻁﺑﻳﻌﻳﺔ ﻭﺩﺧﻭﻝ ﻣﺭﺱ ﺍﻟﺗﺄﺭﻳﺽ‬ ‫‪‬‬
‫ﺇﻟﻰ ﺑﺋﺭ ﺍﻟﺗﺄﺭﻳﺽ ﻭﺇﻟﻰ ﻗﻧﺎﺓ ﺍﻟﻠﻭﺣﺎﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺭﺋﻳﺳﻳﺔ ﺑﺷﻛﻝ ﻓﻧﻲ‪ ,‬ﻭﻭﺻﻝ ﻣﺭﺱ ﺍﻟﺗﺄﺭﻳﺽ ﻣﻊ ﺃﻣﺎﻛﻥ ﺍﻟﺗﺄﺭﻳﺽ‬
‫ﻳﺗﻭﺟﺏ ﻋﻠﻰ ﺍﻟﻣﺗﻌﻬﺩ ﺇﺣﺿﺎﺭ ﺟﻬﺎﺯ ﻟﻔﺣﺹ ﻣﻘﺎﻭﻣﺔ ﺍﻷﺭﺿﻲ ﻭﻋﻠﻰ ﻧﻔﻘﺗﻪ ﺍﻟﺧﺎﺻﺔ ﻭﻳﻌﺗﺑﺭ ﻫﺫﺍ ﺍﻻﺧﺗﺑﺎﺭ‬ ‫‪‬‬
‫ﺃﺳﺎﺱ ﻓﻲ ﻋﻣﻠﻳﺔ ﺍﻻﺳﺗﻼﻡ‪.‬‬

‫ﻣﺧﻁﻁ ﻧﻅﺎﻡ ﺗﺄﺭﻳﺽ ﻛﺎﻣﻝ ﻷﻋﻣﺎﻝ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬


‫‪ ‬ﺗﻘﺪﻳﻢ ﻭﺗﺮﻛﻴﺐ ﻭﺗﻮﺻﻴﻞ ﺷﺒﻜﺔ ﻣﺎﻧﻌﺎﺕ ﺍﻟﺼﻮﺍﻋﻖ ﻣﻊ ﺗﻘﺪﻳﻢ ﻭﺗﺮﻛﻴﺐ ﺃﻣﺮﺍﺱ ﻭﻛﺎﺑﻼﺕ ﻭﺃﻭﺗﺎﺩ‬
‫ﻣﻊ ﻛﻞ ﻣﺎﻳﻠﺰﻡ‪/ :‬ﻣﻘﻄﻮﻉ‪/‬‬
‫ﻳﺗﺿﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻭﺗﻧﻔﻳﺫ ﻭﺗﻭﺻﻳﻝ ﺷﺑﻛﺔ ﻣﺎﻧﻌﺔ ﺻﻭﺍﻋﻖ ﺑﺟﻭﺩﺓ ﻓﻧﻳﺔ ﻋﺎﻟﻳﺔ ﺟﺎﻫﺯﺓ ﻟﻺﺳﺗﺛﻣﺎﺭ ﻓﻲ ﻛﻝ ﻣﻭﻗﻊ ﻣﻥ ﻣﻭﺍﻗﻊ‬
‫ﺍﻟﻣﺷﺎﺭﻳﻊ ﺍﻟﺛﻼﺙ ﻭ ﺑﺎﻟﻛﻣﻳﺔ ﺍﻟﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﻓﻲ ﺍﻟﻛﺷﻑ ﺍﻟﺗﻘﺩﻳﺭﻱ ﺑﺎﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺗﺎﻟﻳﺔ‪:‬‬
‫‪٢‬‬
‫‪-‬ﺍﻟﻣﺭﺱ ﻧﺣﺎﺳﻲ ﺑﻣﻘﻁﻊ )‪ (٥٠‬ﻣﻡ‬
‫‪-‬ﺍﻹﺑﺭ ﻧﺣﺎﺳﻳﺔ ﻣﺗﺷﻌﺑﺔ ﺑﻁﻭﻝ )‪ (٥٠‬ﺳﻡ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﺟﻳﺩ ﻭﺍﻟﻣﺗﻭﺍﻓﺭ ﺑﺎﻷﺳﻭﺍﻕ ﺍﻟﻣﺣﻠﻳﺔ‪.‬‬
‫‪٢‬‬
‫‪ -‬ﺍﻟﻧﺎﺯﻝ‪ :‬ﻣﻥ ﻧﻭﺍﻗﻝ ﻣﻌﺩﻧﻳﺔ ﻏﻳﺭ ﻗﺎﺑﻠﺔ ﻟﻠﺻﺩﺃ ﻣﻥ ﺍﻟﻧﺣﺎﺱ ﻭﺑﻣﻘﻁﻊ )‪ (٥٠‬ﻣﻡ‬
‫‪ -‬ﻳﺟﺏ ﺍﻟﺳﻌﻲ ﻟﺗﻣﺩﻳﺩ ﺍﻟﻧﻭﺍﺯﻝ ﺑﺄﻗﺭﺏ ﻁﺭﻳﻖ ﺷﺎﻗﻭﻟﻲ ﻣﻣﻛﻥ ﺑﻳﻥ ﺍﻹﺑﺭ ﻭﺍﻷﺭﺽ ﺩﻭﻥ ﺍﻧﺣﻧﺎءﺍﺕ ﺣﺎﺩﺓ ﻓﻲ ﻣﺳﺎﺭﻫﺎ‪.‬‬
‫‪ -‬ﻳﺟﺏ ﺃﻥ ﻻ ﺗﻘﻝ ﺍﻟﻣﺳﺎﻓﺔ ﺑﻳﻥ ﺍﻟﻧﻭﺍﺯﻝ ﻭﻓﺗﺣﺎﺕ ﺍﻷﺑﻭﺍﺏ ﻋﻥ )‪ (٥٠‬ﺳﻡ‬
‫‪ -‬ﻳﺟﺏ ﺃﻥ ﻻ ﺗﻘﻝ ﺍﻟﻣﺳﺎﻓﺔ ﺑﻳﻥ ﺍﻟﻧﻭﺍﺯﻝ ﻭﺍﻟﺗﻣﺩﻳﺩﺍﺕ ﺍﻟﻛﻬﺭﺑﺎ ﺋﻳﺔ ﻋﻥ )‪ (١٠٠‬ﺳﻡ‬
‫‪ -‬ﺗﺛﺑﺕ ﺍﻟﻣﺭﺱ ﻭﺍﻟﻧﻭﺍﺯﻝ ﻋﻠﻰ ﻭﺍﺟﻬﺔ ﺍﻟﻣﺑﻧﻰ ﺑﺷﻛﻝ ﻅﺎﻫﺭ ﺑﻣﺛﺑﺗﺗﺎﺕ ﻣﻥ ﺍﻟﺑﻳﻛﺎﻟﻳﺕ ﻣﺗﻭﺳﻁﺔ ﺍﻟﺣﺟﻡ ﻭﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﻣﻌﻛﻭﻑ‬
‫ﺑﺣﻳﺙ ﺗﻘﻭﻡ ﻫﺫﻩ ﺍﻟﻣﺛﺑﺗﺎﺕ ﺑﺎﺑﻌﺎﺩ ﺍﻟﻧﻭﺍﺯﻝ ﻋﻥ ﺍﻟﺑﻧﺎء ﺑﺷﻛﻝ ﺟﻳﺩ ﻭﺗﺣﻣﻰ ﻣﻳﻛﺎﻧﻳﻛﻳﺎ ﺣﺗﻰ ﺍﺭﺗﻔﺎﻉ )‪ (٢‬ﻡ ﻣﻥ ﺳﻁﺢ ﺍﻷﺭﺽ‬
‫ﺑﻭﺍﺳﻁﺔ ﻗﺳﺎﻁﻝ ﺑﻼﺳﺗﻳﻛﻳﺔ ﻣﻧﺎﺳﺑﺔ ﺫﺍﺕ ﺿﻐﻁ ﻋﺎﻝ ﻭﺑﻘﻁﺭ )‪ (٢‬ﺃﻧﺵ‪.‬‬
‫‪ -‬ﺍﻟﻧﺎﺯﻝ ﻣﻥ ﺍﻹﺑﺭﺓ ﻳﺭﺗﺑﻁ ﺑﻌﻠﺑﺔ ﻗﻳﺎﺱ ﻭﻣﺭﺍﻗﺑﺔ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﺑﻼﺳﺗﻳﻛﻲ ﺍﻟﺟﻳﺩ ﻋﻠﻰ ﺍﺭﺗﻔﺎﻉ )‪ (٢‬ﻡ ﻣﻥ ﺳﻁﺢ ﺍﻷﺭﺽ‪.‬‬
‫‪ -‬ﻳﺟﺏ ﺃﻥ ﻻ ﺗﺯﻳﺩ ﺍﻟﻣﻘﺎﻭﻣﺔ ﺍﻷﺭﺿﻳﺔ ﻟﺑﺋﺭ ﺍﻟﺗﺄﺭﻳﺽ ﻋﻥ )‪ (٣‬ﺃﻭﻡ‪.‬‬
‫ﻣﻭﺍﺻﻔﺎﺕ ﺑﺋﺭ ﺍﻟﺗﺄﺭﻳﺽ‪ :‬ﺟﻭﺭﺓ ﺍﻟﺗﻔﺗﻳﺵ ﺑﺄﺑﻌﺎﺩ )‪ (٤٠×٤٠×٤٠‬ﺳﻡ ﻋﺩﺩﻫﺎ )‪ (٣‬ﻭﺗﻛﻭﻥ ﺣﻭﺍﻓﻬﺎ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﺍﻟﺧﺎﺭﺟﻳﺔ‬
‫ﻣﻥ ﺍﻟﺑﻳﺗﻭﻥ ﺍﻟﻣﺳﻠﺢ ﻭﻳﻭﺿﻊ ﻋﻠﻳﻬﺎ ﻏﻁﺎء ﻣﻥ ﺍﻟﺑﻳﺗﻭﻥ ﻣﻥ ﻧﻔﺱ ﺍﻷﺑﻌﺎﺩ ﻭﻗﺎﺑﻝ ﻟﻠﻔﺗﺢ ﻭﺍﻹﻏﻼﻕ ﻭﺃﻥ ﻻ ﺗﺯﻳﺩ ﻣﻘﺎﻭﻣﺔ ﺍﻟﺗﺄﺭﻳﺽ‬
‫ﻋﻥ )‪ (٣‬ﺃﻭﻡ ﻭﻳﺗﻭﺟﺏ ﻋﻠﻰ ﺍﻟﻣﺗﻌﻬﺩ ﻗﻳﺎﺱ ﻣﻘﺎﻭﻣﺔ ﺍﻟﺗﺄﺭﻳﺽ ﻭﺍﻟﻌﻣﻝ ﻋﻠﻰ ﺗﺧﻔﻳﺽ ﻣﻘﺎﻭﻣﺔ ﺍﻷﺭﺽ ﺑﺎﻟﻁﺭﻕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺗﻲ‬
‫ﻳﺭﺍﻫﺎ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﻣﻧﺎﺳﺑﺔ ﺑﻐﻳﺔ ﺍﻟﻭﺻﻭﻝ ﺇﻟﻰ ﻣﻘﺎﻭﻣﺔ ﺍﻟﺗﺄﺭﻳﺽ )‪ (٣‬ﺃﻭﻡ ﺍﻟﻣﻁﻠﻭﺑﺔ‪.‬‬
‫‪ -‬ﺷﺑﻛﺔ ﺗﺄﺭﻳﺽ ﺍﻟﻣﺂﺧﺫ ﻭﺷﺑﻛﺎﺕ ﺍﻟﺗﺄﺭﻳﺽ ﺍﻷﺧﺭﻯ ﻣﺳﺗﻘﻠﺔ ﻋﻥ ﺷﺑﻛﺔ ﺍﻷﺭﺿﻲ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻟﺣﻣﺎﻳﺔ ﻣﻥ ﺍﻟﺻﻭﺍﻋﻖ ﻭﺗﺑﻌﺩ ﻋﻧﻬﺎ‬
‫ﻣﺳﺎﻓﺔ ﻻ ﺗﻘﻝ ﻋﻥ )‪ (١٠‬ﻣﺗﺭ‪.‬‬
‫ﻋﺩﺩ ﺍﻟﺻﻔﺣﺎﺕ )‪ (16‬ﻣﺗﺿﻣﻧﺔ ﻫﺫﻩ ﺍﻟﺻﻔﺣﺔ‬

‫ﻣﺷﺭﻭﻉ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻣﻧﻅﻭﻣﺔ ﻁﺎﻗﺔ ﻛﻬﺭﺿﻭﺋﻳﺔ‬


‫ﻟﻣﺳﺗﻭﺻﻑ ﺍﻟﻬﻼﻝ ﺍﻷﺣﻣﺭ ﺍﻟﻌﺭﺑﻲ ﺍﻟﺳﻭﺭﻱ‬

‫ﻣﺩﻳﻧﺔ ﺍﻟﺳﻠﻣﻳﺔ ‪ -‬ﻣﺣﺎﻓﻅﺔ ﺣﻣﺎﺓ‬

‫ﺩﻓﺗﺭ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‬

‫ﺇﺩﺍﺭﺓ ﺍﻟﻣﻳﺎﻩ ﻭﺇﻋﺎﺩﺓ ﺍﻟﺗﺄﻫﻳﻝ‬

‫ﻣﻧﻅﻣﺔ ﺍﻟﻬﻼﻝ ﺍﻷﺣﻣﺭ ﺍﻟﻌﺭﺑﻲ ﺍﻟﺳﻭﺭﻱ‬

‫ﺁﺫﺍﺭ ‪٢٠٢٣ -‬‬


‫‪ -١‬ﺍﻟﻐﺎﻳﺔ ﻣﻥ ﺍﻟﻌﻣﻝ‪:‬‬
‫ﺍﻟﻐﺎﻳﺔ ﻣﻥ ﺍﻟﻌﻣﻝ ﻫﻭ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻣﻥ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷ ﻣﺳ ﻳﺔ ﻟﺯﻭﻡ ﺗﺄﻣﻳﻥ ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻟﺗﺷ ﻐﻳﻝ‬
‫ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻣﻳﻛﺎﻧﻳﻛﻳﺔ ﻭﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻟﻣﺳ ﺗﻭﺻ ﻑ ﺍﻟﺳ ﻠﻣﻳﺔ ﻓﻲ ﻣﺣﺎﻓﻅﺔ ﺣﻣﺎﺓ ‪ ،‬ﻛﺑﺩﻳﻝ ﻋﻥ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ‬
‫ﺍﻻﺣﺗﻳﺎﻁﻳﺔ )ﺷ ﺑﻛﺔ ‪ -‬ﻣﺟﻣﻭﻋﺔ( ﻟﺗﻐﻁﻳﺔ ﺣﻣﻭﻻﺕ ﺃﻋﻅﻣﻳﺔ ‪ ١٥‬ﻛﻳﻠﻭ ﻭﺍﻁ‪ ،‬ﻣﻊ ﺗﺩﺭﻳﺏ ﻟﻠﻛﺎﺩﺭ ﺍﻟﻔﻧﻲ ﺍﻟﻣﺳ ﺅﻭﻝ‬
‫ﻋﻥ ﺗﺷﻐﻳﻝ ﻭﻣﺭﺍﻗﺑﺔ ﻋﻣﻝ ﺍﻟﻣﻧﻅﻭﻣﺔ‪.‬‬

‫‪ - ٢‬ﻭﺻﻑ ﺍﻟﻣﺷﺭﻭﻉ‪:‬‬
‫ﻳﻘﻊ ﺍﻟﻣﺳﺗﻭﺻﻑ ﻓﻲ ﻣﺩﻳﻧﺔ ﺳﻠﻣﻳﺔ ‪ -‬ﻣﺣﺎﻓﻅﺔ ﺣﻣﺎﺓ‪.‬‬

‫‪2|Page‬‬
‫ﻣﺳﻘﻁ ﺳﻁﺢ ﺍﻟﻣﺳﺗﻭﺻﻑ‪:‬‬

‫‪ - ٣‬ﺍﻷﻋﻣﺎﻝ ﺍﻟﺗﺣﺿﻳﺭﻳﺔ‪:‬‬
‫ﺗﻌﺗﺑﺭ ﺍﻟﺷ ﺭﻭﻁ ﻭﺍﻟﻣﻭﺍﺻ ﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﻭﺿ ﻭﻋﺔ ﻣﻥ ﻗﺑﻝ ﺇﺩﺍﺭﺓ ﺍﻟﻣﻧﻅﻣﺔ ﻫﻲ ﺍﻷﺳ ﺎﺱ ﻟﻘﻳﺎﻡ ﺍﻟﻣﺗﻌﻬﺩ ﺑﺗﺄﻣﻳﻥ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﻭﺍﻟﺗﺣﺿ ﻳﺭ‬
‫ﻟﻠﻣﺧﻁﻁﺎﺕ ﺍﻟﺗﻔﺻﻳﻠﻳﺔ )‪ (Shop Drawings‬ﻟﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﺑﻣﺎﻳﺗﻧﺎﺳﺏ ﻣﻊ ﻁﺑﻳﻌﺔ ﺍﻟﻣﻭﻗﻊ ﺍﻟﻌﺎﺋﺩ ﻟﻠﻣﺷﺭﻭﻉ‪.‬‬

‫‪ - ٤‬ﺍﻟﺷﺭﻭﻁ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻟﺗﻭﺭﻳﺩ‪:‬‬


‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺍﻷﺟﻬﺯﺓ ﺍﻟﻣﻘﺩﻣﺔ ﻣﺻﻧﻌﺔ ﻣﻥ ﻗﺑﻝ ﺇﺣﺩﻯ ﺍﻟﺷﺭﻛﺎﺕ ﺍﻟﻣﺧﺗﺻﺔ ﺑﺗﻁﺑﻳﻖ ﺃﺣﺩﺙ ﺍﻟﺗﻘﻧﻳﺎﺕ ﻓﻲ ﻣﺟﺎﻝ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ‬ ‫‪-‬‬
‫ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻣﻥ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﻭﺃﻥ ﺗﻛﻭﻥ ﺟﻣﻳﻊ ﺃﺟﺯﺍء ﺍﻟﻣﻧﻅﻭﻣﺔ ﻣﻊ ﻛﺎﻓﺔ ﻣﻠﺣﻘﺎﺗﻬﺎ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﻌﺎﻟﻲ ﺍﻟﺟﻭﺩﺓ ﻭﺍﻟﻣﺻﻧﻌﺔ‬
‫ﻭﻓﻖ ﺃﺣﺩﺙ ﺍﻟﻣﻌﺎﻳﻳﺭ ﺍﻟﻌﺎﻟﻣﻳﺔ‪ ،‬ﻭﺗﻘﺩﻳﻡ ﺍﻟﻛﺗﺎﻟﻭﻛﺎﺕ ﻭﺍﻟﻧﺷﺭﺍﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺧﺎﺻﺔ ﺑﺗﻠﻙ ﺍﻷﺟﻬﺯﺓ ﻣﻭﺿﺢ ﻋﻠﻳﻬﺎ ﺍﻻﺳﺗﻁﺎﻋﺎﺕ‬

