Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

Vibration Analysis Utico – AHWC

Report
RO # 7 Booster – Motor
Date 22-09-2020 Equipment Name
No load Test

MACHINE SKETCH

Vibration Limit for this Equipment – Velocity in mm/Sec(RMS)


STATUS NORMAL ALERT ALARM
LIMIT 4.5 4.5 to 7.0 Above 7.0
EQUIPMENT SPECIFICATION
DESCRIPTION DRIVE DRIVEN MOUNTING Y/N
Rated speed 2987 At Ground N
Power rating 560 Kw On Rigid Concrete Y
Tested Frequency Above Ground level Y
Equipment Details ABB On Steel Structure Y
AMPLITUDES AND HEALTH CONDITION
Velocity – RMS[mm/s]
Location Health Condition
A T R
Motor Non Drive End 0.3 0.2 0.4
Motor Drive End 0.25 0.27 0.7
Pump Drive End
NORMAL
Pump Non Drive End
Observation: Equipment indicating a “Normal” behavior with the maximum vibration
amplitudes of 0.7 mm/s recorded is at motor drive end.
Analysis:

Action Plan:

Note:
Motor Non Drive End

Motor Drive End