Download as pdf or txt
Download as pdf or txt
You are on page 1of 25

Electric Machines Principles

Applications and Control Schematics


2nd Edition Dino Zorbas Solutions
Manual
Visit to download the full and correct content document: https://testbankdeal.com/dow
nload/electric-machines-principles-applications-and-control-schematics-2nd-edition-di
no-zorbas-solutions-manual/
8W: Electrical Safety and Reduction in Energy Consumption

8W Electrical Safety and


Reduction in Energy Consumption

Solutions To Exercises

EXERCISE 8W-1

a) When the current in a circuit increases from 25% above nominal to 6 times

nominal is referred as an “overload condition” while at higher currents than that is

referred to as an “overcurrent condition”.

b) “Bolted” short circuit signifies that the conductors while energized are solidly

shorted. Intermittent faults, as the name implies, are short circuits of repetitive

restriking nature.

c) I = 1.35 Ir = 1.35 (15) = 20.35 A.

d) The ground resistance depends on the length of the current path, the ground’s

chemical configuration and ambient conditions.

EXERCISE 8W-2

120 120
a) I= = = 8.289 A
7.5 + 7.5 / /100 7.5 + 6.9767

120 120
b) I) If = = 8.289A, I h = = 0.0A
7.5 + 7.5 / /100 7.5 + 7.5 / /100

120
II) If = = 8.0743 A
7.5 + 7.5 / / 400

120 − 8.0743(7.5)
Ih = = 148.61 m A
100 + 300

263
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Zorbas/Electric Machines, 2e

EXERCISE 8W-3

a) Faulty hook up: most probably the neutral and the ground wires are connected

together at the load.

b) The resistance of the ground wire is a fraction of an Ohm and the current of 8 A

will produce a voltage of less than say 5 V which does not constitute a safety

hazard.

c) The enclosure’s ground wire increases the fault current—in case of equipment’s

internal short—and thus may cause the protective device to interrupt the current,

which will disconnect the affected equipment from its voltage supply. It provides

a path for the discharge of static electricity to ground and above all prevents

injury to Personnel that come in contact with the enclosure.

d) When an individual troubleshoots an ungrounded energized “cloth dryer” while

his other hand touches the adjacent grounded “cloth washer” most likely will be

seriously injured because of the relatively small resistance of the current path

from one hand-to-the other.

e) The ground wire carries no current under normal operating conditions. When,

however, a short circuit takes place within the apparatus the supply current is

returned through the neutral and the ground wire. The ground current is in the

opposite direction to that of the power wires. Its magnetic flux lines are opposite

those of the power cable. This leads to reduction in the circuit’s inductance, an

increase in the short circuit current and a decrease in the time that it takes for the

protective device to interrupt the current. When the ground wire is installed

outside the conduit the previously described advantage is mitigated.

264
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
8W: Electrical Safety and Reduction in Energy Consumption

EXERCISE 8W-4

Similar to Example 8W-4

Ι1 − Ι2 − Ι3 = 0

−10 Ι1 + 0 Ι2 − 25 Ι3 = −120

10 Ι1 + 90 Ι2 + 0 Ι3 = 240

From above

Ι1 = 4.942

Ι2 = 2.12

Ι3 = 2.824

VR1 = 10 (4.942) = 49.42

VR2 = 90 (2.12) = 190.58

VAB = 120 − 10 (4.942)

= 70.58 V

EXERCISE 8W-5

a) “ARC Flash” takes place when the dielectric between two conductors breaks

down due to high currents that result from a short circuit. A preventive measure is

to avoid working on energized equipment and if this is not possible one has to

wear protective gear and be, depending on the voltage, at a certain distance away.

b) The shortening of the distance between the live conductors produced a “flash

over” because the developed electric field intensity was larger than 30,000 V/cm.

The dielectric of the air just broke down.

265
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Zorbas/Electric Machines, 2e

EXERCISE 8W-6

a) υ=L

If the current interruption takes place within a very short time period, is very

high and so is the voltage. A hazardous condition.

b) The inductance of an electric circuit is analogous to a mass of a moving object.

The higher the mass of a body the more difficult is to stop its motion.

