Professional Documents
Culture Documents
Nobu Hotel - Air Cooled and Adiabatic Chiller Options
Nobu Hotel - Air Cooled and Adiabatic Chiller Options
Bulk Loads
HVAC - Chiller Plant 1600 1600
HVAC - Critical Cooling 85 85 85 85
HVAC - Fans 125 125
Smoke Management System 125 125 40 125
Public Health 285 285 155 80
Vertical Transportation 100 100 25 25
ICT & Security 310 310 225 160
Lighting - Façade 25 25
Lighting - Landscape & External 60 60
Emergency Lighting 10 10 5 5
Fire Alarm and Voice Evacuation 5 5 5 5
Kitchen and Waste Management 20 20
TCL [kW] 30427 23843 6584 0 85 107 40 2 165 Err:504 2750 Err:504 540 485
Spare [10%] Err:504 54 49
TCL incl. Spare [kW] Err:504 594 534
Transformer Quantity at 1500kVA Err:504
Min. Generator Rating [kVA] 743 667
Generator Rating [kVA] 900
REVISION CONTROL
REVISION: 00 DATE: 12/04/18
PREPARED BY RA
CHECKED BY: YM
Option A - All Air Cooled Chillers Option B - All Air Cooled Chillers
Components Air Cooled Chillers for Hotel and Air cooled chillers for Residential Air Cooled Chillers for Hotel and Air cooled chillers for Residential
without Adiabatic cooling plant with Adiabatic cooling plant
Supply and installation of air 4 Nos. (250 TR / 880 kW each) for Residential Towers. 4 Nos. (250 TR / 880 kW each) for Residential Towers.
cooled chiller 3 Nos. (430 TR / 1,512 kW each) for Hotel Building. 3 Nos. (430 TR / 1,512 kW each) for Hotel Building.
Supply and installation of 4 Nos. for Residential towers (2 each for each tower)
N/A
Adiabatic cooling plant 3 Nos. for Hotel tower
6 Nos. (23.4L/s, 22 kW each) Variable Primary Chilled Water Pumps for 6 Nos. (23.4L/s, 22 kW each) Variable Primary Chilled Water Pumps for
Residential Towers. Residential Towers.
Primary chilled water pumps
4 Nos. (40.2L/s, 38 kW each) Variable Primary Chilled Water Pumps for 4 Nos. (40.2L/s, 38 kW each) Variable Primary Chilled Water Pumps for
Hotel Building. Hotel Building.
Hybrid Adiabatic precooling Consists of Water preparation equipment , high pressure nozzle duct,
N/A
modular system condenser protective pads, smart control panel.
Model Refence TCL [kW] PD [W/m2] Standard Room Family Room 1-Bed Deluxe Room 2-Bed Deluxe Room
QTY TCL [kW] QTY TCL [kW] QTY TCL [kW] QTY TCL [kW]
Lighting
Decorative Luminaires 0.10 17 1.70 17 1.70 17 1.70 18 1.80
LED Luminaires 0.05 34 1.70 34 1.70 34 1.70 57 2.85
Small Power
5A Single Socket Outlets: 6 1.20 8 1.60 9 1.80 12 2.40
Table Lamp 0.05 1 0.40 2 0.80 2 0.80 3 1.20
Floor Lamp 0.05 1 0.05 1 0.05 1 0.05 1 0.05
HVAC
FCU 0.10 1 0.10 1 0.10 1 0.10 1 0.10
Public Health
Water Heater 1.20
Miscellaneous
Motorised Blind 0.10 1 0.10 1 0.10 1 0.10 1 0.10
Demister 0.10 1 0.10 1 0.10 1 0.10 1 0.10
Kitchen Appliances
Cooker - Gas Shutoff Valve 0.05
Cooker - Cooking Range Ignitor 0.05
Countertop - Twin Socket Outlet 0.40
Countertop - Single Socket Outle 0.20
Dishwasher 2.10
Kitchen Hood 0.10
Refrigerator 0.20
Washing Machine & Dryer 2.05
Notes:
1. Changes to the loads have been discussed with Emaar, and it was agreed at the meeting held on 12/08/2018 that this shall be updated at DD stage.
2. Lighting load shall be updated subject to final coordination between ID/Specialist Lighting Designer and Emaar