‫‪3|Page‬‬
‫ﺍﻟﻣﻁﻠﻭﺑﺔ ﻭﺍﻟﻧﻣﺎﺫﺝ ﺍﻟﻣﺧﺗﺎﺭﺓ ﻟﺗﻠﻙ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ‪ ،‬ﻭﻳﻠﺗﺯﻡ ﺍﻟﻌﺎﺭﺽ ﺑﺗﺄﻣﻳﻥ ﻛﺎﺩﺭ ﻓﻧﻲ ﺫﻭ ﺧﺑﺭﺓ ﺟﻳﺩﺓ ﻟﺗﻧﻔﻳﺫ ﺃﻋﻣﺎﻝ ﺍﻟﺗﺭﻛﻳﺏ‬
‫ﻭﺍﻟﺗﺷﻐﻳﻝ‪.‬‬
‫ﻭﻳﻘﻊ ﻋﻠﻰ ﻋﺎﺗﻖ ﺍﻟﻣﺗﻌﻬﺩ ﺇﻋﺩﺍﺩ ﺍﻟﺩﺭﺍﺳﺔ ﺍﻟﺗﻧﻔﻳﺫﻳﺔ ﻟﻠﺣﻭﺍﻣﻝ ﺍﻟﻣﻌﺩﻧﻳﺔ ﻟﻧﻅﺎﻡ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻼﺯﻣﺔ ﻟﺗﺛﺑﻳﺗﻪ ﺑﺣﻳﺙ ﺗﺗﺣﻣﻝ‬ ‫‪-‬‬
‫ﺳﺭﻋﺔ ﻫﺑﺔ ﺭﻳﺎﺡ ﻻ ﺗﻘﻝ ﻋﻥ )‪.(50Km/h‬‬
‫ﻳﺟﺏ ﺗﻭﺭﻳﺩ ﺗﺟﻬﻳﺯﺍﺕ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﺑﺷﻛﻝ ﻳﺿﻣﻥ ﺳﻼﻣﺗﻬﺎ ﻭﻭﺻﻭﻟﻬﺎ ﺇﻟﻰ ﻣﻭﻗﻊ ﺍﻟﺗﺭﻛﻳﺏ ﻛﻣﺎ ﻫﻲ ﻣﻭﺭﺩﺓ ﻣﻥ‬ ‫‪-‬‬
‫ﻣﺻﺩﺭﻫﺎ‪.‬‬
‫ﻳﺟﺏ ﺗﻘﺩﻳﻡ ﻧﺷﺭﺍﺕ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺻﻳﺎﻧﺔ ﻭﺷﻬﺎﺩﺍﺕ ﺑﻠﺩ ﺍﻟﻣﻧﺷﺄ ﺣﻳﺙ ﻳﻠﺯﻡ ﺑﻌﺩ ﺍﻟﺗﺭﺳﻳﺔ‪.‬‬ ‫‪-‬‬
‫ﻳﻘﻊ ﻋﻠﻰ ﻋﺎﺗﻖ ﺍﻟﻌﺎﺭﺽ ﺃﻥ ﻳﻘﺩﻡ ﻓﻲ ﻋﺭﺿﻪ ﻣﺎ ﻳﺛﺑﺕ ﺍﻟﺗﺯﺍﻣﻪ ﺑﺗﻘﺩﻳﻡ ﻗﻁﻊ ﺍﻟﻐﻳﺎﺭ ﻭﺧﺩﻣﺔ ﻣﺎ ﺑﻌﺩ ﺍﻟﺑﻳﻊ‪.‬‬ ‫‪-‬‬
‫ﻳﻘﻊ ﻋﻠﻰ ﻋﺎﺗﻖ ﺍﻟﻌﺎﺭﺽ ﺗﻘﺩﻳﻡ ﻣﻊ ﺍﻷﺟﻬﺯﺓ ﺍﻟﻣﻘﺩﻣﺔ ﺻﻧﺩﻭﻕ ﻋﺩﺓ ﻳﺩﻭﻳﺔ ﻟﻠﺻﻳﺎﻧﺔ ﻭﺍﻟﻘﻳﺎﺱ‪.‬‬ ‫‪-‬‬

‫‪ - ٥‬ﺍﻟﺷﺭﻭﻁ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻟﺗﺭﻛﻳﺏ‪:‬‬


‫ﻳﺧﺿﻊ ﺍﻟﻣﺗﻌﻬﺩ ﺑﺎﻻﺿﺎﻓﺔ ﺇﻟﻰ ﺩﻓﺗﺭ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻰ ﻛﺎﻓﺔ ﺍﻟﻧﺷﺭﺍﺕ ﻭﺍﻟﻛﺗﺎﻟﻭﻛﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻟﺗﻌﻬﺩ ﻭﺍﻟﻣﺭﻓﻘﺔ‬ ‫‪-‬‬
‫ﺑﺎﻟﻌﺭﺽ ﺍﻟﻔﻧﻲ ﺍﻟﺗﻲ ﻳﺟﺏ ﺃﻥ ﺗﻭﺿﺢ ﻛﺎﻓﺔ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻼﺯﻣﺔ ﻟﺗﻧﻔﻳﺫ ﺍﻟﻣﺷﺭﻭﻉ‪ .‬ﻭﻳﺗﻭﺟﺏ ﻋﻠﻳﻪ ﻭﻋﻠﻰ ﻣﺳﺅﻭﻟﻳﺗﻪ‬
‫ﺇﺧﺗﻳﺎﺭ ﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﺑﺷﻛﻝ ﻳﺗﻭﺍﻓﻖ ﻣﻊ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻟﻣﻁﻠﻭﺑﺔ ﻭﺍﻟﺗﻲ ﺳﻳﻘﻭﻡ ﺍﻟﻣﺗﻌﻬﺩ ﺑﺗﻭﺭﻳﺩﻫﺎ ﻟﺗﺟﻬﻳﺯ ﺍﻟﻣﻧﻅﻭﻣﺔ‪.‬‬
‫ﻳﺟﺏ ﺗﻭﺭﻳﺩ ﺗﺟﻬﻳﺯﺍﺕ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﺑﺷﻛﻝ ﻳﺿﻣﻥ ﺳﻼﻣﺗﻬﺎ ﻭﻭﺻﻭﻟﻬﺎ ﺇﻟﻰ ﻣﻭﻗﻊ ﺍﻟﺗﺭﻛﻳﺏ ﻛﻣﺎ ﻫﻲ ﻣﻭﺭﺩﺓ ﻣﻥ‬ ‫‪-‬‬
‫ﻣﺻﺩﺭﻫﺎ‪.‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻧﻔﺫ ﺍﻟﺣﻭﺍﻣﻝ ﺍﻟﻣﻌﺩﻧﻳﺔ ﺑﺣﻳﺙ ﺗﺗﺣﻣﻝ ﺟﻣﻳﻊ ﺍﻟﻘﻭﻯ ﻭﺍﻟﺣﻣﻭﻻﺕ ﺍﻟﻣﺗﻭﻗﻌﺔ‪.‬‬ ‫‪-‬‬
‫ﻳﺟﺏ ﺗﻘﺩﻳﻡ ﻧﺷﺭﺍﺕ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺻﻳﺎﻧﺔ ﻭﺷﻬﺎﺩﺍﺕ ﺑﻠﺩ ﺍﻟﻣﻧﺷﺄ ﺣﻳﺙ ﻳﻠﺯﻡ ﺑﻌﺩ ﺍﻟﺗﺭﺳﻳﺔ‪.‬‬ ‫‪-‬‬
‫ﻳﻘﻊ ﻋﻠﻰ ﻋﺎﺗﻖ ﺍﻟﻣﺗﻌﻬﺩ ﻋﻧﺩ ﺍﻻﻧﺗﻬﺎء ﻣﻥ ﺗﺭﻛﻳﺏ ﺗﺟﻬﻳﺯﺍﺗﻪ ﺍﻟﻘﻳﺎﻡ ﺑﺗﺟﺭﺑﺔ ﻭﺗﺷﻐﻳﻝ ﻫﺫﻩ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﻭﺍﺧﺗﺑﺎﺭﻫﺎ ﻭﻣﻌﺎﻳﺭﺗﻬﺎ‬ ‫‪-‬‬
‫ﺗﻣﻬﻳﺩﺍ ً ﻟﻼﺳﺗﻼﻡ ‪.‬‬

‫‪ - ٦‬ﺍﻟﺗﺯﺍﻣﺎﺕ ﺍﻟﻌﺎﺭﺽ‪:‬‬
‫‪ -١‬ﺗﻘﺩﻳﻡ ﺧﺻﺎﺋﺹ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﺗﻲ ﺳﻳﻘﻭﻡ ﺑﺗﻘﺩﻳﻣﻬﺎ ﻭﺗﻧﻔﻳﺫﻫﺎ ﻭﺗﺣﺩﻳﺩ ﺍﻧﻌﻛﺎﺳﺎﺗﻬﺎ ﻣﻥ ﺣﻳﺙ ﻛﻔﺎﺑﺗﻬﺎ ﻟﺗﻐﻁﻳﺔ ﺍﻟﺣﻣﻭﻟﺔ‬
‫ﺍﻷﻋﻅﻣﻳﺔ ﺍﻟﻣﻁﻠﻭﺑﺔ ﺧﻼﻝ ﺍﻟﻔﺗﺭﺓ ﺍﻟﺯﻣﻧﻳﺔ ﺍﻟﻣﺣﺩﺩﺓ ﺑﻭﺍﺳ ﻁﺔ ﺍﻟﻧﻅﺎﻡ ﺍﻟﻣﻘﺩﻡ ﻣﻥ ﻗﺑﻠﻪ ﻭﻓﻘﺎ ً ﻟﺗﻘﺩﻳﺭﻩ ﻟﺧﺻ ﺎﺋﺹ ﺍﻟﻭﺿ ﻊ ﺍﻟﺟﻐﺭﺍﻓﻲ‬
‫ﻟﻣﻭﻗﻊ ﺍﻟﻣﺷﺭﻭﻉ‪.‬‬
‫‪ -٢‬ﻳﺗﻌﻬﺩ ﺍﻟﻌﺎﺭﺽ ﺑﺗﺩﺭﻳﺏ ﻣﻬﻧﺩﺳﻳﻥ ﻭﻓﻧﻳﻳﻥ ﻹﻏﻧﺎء ﺧﺑﺭﺍﺗﻬﻡ ﻓﻲ ﻣﺟﺎﻝ ﺍﻟﺗﺷﻐﻳﻝ ﻭﺍﻟﺻﻳﺎﻧﺔ ﻓﻲ ﻣﺟﺎﻝ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ‪.‬‬
‫‪ -٣‬ﻳﺗﻌﻬﺩ ﺍﻟﻌﺎﺭﺽ ﺑﻌﺩ ﺍﻻﻧﺗﻬﺎء ﻣﻥ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺗﺷ ﻐﻳﻝ ﺇﺟﺭﺍء ﺍﻟﻘﻳﺎﺳ ﺎﺕ ﺍﻟﻼﺯﻣﺔ ﺧﻼﻝ ﻓﺗﺭﺍﺕ ﺍﻟﻌﻣﻝ ﺍﻟﺻ ﺑﺎﺣﻳﺔ ﻭﻟﻣﺩﺓ ﺛﻼﺛﺔ ﺃﻳﺎﻡ‬
‫ﻣﺗﻭﺍﺻﻠﺔ ﺃﻭ ﻣﻧﻔﺻﻠﺔ ﻳﻛﻭﻥ ﻓﻳﻬﺎ ﺍﻟﺳﻁﻭﻉ ﺍﻟﺷﻣﺳﻲ ﻛﺎﻓﻲ ﺣﻳﺙ ﻳﺗﻡ ﺗﻘﻳﻳﻡ ﺍﻟﻣﺷﺭﻭﻉ ﻣﻥ ﺧﻼﻟﻬﺎ )ﻓﺗﺭﺓ ﺍﻟﺗﺷﻐﻳﻝ ﺍﻟﺗﺟﺭﻳﺑﻲ(‪.‬‬
‫‪ -٤‬ﺗﻘﺩﻡ ﻛﺎﻓﺔ ﺍﻟﻧﺷ ﺭﺍﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺧﺎﺻ ﺔ ﺑﺎﻟﻣﻌﺭﺝ ﻭﺍﻟﻠﻭﺍﻗﻁ ﺍﻟﻛﻬﺭﻭﺿ ﻭﺋﻳﺔ ﻭﺍﻟﻣﺧﻁﻁﺎﺕ ﺍﻟﺗﺻ ﻣﻳﻣﻳﺔ ﺍﻷﻭﻟﻳﺔ ﻟﻠﺣﻭﺍﻣﻝ ﺍﻟﻣﻌﺩﻧﻳﺔ‬
‫ﻭﺍﻟﻘﻭﺍﻋﺩ ﺍﻻﺳ ﻣﻧﺗﻳﺔ ﺃﻭ ﺍﻟﻣﻌﺩﻧﻳﺔ ﻋﻧﺩ ﺗﻘﺩﻳﻡ ﺍﻟﻌﺭﺽ ﻣﺑﻳﻧﺎ ً ﺑﺷ ﻛﻝ ﻭﺍﺿ ﺢ ﻛﺎﻓﺔ ﺍﻟﻣﻭﺍﺻ ﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻭﻓﻘﺎ ً ﻟﻣﺎ ﻫﻭ ﻣﺑﻳﻥ ﻓﻲ ﺑﻧﻭﺩ‬
‫‪4|Page‬‬
‫ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﺩﺭﺟﺔ ﺃﺩﻧﺎﻩ ﻭﻛﺫﻟﻙ ﺍﻟﻣﺎﺭﻛﺔ ﻭﺍﻟﻁﺭﺍﺯ ﻭﺑﻠﺩ ﺍﻟﻣﻧﺷﺄ‪.‬‬

‫‪ - ٧‬ﺗﻌﻠﻳﻣﺎﺕ ﺍﻟﺗﺷﻐﻳﻝ ﻭﺍﻟﺻﻳﺎﻧﺔ‪:‬‬


‫ﻳﺟﺏ ﺗﻘﺩﻳﻡ ﺗﻌﻠﻳﻣﺎﺕ ﺍﻟﺗﺷ ﻐﻳﻝ ﻭﺍﻟﺻ ﻳﺎﻧﺔ ﻟﻛﺎﻓﺔ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﻭﺗﺳ ﻠﻳﻣﻬﺎ ﺇﻟﻰ ﻟﻔﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ‪ ،‬ﻭﻋﻠﻰ ﺍﻟﺟﻬﺔ ﺍﻟﻣﻧﻔﺫﺓ ﺗﺩﺭﻳﺏ ﻋﻧﺎﺻ ﺭ‬
‫ﺍﻟﺻ ﻳﺎﻧﺔ ﻣﻥ ﺍﻹﺩﺍﺭﺓ ﻭﻟﻣﺩﺓ ﺛﻼﺛﺔ ﺃﻳﺎﻡ ﻋﻠﻰ ﺗﺷ ﻐﻳﻝ ﺗﻠﻙ ﺍﻷﺟﻬﺯﺓ ﻭﺇﻋﺩﺍﺩ ﻟﻭﺣﺔ ﺧﺎﺻ ﺔ ﺑﺗﻌﻠﻳﻣﺎﺕ ﻭﺧﻁﻭﺍﺕ ﺗﺷ ﻐﻳﻝ ﻭﻣﺭﺍﻗﺑﺔ‬
‫ﺍﻟﻣﻧﻅﻭﻣﺔ ﻭﺗﺣﺩﻳﺩ ﻗﻳﻡ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻟﻌﻅﻣﻰ ﺍﻟﻣﺳﻣﻭﺡ ﺑﺎﺳﺗﺟﺭﺍﺭﻫﺎ ﺣﺳﺏ ﺣﺎﻟﺔ ﺍﻟﻌﻣﻝ ﻭﺗﺛﺑﻳﺗﻬﺎ ﺟﺎﻧﺏ ﺍﻟﻣﺟﻣﻭﻋﺔ ﻭﻭﺿﻊ ﺍﻟﺗﺳﻣﻳﺎﺕ‬
‫ﺍﻟﻣﻧﺎﺳﺑﺔ ﻭﺍﻟﺿﺭﻭﺭﻳﺔ ﻋﻠﻰ ﻟﻭﺣﺔ ﺍﻟﺗﺷﻐﻳﻝ ﻭﺍﻟﻣﻔﺎﺗﻳﺢ ﺍﻟﺿﺭﻭﺭﻳﺔ‪.‬‬

‫‪- ٨‬ﺍﺳﺗﻼﻡ ﺃﻋﻣﺎﻝ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ‪:‬‬


‫ﻋﻠﻰ ﺍﻟﻣﺗﻌﻬﺩ ﺍﺧﺗﺑﺎﺭ ﻭﺗﺷ ﻐﻳﻝ ﻧﻅﺎﻡ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷ ﻣﺳ ﻳﺔ ﻭﻓﻘﺎ ً ﻟﻣﺎ ﻫﻭ ﻣﻁﻠﻭﺏ ﻓﻲ ﺍﻟﺗﺷ ﻐﻳﻝ ﺍﻟﺗﺟﺭﻳﺑﻲ‪ .‬ﻭﺗﺗﻡ ﻋﻣﻠﻳﺔ ﺍﻻﺳ ﺗﻼﻡ ﺍﻷﻭﻟﻲ‬
‫ﻷﻋﻣﺎﻝ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﺑﻌﺩ ﺍﺟﺗﻳﺎﺯﻫﺎ ﺑﻧﺟﺎﺡ ﻣﺭﺣﻠﺔ ﺍﻟﺗﺷﻐﻳﻝ ﺍﻟﺗﺟﺭﻳﺑﻲ ﺍﻟﻣﺑﻳﻧﺔ ﺃﻋﻼﻩ‪.‬‬

‫‪ - ٩‬ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻟﻣﻛﻭﻧﺎﺕ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ‪:‬‬


‫‪ -١-٩‬ﻣﻭﺍﺻﻔﺎﺕ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻭﺗﺷﻐﻳﻝ ﻧﻅﺎﻡ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﻣﻊ ﺍﻟﻬﻳﺎﻛﻝ ﺍﻟﺣﺎﻣﻠﺔ‪:‬‬
‫ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻ ﻳﻝ ﻭﺗﺷ ﻐﻳﻝ ﻣﺟﻣﻭﻋﺔ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷ ﻣﺳ ﻳﺔ ﻟﺯﻭﻡ ﺗﻭﻟﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﻼﺯﻣﺔ ﻟﺗﻐﻁﻳﺔ‬
‫ﺣﻣﻭﻟﺔ ﺃﻋﻅﻣﻳﺔ ‪ ١٥‬ﻛﻳﻠﻭ ﻭﺍﻁ ﻋﻠﻰ ﺃﻥ ﻳﻛﻭﻥ ﻋﺩﺩ ﺍﻷﻟﻭﺍﺡ ‪ ٣٣‬ﻟﻭﺡ ﻭﻓﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﺗﺎﻟﻳﺔ‪:‬‬
‫ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﺟﺩﻳﺩﺓ ﻭﻏﻳﺭ ﻣﺟﺩﺩﺓ‪.‬‬ ‫‪-‬‬
‫ﻛﺎﻓﺔ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﻧﻔﺱ ﺍﻟﻁﺭﺍﺯ ﻭﺍﻻﺳﺗﻁﺎﻋﺔ ﻭﺍﻟﺷﺭﻛﺔ ﺍﻟﻣﺻﻧﻌﺔ‪.‬‬ ‫‪-‬‬
‫ﺗﺗﻛﻭﻥ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﻣﻥ ﻣﺟﻣﻭﻋﺔ ﺧﻼﻳــ ــ ـﺎ ﺳﻠﻳﻛﻭﻧﻳﺔ ﻣﻥ ﻧ ــ ــﻭﻉ ﺃﺣﺎﺩﻱ ﺃﻭ ﻣﺗﻌﺩﺩ ﺍﻟﺑﻠﻭﺭﺍﺕ ﻣﺟﻣﻌﺔ ﺿﻣﻥ ﺇﻁﺎﺭ‬ ‫‪-‬‬
‫ﻣﻥ ﺍﻷﻟﻣﻧﻳﻭﻡ ﻭﻣﺯﻭﺩﺓ ﺑﺯﺟﺎﺝ ﻣﻐﺷﻰ ﺣﺭﺍﺭﻱ ﻣﻧﺧﻔﺽ ﺍﻟﺣﺩﻳﺩ ﻭﻳﺗﻡ ﻟﺻﻘﻪ ﺑﻭﺍﺳﻁﺔ ﻁﺑﻘﺔ ﺧﺎﺻﺔ ‪Ethylene-) EVA‬‬
‫‪ (Vinyl Acetate‬ﻟﻠﺣﻣﺎﻳﺔ ﻭﺗﺄﻣﻳﻥ ﺍﻟﻠﺻ ﻖ ﺍﻟﺟﻳﺩ‪ ،‬ﻭﺗﺯﻭﺩ ﺍﻟﺧﻼﻳﺎ ﺑﺧﻠﻔﻳﺔ ﻟﻠﺣﻣﺎﻳﺔ ﻣﻥ ﺍﻟﺻ ﺩﻣﺎﺕ ﻭﺍﻟﻅﺭﻭﻑ ﺍﻟﻣﻧﺎﺧﻳﺔ‬
‫‪ (Tedlar-polyester-Tedlar)TPT‬ﻭﺗﻛﻭﻥ ﺍﻷﻟﻭﺍﺡ ﻣﺣﻣﻳﺔ ﺑﺷ ﻛﻝ ﻋﺎﻡ ﻭﻛﺗﻳﻣﺔ ﻣﻥ ﺍﻟﺩﺍﺧﻝ ﻭﺗﻛﻭﻥ ﻣﻥ ﺻ ﻧﺎﻋﺔ‬
‫ﺇﺣﺩﻯ ﺍﻟﺷ ﺭﻛﺎﺕ ﺍﻟﻣﻌﺭﻭﻓﺔ ﻓﻲ ﻫﺫﺍ ﺍﻟﻣﺟﺎﻝ )‪ ....yingli-solarworld-JASOLAR‬ﺃﻭﻣﺎﻳﻌﺎﺩﻟﻬﺎ( ﺣﺎﺋﺯﺓ ﻋﻠﻰ‬
‫ﺷﻬﺎﺩﺓ ﺻﺎﺩﺭﺓ ﻋﻥ ﺟﻬﺎﺕ ﻣﻌﺗﻣﺩﺓ ﻋﺎﻟﻣﻳﺎ ً ﻭﺗﺣﻘﻖ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻹﺳﻣﻳﺔ ﺍﻟﺗﺎﻟﻳﺔ‪:‬‬
‫ﺗﻭﺗﺭ ﺍﻟﻌﻣﻝ ﺍﻻﺳﻣﻲ ﻻﻳﻘﻝ ﻋﻥ )‪ ٥٠‬ﻓﻭﻟﺕ(ﺗﻘﺭﻳﺑﺎً‪.‬‬ ‫‪‬‬
‫ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻹﺳﻣﻳﺔ ﻻﺗﻘﻝ ﻋﻥ )‪ ٥٤٠‬ﻭﺍﻁ( ﻋﻧﺩ ﺩﺭﺟﺔ ﺣﺭﺍﺭﺓ )‪ ٢٥‬ﺩﺭﺟﺔ ﻣﺋﻭﻳﺔ(‪.‬‬ ‫‪‬‬
‫ﺍﻻﺷﻌﺎﻉ ﺍﻟﺷﻣﺳﻲ )‪ ١٠٠٠‬ﻭﺍﻁ‪/‬ﻡ‪ (٢‬ﻭﻓﻘﺎ ً ﻹﺧﺗﺑﺎﺭﺍﺕ ‪ STC‬ﺑﺩﺭﺟﺔ ﺣﺭﺍﺭﺓ ‪ ٢٥‬ﻣﺋﻭﻳﺔ ﻭﺑﻁﻳﻑ ‪.AM 1.5‬‬ ‫‪‬‬
‫ﻋﺩﺩ ﺍﻷﻟﻭﺍﺡ ﻛﺎﻓﻳﺔ ﻟﺗﺄﻣﻳﻥ ﺍﺳﺗﻁﺎﻋﺔ ﺇﺟﻣﺎﻟﻳﺔ )‪ (17 KW‬ﻓﻲ ﻅﺭﻭﻑ ﺍﻟﻣﻭﻗﻊ‪.‬‬ ‫‪‬‬