Similarly, the higher the inductance of a circuit the more difficult is to

interrupt the current.

c) Capacitor

When a voltage is applied to a capacitor one of its plates is positive charged while

the other is negatively charged. These charges are held together by a force that

accompanies the electric flux lines that are directed from the positive charges to

the electric charges. At the instant of current interruption these electric charges

remain on the capacitor plates and as result the capacitors—when a discharge

 1 1Q 2 
resistor is not provided—retain the energy  w = CV 2 = .
 2 2C 

Inductors

 1 
The energy storage in a magnetic field  w = L I 2  exists only when there is a
 2 

current flow. On current interruption this energy decays to zero in a time that is

 L
inversely proportional to the circuit’s resistance  time constant =  .
 R

Solutions To Problems

266
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
8W: Electrical Safety and Reduction in Energy Consumption

PROBLEM 8W-1

a) The grounding of the neutral at Utility’s step down transformer is mainly to

protect the transformer from lightning strokes and from high transient voltages

that are associated with their switching operations.

b) The grounding of the neutral at the electrical entrance is to protect the distribution

from the possible destructive effects of the lightning strokes and high transient

voltages.

c) The grounding of the equipment’s enclosure provides a small resistance to current

flow in case of internal faults. This increases the current through the protective

device and thus the troubled load is disconnected from the supply voltage.

d) The grounding of the highest sections of a roof is to provide a small resistance

path to high lightning currents towards the earth.

e) The bonding maintains the metallic frames of the building at the same potential.

f) R=ρ because of the large cross section of the earth its resistance should be

theoretically small. IEEE recommends that a home’s grounding resistance should

be about 25 Ohms. Factors that significantly impact the earth ground resistance

include the contact resistance of the grounding conductor to the electrode, the type

of electrode used and the resistivity of the soil. The soil resistivity is dependent on

the salt, mineral and moisture content of the soil. The “best earth ground” will be

achieved when the grounding electrode system is in contact with corrosive soil

that has permanent moisture. This can be accomplished by driving ground rods

deep into the earth’s permanent water table, and/or by installing electrodes

underneath a building or in direct contact with concrete

267
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Zorbas/Electric Machines, 2e

PROBLEM 8W-2

a) The resistance of the grounding rods is negligible because of their relative short

lengths and large diameter.

b) R = = = 240 Ohms

PROBLEM 8W-3

a) When an individual with one hand touches an energized and faulted equipment—

whose ground wire is disconnected—while with the other hand is in contact with

the enclosure of an energized/de-energized apparatus he or she will most likely be

injured regardless of the resistance of the rubber mat.

b) In order to prevent injury.

c) R1: Resistance through the partially shorted load.

R2: Resistance of the load winding that is in contact with the enclosure of the

faulted load.

R3: Resistance of the human body, shoes and ground.

R3 >> (R1 + R2)

d) To insure that the enclosure of the equipment is at zero relative potential.

e) We do not know why the human heart stops at about 24 hours following a serious

contact with a live conductor.

f) 1. When one touches the enclosure of an electrical device he or she is in

268
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
8W: Electrical Safety and Reduction in Energy Consumption

contact with the transformer’s center tap through the enclosure’s ground

wire, and neutral wire.

2. The feet of an individual are in contact with the transformer’s center tap

through the ground and the ground wire of the utility’s transformer.

PROBLEM 8W-4

a) 8.84 A

The breaker will not trip.

b) It does not constitute a danger. The enclosure with respect to ground is at about

zero volts.

c) When the equipment’s ground wire is disconnected, a potential danger exists.

(A 10-year old was electrocuted when on exit from a swimming pool tried to get a

soft drink from a dispensing machine in the pool area that had no ground and an

internal fault).

d) With an Ohmmeter just measure the resistance between the equipment’s enclosure

and the nearest metallic conduit. It should be less than 1.0 ohm.

PROBLEM 8W-5

In case of a fault between any of the lines and ground there will be large currents that will

flow in the vicinity of the substation ground.

These currents:

269
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Zorbas/Electric Machines, 2e

I) Will raise the potential of the metallic enclosure and when an individual

comes in contact with it (touch potential) will be in danger of being

injured.

II) The ground currents set-up a potential along their path (V = I R) and thus

between the two shoes of the individual is a voltage (step potential) that

may be hazardous.

