Al Shatti Hotel
General Information
Unit Type Standard Efficiency with AFD
Unit Size 250
EcoDesign Compliance
SEER 6
ETAsc 227.00 %
SEER Compliance 2018 Compliant
SEER Compliance 2021 Non compliant
SEPRHT 6.01
SEPR HT Compliance 2018 Non-compliant
SEPR HT Compliance 2021 Non-compliant
SEPRMT 4.73
SEPR MT Compliance 2018 Compliant
SCOP 6.30
ETAsh 244.00
SCOP Compliance 2017 Non compliant
Al Shatti Hotel
WWHP
Heating mode heating rejection capacity 815.8 kW Cooling mode heating capacity 991.0 kW
Heating mode heating efficiency 2.824 COP (kW/kW) Cooling mode heating efficiency 4.960 COP (kW/kW)
Heating mode refrigeration capacity 518.9 kW Cooling mode refrigeration capacity 788.6 kW
Heating mode cooling efficiency 1.747 EER (kW/kW) Cooling mode cooling efficiency 3.945 EER (kW/kW)
Heating mode leaving fluid evap 5.50 C Cooling mode leaving fluid evap 5.50 C
Heating mode flow evap 13.70 L/s Cooling mode flow evap 20.86 L/s
Heating mode entering fluid evap 14.52 C Cooling mode entering fluid evap 14.50 C
Heating mode fluid press drop evap 12.1 kPa Cooling mode fluid press drop evap 27.8 kPa
Heating mode entering fluid cond 60.00 C Cooling mode entering fluid cond 35.00 C
Heating mode flow cond 40.83 L/s Cooling mode flow cond 47.79 L/s
Heating mode leaving fluid cond 65.00 C Cooling mode leaving fluid cond 40.00 C
Evaporator Information
Leaving temperature Fluid type Water
Fluid flow rate Fluid concentration evap
Entering temperature
Pressure drop
Fouling factor evap 0.0176 m2-deg K/kW
Condenser Information
Leaving temperature Cond fluid type Water
Fluid flow rate Fluid concentration cond
Entering temperature
Pressure drop
Fouling factor cond 0.0440 m2-deg K/kW
Physical Information
Length 3160 mm Width 1380 mm
Height 2080 mm Shipping weight 3807 kg
Operating weight 4103 kg Sound Pressure (10m) 71 dBA
Sound power 103 dBA
Al Shatti Hotel
Electrical Information
Unit voltage 400.0V-50.0Hz-3Ph
Max Amps 510.00 A
Total power
Unit starting current 622.00 A
Run Load Amps 470.23 A
EcoDesign Disclaimer
3. EcoDesign - For MT Process Cooling - From 1 January 2018 this product can not be placed on the European Union/Switzerland/ Turkey
markets due to non-compliance to requirements as defined in Ecodesign Regulation (EU) 2015/1095, dated 5.May 2015
4. EcoDesign - (Tier 2) - MT Process Cooling - From 1 July 2018 this product can not be placed on the European Union/Switzerland/ Turkey
markets due to non-compliance to requirements as defined in Ecodesign Regulation (EU) 2015/1095, dated 5.May 2015
Outside the scope of AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Using
Vapor Compression Cycle Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P)
and AHRI Standard 551/591 (SI).