‫‪5|Page‬‬
‫ﺃﻟﻭﺍﺡ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﻗﺎﺑﻠﺔ ﻟﻠﺗﻭﺻﻳﻝ ﻣﻊ ﺑﻌﺿﻬﺎ ﺍﻟﺑﻌﺽ ﺑﺷﻛﻝ )ﺗﺳﻠﺳﻠﻲ‪ -‬ﺗﻔﺭﻋﻲ( ﺑﺣﻳﺙ ﺗﺅﻣﻥ ﺍﻟﺗﻭﺗﺭ ﺍﻻﺳﻣﻲ ﺍﻟﻣﻧﺎﺳﺏ‬ ‫‪‬‬
‫ﻟﺗﻐﺫﻳﺔ ﺍﻟﻣﻌﺭﺝ‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻌﻣﻝ ﺍﻟﺧﻼﻳﺎ ﺍﻟﺷﻣﺳﻳﺔ ﺿﻣﻥ ﻣﺟﺎﻝ ﺗﻐﻳﻳﺭ ﺩﺭﺟﺔ ﺍﻟﺣﺭﺍﺭﺓ ﻣﻥ )‪ ٤٠-‬ﺩﺭﺟﺔ ﻣﺋﻭﻳﺔ( ﺇﻟﻰ )‪ ٨٥‬ﺩﺭﺟﺔ ﻣﺋﻭﻳﺔ(‪.‬‬ ‫‪‬‬
‫ﻳﺟﺏ ﺃﻥ ﻻ ﻳﻘﻝ ﺍﻟﻣﺭﺩﻭﺩ ﺍﻻ ﺳﻣﻲ ﻟﻠﺧﻼﻳﺎ ﺍﻟ ﺷﻣ ﺳﻳﺔ ﻋﻥ ‪ ،%21.3‬ﻭﺃﻥ ﻻ ﻳﻧﺧﻔﺽ ﻣﺭﺩﻭﺩ ﺍﻟﺧﻼﻳﺎ ﺍﻟ ﺷﻣ ﺳﻳﺔ ﻋﻥ ‪ %٩٠‬ﻣﻥ‬ ‫‪‬‬
‫ﻣﺭﺩﻭﺩﻫﺎ ﺍﻹﺳﻣﻲ ﺧﻼﻝ )‪١٠‬ﺳﻧﻭﺍﺕ( ﻭﻳﺑﻳﻥ ﺫﻟﻙ ﻓﻲ ﺍﻟﻧﺷﺭﺍﺕ ﻭﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﻗﺑﻝ ﺍﻟﻣﺗﻌﻬﺩ‪.‬‬
‫ﺍﻟﺗﻐﻳﺭ ﻓﻲ ﺍﺳﺗﻁﺎﻋﺔ ﺍﻟﻠﻭﺡ ﺍﻟﺷﻣﺳﻲ ﻋﻧﺩ ﺍﻟﺷﺭﻭﻁ ﺍﻟﻘﻳﺎﺳﻳﺔ ﻣﻥ)‪.%(3-0‬‬ ‫‪‬‬
‫ﻛﻣﺎ ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻛﺎﻓﺔ ﻣﺳ ﺗﻠﺯﻣﺎﺕ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺗﻭﺻ ﻳﻝ ﻣﻥ )ﻛﺎﺑﻼﺕ ﻭﺑﺭﺍﻏﻲ ﻭﻋﺯﻕ ﻭﻭﺻ ﻼﺕ ﻣﻌﺩﻧﻳﺔ ﻭﻗﻭﺍﻋﺩ‬ ‫‪‬‬
‫ﻣﻌﺩﻧﻳﺔ ﻣﺅﺭﺿﺔ ﻣﻐﻠﻔﻧﺔ ﻏﻳﺭ ﻗﺎﺑﻠﺔ ﻟﻠﺻﺩﺃ ﺃﻭ ﺍﻟﺗﺂﻛﻝ‪.....‬ﺍﻟﺦ(‪.‬‬
‫ﻋﻠﺑﺔ ﺍﻟﺗﻭﺻﻳﻝ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﺫﺍﺕ ﺩﺭﺟﺔ ﺣﻣﺎﻳﺔ ﻻﺗﻘﻝ ﻋﻥ ‪IP67‬‬ ‫‪‬‬
‫ﺣﻳﺙ ﻳﻘﻊ ﻋﻠﻰ ﻋﺎﺗﻖ ﺍﻟﺟﻬﺔ ﺍﻟﻣﻧﻔﺫﺓ ﺗﻘﺩﻳﻡ ﻛﺎﻓﺔ ﺍﻟﻣﺧﻁﻁﺎﺕ ﺍﻟﺗﺻ ﻣﻳﻣﻳﺔ ﻭﺍﻟﻣﻭﺍﺻ ﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻟﺗﻧﻔﻳﺫ ﺍﻟﻬﻳﻛﻝ ﺍﻟﻣﻌﺩﻧﻲ ﻟﺗﺛﺑﻳﺕ‬ ‫‪‬‬
‫ﺍﻟﻬﻳﺎﻛﻝ ﺍﻟﺣﺎﻣﻠﺔ ﻟﻸﻟﻭﺍﺡ ﺍﻟﺷ ﻣﺳ ﻳﺔ ﻛﻣﺎ ﻫﻲ ﻣﺑﻳﻧﺔ ﻓﻲ ﺑﻧﻭﺩ ﺍﻷﻋﻣﺎﻝ ﺍﻹﻧﺷ ﺎﺋﻳﺔ ﻭﺍﻟﻣﻌﺩﻧﻳﺔ ﻣﻥ ﺩﻓﺗﺭ ﺍﻟﺷ ﺭﻭﻁ ﺍﻟﻔﻧﻳﺔ ﻋﻠﻰ ﺃﻥ ﻳﺗﻡ‬
‫ﺍﻟﺗﻧﻔﻳﺫ ﺑﺟﻭﺩﺓ ﻓﻧﻳﺔ ﻋﺎﻟﻳﺔ ﺟﺎﻫﺯﺍ ً ﻟﻼﺳﺗﺛﻣﺎﺭ ‪ ،‬ﻣﻊ ﺗﺯﻭﻳﺩ ﺍﻟﻣﻧﻅﻭﻣﺔ ﺑﺷﺑﻛﺔ ﻣﺎﻧﻌﺎﺕ ﺍﻟﺻﻭﺍﻋﻖ‪.‬‬

‫ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺍﻟﺗﻭﺿ ﻳﺢ ﻓﻲ ﻋﺭﺿ ﻪ ﺍﻟﻔﻧﻲ ﺍﻟﻣﻭﺍﺻ ﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﺷ ﺎﺭ ﺇﻟﻳﻬﺎ ﻓﻲ ﺍﻟﺟﺩﻭﻝ ﺭﻗﻡ ‪) /١/‬ﺑﻣﻠﺣﻖ‬
‫ﺩﻓﺗﺭ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ( ﻭﺑﺷﻛﻝ ﻣﻧﻔﺻﻝ ﻣﺩﻋﻣﺔ ﺑﺎﻟﻧﺷﺭﺍﺕ ﺍﻟﻔﻧﻳﺔ ﻭﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﺑﻘﻠﻡ ﻋﻼﻡ ﺑﺷﻛﻝ ﻭﺍﺿﺢ‪.‬‬

‫‪ -٢-٩‬ﻣﻭﺍﺻﻔﺎﺕ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻭﺗﺷﻐﻳﻝ ﺍﻟﻣﻌﺭﺟﺎﺕ )ﺍﻹﻧﻔﻳﺭﺗﺭ(‪:‬‬


‫ﻳﺗﺿﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﺍﻟﻣﻌﺭﺟﺎﺕ ﺍﻟﻼﺯﻣﺔ ﻟﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗـ ـ ـ ـ ـ ﺔ ﺍﻟﺷﻣﺳﻳﺔ ﻣﻥ ﺷﺭﻛﺎﺕ ﻋﺎﻟﻣﻳﺔ‬ ‫‪-‬‬
‫ﻣﺗﺧﺻﺻﺔ ) ‪ ........ -GROWATT -SOLartech-AB‬ﺃﻭ ﻣﺎﻳﻌﺎﺩﻟﻬﺎ( ﺑﺣﻳﺙ ﺗﺣﻘﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺗﺎﻟﻳﺔ‪:‬‬
‫ﺃﻥ ﺗﻛﻭﻥ ﺍﻟﻣﻌﺭﺟﺎﺕ ﺟﺩﻳﺩﺓ ﻭﻏﻳﺭ ﻣﺟﺩﺩﺓ ‪.‬‬ ‫‪-‬‬
‫ﺃﻥ ﻳﻛﻭﻥ ﺍﻟﻣﻌﺭﺝ ﺍﻟﻣﻁﻠﻭﺏ ﺗﻘﺩﻳﻣﻪ ﺛﻼﺛﻲ ﺍﻟﻁﻭﺭ ﺑﺎﺳ ﺗﻁﺎﻋﺔ ﻻﺗﻘﻝ ﻋﻥ ‪ ١٥‬ﻛﻳﻠﻭ ﻭﺍﻁ ﺃﻭ ﺑﺎﻟﺣﺩ ﺍﻷﻋﻠﻰ ﺛﻼﺙ ﻣﻌﺭﺟﺎﺕ‬ ‫‪-‬‬
‫ﺃﺣﺎﺩﻳﺔ ﺍﻟﻁﻭﺭ ﻗﺎﺑﻠﺔ ﻟﻠﺗﻭﺻﻳﻝ ﻋﻠﻰ ﺍﻟﺗﺳﻠﺳﻝ ﺑﺷﻛﻝ ﻓﻧﻲ ﺑﺣﻳﺙ ﻳﻛﻭﻥ ﺍﺳﺗﻁﺎﻋﺔ ﺍﻟﻣﻌﺭﺝ ﺍﻟﻭﺍﺣﺩ ﻻ ﻳﻘﻝ ﻋﻥ ‪ ٥‬ﻛﻳﻠﻭ ﻭﺍﻁ‬
‫ﻭﻳﻔﺿﻝ ﺍﻷﻋﻠﻰ ‪.‬‬
‫ﺃﻥ ﺗﻛﻭﻥ ﺟﻣﻳﻊ ﺍﻟﻣﻌﺭﺟﺎﺕ ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﻧﻔﺱ ﺍﻟﺷﺭﻛﺔ ﺍﻟﺻﺎﻧﻌﺔ‪.‬‬ ‫‪-‬‬
‫ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻻﺟﻣﺎﻟﻳﺔ ﻟﺧﺭﺝ ﺍﻟﻣﻌﺭﺟﺎﺕ ﺗﻐﻁﻲ ﺣﻣﻭﻻﺕ ﻻﺗﻘﻝ ﻋﻥ )‪.(15 KW‬‬ ‫‪-‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺍﻟﻣﻌﺭﺟﺎﺕ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﻘﺎﺑﻝ ﻟﻠﺑﺭﻣﺟﺔ ﻭﺍﻟﺧﺎﺻﺔ ﺑﺄﻧﻅﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ‪.‬‬ ‫‪-‬‬
‫ﺍﻟﻣﻌﺭﺟﺎﺕ ﻣﺯﻭﺩﺓ ﺑﺷ ﺎﺷ ﺔ ﺇﻅﻬﺎﺭ ﺭﻗﻣﻳﺔ ﺗﻭﺿ ﺢ ﺣﺎﻟﺔ ﺍﻟﻌﻣﻝ ﻟﻠﻣﻧﻅﻭﻣﺔ ﻭﺍﻟﻣﺣﺩﺩﺍﺕ ﺍﻟﺭﺋﻳﺳ ﻳﺔ ﻟﻠﻣﻧﻅﻭﻣﺔ )ﺟﻬﺩ ﻭﺗﻳﺎﺭ‬ ‫‪-‬‬
‫ﻭﺍﺳ ﺗﻁﺎﻋﺔ ﺩﺧﻝ ﺍﻟﻣﻌﺭﺝ ‪ -‬ﺟﻬﺩ ﻭﺗﺭﺩﺩ ﻭﺗﻳﺎﺭ ﺧﺭﺝ ﺍﻟﻣﻌﺭﺝ – ﺩﺭﺟﺔ ﺣﺭﺍﺭﺓ ﺍﻟﻣﻌﺭﺝ – ﺍﻟﻭﻗﺕ ﻭﺍﻟﺗﺎﺭﻳﺦ – ﺍﻟﻁﺎﻗﺔ‬

‫‪6|Page‬‬
‫ﺍﻟﻣﻧﺗﺟﺔ ﻓﻲ ﺍﻟﻳﻭﻡ ﺟﻬﺩ ﻧﻘﻁﺔ ﺍﻻﺳ ﺗﻁﺎﻋﺔ ﺍﻷﻋﻅﻣﻳﺔ ﻓﻲ ﺍﻟﻳﻭﻡ – ﺗﻭﻗﻳﺕ ﺑﺩء ﻭﺍﻧﺗﻬﺎء ﻋﻣﻝ ﺍﻟﻣﻌﺭﺝ ﺑﺎﻟﻳﻭﻡ ‪-‬ﻋﺩﺩ ﺳ ﺎﻋﺎﺕ‬
‫ﻋﻣﻝ ﺍﻟﻣﻌﺭﺝ ﺑﺎﻟﻳﻭﻡ(‪.‬‬
‫ﻳﺟ ﺏ ﺃﻥ ﻳﻛﻭﻥ ﺧﺭﺝ ﺍﻟﻣﻌﺭﺝ ﺍﻟﻣﻘ ﺩﻡ ﺛﻼﺛﻳ ﺔ ﺍﻟﻁﻭﺭ ﺃﻭ ﺛﻼﺙ ﻣﻌﺭﺟ ﺎﺕ ﺃﺣ ﺎﺩﻳ ﺔ ﺍﻟﻁﻭﺭ‪ ،‬ﻭﺗﻌﻣ ﻝ ﺑﺗﻘﻧﻳ ﺔ ﻣﻼﺣﻘ ﺔ ﻧﻘﻁ ﺔ‬ ‫‪-‬‬
‫ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻷﻋﻅﻣﻳﺔ )‪.(MPPT‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺇﺷﺎﺭﺓ ﺧﺭﺝ ﺍﻟﻣﻌﺭﺟﺎﺕ ﺟﻳﺑﻳﺔ ﻭﻧﻘﻳﺔ‪.‬‬ ‫‪-‬‬
‫ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺗﺣﺩﻳﺩ ﻣﺎﻳﻠﻲ‪:‬‬ ‫‪-‬‬
‫ﺩﺭﺟﺔ ﺣﻣﺎﻳﺔ ﺍﻟﻣﻌﺭﺝ‪.‬‬ ‫‪‬‬
‫ﻧﻭﻉ ﺍﻟﻣﻌﺭﺝ ‪ Outdoor‬ﺃﻭ ‪ indoor‬ﺣﺳﺏ ﺍﻟﻣﻭﻗﻊ ﺍﻟﻣﺣﺩﺩ ﻟﻠﺗﺭﻛﻳﺏ‪.‬‬ ‫‪‬‬
‫ﻣﺭﺩﻭﺩ ﺍﻟﻣﻌﺭﺝ ﻻﻳﻘﻝ ﻋﻥ ‪.%95‬‬ ‫‪‬‬
‫ﻣﺟﺎﻝ ﺗﻐﻳﺭ ﺍﻟﺗﻭﺗﺭ ﻟﺩﺧﻝ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭ )‪ (Dc‬ﻣﻥ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ‪.‬‬ ‫‪‬‬
‫ﺟﻬﺩ ﺍﻟﺩﺧﻝ ﺍﻷﻋﻅﻣﻲ ﻟﻠﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭ‪.‬‬ ‫‪‬‬
‫ﻣﺟﺎﻝ ﺗﻐﻳﺭ ﺍﻟﺗﻭﺗﺭ ﻟﺧﺭﺝ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺗﻧﺎﻭﺏ )‪.(Ac‬‬ ‫‪‬‬
‫ﻣﺟﺎﻝ ﺗﻐﻳﺭ ﺍﻟﺗﺭﺩﺩ ﻟﻠﺗﻳﺎﺭ ﺍﻟﻣﺗﻧﺎﻭﺏ‪.‬‬ ‫‪‬‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﺟﺎﻝ ﺍﻟﺣﺭﺍﺭﻱ ﻟﻌﻣﻝ ﺍﻟﻣﻌﺭﺝ ﺣﻳﺙ ﻳﻔﺿﻝ )‪.(C 50 +  C 10-‬‬ ‫‪‬‬
‫ﺗﺣﺩﻳﺩ ﻗﻳﻣﺔ ﺗﻳﺎﺭ ﺍﻟﺧﺭﺝ ﺍﻻﺳﻣﻲ ﻟﻠﻣﻌﺭﺝ‪.‬‬ ‫‪‬‬
‫ﺗﺣﺩﻳﺩ ﺍﺳﺗﻁﺎﻋﺔ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﺍﻟﻣﻣﻛﻥ ﺭﺑﻁﻬﺎ ﻣﻊ ﺍﻟﻣﻌﺭﺝ‪.‬‬ ‫‪‬‬
‫ﺗﺣﺩﻳﺩ ﻋﺩﺩ ﻣﺩﺍﺧﻝ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭﻟﻠﻣﻌﺭﺟﺎﺕ‪.‬‬ ‫‪‬‬
‫ﻳﺟﺏ ﺃﻥ ﻳﺣﺗﻭﻱ ﺍﻟﻣﻌﺭﺝ ﻋﻠﻰ ﻛﺎﻓﺔ ﺍﻟﺣﻣﺎﻳﺎﺕ ﺍﻟﻼﺯﻣﺔ‪:‬‬ ‫‪‬‬
‫)ﺣﻣﺎﻳﺔ ﻣﻥ ﺯﻳﺎﺩﺓ ﺍﻟﺣﻣﻝ – ﺣﻣﺎﻳﺔ ﻣﻥ ﺗﻳﺎﺭ ﺍﻟﻘﺻﺭ – ﺣﻣﺎﻳﺔ ﻣﻥ ﺯﻳﺎﺩﺓ ﺃﻭ ﺍﻧﺧﻔﺎﺽ ﺍﻟﺗﻭﺗﺭ ﺃﻭ ﻋﺩﻡ ﺗﺗﺎﺑﻊ ﺍﻷﻁﻭﺍﺭ‬
‫ﺣﻣﺎﻳﺔ ﻣﻥ ﺍﺭﺗﻔﺎﻉ ﺩﺭﺟﺔ ﺍﻟﺣﺭﺍﺭﺓ ‪.......-‬ﺍﻟﺦ(‪.‬‬
‫ﻳﺗﻭﺟﺏ ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺗﻘﺩﻳﻡ ﺷﻬﺎﺩﺍﺕ ﺍﻻﺧﺗﺑﺎﺭ ﺍﻟﻣﻌﺗﻣﺩﺓ ﻋﺎﻟﻣﻳﺎ ً ﺍﻟﺧﺎﺻﺔ ﺑﺎﻟﻣﻌﺭﺟﺎﺕ ﺍﻟﻣﻘﺩﻣﺔ‪.‬‬ ‫‪‬‬