PROBLEM 8W-6

a) The “OFF” switch of a plugged in radio is by passed by the bathtub’s water and as

a result the bathtub is at about 120 V. Also the bathroom’s receptacles should be

protected through a “Ground Current Interrupter” (GFI).

b) When the assistant technician touched the electrician, who was in contact with a

live conductor, a current path was developed between the conductor, the

electrician, his assistant and the earth. As a result, a repulsive force was created

that kicked the man off the ladder.

PROBLEM 8W-7

In the phase of the missing contact “C” there will be a current flowing (Faulted Winding-

enclosure and grounded Points) which may not be sufficient to trip the breaker. In either

Delta or Star-connected load a potential danger exists of fire and injury to Personnel

especially when the ground wire is missing or its terminations are loose.

270
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
8W: Electrical Safety and Reduction in Energy Consumption

PROBLEM 8W-8

1. Under normal operation the supply (I1) and return currents (In) are equal and in

opposite direction. Therefore their corresponding fluxes cancel each other and

there is no voltage induced on the voltage sensor.

The underlying principles are:

• The right hand rule that gives the direction of the flux lines.

• Ohm’s law in magnetic circuits

NI
φ=
R

where N is the number of turns and R is the reluctance of the

magnetic path through which the flux lines close their loop.

2. In case of an internal fault some of the supply current (I2) returns through the

neutral wire (I2n) and the remaining through the ground wire (Ig).

I2 = I2n + Ig

Since there is a current unbalance through the voltage sensing coil there will be a

voltage induced which when amplified will trip the ground fault protection

breaker.

PROBLEM 8W-9

a) The current Ι originates from the transformer and goes through each resistor.

Then, from Ohm’s law,

V 240
I= = = 8.0 A
R 18 + 12

and the load voltages are

271
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Zorbas/Electric Machines, 2e

VR1 = 8 (18) = 144 V

and its percentage change with regard to voltage is

= 1.2 or 20% overvoltage

VR2 = 12 (8) = 96 V,

and its percentage change with regard to nominal voltage is

= 0.80, undervoltage condition

b) Undervoltages can damage motors, dim lights while overvoltage can damage

equipment, and cause lights to become brighter.

c) The voltage across the disconnected neutral is found by applying KVL in the

upper loop.

120 − 8 (18) + VAB = 0

From which

VAB = 24 V (VA > VB)

Considering the lower loop

120 − VAB − 8 (12) = 0

VAB = 24 V, (VA > VB)

The interruption of the neutral’s wire current caused the flash over.

d) Approximately, Ι = ≈ 48 m A

e) Eight (8) resistors rated at 100 W and 120 V when connected in parallel yield

18 W.

TABLE 1 Summary of results when a residence’s neutral wire is disconnected

272
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
8W: Electrical Safety and Reduction in Energy Consumption

Voltage
Effects when Rg = :
Condition

Lights dim, microprocessors and motors may


Undervoltage
be damaged (stall condition)

Lights become brighter, microprocessors and


Overvoltages
motors may be damaged and may cause fires.

PROBLEM 8W-10

a) Most likely the plumber steps in wet ground.

b) It is an open neutral condition that can cause damage of equipment, fires and

injure personnel.

PROBLEM 8W-11

a) LI→MU

2 ( 4160 ) 3
b) = 9607 V/m , Approximate.
0.5

For the effects of a coil’s energy on its discharge resistor see solution of Exercise

8W-6.

c) The ground voltage momentarily increased. The entire distribution network was

disconnected because of the operation of the upstream high-speed protective

devices.

273
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Zorbas/Electric Machines, 2e

PROBLEM 8W-12

The supply current to the operating motor is a non-sinusoidal waveform whose

fundamentals and harmonics induced a voltage on the adjacent cables of the idle motor.

The induced voltages injured the Maintenance Personnel.

PROBLEM 8W-13

I) When the secondary of a voltage transformer is shorted high currents will flow

which can cause fires.

II) When the secondary of a current transformer is open—while its primary is

connected to the cables of an energized load—a very high voltage is developed

across the open terminals, which can injure Personnel and cause fires (see Chapter

on Transformers).

