Lal G Schedule
Lal G Schedule
LOAD DIS
DB NAME,,,, DB GROUND FLOOR
FED FROM,,,,SMDB
RATING RATING CKT, ECC CONNEC
OF OF SL CKT MCB WIRE WIRE ROOM CHAND
INCOMER ELCB NO NO RTG. SIZE SIZE AREA LTG LER
LTG
1 R1 10 2.5 2.5 dinning/living 2 2
2 Y1 10 2.5 2.5 hall 2
4P 40A 3 B1 10 2.5 2.5 lobby/laundary 8
100mA 4 R2 10 2.5 2.5 kitchen/store 5
E.L.C.B.1 5 Y2 10 2.5 2.5 dinning/majlis 5 2
6 B2 10 2.5 2.5 boundarywall 8
TP 80 A 4P 40A 7 R3
ISOLATOR 100mA 8 Y3 32 6 4 kitchen
E.L.C.B.2 9 B3 10 2.5 2.5 boundarywall 8
10 R4 20 4 2.5 gate
11 Y4 20 4 2.5 boundarywall
4P 40A 12 B4 space
30mA 13 R5 space
E.L.C.B.3 14 Y5 32 4 2.5 dinning/living
15 B5 20 4 2.5 yard
16 R6 32 4 2.5 kitchen/store
17 Y6 32 4 2.5 dinning/majlis
18 B6 20 4 2.5 lobby/laundary
LTG,,,LIGHT POINT EX.FAN,,,,,,, EXHAUST FANFCU,,,,,,FAN COIL UNIT CU,,,,, CONDENSATE UNIT
PROJECT,,,,,,,G+1 VILLA
LOAD DIS
DB NAME,,,, DB GROUND FLOOR
FED FROM,,,,SMDB
LTG
4P 40A 19 R7 TP
100mA 20 Y7 32 6 4 living/dinning
E.L.C.B.4 21 B7 A
4P 40A 22 R8 TP
100mA 23 Y8 32 6 4 hall/stairs
E.L.C.B.5 24 B8 A
4P 40A 25 R9 TP
TP 80 A 100mA 26 Y9 32 6 4 majlis/ dinning
ISOLATOR E.L.C.B.6 27 B9 A
4P 40A 28 R10 25 6 4 laundary
100mA 29 Y10
E.L.C.B.7 30 B10 32 6 4 kitchen
31
32
33
34
35
36
LTG,,,LIGHT POINT EX.FAN,,,,,,, EXHAUST FANFCU,,,,,,FAN COIL UNIT CU,,,,, CONDENSATE UNIT
PROJECT,,,,,,,G+1 VILLA
LOAD DIS
DB NAME,,,, DB FF
FED FROM,,,,SMDB
LTG
1 R1 10 2.5 2.5 masterbedroom 5
2 Y1 10 2.5 2.5 bedroom-1 5
4P 40A 3 B1 10 2.5 2.5 bedroom-3 5
100mA 4 R2 10 2.5 2.5 bedroom-2 5
E.L.C.B.1 5 Y2 space
6 B2 10 2.5 2.5 sitting area 4
TP 125 A 7 R3 space
ISOLATOR 8 Y3 10 2.5 2.5 roof 2
9 B3 space
10 R4 32 4 2.5 masterbedroom
11 Y4 32 4 2.5 bedroom 1
4P 40A 12 B4 32 4 2.5 sitting area
30mA 13 R5 32 4 2.5 bedroom-3
E.L.C.B.2 14 Y5 20 4 2.5 roof
15 B5 20 4 2.5 roof
16 R6 32 4 2.5 bedroom 2
17 Y6 space
18 B6 20 4 2.5 passage
LTG,,,LIGHT POINT EX.FAN,,,,,,, EXHAUST FANFCU,,,,,,FAN COIL UNIT CU,,,,, CONDENSATE UNIT
PROJECT,,,,,,,G+1 VILLA
LOAD DIS
DB NAME,,,, DB FF
FED FROM,,,,SMDB
LTG
4P 40A 1 R7 TP
100mA 2 Y7 32 6 4 master bed
E.L.C.B.3 3 B7 A
4P 40A 4 R8 TP
100mA 5 Y8 25 6 4 bedroom-1
TP 125A E.L.C.B.4 6 B8 A
ISOLATOR 4P 40A 7 R9 TP
100mA 8 Y9 32 6 4 sitting area
E.L.C.B.5 9 B9 A
4P 40A 10 R10 25 6 4 bedroom-2
100mA 11 SPACE
E.L.C.B.6 12 B10 25 6 4 bedroom-3
4P 40A 13 R11 space
100mA 14 Y11 25 6 4 roof
E.L.C.B7 15 B11 space
16 R12 space
17 Y12 25 6 4 roof
18 B12 space
LTG,,,LIGHT POINT EX.FAN,,,,,,, EXHAUST FANFCU,,,,,,FAN COIL UNIT CU,,,,, CONDENSATE UNIT
PLOT NO….7116462
LOAD DISTRIBUTION SCHEDULE
1 3000 3000
100 800
1 1500 1500
3 200 600
7 200 1400
1 1 1500 1500
6 200 1200
6 200 1200
4 200 800
6400 4700
PLOT NO….7116462
LOAD DISTRIBUTION SCHEDULE
PLOT NO….7116462
LOAD DISTRIBUTION SCHEDULE
14 100/50 1100
100 200
6 200 1000
6 200 1200
5 200 1000
5 200 1000
2 200 400
1 1 1500 1500
5 200 1000
2 200 400
5500 2600 5000
PLOT NO….7116462
LOAD DISTRIBUTION SCHEDULE
1 1 3270 3270
3C armourerd cable
45A DP switch
3C armourerd cable
3C armourerd cable TOTAL CONNECTED LOAD PER PHASE
RING 3,,,125A-16
3C armourerd cable
RING
RING
PLOT NO….7116462
REMARKS
UVR+TIMER+RELAY
UVR+TIMER+RELAY
UVR+TIMER+RELAY
UVR+TIMER+RELAY
UVR+TIMER+RELAY
UVR+TIMER+RELAY
40704
PLOT NO….7116462
REMARKS
ring
ring
ring
ring
ring
PLOT NO….7116462
REMARKS
UVR+TIMER+RELAY
UVR+TIMER+RELAY
UVR+TIMER+RELAY
UVR+TIMER+RELAY
UVR+TIMER+RELAY
32A isolator
32A isolator
38323
SUMMARY SHEET
ATOR AS INCOMER TO MDB, 1X4C 95 mm2 XLPE/SWA/PVC +1X1C 50 mm2 Y/G AS LOAD CABLE
1x1c 25 1X4C35 1X1C25 13.97 13.31 13.09 40.7
1x1c 25 1X4C35 1X1C25 11.81 13.62 12.51 38.32
78.31