‫ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺍﻟﺗﻭﺿ ﻳﺢ ﻓﻲ ﻋﺭﺿ ﻪ ﺍﻟﻔﻧﻲ ﺍﻟﻣﻭﺍﺻ ﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﺷ ﺎﺭ ﺇﻟﻳﻬﺎ ﻓﻲ ﺍﻟﺟﺩﻭﻝ ﺭﻗﻡ ‪) /٢/‬ﺑﻣﻠﺣﻖ ﺩﻓﺗﺭ ﺍﻟﻣﻭﺍﺻ ﻔﺎﺕ‬
‫ﺍﻟﻔﻧﻳﺔ( ﺑﺷﻛﻝ ﻣﻧﻔﺻﻝ ﻣﺩﻋﻣﺔ ﺑﺎﻟﻧﺷﺭﺍﺕ ﺍﻟﻔﻧﻳﺔ ﻭﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﺑﻘﻠﻡ ﻋﻼﻡ ﺑﺷﻛﻝ ﻭﺍﺿﺢ‪.‬‬

‫‪ -٣-٩‬ﻣﻭﺍﺻﻔﺎﺕ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﻭﺷﺣﻥ ﻭﺗﺷﻐﻳﻝ ﺍﻟﻣﺩﺧﺭﺍﺕ‪:‬‬


‫ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻭﻧﻘﻝ ﻭﺗﺭﻛﻳﺏ ﻭ ﺗﻭﺻ ﻳﻝ ﻭﺷ ﺣﻥ ﻭﺗﺷ ﻐﻳﻝ ﻣﺩﺧﺭﺍﺕ ﻛﺎﻓﻳﺔ ﻟﺗﻐﻁﻳﺔ ﺍﻻﺳ ﺗﻁﺎﻋﺔ ﺍﻷﻋﻅﻣﻳﺔ ﻟﺧﺭﺝ ﺍﻟﻣﻌﺭﺟﺎﺕ‬
‫ﻟﺯﻭﻡ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷ ﻣﺳ ﻳﺔ ﻭﻋﺩﺩﻫﺎ ﺑﺎﻟﺣﺩ ﺍﻷﺩﻧﻰ ‪ ٣٢‬ﻣﺩﺧﺭﺓ ﻟﺗﻐﻁﻳﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﻼﺯﻣﺔ ﻟﻠﻣﺷ ﺭﻭﻉ ﻟﻣﺩﺓ ‪ ٣‬ﺳ ﺎﻋﺎﺕ‬
‫ﻓﻲ ﺣﺎﻝ ﺍﻧﺧﻔﺎﺽ ﺍﻟﺳﻁﻭﻉ ﺍﻟﺷﻣﺳﻲ ﻭﺍﻟﻌﻣﻝ ﺧﺎﺭﺝ ﺃﻭﻗﺎﺕ ﺍﻟﺩﻭﺍﻡ ﺍﻟﺭﺳﻣﻲ ﻓﻲ ﺣﺎﻻﺕ ﺍﻟﻁﻭﺍﺭﺉ ﻭﺍﻟﻛﻭﺍﺭﺙ ‪.‬‬

‫‪7|Page‬‬
‫ﻭﺗﺣﻘﻖ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺗﺎﻟﻳﺔ‪:‬‬
‫ﻧﻭﻉ ﺍﻟﻣﺩﺧﺭﺍﺕ ﺍﻟﻣﻘﺩﻣﺔ ‪.Gel‬‬ ‫‪-‬‬
‫ﺍﻟﻣﺩﺧﺭﺓ ﺍﻟﻭﺍﺣﺩﺓ ﻻﺗﻘﻝ ﻋﻥ ) ‪ 200A - 12 V‬ﻋﻧﺩ ‪(C10‬‬ ‫‪-‬‬
‫ﺍﻟﺳﻌﺔ ﺍﻹﺟﻣﺎﻟﻳﺔ ﻟﻠﻣﺩﺧﺭﺍﺕ ﺗﺅﻣﻥ ﺗﻐﺫﻳﺔ ﻣﺳﺗﻣﺭﺓ ﻷﺣﻣﺎﻝ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﺳﺗﻁﺎﻋﺗﻬﺎ ﺍﻹﺟﻣﺎﻟﻳﺔ ﻻﺗﻘﻝ ﻋﻥ )‪.(10 KW‬‬ ‫‪-‬‬
‫ﻋﻣﻖ ﺍﻟﺗﻔﺭﻳﻎ ﻻﻳﺯﻳﺩ ﻋﻥ ‪.%٦٠‬‬ ‫‪-‬‬
‫ﻋﺩﺩ ﺩﻭﺭﺍﺕ ﺍﻟﻌﻣﻝ ﻟﻠﻣﺩﺧﺭﺓ ﻋﻧﺩ ﻋﻣﻖ ﺍﻟﺗﻔﺭﻳﻎ ﻻﻳﻘﻝ ﻋﻥ ‪.%٥٠‬‬ ‫‪-‬‬
‫ﺗﺣﺩﻳﺩ ﺗﻳﺎﺭ ﺍﻟﺷﺣﻥ ﻟﻠﻣﺩﺧﺭﺓ‪.‬‬ ‫‪-‬‬
‫ﺗﺣﺩﻳﺩ ﺗﻳﺎﺭﺍﻟﺗﻔﺭﻳﻎ ﻟﻠﻣﺩﺧﺭﺓ‪.‬‬ ‫‪-‬‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﺟﺎﻝ ﺍﻟﺣﺭﺍﺭﻱ ﻟﻌﻣﻝ ﺍﻟﻣﺩﺧﺭﺓ‪.‬‬ ‫‪-‬‬
‫ﺗﺣﺩﻳﺩ ﻭﺯﻥ ﻭﺗﺎﺭﻳﺦ ﺇﻧﺗﺎﺝ ﺍﻟﻣﺩﺧﺭﺓ‪.‬‬ ‫‪-‬‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻌﻣﺭ ﺍﻻﻓﺗﺭﺍﺿﻲ ﻟﻠﻣﺩﺧﺭﺓ‪.‬‬ ‫‪-‬‬
‫ﺗﺣﺩﻳﺩ ﻋﻣﻖ ﺍﻟﺗﻔﺭﻳﻎ ﺍﻷﻋﻅﻣﻲ ﻟﻠﻣﺩﺧﺭﺓ‪.‬‬ ‫‪-‬‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﻘﺎﻭﻣﺔ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻟﻠﻣﺩﺧﺭﺓ‬ ‫‪-‬‬
‫ﻳﺗﻡ ﺗﺭﻛﻳﺏ ﻭﺗﺛﺑﻳﺕ ﺍﻟﻣﺩﺧﺭﺍﺕ ﻋﻠﻰ ﻗﻭﺍﻋﺩ ﺍﻭ ﺧﺯﻥ ﻣﻌﺩﻧﻳﺔ ﺑﺷ ﻛﻝ ﻓﻧﻲ ﻣﻊ ﺗﻘﺩﻳﻡ ﻛﺎﻓﺔ ﺍﻟﻠﻭﺍﺯﻡ ﻭﺍﻟﺗﺛﺑﻳﺕ ﻭﺍﻟﺗﻭﺻ ﻳﻝ‬ ‫‪-‬‬
‫ﺑﺣﻳﺙ ﻳﻛﻭﻥ ﺍﻟﻌﻣﻝ ﻣﻧﻔﺫ ﺑﺟﻭﺩﺓ ﻓﻧﻳﺔ ﻋﺎﻟﻳﺔ ﻭﺣﺳﺏ ﺗﻭﺟﻳﻬﺎﺕ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ‪.‬‬
‫ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺍﻟﺗﻭﺿ ﻳﺢ ﻓﻲ ﻋﺭﺿ ﻪ ﺍﻟﻔﻧﻲ ﺍﻟﻣﻭﺍﺻ ﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻣﺷ ﺎﺭ ﺇﻟﻳﻬﺎ ﻓﻲ ﺍﻟﺟﺩﻭﻝ ﺭﻗﻡ ‪) /٣/‬ﺑﻣﻠﺣﻖ ﺩﻓﺗﺭ‬ ‫‪-‬‬
‫ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ( ﺑﺷﻛﻝ ﻣﻧﻔﺻﻝ ﻣﺩﻋﻣﺔ ﺑﺎﻟﻧﺷﺭﺍﺕ ﺍﻟﻔﻧﻳﺔ ﻭﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﺑﻘﻠﻡ ﻋﻼﻡ ﺑﺷﻛﻝ ﻭﺍﺿﺢ‪.‬‬

‫‪ -٤-٩‬ﻣﻭﺍﺻﻔﺎﺕ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﺍﻹﻛﺳﺳﻭﺍﺭﺍﺕ ﺍﻟﻣﻠﺣﻘﺔ ﺑﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ‪:‬‬


‫ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻛﺎﻓﺔ ﺍﻹﻛﺳ ﺳ ﻭﺍﺭﺍﺕ ﺍﻟﻼﺯﻣﺔ ﻟﻌﻣﻠﻳﺔ ﺍﻟﺗﻭﺻ ﻳﻼﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﻼﺯﻣﺔ ﻓﻲ ﺣﻘﻝ ﺍﻟﻠﻭﺍﻗﻁ ﺍﻟﻛﻬﺭﻭﺿ ﻭﺋﻳﺔ ﻣﻥ‬
‫)ﻋﻠﺏ ﺗﻭﺻ ﻳﻝ – ﻛﺎﺑﻼﺕ ﺗﻐﺫﻳﺔ ﻭﻧﻘﻝ ﺇﺷ ﺎﺭﺓ ﺑﻣﻘﺎﻁﻌﻬﺎ ﺍﻟﻣﺧﺗﻠﻔﺔ – ﻣﺟﺎﺭﻱ ﻣﻌﺩﻧﻳﺔ ﻣﻐﻠﻔﻧﺔ ﻟﺯﻭﻡ ﺗﻣﺩﻳﺩ ﺍﻟﻛﺎﺑﻼﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﻭﺍﻟﺧﺎﺭﺟﻳﺔ ﻣﻥ ﺧﻼﻟﻬﺎ ‪ -‬ﻗﻭﺍﻁﻊ ﻭﺣﻣﺎﻳﺎﺕ – ﺻ ﻭﻟﻳﺎﺕ – ﺟﻧﻛﺳ ﻳﻭﻧﺎﺕ ‪ -‬ﺭﺅﻭﺱ ﺩﺑﻭﺱ ‪....‬ﺍﻟﺦ ﺣﻳﺙ ﻳﻠﺯﻡ ﺍﻟﻌﻣﻝ ﺍﻟﻔﻧﻲ( ﺑﺣﻳﺙ‬
‫ﺗﻛﻭﻥ ﻛﺎﻓﺔ ﻣﺳﺗﻠﺯﻣﺎﺕ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺗﻭﺻﻳﻝ ﻭﺍﻟﺗﺛﺑﻳﺕ ﻭﺍﻟﺗﺭﻗﻳﻡ ﻟﺑﺩﺍﻳﺔ ﻭﻧﻬﺎﻳﺔ ﺍﻟﻛﺑﻝ ﺑﺎﻟﻣﻘﺎﻁﻊ ﺍﻟﻣﻧﺎﺳﺑﺔ ﻟﻼﺳﺗﻁﺎﻋﺎﺕ ﻭﺃﻥ ﺗﻛﻭﻥ ﻣﻥ‬
‫ﺃﺟﻭﺩ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻟﺗﺄﻣﻳﻥ ﺟﺎﻫﺯﻳﺔ ﺍﻟﻌﻣﻝ ﺑﺟﻭﺩﺓ ﻓﻧﻳﺔ ﻋﺎﻟﻳﺔ‪.‬‬

‫‪8|Page‬‬
‫ﻣﻠﺣﻖ ﺩﻓﺗﺭ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‬

‫ﺍﻟﺟﺩﺍﻭﻝ ﻟﺗﺟﻬﻳﺯﺍﺕ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ‬

‫ﻣﻭﺍﺻﻔﺎﺕ ﺗﺟﻬﻳﺯﺍﺕ ﻧﻅﺎﻡ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ ﻣﻊ ﺍﻟﻬﻳﺎﻛﻝ ﺍﻟﺣﺎﻣﻠﺔ ﻭﻣﻠﺣﻘﺎﺗﻬﺎ ﻭﻓﻖ ﺍﻟﺟﺩﻭﻝ ﺭﻗﻡ ‪/١/‬‬

‫ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﻗﺑﻝ ﺍﻟﻌﺎﺭﺽ‬ ‫ﺍﻟﻭﺣﺩﺓ‬ ‫ﺑﻳﺎﻥ ﺍﻟﻣﺎﺩﺓ ﻭﻣﻭﺍﺻﻔﺎﺗﻬﺎ‬ ‫ﺭﻗﻡ‬

‫‪٢‬‬ ‫ﺗﺣ ﺩﻳ ﺩ ﻣﺳ ﺎﺣ ﺔ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷ ﻣﺳ ﻳ ﺔ ﻭﻁﺭﻳﻘ ﺔ ﺍﻟﺗﺭﻛﻳ ﺏ‬


‫ﻡ‬ ‫‪١‬‬
‫ﻣﻊ ﺗﻘﺩﻳﻡ ﺍﻟﻣﺧﻁﻁ ﺍﻟﻼﺯﻡ‬
‫ﺍﻻﻟﺗﺯﺍﻡ ﺑﺯﺍﻭﻳﺔ ﻣﻳﻝ ﺃﻟﻭﺍﺡ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷ ﻣﺳ ﻳﺔ ﻣﻥ )‪ ٣٠-٢٠‬ﺩﺭﺟﺔ‬
‫‪-‬‬ ‫‪٢‬‬
‫ﻣﺋﻭﻳﺔ( ﻣﻊ ﺍﻟﻣﺧﻁﻁﺎﺕ ﺍﻟﻼﺯﻣﺔ‬

‫ﻭﺍﻁ‬ ‫ﺗﺣﺩﻳﺩ ﺍﺳﺗﻁﺎﻋﺔ ﻧﻅﺎﻡ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ )ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ(‬ ‫‪٣‬‬

‫ﻛﻳﻠﻭ ﻭﺍﻁ‬ ‫ﺍﺳﺗﻁﺎﻋﺔ ﺍﻟﻣﺣﻭﻟﺔ )ﺍﻹﻧﻔﺭﺗﺭ(‬ ‫‪٤‬‬

‫‪-‬‬ ‫ﺗﺣﺩﻳﺩ ﻣﻭﺍﺻﻔﺎﺕ ﻣﻌﺩﻥ ﺍﻟﻬﻳﻛﻝ ﺍﻟﻣﻌﺩﻧﻲ )ﺣﺩﻳﺩ ﻣﻐﻠﻔﻥ ﺃﻭ ﺃﻟﻣﻧﻳﻭﻡ(‬ ‫‪٥‬‬

‫‪٢‬‬
‫ﻣﻠﻡ‬ ‫ﺗﺣﺩﻳﺩ ﻣﻘﻁﻊ ﺍﻟﻬﻳﻛﻝ ﺍﻟﻣﻌﺩﻧﻲ ﻭﺷﻛﻠﻪ‬ ‫‪٦‬‬

‫ﺍﻻﻟﺗﺯﺍﻡ ﺑﺗﻘﺩﻳﻡ ﻛﺎﻓﺔ ﻣﺳ ﺗﻠﺯﻣﺎﺕ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺗﻭﺻ ﻳﻝ ﻭﺍﻟﺗﺛﺑﻳﺕ‬


‫‪-‬‬ ‫‪٧‬‬
‫ﻭﻓﻖ ﻣﻭﺍﺻﻔﺎﺕ ﺩﻓﺗﺭ ﺍﻟﺷﺭﻭﻁ ﺍﻟﻔﻧﻳﺔ‬
‫ﺗﺣﺩﻳﺩ ﻧﻭﻉ ﻭﻣﻘﻁﻊ ﻭﻁﻭﻝ ﺍﻟﻛﺑﻝ ﺍﻟﻣﺳﺗﺧﺩﻡ ﺑﻳﻥ ﻣﺧﺭﺝ‬
‫ﻣﻠﻡ‪/٢‬ﻡ‬ ‫‪٨‬‬
‫ﺍﻟﻠﻭﺍﻗﻁ ﺍﻟﺷﻣﺳﻳﺔ ﻭﺍﻟﻣﻌﺭﺝ )‪ NYY‬ﺷﻌﺭﻱ(‬
‫ﺗﺣﺩﻳﺩ ﻧﻭﻉ ﻭﻣﻘﻁﻊ ﻭﻁﻭﻝ ﺍﻟﻛﺑﻝ ﺍﻟﺩﺍﺧﻠﻲ ﻟﻠﻠﻭﺍﻗﻁ ﺍﻟﺷ ﻣﺳ ﻳﺔ‬
‫ﻣﻠﻡ‪/٢‬ﻡ‬ ‫‪٩‬‬
‫)‪ NYY‬ﺷﻌﺭﻱ(‬

‫‪-‬‬ ‫ﺫﻛﺭ ﺷﻬﺎﺩﺍﺕ ﺍﻻﺧﺗﺑﺎﺭ ﻭﺗﻘﺩﻳﻡ ﻧﺳﺧﺔ ﻋﻧﻬﺎ‬ ‫‪١٠‬‬

‫‪9|Page‬‬
‫ﺍﻟﺧﺻﺎﺋﺹ ﺍﻟﺗﻘﻧﻳﺔ‬
‫‪-‬‬ ‫ﺗﺣﺩﻳﺩ ﺑﻠﺩ ﺍﻟﻣﻧﺷﺄ ﻭﺍﻟﺷﺭﻛﺔ ﺍﻟﺻﺎﻧﻌﺔ‬ ‫‪١‬‬
‫ﻡ‬ ‫ﺗﺣﺩﻳﺩ ﺃﺑﻌﺎﺩ ﺍﻷﻟﻭﺍﺡ ﺍﻟﺷﻣﺳﻳﺔ‬ ‫‪٢‬‬
‫‪-‬‬ ‫ﺗﺣﺩﻳﺩ ﻧﻭﻉ ﺍﻟﺧﻠﻳﺔ ﻳﻔﺿﻝ ‪/mono/‬‬ ‫‪٣‬‬
‫ﻡ‬ ‫ﺗﺣﺩﻳﺩ ﺃﺑﻌﺎﺩ ﺍﻟﺧﻠﻳﺔ‬ ‫‪٤‬‬
‫ﻋﺩﺩ‬ ‫ﺗﺣﺩﻳﺩ ﻋﺩﺩ ﺍﻟﺧﻼﻳﺎ ﺿﻣﻥ ﺍﻟﻠﻭﺡ ﺍﻟﺷﻣﺳﻲ )‪ ٦٠‬ﺃﻭ ‪(٧٢‬‬ ‫‪٥‬‬
‫‪%‬‬ ‫ﺗﺣﺩﻳﺩ ﻋﺎﻣﻝ ﺍﻹﻣﺗﻼء )‪(FF‬‬ ‫‪٦‬‬
‫ﻛﻎ‬ ‫ﺗﺣﺩﻳﺩ ﻭﺯﻥ ﺍﻟﻠﻭﺡ‬ ‫‪٧‬‬
‫ﺗﺣﺩﻳﺩ ﻋﺩﺩ ﺧﻁﻭﻁ ﺍﻟﺗﻭﺻﻳﻝ ﺿﻣﻥ ﺍﻟﺧﻠﻳﺔ ﻻ ﺗﻘﻝ ﻋﻥ ‪ ٥‬ﺧﻁﻭﻁ‬
‫ﻋﺩﺩ‬ ‫‪٨‬‬
‫)‪(Sbb‬‬
‫‪-‬‬ ‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﻭﺻﻼﺕ ﺍﻟﺭﺑﻁ ‪ /‬ﻣﻁﺎﻁﻳﺔ ﻣﻘﺎﻭﻣﺔ ‪(MC4) /‬‬ ‫‪٩‬‬

‫ﺗﺣ ﺩﻳ ﺩ ﻣﻭﺍﺻ ﻔ ﺎﺕ ﻋﻠ ﺏ ﻭﻣ ﺂﺧ ﺫ ﺗﻭﺻ ﻳ ﻝ ﺍﻟﻠﻭﺍﻗﻁ‬


‫‪-‬‬ ‫‪١٠‬‬
‫ﻭﻋﺩﺩ ﺩﻳﻭﺩﺍﺕ ﺍﻟﺗﻣﺭﻳﺭ‬

‫‪%‬‬ ‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﻌﺎﻣﻝ ﺍﻟﺣﺭﺍﺭﻱ ﺍﻟﺧﺎﺹ ﺑﺎﻟﺗﻭﺗﺭ‬ ‫‪١١‬‬


‫‪%‬‬ ‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﻌﺎﻣﻝ ﺍﻟﺣﺭﺍﺭﻱ ﺍﻟﺧﺎﺹ ﺑﺎﻟﺗﻳﺎﺭ‬ ‫‪١٢‬‬
‫‪%‬‬ ‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﻌﺎﻣﻝ ﺍﻟﺣﺭﺍﺭﻱ ﺍﻟﺧﺎﺹ ﺑﺎﻻﺳﺗﻁﺎﻋﺔ‬ ‫‪١٣‬‬
‫ﺍﻟﺧﺻﺎﺋﺹ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ‬
‫ﺗﺣﺩﻳﺩ ﺍﻻﺳ ﺗﻁﺎﻋﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻻﺳ ﻣﻳﺔ ﻟﻠﻭﺡ ﺑﺣﻳﺙ ﻻ ﺗﻘﻝ ﻋﻥ‬
‫ﻭﺍﻁ‬ ‫‪١‬‬
‫‪ 540‬ﻭﺍﻁ‬
‫ﺃﻣﺑﻳﺭ‬ ‫ﺗﺣﺩﻳﺩ ﺷﺩﺓ ﺗﻳﺎﺭ ﻗﺻﺭ ﺍﻟﺩﺍﺭﺓ‬ ‫‪٢‬‬