PROBLEM 8W-14

a) When non-professional or unprotected electricians try to replace panel breakers or

trace circuits through its interior, risk the danger of creating electrical shorts

(ARC Flash) with destructive consequences.

b) The loosening of the screws shortened the distance between the bus bars resulting

in breakdown of the dielectric between them.

274
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
8W: Electrical Safety and Reduction in Energy Consumption

PROBLEM 8W-15

1. The European System (50 Hz) is more dangerous relative to that of North

America (60 Hz) because they use 240 V while North America uses 120 V and

240 V.

2. The European System does not incorporate a neutral and thus is protected from

the problems associated with open neutral (N A).

PROBLEM 8W-16

a) When the resulting short circuit current through the green wire is high then the

equipment’s enclosure is at a raised potential.

b) It results in disconnected ground wire.

PROBLEM 8W-17

a) 6.65 A

b)

and

214.93 m A

275
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Zorbas/Electric Machines, 2e

PROBLEM 8W-18

a) Anytime there is current through the ground at any two points across its path there

will be a voltage commonly known as stray voltages. It can be caused from

lightning strokes, damage underground power cables, improper equipment

grounding and induction currents.

b) The GFCI of a home monitors and reacts to the current downstream of it. It has

nothing to do with stray voltages. When the coating paint of interior surface of a

pool is chipped there is possibility of electrocution from ground leakage currents.

c) When the flux lines of the power distribution cables impinge on the ground the

latter will create its own flux lines—and thus current—to oppose the disturbance.

PROBLEM 8W-19

a) 365 × 24 × 0.14 = $1226.4/year

b) From the Utility invoices

Electricity: 9825 kWh/year

Heating, Natural Gas: 2700 m3/year

Assuming a furnace efficiency of 96% we obtain:

1   37.5  
 9825 + 2700   ( 0.96 ) 
365   3.6  

= (9825 + 27,000)

= 100.89 kWh/day

c) Water in bath tub: 1.5 × 1.5 × 5 = 11.25 ft3 of water

= 11.25 (62.4)

= 702 ℓb of water

276
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
8W: Electrical Safety and Reduction in Energy Consumption

Change of temperature ∆T = 80 − 65 = 15°F

Energy used

Q = m CP ∆T Btu

702 (1)(15 )
= = 3.08 kWh
3412

d) One m3 of Natural Gas or 1 liter of gasoline each contains 37.5 M J of energy.

Then, actual output energy = (0.96) = 10.0 kWh

e) At starting and for a short period of time the power drawn by large motors could,

depending on the other loads, influence slightly the premises power demand.

f) See Chapter 1 “Effects of Power Factor”.

g) Reducing the power of a lighting fixture increases the heat requirements of the

lighted space and decreases its cooling requirements. The corresponding number

of hours can be calculated from the degree-days.

P0 P1 − PL P P
i) η= = = 1 − L , from which PL = 0 (1− η )
P1 P1 P1 η

PROBLEM 8W-20

a) Higher than nominal voltages and/or currents will correspond to: Higher copper

losses (I2 R).

• With reference to the equipment’s B-H curve it may be also concluded

that the equipment (motors and transformers) will be driven into some

degree of saturation and thus to an increase of magnetic losses.

277
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Zorbas/Electric Machines, 2e

• In general, the output torque will be reduced because of the effects of the

negative sequence magnetic field.

b) The motor nominal losses are

10
PLoss 1 = (1 − 0.96 ) = 0.42 kW
0.96

The average value or the applied voltages is

Vav = (215 + 200 + 202) = 205.67

The voltage unbalance is

Vun = (100) = 4.34%

and the corresponding increase in the winding’s temperature is

2 (4.34)2 = 37.67% increase

Increase in the motor losses

PLoss 2 = 0.42 (4.34) = 1.82%

PROBLEM 8W-21

LED: 22 = (365)(24)

From which

P = 2.51 Watts

Similarly for compact fluorescent

365 (24) = 60

= 6.85 Watts

and for incandescent

P ( 365 ) ( 24 )
= 250
1000

278
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
8W: Electrical Safety and Reduction in Energy Consumption

= 28.54 Watts

PROBLEM 8W-22

a) Q = P tan Θ = 106 tan 36.9 = 79.5 kVAR

106,000
b) Inominal = = 159.37 ∠36.9° A
3 ( 480 ) ( 0.8 )