‫ﺃﻣﺑﻳﺭ‬ ‫ﺗﺣﺩﻳﺩ ﺷﺩﺓ ﺗﻳﺎﺭ ﺍﻟﻌﻣﻝ‬ ‫‪٣‬‬

‫ﻓﻭﻟﺕ‬ ‫ﺗﺣﺩﻳﺩ ﺗﻭﺗﺭ ﻓﺻﻝ ﺍﻟﺣﻣﻭﻟﺔ‬ ‫‪٤‬‬

‫ﻓﻭﻟﺕ‬ ‫ﺗﺣﺩﻳﺩ ﺗﻭﺗﺭ ﺍﻟﻌﻣﻝ‬ ‫‪٥‬‬

‫ﻓﻭﻟﺕ‬ ‫ﺗﺣﺩﻳﺩ ﺍﻟﻘﻳﻣﺔ ﺍﻟﻌﻅﻣﻰ ﻟﻠﺗﻭﺗﺭ ﺍﻟﻛﻬﺭﺑﺎﺋﻲ ﻻ ﺗﻘﻝ ﻋﻥ ‪ ١٠٠٠‬ﻓﻭﻟﺕ‬ ‫‪٦‬‬

‫ﻋﺩﺩ‬ ‫ﺗﺣﺩﻳﺩ ﻋﺩﺩ ﺍﻟﺻﻣﺎﻣﺎﺕ ﺍﻻﻟﺗﻔﺎﻓﻳﺔ‬ ‫‪٧‬‬

‫‪%‬‬ ‫ﺗﺣﺩﻳﺩ ﻧﺳﺑﺔ ﺗﻐﻳﺭ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻟﻠﻭﺡ‬ ‫‪٨‬‬

‫ﻣﻼﺣﻅﺔ‪ :‬ﺟﻣﻳﻊ ﺍﻟﻣﻧﺣﻧﻳﺎﺕ ﺍﻟﺧﺎﺻﺔ ﺑﻧﻅﺎﻡ ﺍﺳﺗﺧﺩﺍﻡ ﺍﻟﻁﺎﻗﺔ ﺍﻟﺷﻣﺳﻳﺔ ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﻣﺭﻓﻘﺔ ﻣﻊ ﻋﺭﺽ ﺍﻟﻣﺗﻌﻬﺩ‬

‫‪10 | P a g e‬‬
‫ﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻣﻌﺭﺟﺎﺕ )ﺍﻻﻧﻔﺭﺗﻳﺭ( ﺟﺩﻭﻝ ﺭﻗﻡ ‪/٢/‬‬
‫ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻣﻘﺩﻣﺔ‬
‫ﺍﻟﻭﺣﺩﺓ‬ ‫ﺑﻳﺎﻥ ﺍﻟﻣﺎﺩﺓ ﻭﻣﻭﺍﺻﻔﺎﺗﻬﺎ‬ ‫ﺭﻗﻡ‬
‫ﻣﻥ ﻗﺑﻝ ﺍﻟﻌﺎﺭﺽ‬
‫‪-‬‬ ‫ﺗﺣﺩﻳﺩ ﺑﻠﺩ ﺍﻟﻣﻧﺷﺄ ﻭﺍﻟﺷﺭﻛﺔ ﺍﻟﺻﺎﻧﻌﺔ ﻭﺍﻟﻁﺭﺍﺯ‬ ‫‪١‬‬
‫ﺍﻟﻣﻌﺭﺟﺎﺕ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﻘﺎﺑﻝ ﻟﻠﺑﺭﻣﺟﺔ ﻭﺍﻟﺧﺎﺻ ﺔ ﺑﺄﻧﻅﻣﺔ ﺍﻟﻁﺎﻗﺔ‬
‫‪-‬‬ ‫‪٢‬‬
‫ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﻣﺩﺭﺟﺔ ﺑﻣﺿﻣﻭﻧﺎﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ‪.‬‬
‫‪-‬‬ ‫ﻧﻭﻉ ﺍﻟﻣﻌﺭﺝ ‪ outdoor‬ﺃﻡ ‪Indoor‬‬ ‫‪٣‬‬
‫‪-‬‬ ‫ﺧﺭﺝ ﺍﻟﻣﻌﺭﺝ ﺛﻼﺛﻲ ﺍﻟﻁﻭﺭ ﺃﻭ ﺛﻼﺙ ﻣﻌﺭﺟﺎﺕ ﺃﺣﺎﺩﻳﺔ ﺍﻟﻁﻭﺭ‬ ‫‪٤‬‬
‫‪-‬‬ ‫ﺍﻻﻟﺗﺯﺍﻡ ﺑﻣﺟﺎﻝ ﺗﻐﻳﺭ ﺗﺭﺩﺩ ﺧﺭﺝ ﺍﻟﻣﻌﺭﺝ)ﻣﻥ ‪ ٠‬ﺇﻟﻰ ‪ ٥٠‬ﻫﺭﺗﺯ(‬ ‫‪٥‬‬
‫‪%‬‬ ‫ﻣﺭﺩﻭﺩ ﺍﻟﻣﻌﺭﺝ ﻻﻳﻘﻝ ﻋﻥ ‪%٩٥‬‬ ‫‪٦‬‬
‫ﻛﻎ‬ ‫ﺗﺣﺩﻳﺩ ﻭﺯﻥ ﺍﻟﻣﻌﺭﺝ‬ ‫‪٧‬‬
‫ﻣﻠﻡ‬ ‫ﺗﺣﺩﻳﺩ ﺃﺑﻌﺎﺩ ﺍﻟﻣﻌﺭﺝ‬ ‫‪٨‬‬
‫‪-‬‬ ‫ﺗﺣﺩﻳﺩ ﺩﺭﺟﺔ ﺍﻟﺣﻣﺎﻳﺔ ﻟﻠﻣﻌﺭﺝ‬ ‫‪٩‬‬
‫ﻙ‪.‬ﻭﺍﻁ‬ ‫ﺗﺣﺩﻳﺩ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻷﻋﻅﻣﻳﺔ ﻟﺩﺧﻝ ﺍﻟﻣﻌﺭﺝ‬ ‫‪١٠‬‬
‫ﻙ‪.‬ﻭﺍﻁ‬ ‫ﺗﺣﺩﻳﺩ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﻼﺳﻣﻳﺔ ﻟﺧﺭﺝ ﺍﻟﻣﻌﺭﺝ‬ ‫‪١١‬‬
‫ﺩﺭﺟﺔ‬
‫ﻣﺋﻭﻳﺔ‬
‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﺟﺎﻝ ﺍﻟﺣﺭﺍﺭﻱ ﻟﻌﻣﻝ ﺍﻟﻣﻌﺭﺝ‬ ‫‪١٢‬‬
‫‪-‬‬ ‫ﺍﻻﻟﺗﺯﺍﻡ ﺑﺄﻥ ﺗﻛﻭﻥ ﺇﺷﺎﺭﺓ ﺧﺭﺝ ﺍﻟﻣﻌﺭﺟﺎﺕ ﺟﻳﺑﻳﺔ ﻭ ﻧﻘﻳﺔ‬ ‫‪١٣‬‬
‫ﻓﻭﻟﺕ‬ ‫ﺗﺣﺩﻳﺩ ﻣﺟﺎﻝ ﺗﻐﻳﺭ ﺍﻟﺗﻭﺗﺭ ﻟﺩﺧﻝ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭ)‪(DC‬‬ ‫‪١٤‬‬
‫ﻓﻭﻟﺕ‬ ‫ﺗﺣﺩﻳﺩ ﻣﺟﺎﻝ ﺗﻐﻳﺭ ﺍﻟﺗﻭﺗﺭ ﻟﺧﺭﺝ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺗﻧﺎﻭﺏ)‪(AC‬‬ ‫‪١٥‬‬
‫ﺃﻣﺑﻳﺭ‬ ‫ﺗﺣﺩﻳﺩ ﻗﻳﻣﺔ ﺗﻳﺎﺭ ﺍﻟﺧﺭﺝ ﺍﻻﺳﻣﻲ ﻟﻠﻣﻌﺭﺝ‬ ‫‪١٦‬‬
‫ﻋﺩﺩ‬ ‫ﺗﺣﺩﻳﺩ ﻋﺩﺩ ﻣﺩﺍﺧﻝ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭ ﻟﻠﻣﻌﺭﺝ‬ ‫‪١٧‬‬
‫ﻓﻭﻟﺕ‬ ‫ﺗﺣﺩﻳﺩ ﺗﻭﺗﺭ ﺍﻟﺩﺧﻝ ﺍﻷﻋﻅﻣﻲ ﻟﻠﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭ‬ ‫‪١٨‬‬
‫‪-‬‬ ‫ﺗﺣﺩﻳﺩ ﻁﺭﻳﻘﺔ ﺍﻟﺗﺑﺭﻳﺩ ﻟﻠﻣﻌﺭﺝ‬ ‫‪١٩‬‬
‫‪-‬‬ ‫ﺗﺣﺩﻳﺩ ﺷﻬﺎﺩﺍﺕ ﺍﻻﺧﺗﺑﺎﺭ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻟﻣﻌﺭﺝ ﻭ ﺗﻘﺩﻳﻡ ﻧﺳﺧﺔ ﻋﻧﻬﺎ‬ ‫‪٢٠‬‬
‫ﺍﻟﺗﺯﺍﻡ‬ ‫ﺍﻟﻣﻌﺭﺝ ﻣﺯﻭﺩ ﺑﻛﺎﻓﺔ ﺍﻟﺣﻣﺎﻳﺎﺕ ﺍﻟﻣﺫﻛﻭﺭﺓ ﺑﺎﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‬ ‫‪٢١‬‬

‫‪11 | P a g e‬‬
‫ﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻣﺩﺧﺭﺍﺕ ﻟﺯﻭﻡ ﺗﺧﺯﻳﻥ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ ﺟﺩﻭﻝ ﺭﻗﻡ ‪/٣/‬‬

‫ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻣﻘﺩﻣﺔ‬
‫ﺍﻟﻭﺣﺩﺓ‬ ‫ﺑﻳﺎﻥ ﺍﻟﻣﺎﺩﺓ ﻭﻣﻭﺍﺻﻔﺎﺗﻬﺎ‬ ‫ﺭﻗﻡ‬
‫ﻣﻥ ﻗﺑﻝ ﺍﻟﻌﺎﺭﺽ‬

‫‪-‬‬ ‫ﺗﺣﺩﻳﺩ ﺑﻠﺩ ﺍﻟﻣﻧﺷﺄ ﻭﺍﻟﺷﺭﻛﺔ ﺍﻟﺻﺎﻧﻌﺔ‬ ‫‪١‬‬

‫‪-‬‬ ‫ﺍﻟﻣﺩﺧﺭﺍﺕ ﻣﻥ ﺍﻟﻧﻭﻉ ‪GEL‬‬ ‫‪٢‬‬

‫ﺗﺣ ﺩﻳ ﺩ ﺍﻟﻌ ﺩﺩ ﺍﻹﺟﻣ ﺎﻟﻲ ﻟﻠﻣ ﺩﺧﺭﺍﺕ ﻟﺗ ﺄﻣﻳﻥ ﺗﻐ ﺫﻳ ﺔ ﻣﺳ ﺗﻣﺭﺓ‬


‫ﻋﺩﺩ‬ ‫‪٣‬‬
‫ﻟﺣﻣﻝ ﺃﻋﻅﻣﻲ ﺍﺳﺗﻁﺎﻋﺗﻪ ﻻ ﻳﻘﻝ ﻋﻥ )‪(15 KW‬‬

‫‪Ah‬‬ ‫ﺍﻟﺳﻌﺔ ﺍﻹﺟﻣﺎﻟﻳﺔ ﻟﻠﻣﺩﺧﺭﺍﺕ‬ ‫‪٤‬‬

‫‪%‬‬ ‫ﺗﺣﺩﻳﺩ ﻋﻣﻖ ﺍﻟﺗﻔﺭﻳﻎ ﺑﺣﻳﺙ ﻻﻳﺯﻳﺩ ﻋﻥ ‪%٦٠‬‬ ‫‪٥‬‬

‫‪%‬‬ ‫ﻋﺩﺩ ﺩﻭﺭﺍﺕ ﺍﻟﻌﻣﻝ ﻟﻠﻣﺩﺧﺭﺓ ﻋﻧﺩ ﻋﻣﻖ ﺍﻟﺗﻔﺭﻳﻎ ﻻﻳﻘﻝ ﻋﻥ ‪%٥٠‬‬ ‫‪٦‬‬

‫ﺃﻣﺑﻳﺭ‬ ‫ﺗﺣﺩﻳﺩ ﺗﻳﺎﺭ ﺍﻟﺷﺣﻥ ﻟﻠﻣﺩﺧﺭﺓ‬ ‫‪٧‬‬

‫ﺃﻣﺑﻳﺭ‬ ‫ﺗﺣﺩﻳﺩ ﺗﻳﺎﺭ ﺍﻟﺗﻔﺭﻳﻎ ﻟﻠﻣﺩﺧﺭﺓ‬ ‫‪٨‬‬

‫ﺩﺭﺟﺔ ﻣﺋﻭﻳﺔ‬ ‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﺟﺎﻝ ﺍﻟﺣﺭﺍﺭﻱ ﻟﻌﻣﻝ ﺍﻟﻣﺩﺧﺭﺓ‬ ‫‪٩‬‬

‫ﻛﻎ‪/‬ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﺣﺩﻳﺩ ﻭﺯﻥ ﻭﺗﺎﺭﻳﺦ ﺇﻧﺗﺎﺝ ﺍﻟﻣﺩﺧﺭﺓ‬ ‫‪١٠‬‬

‫ﺳﻧﺔ‬ ‫ﺗﺣﺩﻳﺩ ﺍﻟﻌﻣﺭ ﺍﻹﻓﺗﺭﺍﺿﻲ ﻟﻠﻣﺩﺧﺭﺓ‬ ‫‪١١‬‬

‫‪%‬‬ ‫ﺗﺣﺩﻳﺩ ﻋﻣﻖ ﺍﻟﺗﻔﺭﻳﻎ ﺍﻷﻋﻅﻣﻲ ﻟﻠﻣﺩﺧﺭﺓ‬ ‫‪١٢‬‬

‫ﻙ‪.‬ﻭﺍﻁ‬ ‫ﺗﺣﺩﻳﺩ ﺍﻻﺳﺗﻁﺎﻋﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻷﻋﻅﻣﻳﺔ ﻟﺩﺧﻝ ﺍﻟﻣﻌﺭﺝ‬ ‫‪١٣‬‬

‫ﺩﺭﺟﺔ ﻣﺋﻭﻳﺔ‬ ‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﺟﺎﻝ ﺍﻟﺣﺭﺍﺭﻱ ﻟﻌﻣﻝ ﺍﻟﻣﻌﺭﺝ‬ ‫‪١٤‬‬

‫ﺃﻭﻡ‬ ‫ﺗﺣﺩﻳﺩ ﺍﻟﻣﻘﺎﻭﻣﺔ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻟﻠﻣﺩﺧﺭﺓ‬ ‫‪١٥‬‬

‫‪12 | P a g e‬‬
‫‪ -١٠‬ﻣﻭﺍﺻ ﻔﺎﺕ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻ ﻳﻝ ﻟﻭﺣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺭﺋﻳﺳ ﻳﺔ ﺟﺩﺍﺭﻳﺔ ﻳﺩﻭﻳﺔ )ﺷ ﺑﻛﺔ –‬
‫ﻛﻬﺭﻭﺿﻭﺋﻳﺔ(‬
‫ﺷﺭﻭﻁ ﺍﻟﺗﻌﻬﺩ‪:‬‬
‫ﻳﺧﺿ ﻊ ﺍﻟﺗﻌﻬﺩ ﺑﺎﻹﺿ ﺎﻓﺔ ﺇﻟﻰ ﺩﻓﺗﺭ ﺍﻟﺷ ﺭﻭﻁ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺧﺎﺻ ﺔ ﻭﺍﻟﺷ ﺭﻭﻁ ﺍﻟﺣﻘﻭﻗﻳﺔ ﻭﺍﻟﻣﺎﻟﻳﺔ ﺇﻟﻰ ﺍﻟﻌﺭﺽ ﺍﻟﻔﻧﻲ ﻭﺍﻟﻛﺗﺎﻟﻭﻛﺎﺕ ﻭﻛﺎﻓﺔ ﺍﻟﻧﺷ ﺭﺍﺕ‬
‫ﺍﻟﻔﻧﻳﺔ ﻭﺍﻟﻭﺛﺎﺋﻖ ﺍﻟﻣﻘﺩﻣﺔ ﻣﻊ ﺍﻟﻌﺭﺽ ﻣﻭﺿﻭﻉ ﺍﻟﺗﻌﻬﺩ ﻭﻳﺗﻡ ﺗﻘﺩﻳﻡ ﺍﻟﻌﺭﺽ ﺍﻟﻔﻧﻲ ﻣﻊ ﺑﻳﺎﻥ ﺍﻟﻣﻌﻠﻭﻣﺎﺕ ﻭﻓﻖ ﻣﺎ ﻳﻠﻲ ‪:‬‬
‫ﻳﺟﺏ ﺗﻘﺩﻳﻡ ﺍﻟﻧﺷ ﺭﺍﺕ ﺍﻟﻔﻧﻳﺔ ﻭﺍﻟﻛﺎﺗﻠﻭﻛﺎﺕ ﻭﺍﻟﻭﺛﺎﺋﻖ ﻭﺍﻟﺷ ﻬﺎﺩﺍﺕ ﻣﺑﻳﻧﺎ ً ﻋﻠﻳﻬﺎ ﺑﺷ ﻛﻝ ﻭﺍﺿ ﺢ ﻛﺎﻓﺔ ﺍﻟﻣﻌﻠﻭﻣﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺣﺳ ﺏ ﻣﺎ ﻫﻭ‬ ‫‪-‬‬
‫ﻭﺍﺭﺩ ﺑﺩﻓﺗﺭ ﺍﻟ ﺷﺭﻭﻁ ﺍﻟﻔﻧﻳﺔ ﻟﻛﺎﻓﺔ ﺍﻟﻣﻛﻭﻧﺎﺕ ﺍﻷ ﺳﺎ ﺳﻳﺔ ﻟﻠﻭﺣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ‪ ،‬ﻭﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺍﻟﻣﻌﻠﻭﻣﺎﺕ ﻭﺍﻟﻣﻭﺍ ﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﻭﺍﺭﺩﺓ‬
‫ﺿﻣﻥ ﺍﻟﻌﺭﺽ ﺍﻟﻔﻧﻲ ﻟﻠﻌﺎﺭﺽ ﻣﻁﺎﺑﻘﺔ ﻟﻠﻣﻌﻠﻭﻣﺎﺕ ﻭﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻭﺍﺭﺩﺓ ﺑﺎﻟﻧﺷﺭﺍﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻷﺳﺎﺳﻳﺔ ﻭﺍﻟﺗﻔﺻﻳﻠﻳﺔ ‪.‬‬
‫ﻳﺗﻌﻬﺩ ﺍﻟﻌﺎﺭﺽ ﺧﻁﻳﺎ ً ﻓﻲ ﻋﺭﺿﻪ ﺑﺗﻘﺩﻳﻡ ﻧﺷﺭﺍﺕ ﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺻﻳﺎﻧﺔ ﻭﺍﻻﺳﺗﺛﻣﺎﺭ ﻋﻧﺩ ﺍﻟﺗﺭﺳﻳﺔ ﺃﻭ ﺍﻟﺗﻭﺭﻳﺩ ‪.‬‬ ‫‪-‬‬
‫)ﻫﺎﻡ ﺟﺩﺍً(‪ :‬ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺍﻟﻠﻭﺣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻭﻛﺎﻓﺔ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻣﻠﺣﻘﺔ ﺑﻬﺎ ﻣﻥ ﺍﻟﻧﻭﻉ ﺫﻭ ﺍﻟﺟﻭﺩﺓ ﺍﻷﻋﻠﻰ ﻭﺍﻟﺩﺭﺟﺔ ﺍﻷﻭﻟﻰ ﻓﻧﻳﺎ ً‬
‫ﻭﺍﻟﻌﻣﺭ ﺍﻟﻔﻧﻲ ﺍﻷﻁﻭﻝ‪High Durability &high quality specifications and first technical Class‬‬
‫ﻣﻥ ﺃﺟﻝ ﺍﻟﺣﻔﺎﻅ ﻋﻠﻰ ﻧﻅﺎﻡ ﺗﺷﻐﻳﻝ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻣﺿﻣﻭﻥ ﺍﻟﻣﺷﺭﻭﻉ ﺍﻟﻣﺫﻛﻭﺭ ﺑﺻﻭﺭﺓ ﺧﺎﻟﻳﺔ ﻣﻥ ﺍﻷﻋﻁﺎﻝ‪.‬‬ ‫‪-‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﻛﺎﻓﺔ ﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻠﻭﺣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺟﺩﻳﺩﺓ ﻭﻏﻳﺭ ﻣﺟﺩﺩﺓ ‪ ,‬ﻣﻊ ﺑﻳﺎﻥ ﺳﻧﺔ ﺍﻟﺻﻧﻊ ﺑﺷﻛﻝ ﻭﺍﺿﺢ ‪.‬‬ ‫‪-‬‬
‫ﻳﻔﺿﻝ ﺃﻥ ﺗﻛﻭﻥ ﺍﻟﻠﻭﺣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻭﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺭﺋﻳﺳﻳﺔ ﻣﻥ ﻧﻔﺱ ﺍﻟﻣﺎﺭﻛﺔ ﻭﺍﻟﻣﻧﺷﺄ ﻟﻛﺎﻓﺔ ﺍﻟﺑﻧﻭﺩ‪.‬‬ ‫‪-‬‬

‫ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ‪:‬‬
‫ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺗﻘﺩﻳﻡ ﺍﻟﻠﻭﺣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺭﺋﻳﺳ ﻳﺔ ﺑﺣﻳﺙ ﺗﻛﻭﻥ ﻗﺎﺑﻠﺔ ﻟﻠﺗﺭﻛﻳﺏ ﺟﺩﺍﺭﻳﺎ ً ﻟﺗﺄﻣﻳﻥ ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻟﻠﻭﺣﺎﺕ ﺍﻟﺛﺎﻧﻭﻳﺔ‬
‫ﻋﻥ ﻁﺭﻳﻖ ﻛﺎﺑﻼﺕ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺗﻭﺻ ﻝ ﺑﺎﻟﻣﺧﺎﺭﺝ ﺍﻟﺧﺎﺻ ﺔ ﺑﺎﻟﻠﻭﺣﺔ ﺍﻟﺭﺋﻳﺳ ﻳﺔ ﻭﻣﻧﻬﺎ ﺇﻟﻰ ﺍﻟﻠﻭﺣﺎﺕ ﺍﻟﺛﺎﻧﻭﻳﺔ ﺍﻟﺟﺩﺍﺭﻳﺔ ﻭﻟﻭﺣﺎﺕ‬
‫)ﺍﻹﻧﺎﺭﺓ ﻭﺍﻟﻣﺂﺧﺫ ﻭﺍﻟﺧﺩﻣﺎﺕ( ﻭﻋﻠﻰ ﺍﻟﻌـــﺎﺭﺽ ﺑﻳـــﺎﻥ ﻣﺎﺭﻛﺔ ﻭﺑﻠﺩ ﺍﻟﺻﻧﻊ ﻭﺍﻟﺗﺟﻣﻳﻊ ﻟﻠﻭﺣـــﺔ ﻭﻛﺫﻟﻙ ﻣﺎﺭﻛﺔ ﻭﺑﻠﺩ ﺍﻟﻣﻧﺷﺄ ﻟﻠﻘﻭﺍﻁﻊ‬
‫ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻭﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﺍﻷﺳﺎﺳﻳﺔ ﺍﻟﻣﻛﻭﻧﺔ ﻟﻠﻭﺣﺔ ﻭﺑﻳﺎﻥ ﻛﺎﻓﺔ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻟﻠﻠﻭﺣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺣﺳﺏ ﻣﺎ ﻳﻠﻲ‪:‬‬

‫‪ -١‬ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﺗﺻﻣﻳﻣﻳﺔ ﺍﻟﻌﺎﻣﺔ ﻭﺍﻷﺳﺎﺳﻳﺔ ﻟﻠﻭﺣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺭﺋﻳﺳﻳﺔ ﺍﻟﺟﺩﺍﺭﻳﺔ‪:‬‬


‫ﺗ ﺻﻣﻡ ﺍﻟﻠﻭﺣﺔ ﻭﻓﻖ ﺍﻟﻣﻭﺍ ﺻﻔﺎﺕ ﻭﺍﻟﻧﻅﻡ ﺍﻟﻌﺎﻟﻣﻳﺔ ﻭﺗ ﺻﻧﻊ ﺍﻟﻠﻭﺣﺔ ﻣﻥ ﺻﻔﺎﺋﺢ ﺍﻟﻔﻭﻻﺫ ﺑﺎﻟ ﺳﻣﺎﻛﺔ ﺍﻟﻣﻧﺎ ﺳﺑﺔ ﺑﺣﺩﻭﺩ )‪٢‬ﻣﻡ( ‪ ،‬ﻭﻣﺩﻋﻣﺔ‬ ‫‪-‬‬
‫ﺑﺑﺭﻭﻓﻳﻝ ﻣﻧﺎﺳ ﺏ ﻭﻫﻲ ﻣﻐﻠﻘﺔ ﻣﻥ ﺍﻟﺟﻭﺍﻧﺏ ﻭﺍﻟﺧﻠﻑ ‪،‬ﻭﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﺟﺩﺍﺭﻳﺔ ﻭﺗﻛﻭﻥ ﻣﻔﺗﻭﺣﺔ ﻣﻥ ﺍﻷﺳ ﻔﻝ ﻟﺩﺧﻭﻝ ﺍﻟﻛﺎﺑﻼﺕ‬
‫ﻭﻳﻔﺿ ﻝ ﺃﻥ ﺗﻛﻭﻥ ﻣﻐﻠﻘﺔ ﺑﻐﻁﺎء ﺳ ﻔﻠﻲ ﻣﺯﻭﺩ ﺑﻔﺗﺣﺎﺕ ﻣﻧﺎﺳ ﺑﺔ ﺃﻭ ﺣﻠﻘﺎﺕ ﺇﺣﻛﺎﻡ ﻟﺩﺧﻭﻝ ﺍﻟﻛﺎﺑﻼﺕ ﻭﻣﻧﻊ ﺩﺧﻭﻝ ﺍﻷﺟﺳ ﺎﻡ ﺍﻟﻐﺭﻳﺑﺔ‬
‫ﻭﺗﻛﻭﻥ ﺍﻟﻠﻭﺣﺔ ﻣﺩﻫﻭﻧﺔ ﺑﺎﻟﺩﻫﺎﻥ ﺍﻹﻟﻛﺗﺭﻭﺳﺗﺎﺗﻳﻙ ﺑﻁﺭﻳﻘﺔ ﺍﻟﺑﺦ ﻭﺍﻟﺷﻭﻱ ﺣﻳﺙ ﻳﺻﺑﺢ ﺍﻟﺩﻫﺎﻥ ﻣﺗﻣﺎﺳﻙ ﻣﻊ ﻣﻌﺩﻥ ﺍﻟﻠﻭﺣﺔ ﻭﻏﻳﺭ ﻗﺎﺑﻝ‬
‫ﻟﻠﺗﻘﺷﺭ)ﻭﻳﻔﺿﻝ ﺗﻘﺩﻳﻡ ﻣﺧﻁﻁ ﺑﺄﺑﻌﺎﺩ ﻭﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻠﻭﺣﺔ ﺿﻣﻥ ﺍﻟﻌﺭﺽ ﺍﻟﻔﻧﻲ(‬
‫ﻳﺟﻬﺯ ﺑﺎﺏ ﺍﻟﻠﻭﺣﺔ ﺑﺟﻭﺍﻧﺎﺕ ﻟﻣﻧﻊ ﺩﺧﻭﻝ ﺍﻟﻐﺑﺎﺭ ﻭﻗﺑﺿﺎﺕ ﻣﻌﺩﻧﻳﺔ ﻭﻗﻔﻝ ﻟﻔﺗﺢ ﺍﻟﺑﺎﺏ‪,‬ﻛﻣﺎ ﺗﺟﻬﺯ ﺑﺣﻠﻘﺎﺕ ﻣﻌﺩﻧﻳﺔ ﺑﺄﻋﻠﻰ ﺍﻟﻠﻭﺣﺔ ﺑﻣﻘﻁﻊ‬
‫ﻣﻧﺎﺳﺏ ﻟﺣﻣﻝ ﺍﻟﻠﻭﺣﺔ ‪.‬‬

‫‪13 | P a g e‬‬
‫ﻭﻳﺟﺏ ﺃﻥ ﺗﺗﺣﻣﻝ ﺟﻣﻳﻊ ﻅﺭﻭﻑ ﺍﻟﻧﻘﻝ ﻭﺍﻟﺗﺣﻣﻳﻝ ﻭﺍﻟﺗﻧﺯﻳﻝ ﻭﺍﻟﺗﺭﻛﻳﺏ ﻭﺍﻟﺗﻭﺻ ﻳﻝ ﻭﺍﻟﺗﺷ ﻐﻳﻝ ﺩﻭﻥ ﺣﺩﻭﺙ ﺍﻟﺗﻭﺍءﺍﺕ ﺃﻭ ﺗﺷ ﻭﻫﺎﺕ‬ ‫‪-‬‬
‫ﺃﻭﺻﺩﺃ ‪.‬‬
‫ﺗﻭﺯﻉ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻅﺎﻫﺭﺓ ﻋﻠﻰ ﻭﺍﺟﻬﺔ ﺍﻟﻠﻭﺣﺔ ﻭﺗﺭﻛﺏ ﺣﺳ ﺏ ﺍﻟﺷ ﺭﻭﻁ ﻭﺍﻹﺻ ﻭﻝ ﺍﻟﻔﻧﻳﺔ ﺑﺣﻳﺙ ﺗﻅﻬﺭ ﻣﻥ ﻭﺍﺟﻬﺔ ﺍﻟﻠﻭﺣﺔ‬ ‫‪-‬‬
‫ﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻣﺭﺍﻗﺑﺔ ﻭﺍﻟﺗﺣﻛﻡ ﻟﻠﻭﺣﺔ )ﻟﻣﺑﺎﺕ ﺍﻻﺷ ﺎﺭﺓ ‪ -‬ﺍﻟﻣﻔﺎﺗﻳﺢ ﻭﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻘﻳﺎﺱ ﺍﻟﻣﺧﺗﻠﻔﺔ( ‪ ،‬ﻭﺗﻛﻭﻥ ﻭﺍﺿ ﺣﺔ ﻟﻠﻣﺭﺍﻗﺑﺔ‬
‫ﻭﺍﻟﺗﺷﻐﻳﻝ‪.‬‬
‫ﺗﻭﺯﻉ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﺗﺭﻛﺏ ﺩﺍﺧﻝ ﺍﻟﻠﻭﺣﺔ ﻋﻠﻰ ﻫﻳﺋﺔ ﺻ ﻔﻭﻑ ﺃﻭ ﺃﻋﻣﺩﺓ ﻣﺗﻭﺍﺯﻳﺔ ﻭﺗﺛﺑﺕ ﻋﻠﻰ ﺳ ﻛﻙ ﻣﺑﺎﺷ ﺭﺓ ﺃﻭ ﺑﻭﺍﺳ ﻁﺔ‬ ‫‪-‬‬
‫ﻗﺎﻋﺩﺓ ﺧﺎﺻ ﺔ ﺣﺳ ﺏ ﺍﻟﻠﺯﻭﻡ‪ ،‬ﻭﻳﺗﻡ ﺗﺭﻛﻳﺏ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﺩﺍﺧﻝ ﺍﻟﻠﻭﺣﺔ ﺑﺗﺑﺎﻋﺩ ﻛﺎﻑ ﻭﺑﺷ ﻛﻝ ﻣﺭﻳﺢ ﻳﺳ ﻣﺢ ﺑﺎﻟﺻ ﻳﺎﻧﺔ ﻭﺍﻟﺗﻭﺳ ﻊ‬
‫ﺍﻟﻣﺳﺗﻘﺑﻠﻲ‪.‬‬
‫ﺗﻛﻭﻥ ﺃﺑﻌﺎﺩ ﺍﻟﻠﻭﺣﺔ ﺑﻣﺎ ﻳﻧﺎﺳﺏ ﺗﻭﻓﺭ ﻓﺭﺍﻏﺎﺕ ﻣﻧﺎﺳﺑﺔ ﺩﺍﺧﻝ ﺍﻟﻠﻭﺣﺔ ﻻﺗﻘﻝ ﻋﻥ ‪ %٢٠‬ﻭﺣﺳﺏ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻘﻳﺎﺳﻳﺔ‪.‬‬ ‫‪-‬‬
‫ﺗﻣﺩﺩ ﺍﻟﺗﻭﺻ ﻳﻼﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺍﻟﺧﺎﺻ ﺔ ﺑﺩﺍﺭﺓ ﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻘﻳﺎﺱ ﻭﺍﻟﻣﺭﺍﻗﺑﺔ ﻭﺍﻟﺗﺣﻛﻡ ﻟﻠﻭﺣﺔ ﺿ ﻣﻥ ﻣﺟﺎﺭﻱ ﺑﻼﺳ ﺗﻳﻛﻳﺔ ﻧﻅﺎﻣﻳﺔ ﻭﺗﻛﻭﻥ‬ ‫‪-‬‬
‫ﺍﻷﺳﻼﻙ ﻣﻣﺩﺓ ﺑﺷﻛﻝ ﻣﺗﻭﺍﺯﻱ ﻋﻠﻰ ﻁﻭﻝ ﺍﻟﻣﺟﺭﻯ ﻭﺧﺎﺭﺝ ﺍﻟﻣﺟﺭﻯ ﻭﻣﺣﺯﻣﺔ ﺑﺣﺯﺍﻣﺎﺕ ﺑﻼﺳﺗﻳﻛﻳﺔ ﺑﺷﻛﻝ ﻓﻧﻲ‪.‬‬
‫ﺗﺟﻬﺯ ﺍﻟﻠﻭﺣﺔ ﺑﻔﺗﺣﺎﺕ ﻧﻅﺎﻣﻳﺔ ﻭﻣﻧﺎﺳﺑﺔ ﻟﺩﺧﻭﻝ ﻛﺎﺑﻼﺕ ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻟﻠﻭﺣﺔ ﻭﺧﺭﻭﺝ ﺍﻟﻛﺎﺑﻼﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ‪.‬‬ ‫‪-‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﻛﺎﺑﻼﺕ ﻭﺃﺳﻼﻙ ﺍﻟﺗﻭﺻﻳﻝ ﺍﻟﺩﺍﺧﻠﻲ ﻧﺣﺎﺳﻳﺔ ﻣﻌﺯﻭﻟﺔ ﻭﺑﻣﻘﺎﻁﻊ ﻣﻧﺎﺳﺑﺔ‪ .‬ﻭﺍﺳﺗﺧﺩﺍﻡ ﻋﺩﺓ ﺃﻟﻭﺍﻥ ﻣﻭﺣﺩﺓ ﻣﻥ ﺍﻷﺳﻼﻙ ‪.‬‬ ‫‪-‬‬
‫ﻛﺎﻓﺔ ﺃﻁﺭﺍﻑ ﺃﺳ ﻼﻙ ﻭﻛﺎﺑﻼﺕ ﺍﻟﺗﺣﻛﻡ )ﺑﺷ ﻛﻝ ﺩﺑﻭﺱ ﺃﻭﺷ ﻭﻛﺔ( ﺗﺟﻬﺯ ﺑﺟﻧﻛﺳ ﻳﻭﻧﺎﺕ ﻭﺻ ﻝ ﻧﻅﺎﻣﻳﺔ ‪Cable Terminal‬‬ ‫‪-‬‬
‫‪ /Extensions/‬ﻟﻠﻭﺻ ﻝ ﻣﻊ ﻛﺎﺑﻼﺕ ﺍﻟﺗﺣﻛﻡ ﺍﻟﺧﺎﺭﺟﻳﺔ ﻭﺗﺭ ّﻣﺯ ﻭﺗﺭﻗّﻡ ﺑﺎﻟﺗﻭﺍﻓﻖ ﻭﺍﻟﺗﻁﺎﺑﻖ ﻣﻊ ﺍﻟﻣﺧﻁﻁ ﺍﻟﺗﺻ ﻣﻳﻣﻲ ﻭﺍﻟﺗﻧﻔﻳﺫﻱ‬
‫ﻟﺩﺍﺭﺓ ﺍﻟﺗﺣﻛﻡ‪.‬‬
‫ﺗﺟﻬﺯ ﺍﻟﻠﻭﺣﺔ ﺑﻠﻭﺣﺎﺕ ﺇﺳﻣﻳﺔ ﻟﻠﺗﺟﻬﻳﺯﺍﺕ ﺧﺎﺭﺝ ﻭﺩﺍﺧﻝ ﺍﻟﻠﻭﺣﺔ ﻭﻳﻠﺻﻖ ﺍﻟﻣﺧﻁﻁ ﺍﻟﺗﺻﻣﻳﻣﻲ ﻭﺍﻟﺗﻧﻔﻳﺫﻱ ﻟﺩﺍﺭﺓ ﺍﻟﺗﺣﻛﻡ ﺩﺍﺧﻝ ﺍﻟﻠﻭﺣﺔ‬ ‫‪-‬‬
‫ﺑﻁﺭﻳﻘﺔ ﻓﻧﻳﺔ ﻏﻳﺭ ﻗﺎﺑﻠﺔ ﻟﻠﺗﻠﻑ‪.‬‬
‫‪ -‬ﻳﻔﺿ ﻝ ﺃﻥ ﺗﺟﻬﺯ ﺍﻟﻠﻭﺣﺔ ﺑﺑﺎﺭﺍﺕ ﻣﺩﺧﻝ ﻟﻭﺻ ﻝ ﻛﺎﺑﻼﺕ ﺍﻟﺗﻐﺫﻳﺔ ﻣﻥ ﺍﻟﺷ ﺑﻛﺔ ﺍﻟﻌﺎﻣﺔ ﻭﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﻭﺿ ﻭﺋﻳﺔ ﻭﻁﻘﻡ ﺑﺎﺭﺍﺕ‬
‫ﻣﺧﺭﺝ ﻟﻭﺻ ﻝ ﻗﻭﺍﻁﻊ ﺍﻟﻣﺧﺎﺭﺝ ﻟﻠﻭﺣﺔ ﺣﻳﺙ ﻳﻠﺯﻡ ﺍﻟﻌﻣﻝ ﺍﻟﻔﻧﻲ‪ ،‬ﻭﻛﺫﻟﻙ ﻳﺟﺏ ﺃﻥ ﺗﺟﻬﺯ ﺍﻟﻠﻭﺣﺔ ﺑﻣﺂﺧﺫ ﺃﻭ ﺟﻧﻛﺳ ﻳﻭﻧﺎﺕ ﻭﺻ ﻝ ﺑﻌﺩﺩ‬
‫ﻗﻭﺍﻁﻊ ﺍﻟﻣﺧﺎﺭﺝ ﻟﻭﺻ ﻝ ﻛﺎﺑﻼﺕ ﺗﻐﺫﻳﺔ ﺍﻟﻠﻭﺣﺎﺕ ﺍﻟﺛﺎﻧﻭﻳﺔ ‪ ,‬ﻭﺗﻛﻭﻥ ﺑﺎﺭﺍﺕ ﺍﻟﻣﺩﺍﺧﻝ ﻭﺍﻟﻣﺧﺎﺭﺝ ﻧﺣﺎﺳ ﻳﺔ ﻭﻣﻁﺎﺑﻘﺔ ﻟﻠﻣﻭﺍﺻ ﻔﺎﺕ‬
‫ﺍﻟﻘﻳﺎﺳﻳﺔ ﻭﻧﻭﻋﻳﺔ ﺍﻟﻧﺣﺎﺱ ﺃﻭﺭﺑﻲ ﺇﻟﻛﺗﺭﻭﻟﻳﺗﻲ‪ ،‬ﻭﻳﻔﺿﻝ ﺃﻥ ﻳﻛﻭﻥ ﻣﻘﻁﻊ ﺍﻟﺑﺎﺭﺍﺕ ﻳﺣﻘﻖ ﻛﺛﺎﻓﺔ ﺗﻳﺎﺭ ﻻ ﺗﺯﻳﺩ ﻋﻥ )‪ ١٫٥‬ﺃﻣﺑﻳﺭ‪/‬ﻣﻠﻡ‪(٢‬‬
‫ﻣﻊ ﺗﺣﺩﻳﺩ ﺃﺑﻌﺎﺩ ﻣﻘﺎﻁﻊ ﺍﻟﺑﺎﺭﺍﺕ ﺣﺳﺏ ﺍﺳﺗﻁﺎﻋﺔ ﺍﻟﻠﻭﺣﺔ‪ ،‬ﻭﺗﺟﻬﺯ ﺍﻟﻠﻭﺣﺔ ﺑﺑﺎﺭ ﺍﻟﻧﺗﺭ ﻭﺑﺎﺭ ﺗﺄﺭﻳﺽ ﻧﺣﺎﺳﻲ ﺑﺷﻛﻝ ﻣﻧﻔﺻﻝ ﻭﺑﻣﻘﻁﻊ‬
‫ﻣﺳﺎﻭﻱ ﻟﺑﺎﺭ ﺍﻟﻧﺗﺭ ﻭﻻ ﻳﻘﻝ ﻋﻥ ﻧﺻﻑ ﻣﻘﻁﻊ ﺑﺎﺭ ﺍﻟﻔﺎﺯ ﻭﻳﺛﺑﺕ ﺍﻟﻧﺗﺭ ﻋﻠﻰ ﻋﻭﺍﺯﻝ ﻭﺗﺟﻬﺯ ﻛﺎﻓﺔ ﺍﻟﺑﺎﺭﺍﺕ ﺑﻣﺭﺍﺑﻁ ﻣﻥ ﺃﺟﻝ ﺍﻟﺗﻭﺻﻳﻝ‬
‫ﻋﻠﻳﻬﺎ‪ ،‬ﻭﻳﺗﻡ ﺗﻌﻠﻳﻡ ﺃﻭ ﺗﻐﻠﻳﻑ ﺍﻟﺑﺎﺭﺍﺕ ﻭﺭﺅﻭﺱ ﺍﻟﻛﺎﺑﻼﺕ ﺑﻼﺻﻖ ﺣﺭﺍﺭﻱ ﻣﻠﻭﻥ ﺣﺳﺏ ﺗﺳﻠﺳﻝ ﺍﻟﺳﺗﺎﻧﺩﺭ ﺍﻟﻌﺎﻟﻣﻲ‪ ,‬ﻣﻊ ﻭﺟﻭﺩ ﺃﻣﺎﻛﻥ‬
‫ﺗﺛﺑﻳﺕ ﻭﺗﻌﻠﻳﻖ ﺿﻣﻥ ﺍﻟﻠﻭﺣﺎﺕ ﻟﻠﻛﺎﺑﻼﺕ ﺗﺿﻣﻥ ﻋﺩﻡ ﺗﺣﻣﻳﻝ ﻭﺯﻥ ﺍﻟﻛﺎﺑﻝ ﻋﻠﻰ ﺍﻟﺑﺎﺭﺍﺕ‪.‬‬