At unity Pf

106,000
I= = 127.50 A
3 ( 480 ) (1)

The new motor losses are about

2
 127.5 
= 6 = 3.84 kW
 159.37 
PLoss 2

and the decrease in losses is

6 − 3.84 = 2.16 kW

PROBLEM 8W-23

a) In 1-hour, the fuel energy used is

100 (1) = 100 kWh

For the Genset to produce this energy in 1-hour

(η) 40 = 416.67 η kWh

From above

η= = 0.24

b) Gasoline used per kWh output is

(0.24) = 2.5 kWh/liter

279
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Zorbas/Electric Machines, 2e

For 100 kWh output, the fuel used is

= 40 liters

Its corresponding cost is

40 (1.25) = $70

Cost of gasoline per kWh

= $0.50/kWh

c) Utility charges: cost of power demand + energy

: 100 (14) + 100 (80) (0.15)

= 1400 + 1200

= $2,600.00/month

Generator costs

40 (1.25) (80) = $4,000/month

Savings 2,600 − 4,000 = $1,400/year (loss)

280
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
8W: Electrical Safety and Reduction in Energy Consumption

PROBLEM 8W-24

Capacitor Requirement (Refer to Fig. P8W-6).

Q = P (tan Φ2 − tan Φ1)

= 20 (tan arc cos 0.45 − tan arc cos 0.9)

= 30 kVAR

Cost (C1) of the capacitor bank

C1 = 30 (50) = $1,500

Utility additional kW charges:

(0.9) − 20 = 20 kW

Corresponding Utility’s charges (C2)

C2 = 20 (13) (12)

= 3,120.00

Effective savings to customer (C3)

C3 = 2 (3120) = $6,240.00/year

Pay-back period = = 0.24 years

FIG. P8W-6 Single-phase representation

PROBLEM 8W-25

281
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Zorbas/Electric Machines, 2e

Existing Motor (Refer to Fig. P8W-7)

Pin = = = 87.2 kW

Loss (PL)

PL = (1 − 0.86) = 12.21 kW

High efficiency motor

Pout = 75 kW

Pin = = 78.95 kW

PL = = 3.95 kW

Reduction in power: 12.21 − 3.95 = 8.26 kW

Apparent savings (C1) is:

C1 = 8.26 (13) (12) + 8.26 (4000) (0.10)

= 1,288.87 + 3,304.77 = $4,593.64/year

Effective savings (C2) is:

C2 = (2) (4,593.64) = $9,187.29/year

10,000
Pay-back period = = 1.09 years
9187.29

FIG. P8W-7

282
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
8W: Electrical Safety and Reduction in Energy Consumption

PROBLEM 8W-26

a) Damper Control (Refer to Fig. P8W-8).

When damper control is used to reduce the airflow there are no substantial

savings.

b) Using Speed Control

The airflow is proportional to speed

Q2  0.8 
N 2 = N1 = 1160  = 928 rpm
Q1  1.0 

and the corresponding power is

3
Q 
3
 0.8 
P2 = P1  2  = 30  = 15.36 kW
Q  1
 1.0 

Reduction in power

30 − 15.36 = 14.64 kW

283
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Zorbas/Electric Machines, 2e

Corresponding operating costs (C2) are

C2 = 14.64 (13)(12) + 14.64 (4000)(0.1)

= 2283.84 + 5856.00

= $8139.84/year (The upstream reduction in losses are not taken into


consideration)

FIG. P8W-8

PROBLEM 8W-27

a) The actual line currents are equal to the load’s nominal current and that due to 3rd

harmonic currents. That is

2
 9
50 = I f 2 +  
 3

If = 49.91 A

b) Neglecting the losses in the neutral we obtain the increase in the load losses as

follows

  50  2 
∆Pincrease = Pnominal    
  49.91  

= 1.0036 Pnominal

284
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
8W: Electrical Safety and Reduction in Energy Consumption

PROBLEM 8W-28

At constant motor load, when the supply voltage is increased by 5% the motor’s current

is decreased by 5%. Then, the decrease in the motor losses is

2
 95 
∆P = Pnominal  
 100 

= 0.90 Pnominal loss

285
© 2015 Cengage Learning. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.

You might also like