‫‪14 | P a g e‬‬
‫‪ -٢‬ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻟﻠﻭﺣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺭﺋﻳﺳﻳﺔ‪ /‬ﺷﺑﻛﺔ ‪ -‬ﻛﻬﺭﻭﺿﻭﺋﻳﺔ ‪: /‬‬
‫ﻋﻠﻰ ﺍﻟﻌﺎﺭﺽ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻ ﻳﻝ ﻭﺗﺷ ﻐﻳﻝ ﻟﻭﺣﺔ ﺗﻐﺫﻳﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺭﺋﻳﺳ ﻳﺔ ﻭﺍﺣﺩﺓ )ﺷ ﺑﻛﺔ – ﻛﻬﺭﻭﺿ ﻭﺋﻳﺔ( ﺟﺩﺍﺭﻳﺔ ﻟﻠﺗﺑﺩﻳﻝ‬
‫ﺍﻟﻳﺩﻭﻱ ﻟﺟﻬﺔ ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﻳﻥ ﺍﻟﻛﻬﺭﺑﺎء )ﺍﻟﺷﺑﻛﺔ ﺍﻟﻌﺎﻣﺔ ‪ -‬ﺍﻟﻣﻭﻟﺩﺓ( ﻭ )ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ( ﻭﻣﺯﻭﺩﺓ ﺑﻘﺎﻁﻊ ﺗﺑﺩﻳﻝ‬
‫ﻳﺩﻭﻱ )ﻓﺻﻝ – ﺗﺷﻐﻳﻝ( ﻟﺧﺭﺝ ﺍﻟﻣﺳﺗﻭﺻﻑ ‪ -‬ﻋﻳﺎﺭ ‪ ٦٣‬ﺃﻣﺑﻳﺭ ﻣﻥ ﺃﺟﻭﺩ ﺍﻟﻣﺎﺭﻛﺎﺕ ﺍﻟﻌﺎﻟﻣﻳﺔ )‪.....ABB,Eaton‬ﺃﻭ ﻣﺎﻳﻌﺎﺩﻟﻬﺎ(‬
‫ﻭﻣﺯﻭﺩﺓ ﺑﻣﺣﻠﻝ ﺷﺑﻛﺔ ﻭﻟﻣﺑﺎﺕ ﺇﺷﺎﺭﺓ‪.....‬ﺍﻟﺦ – ﻭﻓﻘﺎ ﻟﻠﻣﺧﻁﻁ ﺍﻟﺗﺎﻟﻲ‪:‬‬

‫‪ -١١‬ﺗﻘﺩﻳﻡ ﻭﺗﻧﻔﻳﺫ ﻭﺗﻭﺻ ﻳﻝ ﻧﻅﺎﻡ ﺷ ﺑﻛﺔ ﺗﺄﺭﻳﺽ ﻣﻊ ﻛﻝ ﻣﺎﻳﻠﺯﻡ ﻣﻥ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﺃﻣﺭﺍﺱ‬
‫ﻭﻛﺎﺑﻼﺕ ﻭﺃﻭﺗﺎﺩ‬
‫ﻳﺗﻡ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻ ﻳﻝ ﺷ ﺑﻛﺔ ﺗﺄﺭﻳﺽ ﻟﺯﻭﻡ ﺃﻋﻣﺎﻝ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﺣﻳﺙ ﺗﺣﻘﻖ ﺍﻟﺷ ﺑﻛﺔ ﻣﻘﺎﻭﻣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﻻ ﺗﺗﺟﺎﻭﺯ ‪/٣/‬‬
‫ﺃﻭﻡ ﻭﺗﺗﻛﻭﻥ ﺷ ﺑﻛﺔ ﺍﻟﺗﺄﺭﻳﺽ ﻣﻥ ﺑﺋﺭ ﺗﺄﺭﻳﺽ ﺭﺋﻳﺳ ﻲ ﻋﺩﺩ ‪ /١/‬ﻭﺃﻭﺗﺎﺩ ﺗﺄﺭﻳﺽ ﻣﺳ ﺎﻋﺩﺓ ﻋﺩﺩ ‪ /٢/‬ﺑﻣﺳ ﺎﻓﺔ ﺑﻳﻧﻬﺎ ﻻﺗﻘﻝ ﻋﻥ ‪٤‬ﻡ‪،‬‬
‫ﻭﻳﻣﻛﻥ ﺯﻳﺎﺩﺓ ﻋﺩﺩ ﺍﻷﻭﺗﺎﺩ ﺍﻟﻣﺳﺎﻋﺩﺓ ﺣﺗﻰ ﺗﺣﻘﻖ ﺍﻟﻣﻘﺎﻭﻣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﻣﻁﻠﻭﺑﺔ‪.‬‬

‫ﻭﺗﻛﻭﻥ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﻟﺷﺑﻛﺔ ﺍﻟﺗﺄﺭﻳﺽ ﺑﺎﻟﺣﺩ ﺍﻷﺩﻧﻰ ﻛﻣﺎ ﻳﻠﻲ‪:‬‬


‫ﻳﺗﻡ ﺗﺣﺩﻳﺩ ﻣﻭﺍﻗﻊ ﺑﺋﺭ ﺍﻟﺗﺄﺭﻳﺽ ﺍﻟﺭﺋﻳ ﺳﻲ ﻭﺍﻷﻭﺗﺎﺩ ﺍﻟﻣ ﺳﺎﻋﺩﺓ ﺑﻣﻭﺍﻓﻘﺔ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﻭﺗﻔ ﺿﻝ ﺍﻟﻣﻭﺍ ﺿﻊ ﺍﻟﻘﺭﻳﺑﺔ ﻣﻥ ﻗﻧﺎﺓ ﻭﻣ ﺳﺎﺭﺍﺕ‬ ‫‪‬‬
‫ﺍﻟﻛﺎﺑﻼﺕ ﻭﻓﻲ ﺍﻟﻣﻭﺍﻗﻊ ﺍﻟﺗﺭﺍﺑﻳﺔ ﻭﻳﺗﻡ ﺗﺛﺑﻳﺕ ﺗﻠﻙ ﺍﻟﻣﻭﺍﻗﻊ ﻋﻠﻰ ﺍﻟﻣﺧﻁﻁﺎﺕ‪.‬‬
‫ﺟﻭﺭﺓ ﺗﻔﺗﻳﺵ ﺑﻳﺗﻭﻧﻳﺔ ﺑﺄﺑﻌﺎﺩ ﺩﺍﺧﻠﻳﺔ ﻻ ﺗﻘﻝ ﻋﻥ )‪٤٠×٤٠×٤٠‬ﺳﻡ( ﻭﺑﻐﻁﺎء ﺑﻳﺗﻭﻧﻲ ﺃﻭ ﻓﻭﻧﺕ ﺃﻭ ﻣﻌﺩﻧﻲ ﻣﺯﻭﺩ ﺑﻘﺑﺿﺔ ﻟﺭﻓﻌﻪ‪.‬‬ ‫‪‬‬
‫ﻭﺗﺩ ﻣﻥ ﺍﻟﻧﺣﺎﺱ ﺑﻘﻁﺭ ‪ ٢٥‬ﻣﻡ ﻭﻁﻭﻝ ﻻ ﻳﻘﻝ ﻋﻥ ‪ ٢‬ﻡ ﺑﺫﻳﻝ ﺳﻔﻠﻲ ﻣﺩﺑﺏ‪.‬‬ ‫‪‬‬

‫‪15 | P a g e‬‬
‫ﻛﻭﻟﻳﺔ ﺍﻟﺭﺑﻁ ﺑﻳﻥ ﺭﺃﺱ ﺍﻟﻭﺗﺩ ﻭﺃﻣﺭﺍﺱ ﺍﻟﺗﺄﺭﻳﺽ ﻭﻳﻔﺿ ﻝ ﺃﻥ ﺗﻛﻭﻥ ﻣﻥ ﺻ ﻔﺎﺋﺢ ﺍﻟﻧﺣﺎﺱ ﺃﻭ ﺍﻟﻘﺻ ﺩﻳﺭ ﻭﺫﺍﺕ ﺳ ﻣﺎﻛﺔ ﻻ ﺗﻘﻝ ﻋﻥ‬ ‫‪‬‬
‫‪/٦/‬ﻣﻡ‪.‬‬
‫ﺍﻟﺗﻌﺑﺋﺔ ﺑﺎﻟﺭﻣﻝ ﺍﻟﻧﺎﻋﻡ ﻭﻳﻔﺿﻝ ﻣﻊ ﺍﻟﻣﻭﺍﺩ ﺍﻟﻼﺯﻣﺔ ﻟﺣﻔﺭﺓ ﺍﻟﺗﺄﺭﻳﺽ ﻭﺣﺩﻭﺩ ﺍﻟﺗﻌﺑﺋﺔ ﻟﻣﺳﺗﻭﻯ ﺃﺩﻧﻰ ﻣﻥ ﻣﺳﺗﻭﻯ ﻭﺻﻝ ﺍﻷﻣﺭﺍﺱ‪.‬‬ ‫‪‬‬
‫ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﺃﻣﺭﺍﺱ ﺍﻟﺗﻭﺻ ﻳﻝ ﻭﻫﻲ ﺑﻳﻥ ﺭﺃﺱ ﺍﻟﻭﺗﺩ ﺍﻟﻌﻠﻭﻱ ﺑﺑﺋﺭ ﺍﻟﺗﺄﺭﻳﺽ ﺍﻟﺭﺋﻳﺳ ﻲ ﻭﺭﺅﻭﺱ ﺍﻷﻭﺗﺎﺩ ﺍﻟﻣﺳ ﺎﻋﺩﺓ ﻭﻛﺫﻟﻙ ﻣﻊ‬ ‫‪‬‬
‫ﻣﺭﺑﻁ ﺍﻟﺗﻭﺻ ﻳﻝ ﻋﻠﻰ ﺑﺎﺭ ﺍﻟﺗﺄﺭﻳﺽ ﺑﺎﻟﻠﻭﺣﺔ‪ ،‬ﻭﺗﻛﻭﻥ ﻫﺫﻩ ﺍﻷﻣﺭﺍﺱ ﻣﻥ ﺍﻟﻧﺣﺎﺱ ﺍﻟﻌﺎﺭﻱ ﺍﻟﻣﺟﺩﻭﻝ ﺑﻣﻘﻁﻊ ﻣﻧﺎﺳ ﺏ ﻻ ﻳﻘﻝ ﻋﻥ‬
‫‪٥٠‬ﻣﻠﻡ‪٢‬‬
‫)ﻣﺭﺱ ﻧﺣﺎﺳ ﻲ( ﺑﻁﻭﻝ ‪٥٠‬ﻡ ﺗﻘﺭﻳﺑﺎ ً ﻣﻊ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻛﺎﻓﺔ ﻟﻭﺍﺯﻡ ﺍﻟﺗﻣﺩﻳﺩ ﻭﺍﻟﺭﺑﻁ ﻭﺍﻟﻭﺻ ﻝ ﻣﻥ ﺻ ﻭﻟﻳﺎﺕ ﻭﺑﺭﺍﻏﻲ ﻭﺭﻧﺩﻳﻼﺕ‬
‫َ‬ ‫‪‬‬
‫ﻭﻋﺯﻗﺎﺕ ﺑﻧﻭﻋﻳﺔ ﺟﻳﺩﺓ ﻣﻧﺎﺳﺑﺔ ﻟﻠﺗﺄﺭﻳﺽ‪.‬‬
‫ﻭﻳﺗﺿﻣﻥ ﺍﻟﻌﻣﻝ ﻛﻝ ﻣﺎﻳﻠﺯﻡ ﻣﻥ ﺣﻔﺭ ﻭﺗﻣﺩﻳﺩ ﻭﺍﻋﺎﺩﺓ ﺭﺩﻡ ﻭﺍﺳﺗﻌﺎﺩﺓ ﺍﻟﺳﻁﻭﺡ ﺍﻟﻁﺑﻳﻌﻳﺔ ﻭﺩﺧﻭﻝ ﻣﺭﺱ ﺍﻟﺗﺄﺭﻳﺽ ﺇﻟﻰ ﺑﺋﺭ ﺍﻟﺗﺄﺭﻳﺽ‬ ‫‪‬‬
‫ﻭﺇﻟﻰ ﻗﻧﺎﺓ ﺍﻟﻠﻭﺣﺎﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺭﺋﻳﺳﻳﺔ ﺑﺷﻛﻝ ﻓﻧﻲ‪ ,‬ﻭﻭﺻﻝ ﻣﺭﺱ ﺍﻟﺗﺄﺭﻳﺽ ﻣﻊ ﺃﻣﺎﻛﻥ ﺍﻟﺗﺄﺭﻳﺽ‬
‫ﻳﺗﻭﺟﺏ ﻋﻠﻰ ﺍﻟﻣﺗﻌﻬﺩ ﺇﺣﺿ ﺎﺭ ﺟﻬﺎﺯ ﻟﻔﺣﺹ ﻣﻘﺎﻭﻣﺔ ﺍﻷﺭﺿ ﻲ ﻭﻋﻠﻰ ﻧﻔﻘﺗﻪ ﺍﻟﺧﺎﺻ ﺔ ﻭﻳﻌﺗﺑﺭ ﻫﺫﺍ ﺍﻻﺧﺗﺑﺎﺭ ﺃﺳ ﺎﺱ ﻓﻲ ﻋﻣﻠﻳﺔ‬ ‫‪‬‬
‫ﺍﻻﺳﺗﻼﻡ‪.‬‬

‫ﻣﺧﻁﻁ ﻧﻅﺎﻡ ﺗﺄﺭﻳﺽ ﻛﺎﻣﻝ ﻷﻋﻣﺎﻝ ﻣﻧﻅﻭﻣﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻛﻬﺭﻭﺿﻭﺋﻳﺔ‬

‫‪16 | P a g e‬‬
‫‪ -١٢‬ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﻭﺗﻭﺻﻳﻝ ﺷﺑﻛﺔ ﻣﺎﻧﻌﺎﺕ ﺍﻟﺻﻭﺍﻋﻖ ﻣﻊ ﺗﻘﺩﻳﻡ ﻭﺗﺭﻛﻳﺏ ﺃﻣﺭﺍﺱ ﻭﻛﺎﺑﻼﺕ‬
‫ﻭﺃﻭﺗﺎﺩ ﻣﻊ ﻛﻝ ﻣﺎﻳﻠﺯﻡ‪/ :‬ﻣﻘﻁﻭﻉ‪/‬‬
‫ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣﻝ ﺗﻘﺩﻳﻡ ﻭﺗﻧﻔﻳﺫ ﻭﺗﻭﺻ ﻳﻝ ﺷ ﺑﻛﺔ ﻣﺎﻧﻌﺔ ﺻ ﻭﺍﻋﻖ ﺑﺟﻭﺩﺓ ﻓﻧﻳﺔ ﻋﺎﻟﻳﺔ ﺟﺎﻫﺯﺓ ﻟﻺﺳ ﺗﺛﻣﺎﺭ ﻓﻲ ﻛﻝ ﻣﻭﻗﻊ ﻣﻥ ﻣﻭﺍﻗﻊ‬ ‫‪‬‬
‫ﺍﻟﻣﺷﺎﺭﻳﻊ ﺍﻟﺛﻼﺙ ﻭ ﺑﺎﻟﻛﻣﻳﺔ ﺍﻟﻣﺷﺎﺭ ﺇﻟﻳﻬﺎ ﻓﻲ ﺍﻟﻛﺷﻑ ﺍﻟﺗﻘﺩﻳﺭﻱ ﺑﺎﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺗﺎﻟﻳﺔ‪:‬‬
‫ﺍﻟﻣﺭﺱ ﻧﺣﺎﺳﻲ ﺑﻣﻘﻁﻊ )‪ (٥٠‬ﻣﻡ‪٢‬‬ ‫‪‬‬
‫ﺍﻹﺑﺭ ﻧﺣﺎﺳﻳﺔ ﻣﺗﺷﻌﺑﺔ ﺑﻁﻭﻝ )‪ (٥٠‬ﺳﻡ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﺟﻳﺩ ﻭﺍﻟﻣﺗﻭﺍﻓﺭ ﺑﺎﻷﺳﻭﺍﻕ ﺍﻟﻣﺣﻠﻳﺔ‪.‬‬ ‫‪‬‬
‫ﺍﻟﻧﺎﺯﻝ‪ :‬ﻣﻥ ﻧﻭﺍﻗﻝ ﻣﻌﺩﻧﻳﺔ ﻏﻳﺭ ﻗﺎﺑﻠﺔ ﻟﻠﺻﺩﺃ ﻣﻥ ﺍﻟﻧﺣﺎﺱ ﻭﺑﻣﻘﻁﻊ )‪ (٥٠‬ﻣﻡ‪٢‬‬ ‫‪‬‬
‫ﻳﺟﺏ ﺍﻟﺳﻌﻲ ﻟﺗﻣﺩﻳﺩ ﺍﻟﻧﻭﺍﺯﻝ ﺑﺄﻗﺭﺏ ﻁﺭﻳﻖ ﺷﺎﻗﻭﻟﻲ ﻣﻣﻛﻥ ﺑﻳﻥ ﺍﻹﺑﺭ ﻭﺍﻷﺭﺽ ﺩﻭﻥ ﺍﻧﺣﻧﺎءﺍﺕ ﺣﺎﺩﺓ ﻓﻲ ﻣﺳﺎﺭﻫﺎ‪.‬‬ ‫‪‬‬
‫ﻳﺟﺏ ﺃﻥ ﻻ ﺗﻘﻝ ﺍﻟﻣﺳﺎﻓﺔ ﺑﻳﻥ ﺍﻟﻧﻭﺍﺯﻝ ﻭﻓﺗﺣﺎﺕ ﺍﻷﺑﻭﺍﺏ ﻋﻥ )‪ (٥٠‬ﺳﻡ‬ ‫‪‬‬
‫ﻳﺟﺏ ﺃﻥ ﻻ ﺗﻘﻝ ﺍﻟﻣﺳﺎﻓﺔ ﺑﻳﻥ ﺍﻟﻧﻭﺍﺯﻝ ﻭﺍﻟﺗﻣﺩﻳﺩﺍﺕ ﺍﻟﻛﻬﺭﺑﺎ ﺋﻳﺔ ﻋﻥ )‪ (١٠٠‬ﺳﻡ‬ ‫‪‬‬
‫ﺗﺛﺑﺕ ﺍﻟﻣﺭﺱ ﻭﺍﻟﻧﻭﺍﺯﻝ ﻋﻠﻰ ﻭﺍﺟﻬﺔ ﺍﻟﻣﺑﻧﻰ ﺑﺷ ﻛﻝ ﻅﺎﻫﺭ ﺑﻣﺛﺑﺗﺗﺎﺕ ﻣﻥ ﺍﻟﺑﻳﻛﺎﻟﻳﺕ ﻣﺗﻭﺳ ﻁﺔ ﺍﻟﺣﺟﻡ ﻭﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﻣﻌﻛﻭﻑ‬ ‫‪‬‬
‫ﺑﺣﻳﺙ ﺗﻘﻭﻡ ﻫﺫﻩ ﺍﻟﻣﺛﺑﺗﺎﺕ ﺑﺎﺑﻌﺎﺩ ﺍﻟﻧﻭﺍﺯﻝ ﻋﻥ ﺍﻟﺑﻧﺎء ﺑﺷ ﻛﻝ ﺟﻳﺩ ﻭﺗﺣﻣﻰ ﻣﻳﻛﺎﻧﻳﻛﻳﺎ ﺣﺗﻰ ﺍﺭﺗﻔﺎﻉ )‪ (٢‬ﻡ ﻣﻥ ﺳ ﻁﺢ ﺍﻷﺭﺽ‬
‫ﺑﻭﺍﺳﻁﺔ ﻗﺳﺎﻁﻝ ﺑﻼﺳﺗﻳﻛﻳﺔ ﻣﻧﺎﺳﺑﺔ ﺫﺍﺕ ﺿﻐﻁ ﻋﺎﻝ ﻭﺑﻘﻁﺭ )‪ (٢‬ﺃﻧﺵ‪.‬‬
‫ﺍﻟﻧﺎﺯﻝ ﻣﻥ ﺍﻹﺑﺭﺓ ﻳﺭﺗﺑﻁ ﺑﻌﻠﺑﺔ ﻗﻳﺎﺱ ﻭﻣﺭﺍﻗﺑﺔ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﺑﻼﺳﺗﻳﻛﻲ ﺍﻟﺟﻳﺩ ﻋﻠﻰ ﺍﺭﺗﻔﺎﻉ )‪ (٢‬ﻡ ﻣﻥ ﺳﻁﺢ ﺍﻷﺭﺽ‪.‬‬ ‫‪‬‬
‫ﻳﺟﺏ ﺃﻥ ﻻ ﺗﺯﻳﺩ ﺍﻟﻣﻘﺎﻭﻣﺔ ﺍﻷﺭﺿﻳﺔ ﻟﺑﺋﺭ ﺍﻟﺗﺄﺭﻳﺽ ﻋﻥ )‪ (٣‬ﺃﻭﻡ‪.‬‬ ‫‪‬‬
‫ﻣﻭﺍﺻ ﻔﺎﺕ ﺑﺋﺭ ﺍﻟﺗﺄﺭﻳﺽ‪ :‬ﺟﻭﺭﺓ ﺍﻟﺗﻔﺗﻳﺵ ﺑﺄﺑﻌﺎﺩ )‪ (٤٠×٤٠×٤٠‬ﺳ ﻡ ﻋﺩﺩﻫﺎ )‪ (٣‬ﻭﺗﻛﻭﻥ ﺣﻭﺍﻓﻬﺎ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﺍﻟﺧﺎﺭﺟﻳﺔ‬ ‫‪‬‬
‫ﻣﻥ ﺍﻟﺑﻳﺗﻭﻥ ﺍﻟﻣﺳﻠﺢ ﻭﻳﻭﺿﻊ ﻋﻠﻳﻬﺎ ﻏﻁﺎء ﻣﻥ ﺍﻟﺑﻳﺗﻭﻥ ﻣﻥ ﻧﻔﺱ ﺍﻷﺑﻌﺎﺩ ﻭﻗﺎﺑﻝ ﻟﻠﻔﺗﺢ ﻭﺍﻹﻏﻼﻕ ﻭﺃﻥ ﻻ ﺗﺯﻳﺩ ﻣﻘﺎﻭﻣﺔ ﺍﻟﺗﺄﺭﻳﺽ‬
‫ﻋﻥ )‪ (٣‬ﺃﻭﻡ ﻭﻳﺗﻭﺟﺏ ﻋﻠﻰ ﺍﻟﻣﺗﻌﻬﺩ ﻗﻳﺎﺱ ﻣﻘﺎﻭﻣﺔ ﺍﻟﺗﺄﺭﻳﺽ ﻭﺍﻟﻌﻣﻝ ﻋﻠﻰ ﺗﺧﻔﻳﺽ ﻣﻘﺎﻭﻣﺔ ﺍﻷﺭﺽ ﺑﺎﻟﻁﺭﻕ ﺍﻟﻔﻧﻳﺔ ﺍﻟﺗﻲ‬
‫ﻳﺭﺍﻫﺎ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﻣﻧﺎﺳﺑﺔ ﺑﻐﻳﺔ ﺍﻟﻭﺻﻭﻝ ﺇﻟﻰ ﻣﻘﺎﻭﻣﺔ ﺍﻟﺗﺄﺭﻳﺽ )‪ (٣‬ﺃﻭﻡ ﺍﻟﻣﻁﻠﻭﺑﺔ‪.‬‬
‫ﺷﺑﻛﺔ ﺗﺄﺭﻳﺽ ﺍﻟﻣﺂﺧﺫ ﻭﺷﺑﻛﺎﺕ ﺍﻟﺗﺄﺭﻳﺽ ﺍﻷﺧﺭﻯ ﻣﺳﺗﻘﻠﺔ ﻋﻥ ﺷﺑﻛﺔ ﺍﻷﺭﺿﻲ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻟﺣﻣﺎﻳﺔ ﻣﻥ ﺍﻟﺻﻭﺍﻋﻖ ﻭﺗﺑﻌﺩ ﻋﻧﻬﺎ‬ ‫‪‬‬
‫ﻣﺳﺎﻓﺔ ﻻ ﺗﻘﻝ ﻋﻥ )‪ (١٠‬ﻣﺗﺭ‪.‬‬

‫‪ -١٣‬ﺗﻘﺩﻳﻡ ﻭﺗﻣﺩﻳﺩ ﻭﺗﻭﺻﻳﻝ ﻛﺎﺑﻼﺕ ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺭﺋﻳﺳﻳﺔ ﺑﻳﻥ ﺍﻷﻟﻭﺍﺡ ﻭﻣﻧﻬﺎ ﺍﻟﻰ‬
‫ﺍﻻﻧﻔﻳﺭﺗﺭ ﺑﻣﻘﻁﻊ )‪ ٦×١‬ﻣﻡ‪ ( DC) (٢‬ﻭﺑﻣﻘﻁﻊ )‪ ١٦×١‬ﻣﻡ‪ ( DC) (٢‬ﻟﺯﻭﻡ‬
‫ﺍﻟﻣﺩﺧﺭﺍﺕ ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ‪ /‬ﻡ‪.‬ﻁ‬

‫ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣ ﻝ ﺗﻘ ﺩﻳﻡ ﻛ ﺎﺑﻼﺕ ﺗﻐﺫﻳ ﺔ ﻛﻬﺭﺑﺎﺋﻳ ﺔ ﺃﺣﺎﺩﻳ ﺔ ﻣﺑﺭﻭﻣ ﺔ‪ NYY‬ﺷ ﻌﺭﻱ ﺑﻣﻘﻁ ﻊ )‪٦×١‬ﻣ ﻡ‪ DC ( ٢‬ﻟ ﺯﻭﻡ‬
‫ﺍﻟﺗﻭﺻ ﻳﻝ ﺑ ﻳﻥ ﺍﻷﻟ ﻭﺍﺡ ﻭﻣﻧﻬ ﺎ ﺍﻟ ﻰ ﺍﻻﻧﻔﻳﺭﺗ ﺭ ﻭﺑﻣﻘﻁ ﻊ )‪٦×١‬ﻣ ﻡ‪ DC ( ٢‬ﻟ ﺯﻭﻡ ﺍﻟﻣ ﺩﺧﺭﺍﺕ ﻭﻧﻘﻠﻬ ﺎ ﺇﻟ ﻰ ﻣﻭﻗ ﻊ ﺍﻟﻌﻣ ﻝ‬
‫ﺣﻳ ﺙ ﻳ ﺗﻡ ﻧﻘﻠﻬ ﺎ ﻋﻠ ﻰ ﺣﺳ ﺎﺏ ﺍﻟﻣﺗﻌﻬ ﺩ ﺑﺷ ﻛﻝ ﻓﻧ ﻲ ﻭﺳ ﻠﻳﻡ ‪ ,‬ﻭﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣ ﻝ ﻋﻣﻠﻳ ﺎﺕ ﺍﻟﺗﺳ ﺣﻳﺏ ﻭﺍﻟﺗﻣﺩﻳ ﺩ ﺿ ﻣﻥ ﻗﺳ ﺎﻁﻝ‬
‫ﺍﻟ ـ ‪ PVC‬ﺃﻭﻣﺟ ﺎﺭﻱ ﺑﻼﺳ ﺗﻳﻛﻳﺔ ﺃﻭﻣﻌﺩﻧﻳ ﺔ ﺗﺛﺑ ﺕ ﺟ ﺩﺍﺭﻳﺎ" ﺑﺷ ﻛﻝ ﻓﻧ ﻲ ﻭﺫﻟ ﻙ ﺑﻣﻘ ﺎﻁﻊ ﻣﺗﻧﺎﺳ ﺑﺔ ﻣ ﻊ ﻣﻘ ﺎﻁﻊ ﺍﻟﻛ ﺎﺑﻼﺕ‬
‫ﺑﻣﺎ ﻳﺧﺹ ﺍﻟﺗﻭﺻﻳﻝ ﺑﻳﻥ ﻧﻬﺎﻳﺔ ﺍﻷﻟﻭﺍﺡ ﻭﺍﻻﻧﻔﻳﺭﺗﺭ ‪.‬‬
‫ﻭﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣ ﻝ ﺍﻟﺗﺄﻛ ﺩ ﻣ ﻥ ﺟﺎﻫﺯﻳ ﺔ ﻗﺳ ﺎﻁﻝ ﺍﻟﺗﻣﺩﻳ ﺩ ﻭﻓ ﻲ ﺣ ﺎﻝ ﻅﻬ ﻭﺭ ﻗﺳ ﺎﻁﻝ ﻏﻳ ﺭ ﺳ ﺎﻟﻛﺔ ﻳﺗﺭﺗ ﺏ ﻋﻠ ﻰ ﺍﻟﻣﺗﻌﻬ ﺩ‬
‫ﺍﻟﻘﻳ ﺎﻡ ﺑﻌﻣﻠﻳ ﺎﺕ ﺍﻟﺣﻔ ﺭ ﻭﺗﻘ ﺩﻳﻡ ﻭﺗﺭﻛﻳ ﺏ ﻗﺳ ﻁﻝ ﺟﺩﻳ ﺩ ﻭﺇﻋ ﺎﺩﺓ ﺗﺳ ﻭﻳﺔ ﺍﻟﺳ ﻁﻭﺡ ﻛﻣ ﺎ ﻛﺎﻧ ﺕ ﻋﻠﻳ ﻪ ﻭﻛ ﻝ ﻣ ﺎ ﻳﻠ ﺯﻡ ﻟﻠﻣﺳ ﺎﻓﺔ‬

‫‪17 | P a g e‬‬
‫ﺍﻟﺗ ﻲ ﻗ ﺩ ﺗﻅﻬ ﺭ ﻣﻐﻠﻘ ﺔ ﻟﺗ ﺄﻣﻳﻥ ﺟﺎﻫﺯﻳ ﺔ ﺍﻟﻌﻣ ﻝ ﺑﺷ ﻛﻝ ﻓﻧ ﻲ‪ ،‬ﻣ ﻊ ﺗﻘ ﺩﻳﻡ ﻛﺎﻓ ﺔ ﻣﺳ ﺗﻠﺯﻣﺎﺕ ﺍﻟﺗﻣﺩﻳ ﺩ ﻭﺍﻟﺗﺛﺑﻳ ﺕ ﻭﺍﻟﺗﻭﺻ ﻳﻝ‬
‫ﺣﺳﺏ ﻭﺍﻗﻊ ﺍﻟﻌﻣﻝ ﻭﺗﻌﻠﻳﻣﺎﺕ ﻓﺭﻳﻖ ﺍﻟﻣﺭﺍﻗﺑﺔ ﺑﺣﻳﺙ ﻳﻛﻭﻥ ﺍﻟﻌﻣﻝ ﻭﻓﻖ ﺃﻓﺿﻝ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﻭﺍﻟﺟﻭﺩﺓ ﺍﻟﻔﻧﻳﺔ ‪.‬‬
‫ﻳ ﺗﻡ ﺗﻘ ﺩﻳﻡ ﺍﻟﻛ ﺎﺑﻼﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳ ﺔ ﻣ ﻥ ﺍﺣ ﺩﻯ ﺍﻟﺷ ﺭﻛﺎﺕ ﺍﻟﻣﺻ ﻧﻌﺔ ﻟﻠﻛ ﺎﺑﻼﺕ )ﺣ ﻭﺵ ﺑ ﻼﺱ ﺃﻭ ﺍﻟﺳ ﻭﺭﻳﺔ ﻟﻠﻛ ﺎﺑﻼﺕ ﺃﻭ‬
‫ﺍﻻﺗﺣﺎﺩ ‪....‬ﺃﻭﻣﺎﻳﻌﺎﺩﻟﻬﺎ( ﺣﺳﺏ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺳﻭﺭﻳﺔ) ‪ (IEC‬ﺃﻭ ﺣﺳﺏ ﺍﻟﻣﻭﺍﺻﻔﺔ ﺍﻷﻟﻣﺎﻧﻳﺔ ) ‪.(VDE‬‬
‫ﻛﻣ ﺎ ﻳﻘ ﻊ ﻋﻠ ﻰ ﻋ ﺎﺗﻖ ﺍﻟﻣﺗﻌﻬ ﺩ ﺗﻭﺻ ﻳﻝ ﺑ ﺩﺍﻳﺎﺕ ﻭﻧﻬﺎﻳ ﺎﺕ ﺍﻟﻛ ﺎﺑﻼﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳ ﺔ ﺑﺣﻳ ﺙ ﺗﻛ ﻭﻥ ﺟ ﺎﻫﺯﺓ ﻟﻠﻌﻣ ﻝ ﺑﺎﻟﺷ ﻛﻝ ﺍﻷﻣﺛ ﻝ‬
‫ﻭﻓﻘﺎ" ﻟﺗﻌﻠﻳﻣﺎﺕ ﺍﻹﺩﺍﺭﺓ‪.‬‬
‫ﻳﻘﺩﺭ ﺍﻟﻌﻣﻝ ﺑﺎﻟﻣﺗﺭ ﺍﻟﻁﻭﻟﻲ‪.‬‬

‫‪ -١٤‬ﺗﻘﺩﻳﻡ ﻭﺗﻣﺩﻳﺩ ﻭﺗﻭﺻﻳﻝ ﻛﺎﺑﻼﺕ ﻟﺯﻭﻡ ﺗﻐﺫﻳﺔ ﺍﻟﺗﺟﻬﻳﺯﺍﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ )ﺍﻟﺣﻣﻭﻻﺕ(‬


‫ﺑﻣﻘﻁﻊ )‪ ٤×٢‬ﻣﻠﻡ‪AC (٢‬ﻣﻊ ﻛﻝ ﻣﺎ ﻳﻠﺯﻡ‪/‬ﻡ‪.‬ﻁ‪/‬‬

‫ﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣ ﻝ ﺗﻘ ﺩﻳﻡ ﻭﻧﻘ ﻝ ﻛ ﺎﺑﻼﺕ ﺍﻟﺗﻐﺫﻳ ﺔ ﺍﻟﻼﺯﻣ ﺔ ﺑﻣﻘﻁ ﻊ )‪ ٤×٢‬ﻣﻠ ﻡ ‪ AC (٢‬ﺍﻟﺧﺎﺻ ﺔ ﺑﺎﻟﻣﺷ ﺭﻭﻉ ﻭﺗﻣﺩﻳ ﺩﻫﺎ‬
‫ﺿ ﻣﻥ ﻗﺳ ﺎﻁﻝ ﺃﻭ ﻣﺟ ﺎﺭﻱ ﺑﻼﺳ ﺗﻳﻛﻳﺔ ﺃﻭ ﻣﻌﺩﻧﻳ ﺔ ﺗﺗﻧﺎﺳ ﺏ ﻣ ﻊ ﻛﻣﻳ ﺔ ﺍﻟﻛ ﺎﺑﻼﺕ ﺍﻟﻣﻣ ﺩﺓ ﺿ ﻣﻧﻬﺎ ﻣ ﻥ ﻟﻭﺣ ﺔ ﺍﻟﺗﻐﺫﻳ ﺔ‬
‫ﺍﻟﻛﻬﺭﺑﺎﺋﻳ ﺔ ﺣﺗ ﻰ ﻣﻭﺍﻗ ﻊ ﺍﻟﺣﻣ ﻭﻻﺕ‪ .‬ﻭﻳﺗﺿ ﻣﻥ ﺍﻟﻌﻣ ﻝ ﺗﻘ ﺩﻳﻡ ﻭﺗﺭﻛﻳ ﺏ ﻛ ﻝ ﻣ ﺎﻳﻠﺯﻡ ﻣ ﻥ ﻣﺳ ﺗﻠﺯﻣﺎﺕ ﺍﻟﺗﻣﺩﻳ ﺩ ﻭﺍﻟﺗﺛﺑﻳ ﺕ‬
‫ﻭﺍﻟﺗﻭﺻ ﻳﻝ ﻣ ﻥ ﻗﺳ ﺎﻁﻝ ﺃﻭ ﻣﺟ ﺎﺭﻱ ﺃﻭ ﺣﻭﺍﻣ ﻝ ﺃﻭ ﺻ ﻭﻟﻳﺎﺕ ﻭﺻ ﻝ ﻣﻧﺎﺳ ﺏ ﻟﻣﻘ ﺎﻁﻊ ﺍﻟﻛ ﺎﺑﻼﺕ ﻭﺍﻻﺳ ﺗﻁﺎﻋﺔ ﺍﻟﻣﻭﺍﻓﻘ ﺔ‬
‫ﻭﻣ ﻥ ﻧﻭﻋﻳ ﺔ ﺟﻳ ﺩﺓ ﺃﻭ ﻋﻠ ﺏ ﺗﻭﺻ ﻳﻝ ﻛﺗﻳﻣ ﺔ ﺣﺳ ﺏ ﺍﻟﻭﺍﻗ ﻊ ﻭﺗﻌﻠﻳﻣ ﺎﺕ ﻓﺭﻳ ﻖ ﺍﻟﻣﺭﺍﻗﺑ ﺔ ﺑﺣﻳ ﺙ ﻳﻛ ﻭﻥ ﺍﻟﻌﻣ ﻝ ﻭﻓ ﻖ ﺃﻓﺿ ﻝ‬
‫ﺍﻟﻣﻭﺍﺻ ﻔﺎﺕ ﻭﺍﻟﺟ ﻭﺩﺓ ﺍﻟﻔﻧﻳ ﺔ ﻛﻣ ﺎ ﻳﻘ ﻊ ﻋﻠ ﻰ ﻋ ﺎﺗﻖ ﺍﻟﻣﺗﻌﻬ ﺩ ﺗﻭﺻ ﻳﻝ ﺑ ﺩﺍﻳﺎﺕ ﻭﻧﻬﺎﻳ ﺎﺕ ﺍﻟﻛ ﺎﺑﻼﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳ ﺔ ﺑﺣﻳ ﺙ ﺗﻛ ﻭﻥ‬
‫ﺍﻟﺗﻐﺫﻳﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻟﻠﺣﻣﻭﻻﺕ ﺟﺎﻫﺯﺓ ﻟﻠﻌﻣﻝ ﺑﺷﻛﻝ ﻓﻧﻲ ﻭﺫﻟﻙ ﻟﺗﻘﺩﻳﻡ ﺍﻟﻌﻣﻝ ﺑﺎﻟﺷﻛﻝ ﺍﻷﻣﺛﻝ ﻭﻓﻘﺎ" ﻟﺗﻌﻠﻳﻣﺎﺕ ﺍﻹﺩﺍﺭﺓ‪.‬‬
‫ﻳﺗﻡ ﺗﻘﺩﻳﻡ ﺍﻟﻛﺎﺑﻼﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻣﻥ ﺇﺣﺩﻯ ﺍﻟﺷﺭﻛﺎﺕ ﺍﻟﻣﺻﻧﻌﺔ ﻟﻠﻛﺎﺑﻼﺕ )ﺣﻭﺵ ﺑﻼﺱ ﺃﻭ ﺍﻟﺳﻭﺭﻳﺔ ﻟﻠﻛﺎﺑﻼﺕ‪.....‬ﺃﻭ ﻣﺎﻳﻌﺎﺩﻟﻬﺎ(‬
‫ﺣﺳﺏ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﺳﻭﺭﻳﺔ) ‪ (IEC‬ﺃﻭ ﺣﺳﺏ ﺍﻟﻣﻭﺍﺻﻔﺔ ﺍﻷﻟﻣﺎﻧﻳﺔ ) ‪. (VDE‬‬
‫ﻳﻘﺩﺭ ﺍﻟﻌﻣﻝ ﺑﺎﻟﻣﺗﺭ ﺍﻟﻁﻭﻟﻲ‪.‬‬

‫‪18 | P a g e‬‬